The GEL65-12 is a 12V, 68Ah sealed lead-acid battery designed for a lifespan of 3-5 years under standby conditions. It features a maximum discharge current of 650A and operates efficiently within a temperature range of -15℃ to 50℃. The battery is compliant with IEC 60896 standards and is suitable for various applications due to its non-spillable and maintenance-free design.

Uploaded by

Hesham Qataberi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views2 pages

Gel65-12 - Spec-1

The GEL65-12 is a 12V, 68Ah sealed lead-acid battery designed for a lifespan of 3-5 years under standby conditions. It features a maximum discharge current of 650A and operates efficiently within a temperature range of -15℃ to 50℃. The battery is compliant with IEC 60896 standards and is suitable for various applications due to its non-spillable and maintenance-free design.

Uploaded by

Hesham Qataberi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

GEL65-12

SPECIFICATION
Cell per unit 6
Nominal Voltage (V) 12
Nominal Capacity (Ah) C20 68Ah at 20hour rate F.V(1.75/cell)
Nominal Capacity (Ah) C10 65Ah at 10hour rate F.V(1.80/cell)
Weight ±3% 21.50 KGS
Internal Resistance < 6.7mΩ
Max Discharge Current (5s) 650A
Battery Design Life Stand by : 3~5 years
Terminal Type NB(F4)/IT(F8)
Container Material ABS(94-HB & 94V-0 flame retardant case)
Ambient temperature Charge 0℃(32℉) to 40℃ (104℉)
Discharge -15℃(5℉) to 50℃ (122℉)
Storage -15℃(5℉) to 40℃ (104℉)
Charging Instruction (25°C):
Max charge current: Max charge current:20.4A
Cycle use : Charge voltage: 14.4 to 15.0V
Stand by : Charge voltage: 13.50 to 13.80V

DIMENTIONS Length Width Height Total Height

Unit: mm 350±2 167±2 175±2 175±2


Unit: inch 13.78±0.08 6.57±0.08 6.89±0.08 6.89±0.08

Constant current discharge characteristics Unit:A(25℃77℉)


F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 299.62 142.78 79.79 44.56 23.21 17.09 11.61 7.98 6.58 3.43
1.67V 290.89 138.62 79.00 44.12 22.98 16.92 11.55 7.94 6.57 3.42
1.70V 277.04 135.90 76.70 43.72 22.78 16.77 11.50 7.90 6.54 3.41
1.75V 261.36 132.59 76.09 42.86 22.60 16.64 11.44 7.86 6.52 3.40
1.80V 221.49 126.28 73.17 41.62 22.44 16.52 11.38 7.82 6.50 3.40

Constant power discharge characteristics Unit:W/cell(25℃77℉)


F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 543.97 273.46 156.32 88.38 46.90 34.44 23.40 16.19 13.02 6.86
1.67V 524.27 268.56 154.70 87.57 45.31 34.24 23.33 16.08 13.02 6.86
1.70V 503.38 262.06 152.61 86.44 44.97 34.00 23.25 15.85 12.98 6.83
1.75V 474.30 253.91 149.21 84.98 43.90 33.72 23.12 15.66 12.92 6.83
1.80V 409.59 242.53 143.71 82.39 42.50 33.03 22.78 15.41 12.73 6.70

APPLICATIONS GENERAL FEATURES STANDARDS


● All purpose ● 5 years design life (25℃) Compliance with IEC 60896 standards
● Lead calcium alloy, sealed design.
● Non spillable and maintenance free
● AGM separator application
● Designed for a wide range of applications
Battery Discharge Characteristics (25℃/77℉) Battery Charge Characteristic for standby use

Temperature Effects in Relation to Battery Capacity Temperature Effects on Long Term Float Life

Cycle Service Life Self Discharge Characteristics

Charging Procedures Discharge Current VS. Discharge Voltage