0% found this document useful (0 votes)
8 views

Design Load Reports

The document provides a detailed sizing summary for the L1-FCU-SYSTEM at Mecca Tower, including air system information, cooling coil sizing, humidifier data, and ventilation fan specifications. It outlines the peak loads for various zones, along with airflow rates and heating requirements. The analysis is tailored for the climate conditions in Makkah, Saudi Arabia, and includes both cooling and heating load calculations for multiple zones within the building.

Uploaded by

ahmed elgaml
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views

Design Load Reports

The document provides a detailed sizing summary for the L1-FCU-SYSTEM at Mecca Tower, including air system information, cooling coil sizing, humidifier data, and ventilation fan specifications. It outlines the peak loads for various zones, along with airflow rates and heating requirements. The analysis is tailored for the climate conditions in Makkah, Saudi Arabia, and includes both cooling and heating load calculations for multiple zones within the building.

Uploaded by

ahmed elgaml
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

DOAS Sizing Summary for L1-FCU-SYSTEM

(In Alternative: Plant-HVAC)


Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Air System Information
Air System Name L1-FCU-SYSTEM Number of zones 8
Equipment Class TERM Floor Area 34504.1 sqft
Air System Type 2P-FC Location Makkah, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data User-Modified Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 7.3 Tons Load occurs at June 15:00
Total coil load 87.2 MBH OA DB / WB 112.3 / 75.9 F
Total coil load 147.8 CFM/Ton Entering DB / WB 96.6 / 71.7 F
Sensible coil load 60.6 MBH Leaving DB / WB 44.0 / 44.0 F
Coil CFM at June 15:00 1074 CFM
Max coil CFM 1074 CFM
Sensible heat ratio 0.696
Water flow @ 10.0 F rise 17.45 gpm

Humidifier Sizing Data


No peak time 0.00 lb/hr Air mass flow 0.00 lb/hr
Airflow Rate 0 CFM Moisture gain .00000 lb/lb

Dehumidification Reheat Coil Sizing Data


Max coil load 11.0 MBH Load occurs at June 5:00
Coil CFM at June 5:00 1074 CFM BTU/(hr sqft) 0.3
Max coil CFM 1074 CFM Ent. DB / Lvg DB 45.4 / 55.0 F
Water flow @ 20.0 F drop N/A

Ventilation Fan Sizing Data


Design CFM 1074 CFM Fan motor BHP 0.59 BHP
Design CFM/sqft 0.03 CFM/sqft Fan motor kW 0.47 kW
Fan total static 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 1074 CFM CFM/person 5.34 CFM/person
CFM/sqft 0.03 CFM/sqft

Hourly Analysis Program 6.2 Page 1 of 15


Zone Sizing Summary for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Air System Information
Air System Name L1-FCU-SYSTEM Number of zones 8
Equipment Class TERM Floor Area 34504.1 sqft
Air System Type 2P-FC Location Makkah, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data User-Modified Space CFM Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.0 F Peak Coil Zone
Zone Name (MBH) (MBH) (F) (F) (gpm) Load CFM/sqft
Zone- Low/High zone-passanger lobby 47.1 47.1 119.6 / 78.4 82.8 / 68.5 9.44 July 16:00 0.09
Zone- Potential Apartment 7.8 7.6 109.1 / 78.0 76.3 / 68.9 1.55 July 19:00 0.14
Zone1 39.1 38.9 80.2 / 65.0 63.6 / 59.2 7.83 June 16:00 0.62
Zone2 34.8 34.4 77.1 / 63.4 62.1 / 58.0 6.96 June 17:00 0.82
Zone3 38.1 37.6 79.6 / 64.7 63.4 / 59.0 7.61 July 17:00 0.67
Zone4 39.5 37.5 80.0 / 65.1 63.0 / 58.9 7.91 July 17:00 0.62
Zone5 45.2 43.8 79.8 / 64.8 63.1 / 58.9 9.05 August 17:00 0.63
Zone-AHU 11.0 10.9 113.2 / 79.5 78.2 / 70.3 2.21 July 19:00 0.12

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 F Airflow Motor Motor Airflow
Zone Name (MBH) (F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone- Low/High zone-passanger lobby 12.5 68.2 / 78.1 1.25 1193 0.088 0.070 0
Zone- Potential Apartment 1.3 68.2 / 73.8 0.13 215 0.016 0.013 0
Zone1 9.4 66.7 / 70.7 0.94 2182 0.161 0.128 253
Zone2 7.5 66.7 / 70.0 0.75 2140 0.158 0.126 246
Zone3 7.9 66.7 / 70.2 0.79 2161 0.160 0.127 244
Zone4 6.4 67.3 / 70.2 0.64 2049 0.151 0.120 145
Zone5 8.5 67.2 / 70.4 0.85 2450 0.181 0.144 187
Zone-AHU 1.7 68.2 / 73.8 0.17 288 0.021 0.017 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone- Low/High zone-passanger lobby 150.3 July 15:00 12.8 13983.5
Zone- Potential Apartment 14.5 August 15:00 1.3 1532.4
Zone1 67.8 June 15:00 5.7 3546.9
Zone2 62.9 June 15:00 4.1 2618.7
Zone3 72.6 June 15:00 4.5 3246.0
Zone4 69.1 June 15:00 4.3 3284.1
Zone5 84.0 March 15:00 5.8 3916.4
Zone-AHU 21.4 August 15:00 1.8 2376.1

Hourly Analysis Program 6.2 Page 2 of 15


Zone Sizing Summary for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name (MBH) Load (CFM) (MBH) (sqft) CFM/sqft
Zone- Low/High zone-passanger lobby
100-02-Formal Living 8.1 June 15:00 484 0.7 430.5 1.12
unnamed space (1) 142.4 July 15:00 8477 12.2 13552.9 0.63
Zone- Potential Apartment
unnamed space (7) 14.5 August 15:00 863 1.3 1532.4 0.56
Zone1
100-01-Bedroom-01 14.5 June 9:00 862 1.4 564.3 1.53
100-01-Bedroom-01-Dressing 7.9 March 9:00 470 0.4 184.1 2.55
100-01-Bedroom-01-Ensuite 4.6 March 9:00 275 0.3 161.2 1.70
100-01-Bedroom-02 (1) 5.8 June 15:00 343 0.5 244.1 1.41
100-01-Bedroom-02-Ensuite 1.0 July 14:00 58 0.0 63.9 0.92
100-01-Bedroom-03 5.9 June 16:00 349 0.5 255.5 1.37
100-01-Bedroom-03-Ensuite 1.0 July 15:00 57 0.0 61.8 0.93
100-01-Bedroom-Ensuite 0.9 July 14:00 54 0.0 55.8 0.98
100-01-Bedroom-Staff 1.2 July 14:00 73 0.1 122.7 0.60
100-01-BOH 1.3 July 15:00 76 0.1 128.3 0.59
100-01-Corridor-Family-Living 1.2 July 15:00 74 0.1 124.4 0.60
100-01-Dining 7.8 June 15:00 464 0.6 387.6 1.20
100-01-Family Living 9.2 June 15:00 547 0.8 563.2 0.97
100-01-Formal Living 7.6 June 15:00 455 0.6 368.5 1.23
100-01-Foyer 1.3 July 14:00 80 0.1 135.7 0.59
100-01-Foyer BOH 0.5 July 14:00 30 0.0 33.7 0.89
100-01-Foyer-WC 1.0 July 15:00 58 0.1 92.1 0.63
Zone2
100-01-Foyer-WC-1 0.7 July 15:00 41 0.0 75.4 0.54
100-02-Bedroom Dressing 1.0 July 14:00 58 0.0 62.6 0.92
100-02-Bedroom-01 9.4 April 15:00 561 0.6 344.4 1.63
100-02-Bedroom-01-Ensuite 1.6 July 15:00 97 0.1 144.1 0.67
100-02-Bedroom-02 9.0 April 15:00 537 0.6 276.2 1.95
100-02-Bedroom-02-Ensuite 0.9 July 14:00 55 0.0 57.3 0.96
100-02-Bedroom-03 8.8 April 15:00 526 0.5 250.3 2.10
100-02-Bedroom-03-Ensuite 1.0 July 15:00 60 0.0 66.2 0.90
100-02-Bedroom-Ensuite 0.8 July 14:00 49 0.0 44.3 1.11
100-02-Bedroom-Staff 0.6 July 15:00 37 0.0 47.0 0.78
100-02-BOH 1.5 July 14:00 89 0.1 155.2 0.57
100-02-BOH-1 1.1 July 15:00 63 0.1 101.6 0.62
100-02-Corridor 2.0 July 15:00 121 0.1 193.4 0.63
100-02-Dining 7.7 June 15:00 456 0.6 371.9 1.23
100-02-Family Living 17.5 June 16:00 1044 1.2 429.0 2.43
Zone3
100-03-Bedroom-01 9.8 April 15:00 585 0.7 399.8 1.46
100-03-Bedroom-01-Dressing 1.2 July 15:00 71 0.1 90.4 0.79
100-03-Bedroom-01-Ensuite 1.8 July 15:00 109 0.1 167.9 0.65
100-03-Bedroom-02 8.8 April 15:00 526 0.5 253.0 2.08
100-03-Bedroom-02-Ensuite 1.0 July 14:00 60 0.0 66.3 0.90
100-03-Bedroom-03 8.8 April 15:00 524 0.5 249.4 2.10
100-03-Bedroom-03-Ensuite 1.0 July 15:00 58 0.0 62.5 0.92
100-03-Bedroom-Ensuite 1.0 July 14:00 58 0.0 64.0 0.91
100-03-Bedroom-Staff 0.7 July 15:00 43 0.0 61.2 0.71
100-03-BOH 1.3 July 15:00 80 0.1 135.8 0.59
100-03-Corridor 3.4 July 14:00 202 0.2 357.1 0.56
100-03-Dining and Living 21.0 June 16:00 1250 1.4 784.2 1.59
100-03-Famiily Living 10.1 April 15:00 601 0.6 307.2 1.96
100-03-FAmily Living 2.9 July 14:00 170 0.1 181.5 0.94
100-03-Foyer-WC 0.8 July 15:00 46 0.0 65.7 0.69
Zone4
100-04-Bedroom-01 10.1 April 15:00 603 0.7 450.8 1.34
100-04-Bedroom-01-Dressig 1.2 July 15:00 72 0.0 92.0 0.78
100-04-Bedroom-01-Ensuite 1.7 July 15:00 99 0.1 147.3 0.67

Hourly Analysis Program 6.2 Page 3 of 15


Zone Sizing Summary for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name (MBH) Load (CFM) (MBH) (sqft) CFM/sqft
100-04-Bedroom-02 8.8 April 15:00 524 0.5 241.9 2.17
100-04-Bedroom-02-Ensuite 1.0 July 14:00 57 0.0 61.4 0.93
100-04-Bedroom-03 8.8 April 15:00 523 0.5 236.3 2.21
100-04-Bedroom-03-Ensuite 0.9 July 14:00 56 0.0 59.1 0.95
100-04-BOH 0.5 June 15:00 29 0.0 114.6 0.25
100-04-Corridor 2.8 July 14:00 164 0.1 280.1 0.59
100-04-Living 10.0 April 15:00 598 0.6 296.8 2.02
100-04-Living-Dining 20.2 June 16:00 1202 1.5 834.1 1.44
Combined unnamed space (13) and
Combined 100-04-Foyer-WC and unnamed 1.0 July 15:00 59 0.0 79.7 0.74
space (17)
Combined unnamed space (4) and
Combined unnamed space (20) and 100-04- 1.4 July 14:00 83 0.1 138.3 0.60
Foyer
unnamed space (10) 1.0 July 15:00 61 0.0 141.7 0.43
unnamed space (6) 0.7 July 15:00 42 0.0 110.1 0.38
Zone5
100-05-Bedroom-01 17.5 December 14:00 1040 1.1 390.0 2.67
100-05-Bedroom-01-Dressing 1.5 July 15:00 89 0.1 127.3 0.70
100-05-Bedroom-01-Ensuite 7.3 December 13:00 434 0.4 170.3 2.55
100-05-Bedroom-02 8.7 April 15:00 517 0.5 231.9 2.23
100-05-Bedroom-02-Ensuite 0.9 July 14:00 56 0.0 57.8 0.96
100-05-Bedroom-Ensuite 0.9 July 14:00 56 0.0 59.2 0.95
100-05-Bedroom-Staff 0.8 July 15:00 46 0.0 67.0 0.69
100-05-Corridor 1.1 July 15:00 64 0.0 75.5 0.85
100-05-Corridor family living-1 2.2 July 14:00 133 0.1 105.6 1.26
100-05-Foyer 1.5 July 14:00 89 0.1 154.2 0.57
100-05Foyer BOH 1.6 July 14:00 98 0.1 172.6 0.57
100-05-Foyer WC 1.4 July 14:00 81 0.1 138.6 0.58
100-05-Living 12.8 April 15:00 761 0.9 684.3 1.11
Combined 100-05-Bedroom-03 and 100- 12.4 January 15:00 741 0.8 369.9 2.00
05-Bedroom-03-Ensuite (1)
Combined 100-05-Bedroom-03 and 100-
1.0 July 14:00 58 0.0 75.4 0.77
05-Bedroom-03-Ensuite (2)
Combined unnamed space (3) and 100- 19.1 April 15:00 1137 1.5 1036.8 1.10
05-Dining and Living
Zone-AHU
unnamed space (8) 21.4 August 15:00 1274 1.8 2376.1 0.54

Hourly Analysis Program 6.2 Page 4 of 15


Ventilation Sizing Summary for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

No data is available for this report. Space by space ventilation calculations were not performed for this air system because it uses the 'user-defined' sizing option. With this option the system
outdoor ventilation air flow is specified directly by the user. Therefore, space-by-space calculations are not performed.

Hourly Analysis Program 6.2 Page 5 of 15


Air System Heat Balance Summary for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

Table 1. System Loads


DESIGN COOLING - JULY 17:00 DESIGN HEATING
OA DB / WB 109.8 F / 75.0 F OA DB / WB 61.3 F / 51.2 F
Sensible Latent Sensible Latent
COMPONENT LOADS Details Details
[BTU/hr] [BTU/hr] [BTU/hr] [BTU/hr]
Zone Conditioning - 286522 25063 - 42866 0
Plenum Load - 0 0 - 0 0
Exhaust Fan Load 1074 CFM 0 - 1074 CFM 0 -
Ventilation Load 1074 CFM 15662 4252 1074 CFM 7555 0
Ventilation Fan Load 1074 CFM 1593 - 1074 CFM -1593 -
Zone Fan Coil Fans Load - 2537 - - -2536 -
>> Total System Loads - 306313 29315 - 46292 0
Cooling Coil - 59558 25365 - -8791 0
Terminal Unit Cooling - 257411 4764 - 0 0
Terminal Unit Heating - 0 - - 55184 -
Dehumidification Reheat Coil - -10967 - - 0 -
Humidification 0.00 lb/hr 0 0 0.00 lb/hr 0 0
>> Total Conditioning - 306002 30129 - 46393 0
Positive values are cooling loads Positive values are heating loads
Key:
Negative values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads


DESIGN COOLING - JULY 17:00 DESIGN HEATING
OA DB / WB 109.8 F / 75.0 F OA DB / WB 61.3 F / 51.2 F
Sensible Latent Sensible Latent
Zone Heat Balance Component Details Details
[BTU/hr] [BTU/hr] [BTU/hr] [BTU/hr]
Exterior Wall Convection 7279 sqft 18341 - 7279 sqft 2094 -
Roof Convection 34504 sqft 113037 - 34504 sqft 7924 -
Window Convection 5581 sqft 60598 - 5581 sqft 4603 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 0 sqft 0 - 0 sqft 0 -
Floor Convection 34504 sqft 54175 - 34504 sqft 8065 -
Interior Wall Convection 65314 sqft 78189 - 65314 sqft 5881 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 23318 W 49703 - 0W 0 -
Task Lighting Convection 0W 0 - 0W 0 -
Electric Equipment Convection 17373 W 44459 - 0W 0 -
People Convection 201 13955 25735 0 0 0
Infiltration 1487 CFM 61498 40075 1639 CFM 11688 -5588
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 493955 65810 - 40254 -5588
Positive values are cooling loads Positive values are heating loads
Key: Negative values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed
at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The
radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room
air. Therefore, the effect of solar heat gain is found in the surface convection line items.

Hourly Analysis Program 6.2 Page 6 of 15


Hourly Air System Design Day Loads for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

DESIGN MONTH: JULY


Terminal
DOAS DOAS Dehumid. Terminal Heating
OA DOAS Heating Cooling Reheat Cooling Coil
Temp Airflow Coil Coil Coil Coil Sensible
Hour (F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH)
00:00 92.6 1074 0.0 72.7 11.0 241.9 0.0
01:00 91.0 1074 0.0 71.6 11.0 240.1 0.0
02:00 90.0 1074 0.0 70.8 11.0 238.4 0.0
03:00 89.3 1074 0.0 70.2 11.0 236.9 0.0
04:00 88.5 1074 0.0 69.6 11.0 235.4 0.0
05:00 88.0 1074 0.0 69.3 11.0 234.1 0.0
06:00 88.5 1074 0.0 69.6 11.0 233.5 0.0
07:00 90.3 1074 0.0 70.9 11.0 234.1 0.0
08:00 94.6 1074 0.0 73.6 11.0 235.7 0.0
09:00 99.4 1074 0.0 76.7 11.0 238.1 0.0
10:00 103.7 1074 0.0 79.5 11.0 240.7 0.0
11:00 107.5 1074 0.0 81.8 11.0 243.2 0.0
12:00 110.0 1074 0.0 83.5 11.0 245.4 0.0
13:00 112.0 1074 0.0 85.0 11.0 248.6 0.0
14:00 113.3 1074 0.0 86.2 11.0 253.2 0.0
15:00 113.3 1074 0.0 86.6 11.0 257.9 0.0
16:00 111.8 1074 0.0 86.1 11.0 261.3 0.0
17:00 109.8 1074 0.0 84.9 11.0 262.2 0.0
18:00 107.2 1074 0.0 83.0 11.0 259.7 0.0
19:00 103.4 1074 0.0 80.5 11.0 255.4 0.0
20:00 100.7 1074 0.0 78.4 11.0 251.6 0.0
21:00 98.4 1074 0.0 76.7 11.0 248.7 0.0
22:00 96.1 1074 0.0 75.2 11.0 246.3 0.0
23:00 94.3 1074 0.0 73.9 11.0 244.2 0.0

Hourly Analysis Program 6.2 Page 7 of 15


Hourly Zone Loads for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

ZONE: Zone- Low/High zone-passanger lobby


DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 116.6 18 1193 107549 45469 45770 0 0
01:00 91.0 116.3 18 1193 104870 45326 45623 0 0
02:00 90.0 116.0 18 1193 102735 45199 45490 0 0
03:00 89.3 115.8 18 1193 100985 45083 45370 0 0
04:00 88.5 115.6 18 1193 99470 44971 45256 0 0
05:00 88.0 115.4 18 1193 98442 44875 45151 0 0
06:00 88.5 115.3 18 1193 98843 44829 45082 0 0
07:00 90.3 115.3 18 1193 101445 44856 45074 0 0
08:00 94.6 115.5 18 1193 107769 45009 45175 0 0
09:00 99.4 116.0 18 1193 116639 45255 45385 0 0
10:00 103.7 116.5 18 1193 126194 45556 45665 0 0
11:00 107.5 117.2 17 1193 134513 45883 45984 0 0
12:00 110.0 117.8 17 1193 141363 46193 46301 0 0
13:00 112.0 118.4 17 1193 146601 46484 46601 0 0
14:00 113.3 118.9 17 1193 149705 46729 46869 0 0
15:00 113.3 119.3 16 1193 150280 46884 47066 0 0
16:00 111.8 119.4 16 1193 148168 46916 47150 0 0
17:00 109.8 119.3 16 1193 143772 46853 47126 0 0
18:00 107.2 119.0 16 1193 137395 46705 47013 0 0
19:00 103.4 118.6 17 1193 129828 46484 46819 0 0
20:00 100.7 118.2 17 1193 123661 46282 46606 0 0
21:00 98.4 117.8 17 1193 118395 46097 46414 0 0
22:00 96.1 117.5 17 1193 114098 45922 46233 0 0
23:00 94.3 117.2 17 1193 110643 45765 46069 0 0

ZONE: Zone- Potential Apartment


DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 107.8 26 215 11181 7391 7665 0 0
01:00 91.0 107.6 26 215 10921 7369 7648 0 0
02:00 90.0 107.5 26 215 10683 7348 7631 0 0
03:00 89.3 107.3 27 215 10472 7327 7612 0 0
04:00 88.5 107.2 27 215 10289 7306 7594 0 0
05:00 88.0 107.0 27 215 10129 7286 7575 0 0
06:00 88.5 106.8 27 215 9997 7268 7557 0 0
07:00 90.3 106.7 27 215 9991 7253 7540 0 0
08:00 94.6 106.7 27 215 10263 7250 7529 0 0
09:00 99.4 106.7 27 215 10872 7266 7528 0 0
10:00 103.7 107.0 27 215 11730 7301 7541 0 0
11:00 107.5 107.3 26 215 12661 7350 7567 0 0
12:00 110.0 107.7 26 215 13473 7407 7602 0 0
13:00 112.0 108.0 26 215 14004 7461 7640 0 0
14:00 113.3 108.4 26 215 14323 7506 7678 0 0
15:00 113.3 108.7 25 215 14429 7539 7711 0 0
16:00 111.8 108.8 25 215 14341 7559 7737 0 0
17:00 109.8 108.9 25 215 14072 7566 7755 0 0
18:00 107.2 108.9 25 215 13659 7560 7764 0 0
19:00 103.4 108.9 26 215 13146 7543 7764 0 0
20:00 100.7 108.7 26 215 12586 7519 7757 0 0
21:00 98.4 108.6 26 215 12139 7494 7745 0 0
22:00 96.1 108.4 26 215 11779 7470 7731 0 0
23:00 94.3 108.2 26 215 11464 7447 7716 0 0

Hourly Analysis Program 6.2 Page 8 of 15


Hourly Zone Loads for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

ZONE: Zone1
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 79.6 46 2182 36328 40940 35856 0 0
01:00 91.0 79.2 47 2182 35119 40500 35553 0 0
02:00 90.0 78.9 47 2182 34171 40096 35271 0 0
03:00 89.3 78.6 47 2182 33391 39723 35012 0 0
04:00 88.5 78.3 48 2182 32697 39370 34769 0 0
05:00 88.0 78.1 48 2182 32714 39090 34543 0 0
06:00 88.5 78.4 47 2182 38805 39569 34618 0 0
07:00 90.3 79.0 46 2182 46986 40510 35066 0 0
08:00 94.6 79.8 45 2182 54487 41616 35730 0 0
09:00 99.4 80.6 45 2182 59596 42612 36403 0 0
10:00 103.7 81.2 44 2182 61829 43422 36993 0 0
11:00 107.5 81.6 44 2182 61427 43845 37400 0 0
12:00 110.0 81.8 44 2182 60847 44117 37616 0 0
13:00 112.0 82.1 43 2182 63174 44810 37924 0 0
14:00 113.3 82.5 43 2182 65398 45328 38318 0 0
15:00 113.3 82.9 43 2182 66560 45912 38683 0 0
16:00 111.8 83.1 42 2182 65609 45989 38925 0 0
17:00 109.8 83.0 42 2182 61514 45683 38928 0 0
18:00 107.2 82.6 43 2182 54319 44844 38554 0 0
19:00 103.4 81.8 44 2182 46644 43803 37951 0 0
20:00 100.7 81.2 44 2182 43446 43070 37381 0 0
21:00 98.4 80.7 45 2182 41166 42473 36937 0 0
22:00 96.1 80.3 45 2182 39271 41933 36549 0 0
23:00 94.3 79.9 46 2182 37720 41441 36201 0 0

ZONE: Zone2
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 75.3 51 2140 28308 34667 30942 0 0
01:00 91.0 74.9 51 2140 27334 34234 30636 0 0
02:00 90.0 74.6 52 2140 26564 33840 30356 0 0
03:00 89.3 74.3 52 2140 25932 33478 30100 0 0
04:00 88.5 74.0 52 2140 25370 33138 29862 0 0
05:00 88.0 73.8 53 2140 25090 32843 29641 0 0
06:00 88.5 73.8 53 2140 26955 32872 29551 0 0
07:00 90.3 73.9 52 2140 29732 33143 29647 0 0
08:00 94.6 74.3 52 2140 33151 33611 29889 0 0
09:00 99.4 74.7 51 2140 36730 34205 30238 0 0
10:00 103.7 75.2 50 2140 39877 34831 30644 0 0
11:00 107.5 75.7 50 2140 42302 35422 31050 0 0
12:00 110.0 76.1 49 2140 44441 35976 31418 0 0
13:00 112.0 76.9 48 2140 50587 37054 31970 0 0
14:00 113.3 77.9 47 2140 57590 38719 32849 0 0
15:00 113.3 78.9 46 2140 62159 39957 33799 0 0
16:00 111.8 79.6 46 2140 62358 40661 34480 0 0
17:00 109.8 79.6 46 2140 56385 40307 34682 0 0
18:00 107.2 78.9 46 2140 46231 39133 34164 0 0
19:00 103.4 77.8 48 2140 36980 37721 33327 0 0
20:00 100.7 77.1 49 2140 34104 36868 32587 0 0
21:00 98.4 76.5 49 2140 32224 36221 32073 0 0
22:00 96.1 76.1 50 2140 30686 35657 31652 0 0
23:00 94.3 75.7 50 2140 29430 35156 31287 0 0

Hourly Analysis Program 6.2 Page 9 of 15


Hourly Zone Loads for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

ZONE: Zone3
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 78.2 48 2161 33174 38611 34336 0 0
01:00 91.0 77.8 48 2161 32067 38176 34030 0 0
02:00 90.0 77.5 49 2161 31178 37777 33748 0 0
03:00 89.3 77.2 49 2161 30434 37410 33489 0 0
04:00 88.5 77.0 49 2161 29788 37064 33248 0 0
05:00 88.0 76.7 50 2161 29390 36755 33023 0 0
06:00 88.5 76.6 50 2161 30687 36672 32886 0 0
07:00 90.3 76.7 49 2161 33326 36843 32911 0 0
08:00 94.6 77.0 49 2161 37000 37252 33096 0 0
09:00 99.4 77.4 48 2161 40963 37807 33409 0 0
10:00 103.7 77.8 48 2161 44443 38398 33784 0 0
11:00 107.5 78.3 47 2161 47211 38964 34167 0 0
12:00 110.0 78.7 47 2161 49845 39521 34523 0 0
13:00 112.0 79.5 46 2161 57765 40713 35111 0 0
14:00 113.3 80.7 44 2161 66725 42462 36054 0 0
15:00 113.3 81.7 44 2161 72378 43957 37091 0 0
16:00 111.8 82.4 43 2161 72507 44660 37849 0 0
17:00 109.8 82.5 43 2161 65254 44251 38051 0 0
18:00 107.2 81.7 44 2161 53486 43084 37534 0 0
19:00 103.4 80.7 45 2161 43151 41671 36713 0 0
20:00 100.7 80.0 46 2161 39823 40817 35986 0 0
21:00 98.4 79.4 46 2161 37651 40172 35474 0 0
22:00 96.1 79.0 47 2161 35888 39610 35053 0 0
23:00 94.3 78.6 47 2161 34450 39109 34687 0 0

ZONE: Zone4
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 77.5 49 2049 30000 35898 35750 0 0
01:00 91.0 77.2 50 2049 28886 35495 35425 0 0
02:00 90.0 76.8 50 2049 27943 35126 35125 0 0
03:00 89.3 76.6 50 2049 27189 34785 34849 0 0
04:00 88.5 76.3 51 2049 26541 34463 34591 0 0
05:00 88.0 76.0 51 2049 26143 34174 34350 0 0
06:00 88.5 75.9 51 2049 27514 34095 34201 0 0
07:00 90.3 76.0 51 2049 30253 34249 34220 0 0
08:00 94.6 76.3 51 2049 33822 34617 34404 0 0
09:00 99.4 76.7 50 2049 37675 35117 34720 0 0
10:00 103.7 77.1 49 2049 41082 35650 35104 0 0
11:00 107.5 77.5 49 2049 43789 36161 35497 0 0
12:00 110.0 77.9 48 2049 46396 36669 35866 0 0
13:00 112.0 78.8 47 2049 54294 37778 36483 0 0
14:00 113.3 79.9 46 2049 63215 39232 37459 0 0
15:00 113.3 81.0 45 2049 68840 40509 38483 0 0
16:00 111.8 81.7 44 2049 68973 41238 39252 0 0
17:00 109.8 81.7 44 2049 61753 41072 39513 0 0
18:00 107.2 80.9 45 2049 50054 40000 39056 0 0
19:00 103.4 79.9 47 2049 39804 38688 38232 0 0
20:00 100.7 79.2 47 2049 36520 37916 37486 0 0
21:00 98.4 78.7 48 2049 34377 37330 36952 0 0
22:00 96.1 78.3 48 2049 32651 36817 36508 0 0
23:00 94.3 77.9 49 2049 31246 36357 36122 0 0

Hourly Analysis Program 6.2 Page 10 of 15


Hourly Zone Loads for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

ZONE: Zone5
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 77.3 49 2450 35585 42201 40678 0 0
01:00 91.0 76.9 49 2450 34228 41704 40288 0 0
02:00 90.0 76.6 50 2450 33125 41250 39928 0 0
03:00 89.3 76.3 50 2450 32211 40832 39598 0 0
04:00 88.5 76.0 50 2450 31423 40437 39290 0 0
05:00 88.0 75.7 51 2450 30950 40085 39004 0 0
06:00 88.5 75.7 51 2450 32760 40021 38838 0 0
07:00 90.3 75.8 51 2450 36340 40277 38897 0 0
08:00 94.6 76.1 50 2450 41223 40824 39176 0 0
09:00 99.4 76.6 49 2450 46403 41547 39629 0 0
10:00 103.7 77.1 49 2450 50765 42305 40165 0 0
11:00 107.5 77.6 48 2450 54224 43025 40708 0 0
12:00 110.0 78.1 48 2450 57369 43717 41212 0 0
13:00 112.0 78.9 46 2450 65625 45022 41957 0 0
14:00 113.3 80.0 45 2450 74440 46641 43045 0 0
15:00 113.3 81.0 44 2450 79426 47996 44136 0 0
16:00 111.8 81.5 44 2450 78487 48678 44901 0 0
17:00 109.8 81.5 44 2450 70388 48371 45092 0 0
18:00 107.2 80.7 45 2450 58167 47111 44533 0 0
19:00 103.4 79.8 46 2450 47663 45616 43592 0 0
20:00 100.7 79.0 47 2450 43824 44679 42739 0 0
21:00 98.4 78.5 47 2450 41141 43957 42108 0 0
22:00 96.1 78.1 48 2450 38932 43325 41579 0 0
23:00 94.3 77.6 48 2450 37157 42758 41117 0 0

ZONE: Zone-AHU
DESIGN MONTH: JULY
OA Zone Zone Sensible Zone Sensible Terminal Terminal Zone Heating
Temp Temp RH Zone Airflow Load Conditioning Cooling Coil Heating Coil Unit
Hour (F) (F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
00:00 92.6 111.9 24 288 16596 10612 10905 0 0
01:00 91.0 111.7 24 288 16252 10586 10886 0 0
02:00 90.0 111.6 24 288 15936 10560 10866 0 0
03:00 89.3 111.5 25 288 15657 10535 10845 0 0
04:00 88.5 111.3 25 288 15416 10511 10824 0 0
05:00 88.0 111.2 25 288 15206 10487 10803 0 0
06:00 88.5 111.1 25 288 15034 10465 10782 0 0
07:00 90.3 110.9 25 288 15048 10448 10763 0 0
08:00 94.6 110.9 25 288 15455 10445 10750 0 0
09:00 99.4 111.0 25 288 16330 10465 10750 0 0
10:00 103.7 111.2 25 288 17537 10509 10766 0 0
11:00 107.5 111.5 24 288 18831 10572 10797 0 0
12:00 110.0 111.8 24 288 19989 10642 10839 0 0
13:00 112.0 112.2 24 288 20817 10711 10886 0 0
14:00 113.3 112.5 24 288 21234 10770 10932 0 0
15:00 113.3 112.8 24 288 21370 10814 10973 0 0
16:00 111.8 112.9 24 288 21227 10841 11006 0 0
17:00 109.8 113.0 24 288 20816 10850 11028 0 0
18:00 107.2 113.0 24 288 20119 10843 11040 0 0
19:00 103.4 113.0 24 288 19278 10820 11040 0 0
20:00 100.7 112.8 24 288 18495 10790 11032 0 0
21:00 98.4 112.7 24 288 17877 10758 11018 0 0
22:00 96.1 112.5 24 288 17390 10728 11002 0 0
23:00 94.3 112.4 24 288 16971 10699 10985 0 0

Hourly Analysis Program 6.2 Page 11 of 15


System Psychrometrics for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

DESIGN COOLING DAY AT JULY 17:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 109.5 0.01124 1074 400 15662 4252
Air-to-Air Energy Recovery Outlet 95.6 0.01124 1074 400 16000 0
Vent - Return Mixing Outlet 95.6 0.01124 1074 400 - -
Vent. Cooling Coil Outlet 44.0 0.00625 1074 400 59558 25365
Ventilation Fan Outlet 45.4 0.00625 1074 400 1593 -
Humidifier Outlet 45.4 0.00625 1074 400 0 0
Dehumid. Reheat Coil Outlet 55.0 0.00625 1074 400 10967 -
Cold Supply Duct Outlet 55.0 0.00625 1074 400 0 -
Zone Air - 100.3 0.01152 1074 1810 286522 25063
Return Air Outlet 81.7 0.01038 1074 1282 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.050 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4613.2 BTU/(hr-CFM)
Site Altitude = 787.0 ft

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone- Low/High zone-
passanger lobby ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 119.5 0.01206 1193 628 - -
Cooling Coil Outlet - 82.8 0.01206 1193 628 47126 0
Heating Coil Inlet - 82.8 0.01206 1193 628 - -
Heating Coil Outlet - 82.8 0.01206 1193 628 0 -
Zone Air - 119.3 0.01206 1193 628 46853 -
Zone- Potential Apartment (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 109.1 0.01400 215 10284 - -
Cooling Coil Outlet - 76.3 0.01385 215 10284 7607 148
Heating Coil Inlet - 76.3 0.01385 215 10284 - -
Heating Coil Outlet - 76.3 0.01385 215 10284 0 -
Zone Air - 108.9 0.01400 215 10289 7566 -
Zone1 ( Cooling )
Ventilation Air - - - 253 - - -
Cooling Coil Inlet - 80.0 0.01002 2182 1139 - -
Cooling Coil Outlet - 63.5 0.00999 2182 1139 38601 328
Heating Coil Inlet - 63.5 0.00999 2182 1139 - -
Heating Coil Outlet - 63.5 0.00999 2182 1139 0 -
Zone Air - 83.0 0.01052 2182 1236 45683 -
Zone2 ( Cooling )
Ventilation Air - - - 246 - - -
Cooling Coil Inlet - 77.0 0.00966 2140 1132 - -
Cooling Coil Outlet - 62.0 0.00963 2140 1132 34365 317
Heating Coil Inlet - 62.0 0.00963 2140 1132 - -
Heating Coil Outlet - 62.0 0.00963 2140 1132 0 -
Zone Air - 79.6 0.01010 2140 1226 40307 -
Zone3 ( Cooling )
Ventilation Air - - - 244 - - -
Cooling Coil Inlet - 79.6 0.00998 2161 1169 - -
Cooling Coil Outlet - 63.4 0.00994 2161 1169 37625 427
Heating Coil Inlet - 63.4 0.00994 2161 1169 - -
Heating Coil Outlet - 63.4 0.00994 2161 1169 0 -
Zone Air - 82.5 0.01046 2161 1267 44251 -
Zone4 ( Cooling )
Ventilation Air - - - 145 - - -

Hourly Analysis Program 6.2 Page 12 of 15


System Psychrometrics for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Cooling Coil Inlet - 80.0 0.01020 2049 1440 - -
Cooling Coil Outlet - 63.0 0.00999 2049 1440 37451 2062
Heating Coil Inlet - 63.0 0.00999 2049 1440 - -
Heating Coil Outlet - 63.0 0.00999 2049 1440 0 -
Zone Air - 81.7 0.01051 2049 1519 41072 -
Zone5 ( Cooling )
Ventilation Air - - - 187 - - -
Cooling Coil Inlet - 79.7 0.01003 2450 1187 - -
Cooling Coil Outlet - 63.1 0.00992 2450 1187 43731 1361
Heating Coil Inlet - 63.1 0.00992 2450 1187 - -
Heating Coil Outlet - 63.1 0.00992 2450 1187 0 -
Zone Air - 81.5 0.01035 2450 1252 48371 -
Zone-AHU ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 113.2 0.01459 288 6861 - -
Cooling Coil Outlet - 78.2 0.01450 288 6861 10905 123
Heating Coil Inlet - 78.2 0.01450 288 6861 - -
Heating Coil Outlet - 78.2 0.01450 288 6861 0 -
Zone Air - 113.0 0.01460 288 6864 10850 -

Hourly Analysis Program 6.2 Page 13 of 15


System Psychrometrics for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 61.3 0.00593 1074 400 -7555 0
Air-to-Air Energy Recovery Outlet 61.3 0.00593 1074 400 0 0
Vent - Return Mixing Outlet 61.3 0.00593 1074 400 - -
Vent. Cooling Coil Outlet 53.6 0.00593 1074 400 8791 0
Ventilation Fan Outlet 55.0 0.00593 1074 400 1593 -
Humidifier Outlet 55.0 0.00593 1074 400 0 0
Dehumid. Reheat Coil Outlet 55.0 0.00593 1074 400 0 -
Cold Supply Duct Outlet 55.0 0.00593 1074 400 0 -
Zone Air - 68.0 0.00593 1074 400 -42866 0
Return Air Outlet 68.0 0.00593 1074 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.050 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4613.2 BTU/(hr-CFM)
Site Altitude = 787.0 ft

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone- Low/High zone-
passanger lobby ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 68.2 0.00593 1192 400 - -
Cooling Coil Outlet - 68.2 0.00593 1192 400 0 0
Heating Coil Inlet - 68.2 0.00593 1192 400 - -
Heating Coil Outlet - 78.1 0.00593 1192 400 12512 -
Zone Air - 68.0 0.00593 1192 400 -12751 -
Zone- Potential Apartment (
Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 68.2 0.00593 215 400 - -
Cooling Coil Outlet - 68.2 0.00593 215 400 0 0
Heating Coil Inlet - 68.2 0.00593 215 400 - -
Heating Coil Outlet - 73.8 0.00593 215 400 1273 -
Zone Air - 68.0 0.00593 215 400 -1316 -
Zone1 ( Heating )
Ventilation Air - - - 253 - - -
Cooling Coil Inlet - 66.7 0.00593 2182 400 - -
Cooling Coil Outlet - 66.7 0.00593 2182 400 0 0
Heating Coil Inlet - 66.7 0.00593 2182 400 - -
Heating Coil Outlet - 70.7 0.00593 2182 400 9362 -
Zone Air - 68.0 0.00593 2182 400 -6297 -
Zone2 ( Heating )
Ventilation Air - - - 246 - - -
Cooling Coil Inlet - 66.7 0.00593 2139 400 - -
Cooling Coil Outlet - 66.7 0.00593 2139 400 0 0
Heating Coil Inlet - 66.7 0.00593 2139 400 - -
Heating Coil Outlet - 70.0 0.00593 2139 400 7541 -
Zone Air - 68.0 0.00593 2139 400 -4571 -
Zone3 ( Heating )
Ventilation Air - - - 244 - - -
Cooling Coil Inlet - 66.7 0.00593 2161 400 - -
Cooling Coil Outlet - 66.7 0.00593 2161 400 0 0
Heating Coil Inlet - 66.7 0.00593 2161 400 - -
Heating Coil Outlet - 70.2 0.00593 2161 400 7893 -
Zone Air - 68.0 0.00593 2161 400 -4955 -
Zone4 ( Heating )
Ventilation Air - - - 145 - - -

Hourly Analysis Program 6.2 Page 14 of 15


System Psychrometrics for L1-FCU-SYSTEM
(In Alternative: Plant-HVAC)
Project: Mecca Tower 01/30/2025
Prepared by: DSA Engineering 17:10
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Cooling Coil Inlet - 67.3 0.00593 2048 400 - -
Cooling Coil Outlet - 67.3 0.00593 2048 400 0 0
Heating Coil Inlet - 67.3 0.00593 2048 400 - -
Heating Coil Outlet - 70.2 0.00593 2048 400 6409 -
Zone Air - 68.0 0.00593 2048 400 -4812 -
Zone5 ( Heating )
Ventilation Air - - - 187 - - -
Cooling Coil Inlet - 67.2 0.00593 2450 400 - -
Cooling Coil Outlet - 67.2 0.00593 2450 400 0 0
Heating Coil Inlet - 67.2 0.00593 2450 400 - -
Heating Coil Outlet - 70.4 0.00593 2450 400 8461 -
Zone Air - 68.0 0.00593 2450 400 -6372 -
Zone-AHU ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 68.2 0.00593 288 400 - -
Cooling Coil Outlet - 68.2 0.00593 288 400 0 0
Heating Coil Inlet - 68.2 0.00593 288 400 - -
Heating Coil Outlet - 73.8 0.00593 288 400 1734 -
Zone Air - 68.0 0.00593 288 400 -1792 -

Hourly Analysis Program 6.2 Page 15 of 15