0% found this document useful (0 votes)
3 views5 pages

Schneider Electric - EasyLogic-PM2000-Power-Meters - METSEPM2110

The document provides detailed technical specifications for the EasyLogic PM2110 Power and Energy meter, including its measurement capabilities, accuracy, and environmental compliance. It outlines various parameters such as measurement types, display features, and electrical characteristics, as well as certifications and environmental impact information. Additionally, it emphasizes Schneider Electric's commitment to sustainability and product lifecycle management.

Uploaded by

ttmyhien1985
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views5 pages

Schneider Electric - EasyLogic-PM2000-Power-Meters - METSEPM2110

The document provides detailed technical specifications for the EasyLogic PM2110 Power and Energy meter, including its measurement capabilities, accuracy, and environmental compliance. It outlines various parameters such as measurement types, display features, and electrical characteristics, as well as certifications and environmental impact information. Additionally, it emphasizes Schneider Electric's commitment to sustainability and product lifecycle management.

Uploaded by

ttmyhien1985
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Bảng thông số sản phẩm

Thông số kỹ thuật

EasyLogic PM2110, Power &


Energy meter, Total Harmonic, LED
display, Pulse, class 1
METSEPM2110

Main
Range EasyLogic

Miễn trừ trách nhiệm: Tài liệu này không nhằm thay thế và không được sử dụng để xác định tính phù hợp hoặc độ tin cậy của các sản phẩm này cho các ứng dụng người dùng cụ thể
product name EasyLogic PM2100

Product or component type Power meter

Device short name PM2110

Complementary
Device application Power monitoring
Sub billing

Power quality analysis total harmonic distortion

Type of measurement Total current harmonic distortion THD (I) per phase
Total voltage harmonic distortion THD (U) per phase
Apparent energy total
Active and reactive energy total
Apparent power total
Active and reactive power total
Current average
Voltage average
Frequency average
Power factor average

Metering type Peak demand power PM, QM, SM


Apparent power S, S1, S2, S3
Current I, I1, I2, I3
Reactive power Q, Q1, Q2, Q3
Calculated neutral current
Voltage U, U21, U32, U13, V, V1, V2, V3
Peak demand currents
Unbalance current
Demand power P, Q, S
Active power P, P1, P2, P3
Active, reactive, apparent energy (signed, four quadrant)

Accuracy class Class 1 active energy conforming to IEC 62053-21


Class 1 reactive energy conforming to IEC 62053-24

Measurement accuracy Apparent power +/- 1 %


Active energy +/- 1 %
Reactive energy +/- 1 %
Active power +/- 1 %
Voltage +/- 0.5 %
Power factor +/- 0.01
Current +/- 0.5 %
Frequency +/- 0.05 %

Measurement current 5…6000 mA

Measurement voltage 35…480 V AC 50/60 Hz between phases


20…277 V AC 50/60 Hz between phase and neutral
480…999000 V AC 50/60 Hz with external VT

Frequency measurement range 45…65 Hz

11 thg 5, 2025 1
[Us] rated supply voltage 44...277 V AC 45...65 Hz +/- 10 %
44...277 V DC +/- 10 %

Network frequency 60 Hz
50 Hz

Ride-through time 100 ms 120 V AC typical


400 ms 230 V AC typical
50 ms 125 V DC typical

[In] rated current 5A


1A

Maximum power consumption in 6 VA at 277 V AC


VA
Maximum power consumption in 3.3 W (power lines (AC))
W 2 W at 277 V (power lines (DC))

input impedance Current (impedance <= 0.3 mOhm)


Voltage (impedance > 5 MOhm)

Tamperproof of settings Protected by access code

Display type 7 segments LED

Display colour Red

Messages display capacity 3 fields of 4 characters

Display digits 12 digit(s) - 14.2 mm in height

Demand intervals Configurable from 1 to 60 min

Information displayed Demand current (past value)


Demand current (present value)
Demand power (past value)
Demand power (present value)
Voltage
Current
Frequency
Energy consumption
Harmonic distortion
Power factor
Active power
Apparent power
Reactive power
Unbalanced in %

Control type 3 x button

Local signalling Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Green LED: module operating (RUN)

Number of inputs 0

Number of outputs 1 pulse

POP parameter Pulse: 20 ms (5...40 V DC, 20 mA max)1...9999000 pulse/ k_h (kWh, kVAh, kVARh)

Impulse duration 20 ms

Communication port protocol POP

Sampling rate 64 samples/cycle

Cybersecurity Enable/disable communication ports

Communication service Remote monitoring

Product certifications CE conforming to IEC 61010-1


CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
RCM
EAC
C-Tick

Mounting mode Clip-on

Mounting position Vertical

2 11 thg 5, 2025
Mounting support Framework

Provided equipment 1 x installation guide

Measurement category Category III 480 V


Category II 480…600 V

Electrical insulation class Double insulation


Class II

Flame retardance V-0 conforming to UL 94

Connections - terminals Current transformer: screw connection (bottom) 6


Voltage inputs: screw connection (top) 4

Material Polycarbonate

Width 96 mm

Depth Total : 76.09 mm


Embedded : 61.64 mm

Height 96 mm

Net weight 300 g

Compatibility code PM2110

Environment
Service life 7 year(s)

IP degree of protection IP54 front: conforming to IEC 60529


IP30 body: conforming to IEC 60529

Relative humidity 5…95 % at 50 °C

Pollution degree 2

Ambient air temperature for -10…60 °C


operation
Ambient air temperature for -25…70 °C
storage
Operating altitude <= 2000 m

Electromagnetic compatibility Electrostatic discharge conforming to IEC 61000-4-2


Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Emission tests conforming to FCC part 15 class A

Overvoltage category III

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 12.000 cm

Package 1 Width 9.000 cm

Package 1 Length 12.400 cm

Package 1 Weight 402.000 g

Unit Type of Package 2 S03

Number of Units in Package 2 18

Package 2 Height 30.000 cm

11 thg 5, 2025 3
Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

Package 2 Weight 7.841 kg

4 11 thg 5, 2025
Environmental Data

Schneider Electric nhắm đến việc đạt được vị trí Net Zero vào năm 2050 thông qua các quan hệ đối tác chuỗi cung ứng, giảm vật
liệu tác động và sự tuần hoàn thông qua chiến dịch "Use Better, Use Longer, Use Again" đang diễn ra của chúng tôi để kéo dài tuổi
thọ sản phẩm và khả năng tái chế.

Dữ liệu môi trường đã giải thích

Cách chúng tôi đánh giá tính bền vững của sản phẩm

Ảnh hưởng môi trường

Environmental Disclosure Product Environmental Profile

Use Better

Vật liệu và Bao bì

Packaging made with recycled cardboard Yes

Packaging without single use plastic No

EU RoHS Directive Compliant with Exemptions

SCIP Number 408f3656-3c4a-4246-a1bc-3e783803af5e

REACh Regulation REACh Declaration

Use Again

Đóng gói lại và tái sản xuất

Circularity Profile End of Life Information

Take-back No

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

11 thg 5, 2025 5

You might also like