Cooling water additives
Cooling water additives
Raw water quality to be used in the closed cooling water circuits of engines has to meet the following
specification.
Use of raw water produced with an evaporator as well as a good quality tap water will normally ensure that an
acceptable raw water quality requirement is fulfilled, but e.g. untreated sea water and rain water are unsuitable
raw water qualities.
In order to prevent corrosion in the cooling water system, the instructions of right dosage and concentration of
active corrosion inhibitors should always be followed. The information can be found in the table below.
Note 1: For many products the recommended minimum and maximum limits are listed in the table above.
Since the amount of active corrosion inhibitors, especially nitrites, is decreasing during the service
of engines, the engine manufacturer recommends to start the dosage from the upper level of indicated
range.
Note 2: The nitrite content of nitrite-based cooling water additives tends to decrease in use. The risk of local
corrosion increases substantially when nitrite content goes below the recommended limit.
Note 3: Cooling water additive manufacturers can indicate the required nitrite content measured either as
sodium nitrite (NaNO2) or as nitrite (NO2). 1 mg/l as NO2 equals to 1.5 mg/l as NaNO2.
Note 4: Nitrite based cooling water additives are not offering a good protection against corrosion for
aluminium and its alloys and thus the use of such products can’t recommended for cooling systems
containing those construction materials.
Note 5: Different cooling water additives shall not be mixed with each other, but if it is desired to start to use
another cooling water additive, the one being used shall be drained from the system before filling
another product. If the cooling water system is dirty, it shall be flushed with good quality water or if
needed use additional chemicals to remove possible deposits, like grease, oil, rust, etc. Though many
cooling water additives are chemically compatible with each other, these can contain e.g. polymers
which can loosen existing deposits from the cooling water system. When the loose deposits become
suspended in the cooling water, they can attach to engine component surfaces, e.g. cylinder head and
will then cause detrimental effects in terms of heat transfer decline, clogging of small diameter water
channels and deposit formation leading to local overheating and corrosion.
In addition to the concentration of active corrosion inhibitor specified in the previous table, treated cooling
water shall meet the following quality requirements:
4. USE OF GLYCOL
If a freezing risk exists, glycol needs to be added to cooling water. However, in case there is no freezing risk,
the use of glycol in cooling water shall be avoided due to its detrimental effect on heat transfer. Since glycol
alone does not protect the engine and cooling water system against corrosion, additionally a validated cooling
water additive must always be used. All validated cooling water additives are compatible with glycol.
Ready-to-use mixtures of commercial coolant brands containing both glycol and corrosion inhibitors are not
allowed to use. Those are typically designed to be used as strong (~ 30 –) 50% / 50 (~ 70) % mixtures. However,
in Wärtsilä engines normally a much lower glycol amount is adequate to protect the cooling water system
against freezing. The outcome of decreasing the glycol amount is that simultaneously also the concentration
of corrosion inhibitors will decrease to too low level resulting in an increased risk of corrosion.
The amount of glycol in closed cooling water system shall always be minimized since heat transfer of water
containing glycol has deteriorated significantly. The engine may therefore be subject to additional output
derating when using glycol in the cooling water, see document DMTA00044163 for more information.
As an alternative to the validated cooling water additives, the Wärtsilä Water Conditioner Unit (WWCU) can
also be used to treat cooling water of engines’ closed water circuits. WWCU is based on the Enwamatic EMM
cooling water treatment system, but includes a number of new features based on Wärtsilä design.
The WWCU protects the engine from corrosion without any chemicals. It acts as a side stream filtration and
water treatment unit and includes the following functions: corrosion protection, scale control, filtration, control
of bacterial growth and air separation.