SIEMENS SINAMICS G120 6SL3210 1KE22 6AP1 Datasheet en

The SINAMICS G120C is a variable frequency drive designed for three-phase AC motors, with input voltage ranging from 380 to 480 V and rated power options of 11.00 kW (LO) and 7.50 kW (HO). It features a high efficiency of 0.97, a sound pressure level of 66 dB, and operates within a temperature range of -10 to 40 °C. The drive supports various control techniques, including V/f control and sensorless vector control, and complies with multiple safety and EMC standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views2 pages

SIEMENS SINAMICS G120 6SL3210 1KE22 6AP1 Datasheet en

The SINAMICS G120C is a variable frequency drive designed for three-phase AC motors, with input voltage ranging from 380 to 480 V and rated power options of 11.00 kW (LO) and 7.50 kW (HO). It features a high efficiency of 0.97, a sound pressure level of 66 dB, and operates within a temperature range of -10 to 40 °C. The drive supports various control techniques, including V/f control and sensorless vector control, and complies with multiple safety and EMC standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Data sheet for SINAMICS G120C

Ordering data
6SL3210-1KE22-6AP1
Figure similar

Client order no. : Item no. :


Order no. : Consignment no. :
Offer no. : Project :
Remarks :

Rated data General tech. specifications


Input Power factor λ 0.70 ... 0.85

Number of phases 3 AC Offset factor cos φ 0.95

Line voltage 380 ... 480 V +10 % -20 % Efficiency η 0.97

Line frequency 47 ... 63 Hz Sound pressure level (1m) 66 dB

Rated current (LO) 33.00 A Power loss 0.35 kW

Rated current (HO) 26.00 A Ambient conditions


Output
Cooling Air cooling using an integrated fan
Number of phases 3 AC

Rated voltage 400 V Cooling air requirement 0.018 m³/s

Rated power (LO) 11.00 kW Installation altitude 1000 m

Rated power (HO) 7.50 kW Ambient temperature

Rated current (IN) 26.00 A Operation -10 ... 40 °C (14 ... 104 °F)

Rated current (LO) 25.00 A Transport -40 ... 70 °C (-40 ... 158 °F)

Rated current (HO) 16.50 A Storage -40 ... 70 °C (-40 ... 158 °F)

Max. output current 33.00 A Relative humidity

Pulse frequency 4 kHz 95 % At 40 °C (104 °F), condensation


Max. operation and icing not permissible
Output frequency for vector control 0 ... 240 Hz

Output frequency for V/f control 0 ... 550 Hz Closed-loop control techniques
V/f linear / square-law / parameterizable Yes

V/f with flux current control (FCC) Yes

V/f ECO linear / square-law Yes


Overload capability
Sensorless vector control Yes
Low Overload (LO)
Vector control, with sensor No
150 % base load current IL for 3 s, followed by 110 % base load current IL for 57 s in a
300 s cycle time
Encoderless torque control No

High Overload (HO) Torque control, with encoder No

200 % base load current IH for 3 s, followed by 150 % base load current IH for 57 s in a
300 s cycle time Communication
Communication PROFIBUS DP

Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Fri Jul 22 08:08:25 CEST 2016
Page 1 of 2
Data sheet for SINAMICS G120C

Ordering data
6SL3210-1KE22-6AP1
Figure similar

Mechanical data Connections


Degree of protection IP20 / UL open type Signal cable

Size FSC Conductor cross-section 0.15 ... 1.50 mm² (28 ... 16 AWG)

Net weight 4.40 kg Line side

Width 140.0 mm Version Plug-in screw-type terminals

Height 295.0 mm Conductor cross-section 6.00 ... 16.00 mm² (10 ... 5 AWG)

Depth 203.0 mm Motor end

Inputs / outputs Version Plug-in screw terminals

Standard digital inputs Conductor cross-section 6.00 ... 16.00 mm² (10 ... 5 AWG)

Number 6 DC link (for braking resistor)

Switching level: 0→1 11 V Version Plug-in screw terminals

Switching level: 1→0 5V Conductor cross-section 6.00 ... 16.00 mm² (10 ... 5 AWG)

Max. inrush current 15 mA PE connection On housing with M4 screw

Fail-safe digital inputs Max. motor cable length

Number 1 Shielded 50 m

Digital outputs Unshielded 100 m

Number as relay changeover contact 1


Converter losses to EN 50598-2*
Output (resistive load) DC 30 V, 1 A
Efficiency class
IE2
Number as transistor 1
Comparison with the reference converter (90% / -66.85 %
100%)
Output (resistive load) DC 30 V, 1 A

Analog / digital inputs


I
227.0 W (1.31 %) 261.0 W (1.50 %) 311.0 W (1.80 %)
Number 1 (Differential input) 100%

Analog outputs

Number 1 (Non-isolated output) 152.0 W (0.88 %) 165.0 W (0.95 %) 183.0 W (1.06 %)


50%

PTC/ KTY interface


126.0 W (0.73 %) 132 W (0.76 %)
25%
1 motor temperature sensor input, sensors that can be connected: PTC, KTY
and Thermo-Click, accuracy ±5 °C

50% 90% f
Standards
The percentage values show the losses in relation to the rated apparent power of the converter.
Compliance with standards UL, cUL, CE, C-Tick (RCM)

The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
EMC Directive 2004/108/EC, Low-Voltage
CE marking generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
Directive 2006/95/EC version of the converter without options/components.

*calculated values; increased by 10% according to the standard

Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Fri Jul 22 08:08:25 CEST 2016
Page 2 of 2