1. Structure (1/4) Introduction
SUSOL & METASOL ACB are developed to meet high breaking capacity required for elevated electricity demend, to satisfy
compact distribution panel size demanded in makers, to achieve 100% N phase current conducting capacity on single phase
Lload and to increase user’s convenience by providing various accessories and connecting method.
SUSOL Series
SUSOL Seriese ACB has high breaking capacity and multi-function product and at the world class level which is used with
P and S type of digital trip relay.
• AH type • Ics=100%Icu at 500V
150KA 150KA
85KA 100KA
METASOL Series
METASOL Seriese ACB has AS type product for the highest breaking capacity for its domestic market, and AN type product
Ffor concentrating on fundamental functions at affordable price.
2 / 30
1. Structure (2/4) External View
⑩
⑫
⑪
⑨
3 / 30
1. Structure (3/4) Internal configuration
1
1 Control terminal block
2 14 15 16 17 18
12 13
2 Control terminal
3 Auxiliary switches
3
4 Closing, Trip, UVT coil
5 Trip relay
4
6 Front cover
7 Mechanism
5 8 Charge handle
9 Trip spring
6
10 Closing spring
11 Draw in-out device
7
12 Arc extinguishing part
8
19 13 Moving contact
9 14 Fixed contact
15 Conductor on Source side
16 Cradle Finger
10 17 Cradle
18 Connecting conductor to
circuit breakers
20
11 19 Power supply CT
20 Conductor on load side
4 / 30
1. Structure (4/4) Terminal configuration
There are many possible terminal configurations when connecting bus bar of distribution panel, vertical, horizontal, plane
type, etc.
5 / 30
2. Rating (1/2)
Breaking
500
Capacity, Icu 65 70 85 70 85 100 100 120 150
Vac
(kA)
Rated short time
withstand current, Icw, 50 65 65 65 85 85 85 100 100
1sec (A rms)
Mechanical 12000 12000 12000 10000 10000 10000 5000 5000 5000
Life cycle
Electrical 5000 5000 5000 5000 5000 5000 2000 2000 2000
Trip Relay N, A, P A, P, SP N, A, P N, A, P A, P, SP N, A, P N, A, P A, P, SP
Rated current of
100 %
Neutral pole (%)
6 / 30
2. Rating (2/2)
N phase
100%
630~2000AF 2000~4000AF 4000~6300AF
4
3
0
mm
m
5m
37
334mm 412mm 785mm
7 / 30
3. Feature (1/4)
SUSOL & METASOL ACBs are the one of next generation in the world class equipped with various accessories and
outstanding performaces.
Feature
8 / 30
3. Feature (2/4) Nameplate
Main Nameplate
9 / 30
3. Feature (3/4)
By dispersing evenly through arch voltage occurred in case of breaking fault current by arc shute, it prevents to save the
insulation recovery time; simultaneously, it shows outstanding breaking performance by reducing arc that can be occurred
in arc contact board.
10 / 30
3. Feature (4/4) Comm.
It allows executing remote input, breaking, temperature monitoring, etc. through the communication network using TRIO
(Temperture & Remote I/O).
But in case of using only communication function of measurment and protection, communication is possible with OCR only.
Subject Function
1 2
1 Comm. Terminal block CB/ DO control, Communication
TRIO unit
Local Systems
PLC RTU
종
Terminationg
단 resistance
RS-485
저 150Ω
항
11 / 30
4. Digital Trip Relay (1/5)
OCR with Multi-functions is to Satisfy Using Conditions for Devise Customers’ Demend.
N type A type P/S type
Susol Metasol Susol Metasol Susol Metasol
Operate as a current relay with its self-power Current Meter + Current relay + DO Control +Communication
Current / Voltage / Frequency / Energy Meter Type + Every function of P type + Harmonics Analysis (63th) +
Current relay + Voltage + Frequency relay + Communication Record Fault Frequency
12 / 30
4. Digital Trip Relay (2/5)
13 / 30
4. Digital Trip Relay (3/5)
① ② ③
①②③ ④⑤
④ ⑤ ⑥
⑦ ⑧ ⑥ ⑦⑧
No Type of knob Mode setting step
(0.5-1-2-4-8-12-16-20-off)× Ir
③ Long-time trippng delay tr
@ 6 Ir
(0.2-0.3-0.4-0.5-0.6-0.7-0.8
⑦ Ground-fault pick-up Ig
-1-off)× In
14 / 30
4. Digital Trip Relay (4/5)
① ②
①② ③④
③ ④ ⑤
⑥ ⑦
⑤ ⑥⑦
No Type of knob Mode setting step
(0.5-1-2-4-8-12-16-20-off)× Ir
② Long-time tripping delay tr
@ 6 Ir
15 / 30
4. Digital Trip Relay (5/5)
16 / 30
5. Accessories (1/13)
Thanks to various accessories, it is much easier to secure the safe usage and system upgrade so that it can be spec-in
in the high-end market.
ACB Main
1. Trip Relay(OCR)
2. Charge Motor
3. Closing Coil
4. Shunt Coil(SHT1, SHT2)
5. Under Voltage Trip Device
6. Door Interlock
7. Mechanical Operated Cell SW
8. Mechanical Interlock
9. Aux Switch
10. Key Lock
11. Counter
12. ON/OFF Button Lock
13. Miss insertion prevent device
14. Automatically discharge mechanism
15. Manual Reset
17 / 30
5. Accessories (2/13)
ACB Cradle
1. Safety Shutter
2. Control connector
3. Zero Arc Space
4. Insulation barrier
5. Cell Switch
6. Door Interlock
7. Mechanical operated cell switch
8. Mechanical Interlock
9. Miss insertion prevent device
10. Cradle mounting block
11. Shorting "b" contact
12. Safety control cover
13. Automatically discharge mechanism
14. Racking Interlock
15. Safety shutter lock
16. Capacitor trip device
17. Door Frame
18. Dust cover
19. OCR Tester
20. ATS Controller
21. Lift Hook
22. Dummy ACB
23. UVT Delay Controller
18 / 30
5. Accessories (3/13)
Prevent the arc which may arise and result in short-circuit between phase in advance
19 / 30
5. Accessories (4/13)
Mechanical Interlock
It interlocks two or three circuit breajers mechanically by controlling and closing and trip operation
mutually.
Door Interlock
It is a safety device which dose not allow the panel door to open when a circuit breaker is in the “ON”
positon.
Interlocking with
PNL door
Interlocking with
ACB
20 / 30
5. Accessories (5/13)
It is the contacts (10a10b) which indicate the ON/OFF condition of ACB by operating mechanically
only when ACB is in “CONNECTED” position and two types are available, Standard type and High
capacity type.
It is a locking device which prevents safety shutter from being opened when it is closed.
Guide
Guide shutter
shutter
Shutter
Shutter lock
lock Key
Key lock
lock Shutter
Shutter plate
plate
21 / 30
5. Accessories (6/13)
Cell Switch, C
It is a contact which indicates the prevent position of ACB (CONNECTED, TEST, DISCONNECTED)
“C”contact
“C”contact
Lift Hooking
22 / 30
5. Accessories (7/13)
If the ratings of ACB dose not match ith cradle, it mechanically prevents ACB from being inserted into
cradle of ACB.
A
B 1
C 2
D 3
E 4
F 5
6
G 7
Cradle Body
23 / 30
5. Accessories (8/13)
The mechanical interlock has two types, Bar type, Wire type and ATS Controller is required additionally
to achieve the function of electrical onterlock.
Operating Status
Operating Status
24 / 30
5. Accessories (9/13)
It is a device which makes ACB tripped automatically to prevent the accident on load side due to under
Voltage or power breakdown. There are two types, Instantaneous type and time delay type.
OCR Tester
25 / 30
5. Accessories (10/13)
Door Frame
It is used as an external guide when structuring the protrude type of panel and it improves the appear-
ance of ACB by attaching it to the panel door.
It gets a circuit breaker tripped electrically within regular time when control power supply is broken down
and is used with Shunt coil, SHT.
Circuit Diagram
26 / 30
5. Accessories (11/13)
Key lock : K1
It is locking device which prevents a certain circuit breaker from being operated y user’s discretion
When two or more circuit breakers are used at the same time.
3 Circuit breakers can be arranged for the continuous power supply to the load side and be interlocked
Mutually by using key lock embedded in each curcuit breaker.
ACB1
ACB1 ACB2
ACB2 ACB3
ACB3
27 / 30
5. Accessories (12/13)
28 / 30
5. Accessories (13/13)
Counter
It displays the total number of ON/OFF operation of ACB.
Charging Motor
Charge the closing spring of a circuit breaker by the external power source.
Operating voltage range is in the range of 85%~110% Vn.
29 / 30
6. Certificates
Susol & Meatsol ACB meet international standards such as IEC(KEMA).