Invertek_Manual-v200-1-20
Invertek_Manual-v200-1-20
Troubleshooting
IP20 & IP66 (NEMA 4X)
Quick Start Up 1
General Information
and Ratings 2
Mechanical Installation 3
Operation 5
Parameters 6
Analog and Digital Input
Macro Configurations 7
Modbus RTU
Communications 8
Technical Data 9
Troubleshooting 10
1. Quick Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 6. Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.1. Important Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 6.1. Standard Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.2. Quick Start Process. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.2. Extended Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.3. Installation Following a Period of Storage. . . . . . . . . . . . . . . . . 5 6.3. Advanced Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.4. P-00 Read Only Status Parameters. . . . . . . . . . . . . . . . . . . . 30
2. General Information and Ratings. . . . . . . . . . . . . . . . . 7
2.1. Identifying the Drive by Model Number. . . . . . . . . . . . . . . . . . . 7 7. Analog and Digital Input Macro Configurations. . . 31
2.2. Drive Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.2. Macro Functions Guide Key . . . . . . . . . . . . . . . . . . . . . . . . . 31
3. Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.3. Macro Functions – Terminal Mode (P-12 = 0). . . . . . . . . . . 32
3.1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.4. Macro Functions - Keypad Mode (P-12 = 1 or 2) . . . . . . . 33
3.2. UL Compliant Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.5. Macro Functions - Fieldbus Control Mode (P-12 = 3, 4, 7, 8
3.3. Mechanical Dimensions and Mounting – IP20 Open Units. . . 9
or 9). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.4. Guidelines for Enclosure Mounting – IP20 Units . . . . . . . . . . 10
7.6. Macro Functions - User PI Control Mode (P-12 = 5 or 6) . . . 34
3.5. Mechanical Dimensions – IP66 (Nema 4X) Enclosed Units. . . 11
7.7. Fire Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.6. Guidelines for mounting (IP66 Units). . . . . . . . . . . . . . . . . . . . 12
7.8. Example Connection Diagrams. . . . . . . . . . . . . . . . . . . . . . . 35
3.7. Gland Plate and Lock Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.8. Removing the Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8. Modbus RTU Communications. . . . . . . . . . . . . . . . . 36
3.9. Routine Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8.1. Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.2. Modbus RTU Specification. . . . . . . . . . . . . . . . . . . . . . . . . . 36
4. Power & Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . 14
8.3. RJ45 Connector Configuration. . . . . . . . . . . . . . . . . . . . . . . 36
4.1. Connection Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.4. Modbus Register Map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2. Protective Earth (PE) Connection. . . . . . . . . . . . . . . . . . . . . . . . 15
4.3. Incoming Power Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . 15 9. Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.4. Motor Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 9.1. Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.5. Motor Terminal Box Connections. . . . . . . . . . . . . . . . . . . . . . . 16 9.2. Rating Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.6. Control Terminal Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 9.3. Single Phase Operation of Three Phase Drives. . . . . . . . . . 37
4.7. Using the REV/0/FWD Selector Switch (Switched Version 9.4. Additional Information for UL Compliance. . . . . . . . . . . . . . 38
Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 9.5. EMC Filter Disconnect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.8. Control Terminal Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 17
10. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.9. Motor Thermal Overload Protection. . . . . . . . . . . . . . . . . . . . . 18
10.1. Fault Code Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.10. EMC Compliant Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.11. Optional Brake Resistor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.1. Managing the Keypad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.2. Operating Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.3. Changing Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.4. Read Only Parameter Access. . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.5. Resetting Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.6. Resetting a Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electromagnetic Compatibility
All Optidrives are designed with high standards of EMC in mind. All versions suitable for operation on Single Phase 230 volt and
Three Phase 400 volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter
is designed to reduce the conducted emissions back into the mains supply via the power cables for compliance with the above
harmonised European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the
EMC legislation of the country of use, and the relevant category. Within the European Union, equipment into which this product is
incorporated must comply with the EMC Directive 2004/108/EC. This User Guide provides guidance to ensure that the applicable
standards may be achieved.
2 Year Warranty
All Invertek Optidrive units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer
accepts no liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The
manufacturer also accepts no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation,
incorrect adjustment of the operating parameters of the drive, incorrect matching of the drive to the motor, incorrect installation,
unacceptable dust, moisture, corrosive substances, excessive vibration or ambient temperatures outside of the design specification.
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local
distributor should be contacted first.
This user guide is the “original instructions” document. All non-English versions are translations of the
“original instructions”.
The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of
continuous improvement, the manufacturer reserves the right to change the specification of the product or its performance or the
contents of the User Guide without notice.
This User Guide is for use with version 3.05 Firmware
User Guide Revision 2.00
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to
date information, the information contained in this User Guide should be used for guidance purposes only and does not form the part
of any contract.
This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance
or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated
equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before
working on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to
discharge to safe voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals
in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
training and experience. They must carefully read this safety The driven motor can start at power up if the enable input signal
information and the instructions in this Guide and follow all is present.
information regarding transport, storage, installation and use of
The STOP function does not remove potentially lethal high
the Optidrive, including the specified environmental limitations.
voltages. ISOLATE the drive and wait 10 minutes before starting
Do not perform any flash test or voltage withstand test on the any work on it. Never carry out any work on the Drive, Motor or
Optidrive. Any electrical measurements required should be Motor cable whilst the input power is still applied.
carried out with the Optidrive disconnected.
The Optidrive can be programmed to operate the driven motor
Electric shock hazard! Disconnect and ISOLATE the Optidrive at speeds above or below the speed achieved when connecting
before attempting any work on it. High voltages are present the motor directly to the mains supply. Obtain confirmation from
at the terminals and within the drive for up to 10 minutes after the manufacturers of the motor and the driven machine about
disconnection of the electrical supply. Always ensure by using a suitability for operation over the intended speed range prior to
1 suitable multimeter that no voltage is present on any drive power
terminals prior to commencing any work.
machine start up.
Do not activate the automatic fault reset function on any systems
Where supply to the drive is through a plug and socket whereby this may cause a potentially dangerous situation.
connector, do not disconnect until 10 minutes have elapsed after
IP20 drives must be installed in a pollution degree 2
turning off the supply.
environment, mounted in a cabinet with IP54 or better.
Ensure correct earthing connections. The earth cable must
Optidrives are intended for indoor use only.
be sufficient to carry the maximum supply fault current which
normally will be limited by the fuses or MCB. Suitably rated When mounting the drive, ensure that sufficient cooling is provided.
fuses or MCB should be fitted in the mains supply to the drive, Do not carry out drilling operations with the drive in place, dust
according to any local legislation or codes. and swarf from drilling may lead to damage.
Ensure correct earthing connections and cable selection as per The entry of conductive or flammable foreign bodies should be
defined by local legislation or codes. The drive may have a prevented. Flammable material should not be placed close to
leakage current of greater than 3.5mA; furthermore the earth the drive
cable must be sufficient to carry the maximum supply fault current Relative humidity must be less than 95% (non-condensing).
which normally will be limited by the fuses or MCB. Suitably Ensure that the supply voltage, frequency and no. of phases (1 or
rated fuses or MCB should be fitted in the mains supply to the 3 phase) correspond to the rating of the Optidrive as delivered.
drive, according to any local legislation or codes.
Never connect the mains power supply to the Output terminals
Do not carry out any work on the drive control cables whilst U, V, W.
power is applied to the drive or to the external control circuits.
Do not install any type of automatic switchgear between the
drive and the motor.
Wherever control cabling is close to power cabling, maintain
a minimum separation of 100 mm and arrange crossings
at 90 degrees. Ensure that all terminals are tightened to the
appropriate torque setting.
Do not attempt to carry out any repair of the Optidrive. In
the case of suspected fault or malfunction, contact your local
Invertek Drives Sales Partner for further assistance.
Quick Start Up
3.6. Guidelines for mounting (IP66 Units) 12
5 Select the correct power and motor cables according 9.2. Rating Tables 37
to local wiring regulations or code, noting the maximum
permissible sizes
6 If the supply type is IT or corner grounded, disconnect the 9.5. EMC Filter Disconnect 38
EMC filter before connecting the supply.
7 Check the supply cable and motor cable for faults or short
circuits.
8 Route the cables
9 Check that the intended motor is suitable for use, noting 4.10. EMC Compliant Installation 19
any precautions recommended by the supplier or 1
manufacturer.
10 Check the motor terminal box for correct Star or Delta 4.5. Motor Terminal Box Connections 16
configuration where applicable
11 Ensure wiring protection is providing, by installing a 4.3.2. Fuse / Circuit Breaker Selection 15
suitable circuit breaker or fuses in the incoming supply line
9.2. Rating Tables 37
12 Connect the power cables, especially ensuring the 4.1. Connection Diagram 14
protective earth connection is made 4.2. Protective Earth (PE) Connection 15
4.3. Incoming Power Connection 15
4.4. Motor Connection 16
13 Connect the control cables as required for the application 4.6. Control Terminal Wiring 16
4.10. EMC Compliant Installation 19
7. Analog and Digital Input Macro Configurations 31
7.8. Example Connection Diagrams 35
14 Thoroughly check the installation and wiring
15 Commission the drive parameters 5.1. Managing the Keypad 20
6. Parameters 22
Switch the mains power on to the unit using the built in isolator
switch on the front panel.
ODE - 3 - 1 2 0021 - 1 F 1 2
110 – 115V ± 10% - 1 Phase Input – 3 Phase 230V Output (Voltage Doubler)
Model Number Output Current
kW HP Frame Size
With Filter Without Filter (A)
Mechanical Installation
L1/L L2/N L3
Drive A B C D E F Weight
Size mm in mm in mm in mm in mm in mm in Kg Ib
1 173 6.81 83 3.27 123 4.84 162 6.38 50 1.97 50 1.97 1.0 1.0
2 221 8.70 110 4.33 150 5.91 209 8.23 63 2.48 63 2.48 1.7 1.7
3 261 10.28 131 5.16 175 6.89 247 9.72 80 3.15 80 3.15 3.2 3.2
4 420 16.54 171 6.73 212 8.35 400 15.75 125 4.92 125 4.92 9.1 9.1
X Y Z Recommended
Drive Size Above & Below Either Side Between airflow
mm in mm in mm in CFM (ft3/min)
1 50 1.97 50 1.97 33 1.30 11
2 75 2.95 50 1.97 46 1.81 22
3 100 3.94 50 1.97 52 2.05 60
4 100 3.94 50 1.97 52 2.05 120
Dimension Z assumes that the drives are mounted side-by-side with no clearance.
Typical drive heat losses are 3% of operating load conditions.
NOTE
Above are guidelines only and the operating ambient temperature of the drive MUST be
maintained at all times.
Mechanical Installation
Drive A B D E F G H I J Weight
Size mm in mm in mm in mm in mm in mm in mm in mm in mm in kg Ib
1 232.0 9.13 207.0 8.15 189.0 7.44 25.0 0.98 179.0 7.05 161.0 6.34 148.5 5.85 4.0 0.16 8.0 0.31 3.1 6.8
2 257.0 10.12 220.0 8.67 200.0 7.87 28.5 1.12 187.0 7.36 188.0 7.40 176.0 6.93 4.2 0.17 8.5 0.33 4.1 9.0
3 310.0 12.20 276.5 10.89 251.5 9.90 33.4 1.31 252 9.92 211.0 8.30 197.5 7.78 4.2 0.17 8.5 0.33 7.6 16.7
Drive X Above & Below Y Either Side Drive Cable Gland Sizes
Size mm in mm in Size Power Cable Motor Cable Control Cables
1 200 7.87 10 0.39 1 M20 (PG13.5) M20 (PG13.5) M20 (PG13.5)
2 200 7.87 10 0.39 2 M25 (PG21) M25 (PG21) M20 (PG13.5)
3 200 7.87 10 0.39 3 M25 (PG21) M25 (PG21) M20 (PG13.5)
Typical drive heat losses are approximately 3% of operating load conditions.
NOTE Above are guidelines only and the operating ambient temperature of the drive MUST be
maintained at all times.
UL rated ingress protection ("Type" ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible-
conduit system which meets the required level of protection ("Type").
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC.
Not intended for installation using rigid conduit system.
Mechanical Installation
3.8. Removing the Terminal Cover
To access the connection terminals, the drive front cover needs to be removed as shown.
M
Power & Control Wiring
Safety Ground
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel
(girder, joist), a floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/
or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
The motor should be connected to the Optidrive U, V, and W terminals using a suitable 3 or 4 core cable. Where a 3 core cable
is utilised, with the shield operating as an earth conductor, the shield must have a cross sectional area at least equal to the phase
conductors when they are made from the same material. Where a 4 core cable is utilised, the earth conductor must be of at least
equal cross sectional area and manufactured from the same material as the phase conductors.
The motor earth must be connected to one of the Optidrive earth terminals.
Maximum permitted motor cable length for all models: 100 metres shielded, 150 metres unshielded.
Where multiple motors are connected to a single drive using parallel cables, an output choke must be installed.
4 Delta
400 400 / 690
Parameters
Switch Position to Set Notes
P-12 P-15
Factory Default Configuration
Run Reverse STOP Run Forward 0 0
Run Forward or Reverse with speed controlled from the Local POT
Run forward with speed controlled form the local POT
STOP STOP Run Forward 0 5,7
Run Reverse - disabled
Run Forward with speed controlled from the Local POT
Preset Speed 1 STOP Run Forward 0 1
Preset Speed 1 provides a ‘Jog’ Speed set in P-20
Run Reverse STOP Run Forward 0 6, 8 Run Forward or Reverse with speed controlled from the Local POT
Run in Hand – Speed controlled from the Local POT
Run in Auto STOP Run in Hand 0 4 Run in Auto 0 Speed controlled using Analog input 2 e.g. from
PLC with 4-20mA signal.
Run in Speed In Speed Control the speed is controlled from the Local POT
STOP Run in PI Control 5 1
Up to four digital inputs are available. The function of the inputs is defined by parameters P-12 and P-15, which are explained in
section 7. Analog and Digital Input Macro Configurations on page 31.
Suitable resistors and guidance on selection can be obtained from your Invertek Sales Partner.
Drive Stopped / Drive is enabled Press the Navigate Press the Navigate If P-10 > 0, pressing
Disabled / running, display key for < 1 second. key for < 1 second. the Navigate key
shows the output The display will The display will for < 1 second will
frequency (Hz) show the motor show the motor display the motor
Operation
5
Press and hold the Use the up and Press the Navigate Adjust the value Press for < 1 second Press for > 2
Navigate key > 2 down keys to key for < 1 second using the Up and to return to the seconds to return
seconds select the required Down keys parameter menu to the operating
parameter display