PANASONIC CU-E9PFE
PANASONIC CU-E9PFE
Air Conditioner
Indoor Unit Outdoor Unit
CS-E9GFEW CU-E9PFE
CS-E12GFEW CU-E12PFE
CS-E18GFEW CU-E18PFE
CS-E9GFEW-2 CU-E9PFE
CS-E12GFEW-2 CU-E12PFE
Destination
Europe
Please file and use this manual together with the Service Manual for Model No. CS-E9GFEW, CS-E12GFEW, CS-E18GFEW,
CS-E9GFEW-2, CS-E12GFEW-2, Order No. RAC0704001C2, MAC0802015C2, MAC0804027A2.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
WARNING This indication shows the possibility of causing death or serious injury.
CAUTION This indication shows the possibility of causing injury or damage to properties.
Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
Engage dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water
4.
leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage,
6.
fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
7.
done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single
8.
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This equipment is strongly recommended to install with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
9.
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
Do not use joint cable for indoor / outdoor connection cable. Use the specified Indoor/Outdoor connection cable, refer to installation
10. instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor / outdoor connection. Clamp the cable so that
no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
11.
cause heat-up or fire at the connection point of terminal, fire or electrical shock.
When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration
12.
cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb
13.
up to outdoor unit and cross over the handrail and causing accident.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
14.
telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
16.
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the
17.
flare may break and cause refrigerant gas leakage.
For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare nut
and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
18.
Thickness or copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
19. piping and valves at opened condition will caused suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion,
injury etc).
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
24. Must not use other parts except original parts described in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of
1.
the unit, it may cause fire.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
2.
furniture.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
3.
break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher.
6. Please use a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
Power supply connection to the room air conditioner.
Use power supply cord 3 x 1.5 mm² (1.0~1.5HP), 3 x 2.5 mm² (2.0HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
7.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0~1.5HP), 16A (2.0HP), power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0~2.0HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum
3.0 mm contact gap.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts.
8.
Take care of the liquid refrigerant, it may cause frostbite.
9. Installation or servicing work: It may need two people to carry out the installation or servicing work.
10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
11. Do not sit or step on the unit, you may fall down accidentally.
Pdesign kW 2.5
SEER (W/W) 6.1
ErP Annual
kWh 143
Consumption
Class A++
Power Factor % – 97 – – 97 – – 96 –
dB-A 38 / 27 / 23
Indoor Noise (H / L / QLo)
Power Level dB 54 / – / –
dB-A 46 / – / –
Outdoor Noise (H / L / QLo)
Power Level dB 61 / – / –
kW 0.85 3.40 5.00 0.85 3.40 5.00 0.85 3.40 5.00
Capacity BTU/h 2900 11600 17100 2900 11600 17100 2900 11600 17100
kcal/h 730 2920 4300 730 2920 4300 730 2920 4300
Running Current A – 3.75 – – 3.60 – – 3.45 –
Input Power W 240 810 1.35k 240 810 1.35k 240 810 1.35k
W/W 3.54 4.20 3.70 3.54 4.20 3.70 3.54 4.20 3.70
COP BTU/hW 12.08 14.32 12.67 12.08 14.32 12.67 12.08 14.32 12.67
kcal/hW 3.04 3.60 3.19 3.04 3.60 3.19 3.04 3.60 3.19
Pdesign kW 2.7
Heating
Tbivalent °C -10
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5. Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6. Specifications are subjected to change without prior notice for further improvement.
Pdesign kW 3.5
SEER (W/W) 5.8
ErP Annual
kWh 211
Consumption
Class A+
Power Factor % – 98 – – 98 – – 98 –
dB-A 39 / 28 / 24
Indoor Noise (H / L / QLo)
Power Level dB 55 / – / –
dB-A 48 / – / –
Outdoor Noise (H / L / QLo)
Power Level dB 63 / – / –
kW 0.85 4.00 6.00 0.85 4.00 6.00 0.85 4.00 6.00
Capacity BTU/h 2900 13600 20500 2900 13600 20500 2900 13600 20500
kcal/h 730 3440 5160 730 3440 5160 730 3440 5160
Running Current A – 4.60 – – 4.40 – – 4.20 –
Input Power W 245 1.00k 1.90k 245 1.00k 1.90k 245 1.00k 1.90k
W/W 3.47 4.00 3.16 3.47 4.00 3.16 3.47 4.00 3.16
COP BTU/hW 11.84 13.60 10.79 11.84 13.60 10.79 11.84 13.60 10.79
kcal/hW 2.98 3.44 2.72 2.98 3.44 2.72 2.98 3.44 2.72
Pdesign kW 3.2
Heating
Tbivalent °C -10
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5. Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6. Specifications are subjected to change without prior notice for further improvement.
10
Pdesign kW 5.0
SEER (W/W) 6.2
ErP Annual
kWh 282
Consumption
Class A++
Power Factor % – 97 – – 97 – – 96 –
dB-A 44 / 36 / 32
Indoor Noise (H / L / QLo)
Power Level dB 60 / – / –
dB-A 47 / – / –
Outdoor Noise (H / L / QLo)
Power Level dB 61 / – / –
kW 0.98 5.80 7.10 0.98 5.80 7.10 0.98 5.80 7.10
Capacity BTU/h 3340 19800 24200 3340 19800 24200 3340 19800 24200
kcal/h 840 4990 6110 840 4990 6110 840 4990 6110
Running Current A – 7.50 – – 7.20 – – 6.90 –
Input Power W 340 1.60k 2.30k 340 1.60k 2.30k 340 1.60k 2.30k
W/W 2.88 3.63 3.09 2.88 3.63 3.09 2.88 3.63 3.09
COP BTU/hW 9.82 12.38 10.52 9.82 12.38 10.52 9.82 12.38 10.52
kcal/hW 2.47 3.12 2.66 2.47 3.12 2.66 2.47 3.12 2.66
Pdesign kW 4.4
Heating
Tbivalent °C -10
11
12
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5. Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6. Specifications are subjected to change without prior notice for further improvement.
13
14
4.1.2 CU-E12PFE
15
16
17
18
19
20
21
22
23
24
25
26
27
28
3 Use separate heat insulation pipes for gas and liquid refrigerant pipes.
29
Use polyvinyl chloride adhesive agent for gluing. Failure to do so may cause water leakage.
For Moldings
o Remove the slit portions on the bottom frame
using nippers.
30
The supplemental plate for installing the main unit must be used, or there will be a gap between the unit and the wall.
31
1 Use drain pan edge for horizontal projection of the indoor unit.
2 Install the indoor unit flush against wall.
10.1.3.3.1 Preparation
Install the unit according to the instructions below. Failure to do so may cause both cooling and heating
failure and the formation of condensation inside the house.
1 Allow enough space between the main unit and ceiling not to obstruct the flow of cool/warm air.
2 Place a partition plate between outlet and inlet sections.
3 Place a partition plate on the right side.
4 Change the upward air flow limit dipswitch.
5 Use a movable lattice at the air outlet to allow the adjustment of cool/warm air flow direction.
6 Lattice size should be 70% or more of open rate.
32
Be sure to turn on the upward air flow limit dipswitch. Failure to do so may cause incomplete cooling/heating and
formation of condensation inside the house.
33
34
Model A B C D
E9*** 570 mm 105 mm 18.5 mm 320 mm
E12*** 540 mm 160 mm 18.5 mm 330 mm
E18*** 613 mm 131 mm 16 mm 360.5 mm
36
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and
vacuum pump adaptor.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note : BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
37
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step e above take
the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step e.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
5 Secure the power supply cord and connection cable onto the control board with the holder.
6 Attach the control board cover back to the original position with screw.
7 For wire stripping and connection requirement, refer to instruction 10.1.6 of indoor unit.
38
Remote control
J_A J_B
number
Short Open A(Default)
Open Open B
Short Short C
Open Short D
39
40
41
42
43
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
1 Remove the 3 screws of the Top Panel. 5 Remove the Control Board as follows:
Fig. 1 Fig. 4
Fig. 2
Fig. 5
3 Remove the screw of the Terminal Board
Cover.
4 Remove the Top Cover of the Control Board
by 4 hooks.
Fig. 6
Fig. 3
44
1 Remove the 5 screws of the Top Panel. 5 Remove the Control Board as follows:
Fig. 1 Fig. 4
Fig. 2
Fig. 5
3 Remove the screw of the Terminal Board
Cover.
4 Remove the Top Cover of the Control Board
by 4 hooks.
Fig. 6
Fig. 3
45
Fig. 4
Fig. 5
Fig. 2
3 Remove the Top Cover of the Electronic Caution! When handling electronic controller, be careful of
Controller. electrostatic discharge.
Fig. 3
46
15.900
Temperature (°C)
15.400
Outdoor
14.900
14.400
13.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
3.000
2.800
Capacity (kW)
2.600
Cooling
2.400
2.200
2.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
3.000
2.800
2.600
2.400
Current
(A)
2.200
2.000
1.800
1.600
1.400
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
1.080
1.060
Gas Side Piping
Pressure (MPa)
1.040
1.020
1.000
0.980
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
47
15.500
15.300
15.200
15.100
15.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.550
2.500
Capacity (kW)
Cooling
2.450
2.400
2.350
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.630
2.580
2.530
Current
(A)
2.480
2.430
2.380
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
1.050
1.040
Gas Side Piping
Pressure (MPa)
1.030
1.020
1.010
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
48
39.000
Temperature (°C)
37.000
Outdoor
35.000
33.000
31.000
29.000
27.000
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
4.200
3.700
Capacity (kW)
3.200
Heating
2.700
2.200
1.700
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
4.000
3.800
3.600
Current
3.400
(A)
3.200
3.000
2.800
2.600
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
2.800
2.600
Gas Side Piping
Pressure (MPa)
2.400
2.200
2.000
1.800
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
49
Temperature (°C)
Outdoor 38.000
37.800
37.600
37.400
37.200
37.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.500
3.400
Capacity (kW)
Heating
3.300
3.200
3.100
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.900
3.800
3.700
Current
(A)
3.600
3.500
3.400
3.300
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.700
Gas Side Piping
Pressure (MPa)
2.600
2.500
2.400
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
50
13.800
Temperature (°C)
13.300
Outdoor
12.800
12.300
11.800
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
4.100
3.900
Capacity (kW)
3.700
Cooling
3.500
3.300
3.100
2.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
5.400
4.900
4.400
Current
(A)
3.900
3.400
2.900
2.400
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
1.000
0.980
Gas Side Piping
Pressure (MPa)
0.960
0.940
0.920
0.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
51
13.100
Temperature (°C)
13.000
Outdoor
12.900
12.800
12.700
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
3.550
3.500
Capacity (kW)
3.450
Cooling
3.400
3.350
3.300
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
4.400
4.350
4.300
4.250
Current
(A)
4.200
4.150
4.100
4.050
4.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
0.970
0.960
Gas Side Piping
Pressure (MPa)
0.950
0.940
0.930
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
52
42.200
Temperature (°C)
40.200
Outdoor
38.200
36.200
34.200
32.200
30.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
5.000
4.500
Capacity (kW)
4.000
Heating
3.500
3.000
2.500
2.000
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
5.000
4.800
4.600
4.400
Current
4.200
(A)
4.000
3.800
3.600
3.400
3.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
3.100
2.900
Gas Side Piping
Pressure (MPa)
2.700
2.500
2.300
2.100
1.900
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13
Outdoor Air Temperature (°C)
53
Temperature (°C)
Outdoor 41.200
41.000
40.800
40.600
40.400
40.200
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
4.100
4.000
Capacity (kW)
3.900
Heating
3.800
3.700
3.600
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
4.800
4.700
4.600
4.500
Current
(A)
4.400
4.300
4.200
4.100
4.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
2.900
Gas Side Piping
Pressure (MPa)
2.800
2.700
2.600
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
54
11.700
11.500
11.300
11.100
10.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
5.600
5.400
5.200
Capacity (kW)
Cooling
5.000
4.800
4.600
4.400
4.200
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
8.000
7.500
7.000
6.500
Current
(A)
6.000
5.500
5.000
4.500
4.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
0.890
0.880
0.870
Gas Side Piping
Pressure (MPa)
0.860
0.850
0.840
0.830
0.820
0.810
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Air Temperature (°C)
55
11.600
11.500
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
5.100
Capacity (kW)
5.000
Cooling
4.900
4.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
7.300
7.200
7.100
Current
7.000
(A)
6.900
6.800
6.700
6.600
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
0.840
0.830
Gas Side Piping
Pressure (MPa)
0.820
0.810
0.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
56
44.000
Temperature (°C)
Outdoor 42.000
40.000
38.000
36.000
34.000
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11
Outdoor Air Temperature (°C)
6.500
6.000
Capacity (kW)
5.500
Heating
5.000
4.500
4.000
3.500
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11
Outdoor Air Temperature (°C)
8.200
7.700
7.200
Current
(A)
6.700
6.200
5.700
5.200
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11
Outdoor Air Temperature (°C)
3.100
2.900
Gas Side Piping
Pressure (MPa)
2.700
2.500
2.300
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11
Outdoor Air Temperature (°C)
57
42.700
Temperature (°C)
Outdoor
42.600
42.500
42.400
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
5.840
5.820
Capacity (kW)
Heating
5.800
5.780
5.760
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
7.600
7.500
7.400
7.300
Current
(A)
7.200
7.100
7.000
6.900
6.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
2.960
2.950
Gas Side Piping
Pressure (MPa)
2.940
2.930
2.920
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
58
CU-E12PFE
CU-E18PFE
59
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
60
61
(NOTE)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
62
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
63
64
(NOTE)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
65
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
66
67
(NOTE)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
Printed in Malaysia
FY0313-0
68