Quint Ups Quick Start Guide (1)

This quick start guide provides instructions for the hardware installation and software setup of the QUINT UPS-IQ uninterruptible power supply and UPS-CONF management software. It includes steps for connecting the power supply, installing the software on Windows XP, and configuring settings for battery management. Additionally, it covers PC shutdown settings and emphasizes the importance of user responsibility in ensuring compliance with current standards.

Uploaded by

quang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views1 page

Quint Ups Quick Start Guide (1)

This quick start guide provides instructions for the hardware installation and software setup of the QUINT UPS-IQ uninterruptible power supply and UPS-CONF management software. It includes steps for connecting the power supply, installing the software on Windows XP, and configuring settings for battery management. Additionally, it covers PC shutdown settings and emphasizes the importance of user responsibility in ensuring compliance with current standards.

Uploaded by

quang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Quick start guide for QUINT UPS-IQ uninterruptible power supply

and UPS-CONF configuration and management software

1 Hardware installation
Complete the following work steps to wire the hardware.

1.1. Connect the 24V output of the 1.2. Wire the I>IN signal contact. 1.3. Connect the load to the UPS output. 1.4. Connect the battery cable. Check 1.5. Plug in the enclosed fuse. After 1.6. If the UPS-CONF software is
QUINT POWER power supply unit the cable cross section in the connecting the mains the hardware to be used, connect the
to the 24V UPS input. respective package slip. is now fully functional. IFS-USB-DATACABLE.
(The fuse should be removed if storing
the battery for a long time).

2 Software installation
Installation on Windows XP:
As soon as the driver installation wizard
opens, please proceed as follows

After you have completed the download from


www.phoenixcontact.net/catalog, open the
installation file by double-clicking and following 2.1. Select "No, not this time" and click "Next". 2.2. Choose "Install software automatically" 2.3. Following successful installation,
the instructions. and then click "Next". confirm with "Done".

3 Brief instructions to UPS-CONF

System menu
Here you find information on basic settings and manufacturer information.
You can adjust the following
software settings:
Device information
• Language setting, changes take
Here you find the UPS device place once the software is
type. Optionally, you restarted (German, English)
can insert text under
• Select temperature unit
"Settings/Advanced/Place of
(Celsius, Kelvin, Fahrenheit)
Installation".
• Check the communication port
for the IFS-USB-DATACABLE
data cable and change if
necessary (COM x)
• Advanced views active: extensive
information about the UPS and
the battery unit appear in the
menu

Software menu with


navigation bar

Intelligent battery management


Note: fully functional only once the battery
is fully charged.
SOC (State Of Charge) – current charging
state and remaining back-up time of the
battery unit.
SOH (State Of Health) – remaining life
expectancy of the battery unit; provides early
warning for a potential battery unit failure.
SOF (State Of Function) – determines the
current performance of the battery unit.

Status bar Action area


The current status of all components The content depends on the navigation.
Important note!
provides a quick overview. The system overview is mapped as an
example. Modules, voltages and signals are This information serves to support the user and
identified and currently displayed. does not exclude an independent inspection, especially
in view of the suitability in individual cases. It is the
­responsibility of the reader to check the current
­standards in content and in reference to the validity
for the task.

4 PC mode: Time settings for shutting down the PC/IPC Please follow the safety notes in the packaging
inserts of the devices.

Requirements: Further details about the hardware and software can


be found at www.phoenixcontact.net/catalog.
• Data cable IFS-USB-DATACABLE
(Order No. 2320500) is installed
• Software UPS-CONF (Order No. 2320403)
is installed, a free download from the E-shop
• Signal cable for data exchange between UPS
and battery unit is installed
© Phoenix Contact 2011

1 Shutdown delay 3 PC shutdown


Delay time is calculated automatically from The time required by the PC/IPC to shut down
the current remaining battery life minus the is set here. PHOENIX CONTACT Deutschland GmbH
time required by the PC / IPC to shut-down. Flachsmarktstraße 8
4 PC restart delay 32825 Blomberg, Germany
Alternatively, a fixed delay time may be chosen.
In the "PC Mode" setting on the UPS Only if the PC/IPC is shut down, and the mains Phone: + 49 5235 3-12000
potentiometer, the UPS functionality follows a 2 Program startup has returned in the meantime, the output voltage Fax: + 49 5235 3-12999
chronological sequence that can be parameterized After the delay time has expired it is possible to will be interrupted for the reset time. The E-mail: [email protected]
MNR 52000237/01.09.2011-00

via software, and is thus individually customized to start a program. Example: a software starts that PC/IPC is then automatically restarted. www.phoenixcontact.de
the respective application. gradually backs up system data.