0% found this document useful (0 votes)
14 views5 pages

A700000008272462

The AF400-30-11-70 is a 3-pole contactor designed for controlling motors up to 200 kW at 400 V AC and switching power circuits up to 600 A. It features a wide control voltage range of 100-250V and built-in surge protection, making it suitable for unstable networks. The product is compliant with various international standards and has a robust design, allowing for easy expansion with auxiliary contact blocks.

Uploaded by

Mahmoud Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views5 pages

A700000008272462

The AF400-30-11-70 is a 3-pole contactor designed for controlling motors up to 200 kW at 400 V AC and switching power circuits up to 600 A. It features a wide control voltage range of 100-250V and built-in surge protection, making it suitable for unstable networks. The product is compliant with various international standards and has a robust design, allowing for easy expansion with auxiliary contact blocks.

Uploaded by

Mahmoud Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

PRODUCT-DETAILS

AF400-30-11-70
AF400-30-11 100-250V 50/60Hz / 100-250V DC
Contactor

General Information
Extended Product Type AF400-30-11-70
Product ID 1SFL577001R7011
EAN 7320500217665
Catalog Description AF400-30-11 100-250V 50/60Hz / 100-250V DC Contactor
The AF400-30-11-70 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted
auxiliary contacts and Main Circuit Bars, controlling motors up to 200 kW / 400 V AC (AC-3)
or 350 hp / 480 V UL and switching power circuits up to 600 A (AC-1) or 550 A UL general
use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250
Long Description V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy
consumptions and ensuring distinct operations in unstable networks. Furthermore, surge
protection is built-in, offering a compact solution. AF contactors have a block type design,
can be easily extended with add-on auxiliary contact blocks and an additional wide range of
accessories.

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Popular Downloads
Data Sheet, Technical 1SBC100192C0206
Information
Instructions and Manuals 1SFC380023-en
Dimension Diagram 53540919-59
AF400-30-11-70 2

Dimensions
Product Net Width 186 mm
Product Net Depth / 216 mm
Length
Product Net Height 278 mm
Product Net Weight 10.6 kg

Technical
Number of Main Contacts 3
NO
Number of Main Contacts 0
NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 1
Contacts NC
Rated Operational Voltage Main Circuit 1000 V
Rated Frequency (f) Main Circuit 50/60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 600 A
Thermal Current (I th )

Rated Operational Current (1000 V) 40 °C 600 A


AC-1 (I e ) (1000 V) 55 °C 500 A
(1000 V) 70 °C 400 A
(690 V) 40 °C 600
(690 V) 55 °C 500
(690 V) 70 °C 400
Rated Operational Current (415 V) 55 °C 400 A
AC-3 (I e ) (440 V) 55 °C 400 A
(500 V) 55 °C 400 A
(690 V) 55 °C 350 A
(1000 V) 55 °C 155 A
(380 / 400 V) 55 °C 400 A
(220 / 230 / 240 V) 55 °C 400
Rated Operational Power (415 V) 220 kW
AC-3 (P e ) (440 V) 220 kW
(500 V) 250 kW
(690 V) 315 kW
(1000 V) 220 kW
(380 / 400 V) 200 kW
(220 / 230 / 240 V) 110 kW
Rated Breaking Capacity 8 x Ie AC-3
AC-3 acc. to IEC 60947-4-
1
Rated Making Capacity 10 x Ie AC-3
AC-3 acc. to IEC 60947-4-
1
Short-Circuit Protective gG Type Fuses 630 A
Devices
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A
Withstand Current (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4000 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3500 A
Maximum Electrical (AC-1) 300 cycles per hour
Switching Frequency (AC-2 / AC-4) 60 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current (110 V) 1-Pole, 40 °C 600 A
DC-1 (I e ) (110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
(600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current (110 V) 1-Pole, 40 °C 600 A
DC-3 (I e ) (110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
AF400-30-11-70 3

(600 V) 3 Poles in Series, 40 °C 600 A


Rated Operational Current (110 V) 1-Pole, 40 °C 600 A
DC-5 (I e ) (110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
(600 V) 3 Poles in Series, 40 °C 600 A
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to UL/CSA 600 V

Rated Impulse Withstand Main Circuit 8 kV


Voltage (U imp )

Mechanical Durability 3 million


Maximum Mechanical 300 cycles per hour
Switching Frequency
Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit 50 Hz 100 ... 250 V
Voltage (U c ) 60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage DC 5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 955 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 955 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 895 V·A
Operate Time Between Coil De-energization and NC Contact Closing 45 ... 55 ms
Between Coil De-energization and NO Contact Opening 48 ... 58 ms
Between Coil Energization and NC Contact Opening 45 ... 115 ms
Between Coil Energization and NO Contact Closing 50 ... 120 ms
Connecting Capacity Main Bar 47 mm²
Circuit Rigid Al-Cable 2x240 mm²
Rigid Cu-Cable 240 mm²
Connecting Capacity Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Auxiliary Circuit Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type Main Circuit: Bars

Technical UL/CSA
Maximum Operating Main Circuit 1000 V
Voltage UL/CSA
General Use Rating (600 V AC) 550 A
UL/CSA
Horsepower Rating (200 V AC) Three Phase 125 hp
UL/CSA (208 V AC) Three Phase 125 hp
(220 ... 240 V AC) Three Phase 150 hp
(440 ... 480 V AC) Three Phase 350 hp
(550 ... 600 V AC) Three Phase 400 hp

Environmental
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
Close to Contactor for Storage -40 ... +70 °C
Maximum Operating 3000 m
Altitude Permissible
Resistance to Shock acc. Shock Direction: A 5 K40
to IEC 60068-2-27 Shock Direction: B1 5 K40
Shock Direction: B2 5 K40
Shock Direction: C1 5 K40
Shock Direction: C2 5 K40
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Certificates and Declarations (Document Number)


AF400-30-11-70 4

ABS Certificate 15-LD1408622-PDA


BV Certificate BV_13409-C0BV
CB Certificate SE-82316
CCC Certificate CQC_2007010304256683
CCS Certificate GB14T00030
CQC Certificate CQC2007010304256683
CQC2011010304514755
cUL Certificate 20121207-E36588
Declaration of Conformity 2020980304001300
- CCC 2020980304001081
Declaration of Conformity 2CMT2019-005796
- CE
DNV Certificate DNV_E-10966
DNV GL Certificate TAE00001W1
EAC Certificate 9AKK107046A8618
Environmental Information 1SFC101004D0202
GL Certificate GL_42988-02HH
Instructions and Manuals 1SFC380023-en
LOVAG Certificate SE-0146190
LR Certificate 16-20064
PRS Certificate TE_2092_880423_16
RINA Certificate ELE060313XG_002
RMRS Certificate 9AKK107045A6978
RoHS Information 2CMT2019-005796
UL Listing Card UL_E36588

Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 280 mm
Package Level 1 Depth / 375 mm
Length
Package Level 1 Height 310 mm
Package Level 1 Gross 12 kg
Weight
Package Level 1 EAN 7320500217665

Classifications
Object Classification Code Q
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
eClass V11.0 : 27371003
UNSPSC 39121529
IDEA Granular Category 4755 >> Contactors
Code (IGCC)
E-Number (Finland) 3709332
E-Number (Norway) 4115288
E-Number (Sweden) 3228336
AF400-30-11-70 5

Where Used (as a spare part for "Products")


Unit Of
Identifier Description Quantity
Measure
FC-0460-0240 No Description Available 1 piece
FC-0460-0300 No Description Available 1 piece
FC-0460-0399 No Description Available 1 piece
FC-0460-0500 DEV 1 No Description Available 1 piece

Product specific part data


Product Category Drive Part Category
FC-0460-0240 MoCon Switches, Relays, Contactors
FC-0460-0300 MoCon Switches, Relays, Contactors
FC-0460-0399 MoCon Switches, Relays, Contactors
FC-0460-0500 DEV 1 MoCon Switches, Relays, Contactors

Categories

Low Voltage Products and Systems → Control Products → Contactors → Block Contactors
Drives → Low voltage AC drives → Legacy AC drives → MoCon

You might also like