LFRD Notes
LFRD Notes
The newly developed load and resistance factor design (LRFD) specification for engineered
wood construction in the United States uses probabilistic methods as the technical basis for
selecting design strength requirements, load combinations and load factors.
What are the load factors that can be used for LRFD?
Using LRFD LC-2, the combined design load equals 1.2 times the dead load plus 1.6 times
the live load, or 15.6 kips. The factor for dead load (1.2) is lower than the factor for live load
(1.6) because dead load is more predictable than live load.
Section 2.2
ASCE 7-05 provides load combination equations for both LRFD and ASD.
The ones that you will use will depend on which of the two design
philosophies that have been chosen for your project.
You will note that several of the load combination equations have
multiple permeations due to use of "or" or "+" in the equations (both
wind, W, and seismic, E, are considered to be + loads). This is true of
both the LRFD and ASD combinations.
Load and Resistance Factor Design
If you chose to use LRFD for your design philosophy, then you are to
make sure that your structure is capable of supporting the loads resulting
from the seven ASCE 7-05 basic load combination equations.
LRFD applies load factors to service level loads so that they are safely
comparable to member strengths (which are generally inelastic) while
maintaining the actual (service) loads in the elastic region. Member
strength (the maximum load that the member will support) is generally
between 1.3 to 1.4 times the force that will cause yielding in a member.
These load factors are applied in the load combination equations and
vary in magnitude according to the load type.
The magnitude of the LRFD load factors reflect the predictability of the
loads. For example, the load factor for D is generally lower than the load
factor for L in any given equation where there is equal probability of
simultaneous occurrence of the full value of each load type. This is
because dead loads are much more predictable than live loads and,
hence, do not require as great of a factor of safety.
Example: Analysis of a structure shows that a particular member
supports 5 kips dead load and 6 kips live load. Using LRFD LC-2, the
combined design load equals 1.2 times the dead load plus 1.6 times the
live load, or 15.6 kips. The factor for dead load (1.2) is lower than the
factor for live load (1.6) because dead load is more predictable than live
load. The load factors are all greater than 1.0 since we want to compare
the result to the ultimate strength of the member instead of the yielding
strength of the member yet we don't want yielding to occur. The
ultimate strength is generally about 1.3-1.4 times the yield strength of
the member.
Allowable Strength Design
For ASD there are eight basic load combination equations. You will notice
that the large load factors found in the LRFD load combinations are
absent from the ASD version of the ASCE 7-05 load combination
equations. Also, the predictability of the loads is not considered. For
example both D and L have the same load factor in equations where they
are both likely to occur at full value simultaneously. The probability
associated with accurate load determination is not considered at all in
the ASD method. Hence the major difference between LRFD and ASD.
Example: Analysis of a structure shows that a particular member
supports 5 kips dead load and 6 kips live load. Using ASD LC-2, the
combined design load equals the dead load plus the live load, or 11.0
kips. The factor for dead load (1.0) is the same as the factor for live load
(1.0), hence not accounting for the fact that the dead load is more
predictable than the live load. The result of the load combination
equation is then generally compared against the yielding strength of the
member to ensure elastic behavior.
The Load Combination Equations
The published load combination equations are:
LRFD
1. 1.4(D + F)
2. 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)
3. 1.2D + 1.6(Lr or S or R) + ((0.5 or 1.0)*L or 0.8W)
4. 1.2D + 1.6W + (0.5 or 1.0)*L + 0.5(Lr or S or R)
5. 1.2D + 1.0E + (0.5 or 1.0)*L + 0.2S
6. 0.9D + 1.6W + 1.6H
7. 0.9D + 1.0E + 1.6H
When atmospheric ice is included, ASCE 7-05 requires modifications to
equations (2), (4), and (6), effectively resulting in three new equations
which are listed here:
2ice. 1.2(D + F + T) + 1.6(L + H) + 0.2Di + 0.5S
4ice. 1.2D + (0.5 or 1.0)*L + Di + Wi + 0.5S
6ice. 0.9D + Di + Wi + 1.6H
*
Note that the load factor for L in equations (3), (4), and (5) is permitted
to equal 0.5 for occupancies in which the unit live load is less than or
equal to 100 psf, except for garages or areas occupied as places of public
assembly.
ASD
1. D + F
2. D + H + F + L + T
3. D + H + F + (Lr or S or R)
4. D + H + F + 0.75(L + T) + 0.75(Lr or S or R)
5. D + H + F + (W or 0.7E)
6. D + H + F + 0.75(W or 0.7E) + 0.75L + 0.75(Lr or S or R)
7. 0.6D + W + H
8. 0.6D + 0.7E + H
For the purposes of this text, we will identify the equations and their
permutations by the labels defined as defined in Table 2.1.
When atmospheric ice is included, ASCE 7-05 requires modifications to
equations (2), (3), and (7), effectively resulting in three new equations
which are listed here:
2ice. D + H + F + L + T + 0.7Di
3ice. D + H + F + 0.7Di + 0.7Wi + S
6ice. 0.6D + 0.7Di + 0.7Wi + H
Table 2.1
ASCE 7-05 Load Combination Equation Permutations
LRFD ASD
* Note that the load factor for L in LRFD equations ASD-LC6i D + H + F + 0.75(0.7E) + 0.75L + 0.75R
(3), (4), and (5) is permitted to equal 0.5 for
occupancies in which the unit live load is less than or ASD-LC6j D + H + F - 0.75(0.7E) + 0.75L + 0.75Lr
equal to 100 psf, except for garages or areas
occupied as places of public assembly. Otherwise ASD-LC6k D + H + F - 0.75(0.7E) + 0.75L + 0.75S
the load factor for L equals 1.0.
ASD-LC6l D + H + F - 0.75(0.7E) + 0.75L + 0.75R
ASD-LC7a 0.6D + W + H
ASD-LC7b 0.6D - W + H
You cannot mix values from different combination equations in the same analysis. The
same equation is applied to each load source. The final structure must have sufficient strength
to support all load conditions in the philosophy (LRFD or ASD) you have chosen for your
project.
Since 1931, the design and construction of highway bridges in the U.S.
has been governed by the Standard Specifications for Highway Bridges
published by AASHTO. Over time, there have been numerous revisions
and updates and the specifications have begun to resemble a patchwork
quilt. A number of major gaps and inconsistencies were compounded by
a lack of commentary to explain the intent or background of any of the
specification provisions. After reviewing several options, AASHTO
decided to develop an entirely new bridge code that would incorporate
state-of-the-art bridge engineering and would be based on the load and
resistance factor design approach. Following review and consideration,
the new specification is expected to be adopted by AASHTO for use by
any agency that designs bridges in the U.S. This new specification is a
radical departure from the traditional design philosophy of Working
Stress Design (WSD), which requires that the total stress caused by all
design loads be less than a specified percentage of the bridge material's
stress limit. While this design concept has worked well for many years,
engineers have known that neither loads nor material properties can be
defined with accuracy and precision. The LRFD code, with its extensive
commentary, is seen as state of the art and technically easy to maintain,
as well as ultimately easy to understand and use by bridge designers.