0% found this document useful (0 votes)
12 views

pvsyst-tutorial-v8-grid-connected-en

PVsyst is a software tool for simulating and analyzing photovoltaic systems, enabling users to design solar energy projects with detailed performance assessments. The document serves as a user manual, detailing the software's features, project design, simulation processes, and utilities, while providing guidance on system configurations and energy management. Users can access online help, tutorials, and forums for additional support and information.

Uploaded by

koaidanhlai1597
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views

pvsyst-tutorial-v8-grid-connected-en

PVsyst is a software tool for simulating and analyzing photovoltaic systems, enabling users to design solar energy projects with detailed performance assessments. The document serves as a user manual, detailing the software's features, project design, simulation processes, and utilities, while providing guidance on system configurations and energy management. Users can access online help, tutorials, and forums for additional support and information.

Uploaded by

koaidanhlai1597
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 83

Introduction

PVsyst is a comprehensive software tool designed for the simulation and analysis of
photovoltaic systems. It allows users to design and optimize solar energy projects by
providing detailed assessments of system performance, energy yields, and financial
viability.
With PVsyst, users can model various types of PV installations with location-specific
climate data and component specifications, while considering factors such as shading
effects on the system, battery storage, grid unavailability and panel degradation.
This document can be seen as a user’s manual, aiming to describe the different windows
and feature of the software. The complete reference manual for PVsyst is the online help
that is accessible from the program through the “Help” entry in the menu, by pressing
the F1 key or by clicking on the help icons inside the windows and dialogs.

PVsyst SA – Grid Connected Systems – User’s manual Page 2


Contents
1 PVsyst Main page .............................................................................................. 5
1.1 Project design and Simulation ..................................................................... 5
1.2 Utilities...................................................................................................... 6
1.3 Documentation .......................................................................................... 7
1.4 Toolbar and Workspace .............................................................................. 7
2 My first simulation ............................................................................................. 8
2.1 Project definition ........................................................................................ 8
3 Orientations ................................................................................................... 11
3.1 Fixed orientations .................................................................................... 12
3.1.1 Fixed plane systems .......................................................................... 12
3.1.2 Seasonal tilt adjustment .................................................................... 12
3.1.3 Domes ............................................................................................. 13
3.1.4 Unlimited sheds ................................................................................ 13
3.1.5 Unlimited sun-shields ....................................................................... 14
3.2 Tracking plane definitions ......................................................................... 14
3.2.1 Unlimited trackers, horizontal axis ..................................................... 14
3.2.2 Tracking, horizontal and tilted axis ...................................................... 15
3.2.3 Tracking, vertical axis ........................................................................ 15
3.2.4 Tracking sun-shields.......................................................................... 16
3.2.5 Tracking, horizontal axis East/West .................................................... 16
3.3 Two axis trackers...................................................................................... 16
3.3.1 Tracking two axis ............................................................................... 16
3.3.2 Tracking 2-axis, frame North/South and East/West .............................. 17
4 System ........................................................................................................... 17
4.1 Sub-arrays ............................................................................................... 17
4.2 Design the array ....................................................................................... 19
4.3 Multi MPPT and Power sharing feature ....................................................... 20
5 Detailed losses ............................................................................................... 22
5.1 Thermal parameters ................................................................................. 22
5.2 Ohmic Losses .......................................................................................... 23
5.2.1 DC circuit: ohmic losses for the subfield ............................................. 23
5.2.2 AC losses after the inverter ................................................................ 24

PVsyst SA – Grid Connected Systems – User’s manual Page 3


5.3 Module quality – LID - Mismatch ................................................................ 26
5.3.1 Module quality loss ........................................................................... 26
5.3.2 LID – Light Induced Degradation ......................................................... 26
5.3.3 Module mismatch losses ................................................................... 27
5.3.4 Strings voltage mismatch................................................................... 27
5.4 Soiling loss .............................................................................................. 28
5.5 IAM Losses .............................................................................................. 28
5.6 Auxiliaries ................................................................................................ 30
5.7 Aging ....................................................................................................... 30
5.8 Unavailability of the System ...................................................................... 31
5.9 Spectral correction .................................................................................. 32
5.10 Losses graph ........................................................................................... 33
6 Self-consumption ........................................................................................... 33
7 Storage .......................................................................................................... 34
7.1 Self-consumption with storage ................................................................. 36
7.2 Peak shaving ............................................................................................ 37
7.3 Weak grid islanding .................................................................................. 38
8 Horizon .......................................................................................................... 40
9 Near shading .................................................................................................. 42
9.1 Compatibility between the 3D Scene and System-Orientation ..................... 43
9.2 Simulation Parameter............................................................................... 44
9.3 Orientations, table, graph buttons ............................................................. 46
9.4 Construction/Perspective, 3D scene ......................................................... 48
9.5 Create Menu ............................................................................................ 51
9.6 Edit Menu ................................................................................................ 54
9.7 Transform Menu ....................................................................................... 54
9.8 Tools Menu .............................................................................................. 55
9.9 Main Menu ............................................................................................... 63
10 Energy management .................................................................................... 77
10.1 Inverter Temperature ................................................................................ 77
10.2 Power Factor ........................................................................................... 78
10.3 Grid Power limitation ................................................................................ 81
10.4 P50 - P90 Estimation ................................................................................ 82

PVsyst SA – Grid Connected Systems – User’s manual Page 4


1 PVsyst Main page
At the first main page you have an overview of the different main components in the
software, such as the Project design and Simulation, Utilities, Documentation as well as
your recent projects and your workspace.

1.1 Project design and Simulation


Project design and simulation is the main part of the software and is used for the
complete study of a project. It involves the choice of meteorological data, system design,
shading studies, losses determination, and economic evaluation. The simulation is
performed over a full year in hourly steps and provides a complete report and many
detailed results.
Within the project design and simulation section, PVsyst allows you to create and
simulate three types of systems.
• Grid-Connected allows you to create a system design that is connected to the
grid. You also have the possibility to define a self-consumption profile and battery
storage with various strategies are possible.

PVsyst SA – Grid Connected Systems – User’s manual Page 5


• Standalone is reserved for a system unconnected to the grid, you are forced to
have a storage option. Production that you cannot utilize, or store will be
curtailed.
• Solar pumping systems are common in certain areas where solar panels are
used to run a pump from a well or a lake that then can be stored in an elevated
tank and the water can then be used for various things at various times.

Recent projects will allow you to quickly find and modify your recent projects.

1.2 Utilities
The Utilities section in PVsyst offers a range of tools and functions designed to enhance
the understanding and the precision of your PV system analysis.

• In Databases you can find all the sites and components already stored in PVsyst.
You can also generate new sites, import weather data and create new
components.

PVsyst SA – Grid Connected Systems – User’s manual Page 6


• In Tools you have some advanced parameters for solar geometry and electrical
optimization instruments.
• In Measured data it is possible to add measured data and to compare
simulations with measurements.

1.3 Documentation
In the Documentation section you find a direct access to the PVsyst Help, the complete
reference manual for PVsyst, also accessible from pvsyst.com/help. Throughout the
software, context-sensitive online help is available via the F1 key and small question
mark icons inside the windows and dialogs, providing more specific information in
certain cases. By using the F1 key, or clicking at the question mark icon, you arrive at the
PVsyst help tool where you can find useful articles with precise information,
explanations and step by step description of how to use different function the PVsyst
software.
You also find the access to the PVsyst forum where you can post your questions and
PVsyst collaborators and other Pvsyst users will guide you forward.
In the PVsyst video channels you find educative videos and tutorials. You also find these
printable users manuals and tutorials here.
1.4 Toolbar and Workspace
It is from the Main page that the settings are made for your entire workspace.
When files are saved, they will automatically be saved in the workspace, in a precise
folder structure. In the workspace you also find a set of templates with the correct
configuration, to be used for instance to define a self-consumption profile. PV
components will be saved to ComposPV, project files will be saved to Projects, etc.
• Under File you find the for example the options to import and export projects and
components.
• The Preliminary design is an easy and basic simulation tool for small and
simplified projects.
• You can start a new project through the Project tab. Here you also find a fourth
type of project not visualized in the Project design and simulation window, that is
the DC-grid project, for the use case of certain public transport companies. From
the Project tab you can also load a project in your workspace or a DEMO project
defined by Pvsyst, that showcase various features and examples of utilization.
• In the Settings you have Preferences where you could for instance define user
info, units to be used as default and possible API keys for certain weather file
providers. In the Advanced parameters, almost all the default values and
thresholds that generates error messages can be modified, but should be
modified only by experts.
• Language can be changed in this language tab, or by clicking the F9 button.
• In the License tab you find all the information about your Account, activation key
etc.

PVsyst SA – Grid Connected Systems – User’s manual Page 7


• The Help will guide you to the various documentation possibilities available.

2 My first simulation
For this first explanatory tutorial, we choose a Grid connected system, but the majority
of steps and information will be relevant also for standalone and pumping systems.
The Workflow in PVsyst is to work in Projects and in Variants. This also illustrates the
hierarchy of the software.
Project contains the geographical site of your system, the reference to a file with the
meteorological data and some general parameters like the albedo definition and
parameters specific to this project. The project will be the central object that allows the
basic definitions in which you then will construct different variants of your system.
The system variant contains all the detailed definitions of your system, which will result
in a simulation calculation. These definitions include the choice and number of solar
panels and inverters, geometrical layout and possible shadings, electrical connections,
different economic scenarios, etc.

2.1 Project definition


By Clicking Grid connected System on the welcome page, PVsyst will automatically open
the most reason project (It’s possible to change the default behavior for opening new
projects. Go to “Settings - Preferences - Default Values,” then modify the “Automatic
Project Loading” section).
You can start a new project by clicking New. You can Load existing projects through the
Load option. You can Import or Export projects through the Import and Export. You also
have the possibility to define a Client for the project and later choose if you wish to print
the Company details on the report.

PVsyst SA – Grid Connected Systems – User’s manual Page 8


In the Project settings you can define overall parameters and preferences for the
project. Note the difference between the Project settings here, that will affect only this
specific project, and the Advanced parameters in the Main page that will be implemented
in all the Projects in your workspace.
In the Project setting you can define for instance the far Albedo, e.g. the albedo around
your site (the albedo under the panels will be defined in the system window in case of
bifacial panels). In the Design conditions you can among other values set the lowest
possible temperature at your site to generate a warning message for the Absolute Voltage
limit, other relevant temperatures to generate graphs in the sizing tool (note that the
simulation will use temperatures from your site, these values is to help you define your
system).

It is in the Project settings you set the limit overload loss for your design, that per default
is set at 3%. If you wish to design a system with a high Pnom ratio, you can increase this
value to avoid warning messages. You here also have the possibility to change other
design parameters, such as the transposition model.
In the Project you must first define the Project’s name, choose your site and define a
weather data File. The site file contains the coordinates of your project, that is used to
calculate the sun position each hour of the calendar year. The site file created will also
include a fallback monthly weather data which is used for fast and rough calculations in
the design part of the program.

There are 2 ways to define a project site. You can either choose a site from the list or
create a new site by typing the name or using the interactive map. You can also import
site if you have data from somewhere, or from another project.

PVsyst SA – Grid Connected Systems – User’s manual Page 9


In the Geographical Coordinates dialog, you can verify the coordinates for the chosen
site and the sun paths corresponding to this site. The sun paths illustrate the position of
the sun at each hour throughout the year.

When creating a geographical site, you can directly import Weather data from a list of
weather data providers, such as Meteonorm, PVGIS, Solcast, Solar Anywhere and
Salargis. For the import to work, you need to have a working internet access. The imports
are automatic based on the coordinates of your site.
It is up to you as a user to evaluate which weather source provider that is most accurate
for your project. For certain providers you need an additional license to have access.
Meteonorm data is included with the PVsyst license, using ground and satellite data and
utilizes monthly averages to create synthetic hourly values using stochastic models. TMY
(Typical Metrological Year) data on the other hand are meteorological hourly data files
constructed on the basis of real measured data series chosen among at least 10 years of
real measurements, according to several statistical criteria.
The data imported are in hourly values, the values are then averaged and displayed as
monthly values. Depending on weather source, you are also provided with Global
horizontal irradiation year-to-year variability, thus the natural fluctuations in the amount
of solar energy received on a horizontal surface from one year to another, that can be
used to calculate statistical analysis such as P50 and P90 of the energy yield predictions
of solar PV systems.
By clicking OK, you will be prompted to save the geographical site, and the synthetical
hourly weather data that have been generated (if your weather source is based on
synthetic data). By clicking open a summary of your weather data is available. Note
that PVsyst is labeling a generic year as 1990.

PVsyst SA – Grid Connected Systems – User’s manual Page 10


3 Orientations
To define the orientation, you must choose the field type. There are 3 categories of field
types, Fixed orientation Planes, One Axis tracking plane as well as a Two Axis tracking
planes.

You may define multiple field types by clicking Add Orientation at the top of the dialog.
To define an Orientation, choose the Field type in the drop down list. The header will show
the name of this orientation. If the box on the right is checked, this will define a name
according to the main parameters of the orientation; but you may give any customized
name.

The field types have in common that you must define the plane tilt and azimuth. In
general, the plane tilt is defined as the angle between the collector plane and the
horizontal. The plane azimuth is the angle between the collector plane and the direction
toward the equator. In the northern hemisphere, this means the azimuth is measured
from due south (toward the equator), with positive values toward the west
(counterclockwise): south = 0°, west = 90°, north = 180°, and east = -90°. In the southern
hemisphere, the azimuth is measured from due north (toward the equator), with negative
values toward the east (clockwise): north = 0°, west = 90°, south = 180°, and east = -90°.

PVsyst SA – Grid Connected Systems – User’s manual Page 11


3.1 Fixed orientations
3.1.1 Fixed plane systems
This is the simplest kind of orientation, it defines the plane tilt and the plane azimuth.
If tables (rectangular fields) are defined in the 3D scene, the base of these tables may be
inclined with respect to horizontal: this is the Base tilt angle, which is usually
named base slope in the 3D scene. In this case the real plane orientation is altered.

In the fixed planes definition, PVsyst displays a quick optimization tool, indicating the
energy yield as a function of the tilt and the azimuth. This is a rough estimation meant for
judging how your orientation choice (violet point) will affect the yield with respect to the
optimum. This may show the annual, summer or winter yield.

3.1.2 Seasonal tilt adjustment

In the seasonal tilt adjustment, you have the possibility to optimize the PV production, by modifying
the tables tilt depending on the season. This option allows to define two seasons with a
corresponding plane tilt and you must specify the months for the winter and the summer position.

PVsyst SA – Grid Connected Systems – User’s manual Page 12


3.1.3 Domes
Domes corresponds to a system with two opposite arrays of tables. In this case, PVsyst
automatically creates a second orientation for the opposite part of the array.
The spacing between the 2 rows of domes is usually very small and no significant
irradiance will be allowed to fall on the ground underneath the dome. Therefore, such a
configuration is not suited for bi-facial systems.

3.1.4 Unlimited sheds


The unlimited sheds are an extension of the fixed tilted plane orientation that adds
geometrical parameters defining the tables arrangement (in regularly arranged rows).
This allows the application of a simplified 2D model of mutual shadings based on these
parameters. This approach is generally faster than defining a 3D shading scene and can
therefore be used for example in more preliminary studies. “Unlimited sheds” refers to
the 2D representation, where the extremities of the rows are ignored in the calculations.
Besides the orientation, this mode specifies parameters describing the PV system, such
as the number of rows (sheds) and parameters such as the width of the (active) collector
band, mechanical top and bottom inactive bands, and the pitch. The number of rows is
necessary for the calculation to take into account that the first row is not shaded. The
collector band width is the width of your sensitive area. For instance, if you have one row
of modules where the panel measures 1x1.5m, if the panels are placed in landscape this
will be 1m, and in portrait this will be 1.5m. The inactive band refers to a physical
structure extending out past the modules, which will cast shadows. The pitch is the
distance between rows.

PVsyst SA – Grid Connected Systems – User’s manual Page 13


The ground covering ratio (GCR) and the limit angle (the profile angle for which you begin
to have mutual shadings) is calculated based on the parameters you choose and shown
in the top of the window. As there are shadings, this tool also allows for some advanced
options to define number of partitions for the calculation of the electrical shading
effects.

3.1.5 Unlimited sun-shields

It is possible to define unlimited sun-shields on a façade. The sun-shield rows parameters are
defined in a similar way as the unlimited sheds.

3.2 Tracking plane definitions


3.2.1 Unlimited trackers, horizontal axis

In a similar way as for unlimited sheds, you may define "unlimited trackers" for
parametric study of a PV trackers system, without using the 3D scene construction.

The axis azimuth refers to the orientation of the axis, where an azimuth of 0 correspond
to an axis running in the north to south direction. The rotation angle around the axis is
called Phi. Mechanical limits on the Phi stroke are required. Phi 0 corresponds to a
horizontal axis; the minimum phi is the lowest angle authorized (counter clockwise from
the horizontal axis) and the maximum phi contrary is the highest angle authorized
(clockwise from the horizontal axis).

The backtracking option will prevent shading between rows of panels by adjusting their
tilt angle based on the sun’s position. The irradiance optimization option will evaluate the
optimal tracking angle on the basis of the transposition model: the angle is adjusted in
order to get the best transposition result of GlobInc, considering the Beam and Diffuse
components.

The other parameters are the same as for “Unlimited sheds”. Note that the electrical
shading parameters are only visible when the backtracking is not activated, as by
definition there are no mutual shadings in backtracking mode.

PVsyst SA – Grid Connected Systems – User’s manual Page 14


By dragging the sun, you have the opportunity of visualizing the tracker's behavior
according to the sun position. This tool will show, namely, the behavior of
the backtracking mode.

3.2.2 Tracking, horizontal and tilted axis

As in “Unlimited Trackers”, you must define the axis orientation and tracking limit angles.
You also have the possibility to add an Axis tilt. You must define the Phi limits
(mechanical stroke), the backtracking strategy, and the tracking calculation mode
(astronomic calculation or irradiance optimization) to be used during the simulation. An
additional parameter, Wind stow defines a security rest position, to be set during the
simulation when the wind speed is too high.

When defining an array of trackers, the construction in the 3D scene is mandatory, as


this is the only way of calculating the mutual shading losses.

3.2.3 Tracking, vertical axis

With trackers with a vertical axis, the collector is kept at a fixed tilt but rotating according
to the sun azimuth. This configuration may be used with "dish" arrangements, when a big
rotating support holds several rows of modules; this particular case is made possible as
the rotating axis of one row may be displaced with respect to the collector. The plane tilt
and the azimuth mechanical limits of the tracker must be defined.

PVsyst SA – Grid Connected Systems – User’s manual Page 15


3.2.4 Tracking sun-shields

It’s possible to define a tracking sun-shield. You need to specify the facade orientation,
as well as the minimum and maximum tilt. Optimizing the balance between sun
protection and PV production is challenging. The backtracking strategy is likely the only
reasonable approach for operating sun-shield trackers.

3.2.5 Tracking, horizontal axis East/West

The tracking horizontal East/West refers to system where the rotation axis normally is
running east/west. With an Axis orientation of 0° in the northern hemisphere, the panels
will be oriented south and the minimum and maximum tilt will define the mechanical
strokes to follow the height of the sun in the southern direction, i.e. mainly the seasonal
variations. This is available in PVsyst, though is only used in very special situations.

3.3 Two axis trackers


3.3.1 Tracking two axis

Two-axis solar trackers adjust both the tilt and orientation of solar panels to stay
perpendicular to the sun's rays throughout the day. You must define the stroke limits for
both the tilt and the azimuth.

PVsyst SA – Grid Connected Systems – User’s manual Page 16


3.3.2 Tracking 2-axis, frame North/South and East/West

There are specific scenarios of 2-axis tracking system. The plane is always perpendicular
to the sun's rays, the tracker orientation within this plane is different. This may lead to
different mutual shadings. You have to define here the parameters related to the
orientation. The mechanical frame characteristics (size, width, etc) will be defined when
creating the 3D field representation. The backtracking may be done between trackers
within the frame, not between adjacent frames.

4 System
In a grid-connected projects, the system is defined as the set of components constituting
the PV-array, i.e. the PV modules, inverters and the design of the array, here separated in
the different background colors.

4.1 Sub-arrays

The system is organized as a set of sub-arrays: one sub-array is constituted of

• A PV module model, chosen in the database,


• An inverter model, chosen in the database,
• The number of inverter inputs,
o either full inverters or

PVsyst SA – Grid Connected Systems – User’s manual Page 17


o number of MPPT inputs,
• The number of modules in series, and the number of module strings.
o The number of strings should ideally be a multiple of the number of MPPT
inputs. However, PVsyst will accept uneven number of strings, and will
distribute them in the most balanced way across the MPPT inputs. A
warning will be issued when the imbalance is too high and you should
consider precising the distribution for a balanced system.
• In some cases, additional devices may be added to the sub-array: for example
Module or String Optimizers.

You can manage (add, copy, rename, move and delete) in the list on the left of the dialog.
There is a Pre-sizing help available, in the upper right corner in the system window. This
tool will suggest an automatic sizing of each sub-array, where you can specify either the
desired nominal power, or the available area for your modules.

As a consequence of this organization in sub-arrays, all the strings of modules connected


to the input of an inverter (or a MPPT input) are homogeneous, identical modules and
inverters, same number of modules in series, same orientation. These homogeneity
requirements in PVsyst are a general rule for any real installation, for instance not to put
a different number of modules in series on a same inverter input since this could have
negative consequences on the operating conditions of your system (namely for the MPP
research). Nor is mixing different module models on a MPPT input advised. Studying
arrays with different module kinds (for example a mix of power classes) is not possible in
PVsyst in the present time.

PVsyst SA – Grid Connected Systems – User’s manual Page 18


Each sub-array will be associated to an orientation. Normally all modules of a sub-array
should be in the same orientation. Mixing PV modules of different orientations within a
given string is not acceptable, as you may have big mismatch current losses due to
different irradiances (the current of a string is governed by the worst cell). However, you
can mix strings in different orientations, because the mismatch in voltage (strings in
parallel) is usually very low. PVsyst allows the creation of sub-arrays with 2 orientations
on a same inverter input.
4.2 Design the array
PV panels have a temperature coefficient, which indicates how their output voltage and
current change with variations in temperature. Typically, as the temperature increases,
the output voltage of the panels decreases.
Voltage at Maximum Power Point (VMPP) changes with temperature due to the
temperature coefficient, so it's crucial to consider the temperature while sizing the
voltage for the PV system.
Inverter Performance: The inverter converts the DC power generated by the PV panels
into AC power for use in the electrical system. Inverters also have temperature limits and
efficiency considerations. If the voltage is not appropriately sized for the temperature
conditions, the inverter may not operate optimally, leading to reduced energy production
or even potential damage to the inverter.

When designing the array, the number of modules in series has to stay within the
requirements of

PVsyst SA – Grid Connected Systems – User’s manual Page 19


• Staying above the minimum inverter’s operation voltage Vmin of MPPT range (i.e.
at max. module operating temperature, 60°C by default)
• Staying below the maximum inverter’s operating voltage (i.e. at min. module
operating temperature, 20°C by default)
• To stay below the absolute maximum inverter’s input voltage (i.e. Voc at min.
temperature, -10°C by default)
• Not exceed the maximum system voltage specified for the PV module.

By clicking Sizing, you find a specific tool that gathers all the constraints relating to the
sizing of a specific system.
• For the number of modules in series and strings: the upper diagram shows the
I/V curve of the PV array, together with the MPPT range, voltage, power, and
current limits of the inverter. The little black dot should be within the safety
limits. In Project setting, these numbers can be modified if needed, this will not
affect the simulation, but the sizing and the IV curve.
• For the inverter sizing: the second graph, known as the system output power
distribution graph, illustrates the annual distribution of power generated by the
photovoltaic system. The horizontal axis displays power intervals, while the
vertical axis shows the total energy produced within each interval. This graph
highlights the most common power ranges, offering insights for optimizing
inverter sizing and assessing possible overload losses.

The optimal sizing of the inverter is based on the acceptable overload loss throughout
the year. It usually leads to over-size the power ratio (PV array nominal power with
respect to the inverter nom. AC power), by a factor of 1.25. Note that this is a first rough
estimation and that you later can define different losses such as near and far shadings.
Specialized tools are also provided to evaluate different losses due to wiring, module
quality, mismatch between modules, soiling, thermal behavior, mechanical mounting,
system unavailability, etc.
4.3 Multi MPPT and Power sharing feature
The MPPT technology, short for Maximum Power Point Tracking, enables a solar inverter
to independently track the maximum power point for each string or group of panels. Thus,
in the case of different length of strings or panels oriented differently on your site, in the
case of partial shading due to objects nearby or in the case of soiling; the multi-MPPT
allows the system to mitigate the impact by adjusting the operation of the affected
strings without affecting the others.
Choosing the option Pnom sharing within the inverter, PVsyst will equally distribute the
Power over the MPPT inputs automatically. If you have different configurations at the
input of Multi-MPPT inverters, you should define a sub-array for each kind of
configuration.

PVsyst SA – Grid Connected Systems – User’s manual Page 20


By selecting Independent MPPT inputs it is possible to consider the single MPPT inputs.
Below the inverter model selection, one thus selects a given number of inputs instead of
a number of inverters. If the inverter has the capability to shift part of the nominal power
between the MPPT inputs, this can be configured in the Power Sharing window. The
Power sharing ensures that the power generated by each MPPT controller is efficiently
distributed across the different strings or groups of panels by assigning each sub-array
to a power sharing group.

PVsyst SA – Grid Connected Systems – User’s manual Page 21


To the left in Power sharing window, you have the inverter configuration. By dragging a
subarray from the list to from the right the Inverter configuration window we can
associate sub-arrays for the same inverter. A summary of the characteristics of the sub
arrays will appear, that is the number of MPPTs, the nominal power at the specific MPPT,
the % of the total nominal power of the inverter, the installed PV power in the subarray as
well as the nominal power ratio in the sub-array. The power sharing will be balanced
automatically if “Auto-equal. Pnom” is checked. You also the option to manually balance
and/or adjust the power allocated to each sub-array if you untick this option. By clicking
the weight icon, the Pnom ratio is balanced and by clicking the rubber it re-sets the pnom
ratio.

5 Detailed losses
There are several parameters that are initialized by PVsyst with reasonable default values
for the first simulation, but that you should modify according to the specificities of your
system to add more accuracy to the simulation. These parameters are accessible with
the button "Detailed losses" in the project dashboard.
5.1 Thermal parameters
The thermal behavior of the array is computed in each simulation step by a thermal
balance. This establishes the instantaneous operating temperature used for the
modeling of the PV modules.
The thermal balance involves the Heat loss factor:

PVsyst SA – Grid Connected Systems – User’s manual Page 22


U = Uc + Uv · WindSpeed [W/m²·K]
In practice, we advise not to use the wind dependency, as the wind speed is usually not
well defined in the weather data, and the parameter Uv is not well known. Therefore, we
put Uv = 0 and include an average wind effect in the constant term.
According to our own measurements on several systems, PVsyst proposes:
• Uc = 29 W/m²K for completely free air circulation around the collectors (free-
standing collectors).
• Uc = 27 W/m²K for domes, a manufacturer has measured the U-value on several
installations (height about 40 to 70 cm above the ground)
• Uc = 20 W/m²K for semi-integrated modules with an air duct on the back.
• Uc = 15 W/m²K for integrated modules (back insulated), as only one surface
participates to the convection/radiation cooling.

The thermal loss effect is shown on the array loss diagram in the final report.
The ‘Standard NOCT factor’ (Nominal Operating Cell Temperature) is the temperature
that the module reaches in equilibrium for very specific surrounding and operating
conditions. It can often be found together with the module specifications supplied by the
manufacturers. It has no real relevance for the simulation because the conditions for
which it is specified are far from a realistic module operation. PVsyst only mentions it for
completeness and for comparison with the manufacturer’s specifications.
5.2 Ohmic Losses
The wiring ohmic resistance induces losses (R · I²) between the power available from the
modules and that at the terminals of the array. These losses can be characterized by just
one parameter R defined for the global array.

5.2.1 DC circuit: ohmic losses for the subfield


The program proposes a default global wiring loss fraction of 1.5% with respect to the
STC running conditions. But you have a specific tool to establish and optimize the ohmic
losses through the Detailed computation button. This tool asks for the average length of
wires for the string loops and between the intermediate junction boxes and the inverter
and helps the determination of the wire sections.

PVsyst SA – Grid Connected Systems – User’s manual Page 23


NB: remember that the wiring loss behaves as the square of the current. Therefore,
operating at half power will lead to only a quarter of the relative loss. The effective loss
during a given period will be given as a simulation result and shown on the loss diagram.
It is usually of the order of 50-60% of the above specified relative loss when operation at
MPP.
In older PV installations, it was common practice to include a blocking diode in series
with each string to prevent reverse current from neighboring strings in the event of a
mismatch. However, this approach is now considered unnecessary. Even when a string
is heavily shaded, its voltage typically remains near its open-circuit voltage (Voc),
rendering the diode ineffective. Additionally, these diodes were prone to failures, which
often went undetected. As far as we know, the use of blocking diodes in modern systems
has been largely abandoned and the Voltage drop across series diode can be left at 0.

5.2.2 AC losses after the inverter


It is also possible to include losses between the output of the inverter and the injection
point (energy counter). You just have to define the distance, and the loss will also appear
in the loss diagram.

In many large PV installations (in the MWp range), the transformer is not part of the
inverter, but an external device directly connected to the MV or even the HV grid.
• One or several Medium Voltage transformers for the whole system. PVsyst will
distribute equally the power output of all inverters to all transformers.
• One Medium Voltage transformer in each sub-array. The transformer properties
may be different in different sub-arrays, but each sub-array has to have one
transformer.
• There is the possibility to add a High Voltage transformer that steps up the voltage
before the injection point.

PVsyst SA – Grid Connected Systems – User’s manual Page 24


Note that, when including transformers, the distance from the inverter to injection
instead correspond to the distance from inverter to Transformer.

The main losses associated with a transformer are:


• The iron losses, which are mostly due to hysteresis and eddy currents in the
transformer core, are proportional to the square of the core flux, i.e. to the square
of the voltage. Since the grid voltage is constant, this will also be a constant loss.
As default value, PVsyst will use 0.1% of the reference nominal power.
• Night disconnect: The iron loss remains active and constant as long as the
transformer is connected to the grid, and this may represent a significant
energy loss. In the simulation results, this will show up as negative a E_Grid
system yield during the night. It may be economically profitable to foresee
a switch that disconnects the transformer from the grid during the night.
To activate this behaviour in the simulation, please check the option "Night
disconnect" next to the number of transformers. This option is global for all
transformers in the system.
• The ohmic losses, also named copper losses, are originated by the resistance of
the primary and the secondary windings of the transformer coils. These may be
represented by a single equivalent resistance R, and in the simulation this loss
will be computed as R * I². Like for the cable losses, this means that the relative
loss is proportional to the current (or power).
You can also specify the actual parameters of the selected transformer (recommended).
The essential information needed includes:
• the Nominal power,
• the Iron loss (often referred to as "no-load loss"),
• and the Copper loss.
Datasheets may provide either the overall loss at PNom or the total efficiency, from
which PVsyst can calculate the copper loss. Setting these real parameters based on the
transformer's datasheet will override the generic values.

PVsyst SA – Grid Connected Systems – User’s manual Page 25


Note: The generic Iron and Copper losses used in the simulation differ from the
transformer datasheet values, as they relate to PVsyst’s Reference PNom rather than the
transformer’s Nominal power.

5.2.2.1 AC ohmic losses: reference power


PVsyst proposes a generic Ohmic loss initial relative value, for the early stage of the
project's development. You can choose the reference power as either:
• PNomPV(ac): The nominal power of the PV array at STC (PNomPV [kWp]),
adjusted by the inverter’s efficiency. This was the default option in PVsyst before
version 7.2.
• PNom(Inv): The nominal output power of the inverter(s), without applying a
temperature correction.
This choice is done for each project, in the project's settings dialog.
In the main menu Settings > Preferences > Physical models > AC Loss references, you
may define the default initial value when creating a new project.
5.3 Module quality – LID - Mismatch
5.3.1 Module quality loss
The aim of this parameter is to reflect the confidence that you put in the matching of your
real module set performance with respect to the manufacturer's specification. By
default, PVsyst initializes the "Module Quality Loss" according to the PV module
manufacturer's tolerance specification. PVsyst will choose a quarter of the difference
between these values. For example, with -3...+3%, it will be 1.5%, and with positive
sorting 0..+3%, it will be -0.75% (i.e. a negative loss value, representing a gain). Note that,
this value of a quarter between low and high tolerance is the PVsyst choice. We usually
consider a conservative option (i.e. the modules will never be better than announced). It
doesn't have any other background reasons.

5.3.2 LID – Light Induced Degradation


LID (Light Induced Degradation) is a loss of performances arising in the very first hours of
exposition to the sun, with Crystalline modules. It may namely affect the real
performance with respect to the final factory flash tests data delivered by some PV
module providers.
It is unclear how it affects the performance with respect to the specified STC values. If
the modules are sorted according to their final factory flash test for determining their
Nominal Power class, the LID will indeed represent a loss with respect to STC.
The LID loss is related to the quality of the wafer manufacturing and may be of the order
of 1% to 3% (or even more).

PVsyst SA – Grid Connected Systems – User’s manual Page 26


It is very difficult to obtain data about the LID effect on a given module sample. This is
never referenced by the manufacturers of course. It depends on the origin of the Silicon
wafers, and may vary from product to product, but also may depend on batches of a given
production. As it is not sufficiently established, the LID loss is not proposed as default by
PVsyst. If you specify it explicitly, the proposed default value is 2%.
The LID effect occurs only with conventional p-type boron-doped wafers. Alternative
technologies using n-type doped wafers are not affected.

5.3.3 Module mismatch losses


Now when installing real modules in the field, the characteristics of each module are
never rigorously identical. The Module mismatch loss is mainly due to the fact that in a
string of modules (or cells), the lowest current drives the current of the whole string. This
parameter acts as a constant loss during the simulation. It is lower for thin film modules.
It can become almost zero if the modules are well sorted according to their real
performance (flash-test results provided by the manufacturer).
PVsyst includes a tool for understanding, and statistically estimating the corresponding
power loss (Detailed calculation). This tool first creates a statistical sample of modules,
setting Voc and Isc values according to a gaussian or square distribution. Then it adds
the I/V characteristics of each module in each string (add voltages) and then gathers the
strings in the array (add currents). Finally, it draws the resulting I/V curve of the array,
and identifies the MPP value, which is then compared to the MPP value of an array with
identical modules.
NB: There is probably a correlation between the Module mismatch losses and the
Module quality loss and LID. The Module quality loss is rather related to the average of
the module's distribution, while the mismatch refers to its width.

5.3.4 Strings voltage mismatch


The mismatch between strings is related to the voltage differences and involves a
displacement on the I/V curves. This results in general in very low power losses. Reasons
for voltage mismatch can be:
• That the string wire length is different from string to string, especially with big
systems (centralized inverters).
• That the temperature may be different from part to part of a big system (colder at
the edges).
• With big systems, the irradiance may be varying from part to part of a system in
case of clouds etc passages.

PVsyst SA – Grid Connected Systems – User’s manual Page 27


This is a transient effect, affecting usually some few seconds or minutes within the hour.
PVsyst neglect this in the present time.
5.4 Soiling loss
Accumulation of dirt and its effect on the system performance is an uncertainty which
strongly depends on the environment of the system, raining conditions, etc. Soiling loss
may become significant in some industrial environments or in desert climates. The
soiling loss can be defined individually for each month to consider periodical cleaning or
rainy periods. This parameter may also be used for describing the effect of snow covering
the panels.

5.5 IAM Losses


The incidence effect (the designated term is IAM, for Incidence Angle Modifier)
corresponds to the decrease of the irradiance really reaching the PV cells’ surface, with
respect to irradiance under normal incidence. This decrease is mainly due to reflections
on the glass cover, which increases with the incidence angle.
The transmission loss (passage of light through materials) is a general phenomenon, due
to the reflection and transmission of the sun's ray at each material interface (air-glass,
glass-EVA, EVA-cell), as well as some absorption in the glass. The IAM only concerns
the angular dependency of this effect, i.e. it is normalized to the transmission at
perpendicular incidence (0° incidence angle).

PVsyst SA – Grid Connected Systems – User’s manual Page 28


PVsyst uses an IAM function, which describes the deficit of transmission as a function of
the incidence angle. This function is applied to the beam component, and to the diffuse
and albedo, using an integral over all seen directions, supposing an isotropic distribution
of the diffuse irradiance.
In principle, this phenomenon obeys the Fresnel's Laws describing transmission and
reflections at the interface of two transparent materials of different refraction indexes.
This is a very general behavior, derived from the general Maxwell's equations describing
all electric phenomena. These laws allow to calculate the light effectively reaching the
cell's surface below the protective layer (usually glass), as a function of the incidence
angle. Now you can add an anti-reflective coating on the top interface air-glass. This thin
layer has a lower refraction index than the glass, which limits the first reflection.

The IAM model is defined with the PV module parameters, page Additional data,
Customized IAM. If the IAM curve is highly over evaluated with respect to the Fresnel’s
laws, you will have a warning message while opening the .PAN file. An over evaluated IAM
curve could lead to an overestimation of your system’s production.

In the Additional Data, Customized IAM you can modify an over evaluated IAM curve by
choosing the Default Fresnel. This manipulation can also be done through the detailed
losses window, IAM Losses tab.

PVsyst SA – Grid Connected Systems – User’s manual Page 29


5.6 Auxiliaries
Auxiliary consumption refers to the energy required to operate the system, including
components such as fans, air conditioning, electronic devices, lighting, or any other
energy usage. This consumption must be subtracted from the PV energy produced before
it is injected into the grid.
It is defined globally for the entire system and is only taken into account in the
simulation if the "Auxiliaries consumption defined" option is activated.

5.7 Aging
The PV module degradation gives rise to a progressive loss of efficiency, which we will
characterize by a Degradation Loss factor.
The simulation may be run for a specified year of the PV system life and will apply the
degradation for this year. The degradation means a decrease of the PV array yield. It may
sometimes have some "positive" effect on the full system behavior, which may lessen a
little bit the degradation effects. This may be namely a diminution of the overpower
losses when the inverter is strongly undersized.
The Manufacturer's warranty should be understood as a lower limit for any individual PV
module. In this tool we define an average degradation rate (for a set of modules). This
loss value may be much lower than this guaranteed limit. Some experimental studies
mention degradation rates of the order of -0.3%/year measured as an average on several
modules (and measured with very old modules manufactured in the years 80-90, with
old technologies). Long-term degradation rate measurements are relatively scarce.
NB: Nothing prevents to limit the lifetime of the PV modules to 25 years. A well-
maintained PV system may probably stay operational over much longer periods.

PVsyst SA – Grid Connected Systems – User’s manual Page 30


Moreover, all the modules will not degrade with the same rate. If you have a distribution
of loss rates around this average, this will produce an additional loss due to mismatch,
increasing with time.
In PVsyst, you can specify the RMS of this distribution (supposed gaussian), and the
program will evaluate the mismatch as function of the age of the system. This calculation
is performed using a Monte-Carlo method (choice of a great number of random
distributions), with the following hypothesis:
• the degradation rate of each module is constant over the years,
• the distribution choice is limited to 2 sigmas (95% of the hits); because high
discrepancies result in very high mismatch losses.
You can choose to tick the box Keep calculated Mismatch values, to ensure that you run
the same Monte Carlo generated values in every simulation. You can also save them as
a model and apply the same random distribution to other projects.
5.8 Unavailability of the System
It is sometimes useful to consider system failures or maintenance stops in the
production expectations. You can define system unavailability as a fraction of time, or
number of days. As this is usually unpredictable, you have the possibility to define
specific periods of unavailability of the system and generate these periods in a random
way. The effective energy loss depends on the season and the weather during the
unavailability periods. Therefore, the unavailability loss has only a statistical meaning.

PVsyst SA – Grid Connected Systems – User’s manual Page 31


5.9 Spectral correction
Spectral correction accounts for changes in the solar spectrum caused by scattering and
absorption in the atmosphere. These changes depend on factors such as atmospheric water
content, aerosols, and the distance light travels through the atmosphere—expressed as Air Mass
(AM).
PVsyst implements several models to describe spectral correction:
1. The CREST model: Used for amorphous silicon modules, this correction is applied
automatically when spectral correction is activated.
2. Spectral correction for PV modules in the Sandia database: This correction is also
applied automatically when spectral correction is activated.
3. The FirstSolar spectral correction model: Disabled by default, but it can be enabled by
the user.

When spectral correction is enabled, the simulation by default uses the set of
coefficients associated with the PV module technology. However, it is possible to modify
this setting by unchecking the corresponding box and selecting another set of
coefficients from the available options. In this case, the coefficient set will no longer
adapt to any changes in the PV module in the system definitions, and it is the user’s
responsibility to ensure a relevant set is chosen for the simulation.
The FirstSolar spectral correction model uses the Air Mass and Precipitable Water
Column as input variables. The air mass is computed from altitude and sun position,
while the precipitable water has either to be present in the weather data file, or be
estimated from relative humidity. Therefore, this correction can only be applied in the
simulation, if either the precipitable water or the relative humidity are present in the
weather data variables. For synthetic hourly weather data files created with PVsyst 6.7.4
or later, the relative humidity is always present.

PVsyst SA – Grid Connected Systems – User’s manual Page 32


If the spectral correction is used in the simulation, this will be mentioned on the final
report. The system summary will list the set of coefficients that was used, and the loss
diagram will feature a contribution called 'spectral losses'.
5.10 Losses graph
To visualize the impact of losses on the I/V behavior of the PV system, click on "Loss
Graph" located at the bottom of the detailed losses settings window. This will open a new
window titled "PV Field Behavior for Each Loss effect." In the new window, at the top right,
you can define the external conditions of the array. In the field below, select the type of
loss you wish to display. The red curve indicates the nominal conditions, representing
the upper limit of the system's performance. For each selected loss, a curve in a different
color will appear.

6 Self-consumption
The self-consumption in PVsyst allows users to assess how much of the solar energy
generated by the PV system is consumed locally within a specific building or facility. This
analysis helps to understand the proportion of their electricity needs that can be met by
solar energy. This type of system is connected to the grid, and any excess energy can be
fed back into the grid when it is not being consumed by the user.
There are various options to define the load profile:
• Fixed constant consumption is the most straight forward method to define the
user's needs. You simply specify a constant power or yearly energy.
• Monthly values allow you to define monthly averages, which the simulation will
treat as constants throughout each month. There is no daily modulation.
- Values are defined using the graphic tool in the "monthly values" tab.

PVsyst SA – Grid Connected Systems – User’s manual Page 33


• Daily profiles allow users define hourly values that can be modulated according
to 4 different profiles:
o Constant over the year: The same profile is used throughout the year
o Seasonal modulation: Different daily profiles for each season
o Monthly normalization: where a daily profile can be defined for each
month
o Weekly modulation: Separate daily profiles for "working days" and
"weekends."
• Probability profiles allow you to establish the probability that you will consume
a certain level of power
• Household consumers provide a list of common domestic appliances,
including unit power and daily usage duration.
• Load values from a CSV hourly/daily file to define custom load profiles. You
can select a template from a predefined list, which can be rescaled to match
your specific consumption needs or upload your own profile, following the
required format.
o The first column should contain the date. For sub-hourly data, PVsyst will
automatically convert it into hourly values for the simulation.
o The date format must include the day, month, year, hour, and minute.
o The second column should contain the load values, with the unit
specified in the second row of this column.
o The file must be a CSV format with semi-colon delimiters.
By running the simulation, we will get results concerning the non consumed energy that
is injected to the grid, the energy consumed by the user and the energy consumption from
the grid, representing the energy needed when there is not sufficient production, for
instance at night.

7 Storage
The battery storage implementation in PVsyst include to 3 storage strategies:
• Increased Self-consumption
• Peak shaving, when the grid-injection power is limited
• Weak grid recovery, for ensuring an electricity supply when the grid is failing.
Each of these strategies have different constraints. For instance, the self-consumption
and Weak grid recovery require the definition of a user's needs hourly profile, where Peak
shaving doesn't involve a user's needs profile. The battery energy will not be used for
feeding the grid, except with peak shaving. The time of release of the battery energy
(discharge) may be different according to the strategies, cost optimizations, etc.
The sizing of the different parts of the system (PV array, battery pack, as function of the
load profile and the electricity price), is a complex problem, specific to each of these

PVsyst SA – Grid Connected Systems – User’s manual Page 34


strategies. PVsyst provide rough sizing rules until some experience has been
accumulated.
After selecting a strategy, you will have one window for the Storage Pack and others for
the specific strategy. The Storage pack window is consistent across all strategies. To
specify the battery set, begin by choosing the battery technology, and selecting a specific
battery from the database. Next, define the number of batteries in series and parallel to
configure a battery pack with the characteristics required. The configuration suggested
by PVsyst will be based on the size of your system, the strategy, the consumption profile
etc and should not be seen as the optimum configuration, but a suggestion.

On the right side of the battery configuration, you can see several figures that summarize
the properties of the battery pack.
• The Battery pack voltage will be rounded to an integer value.
• The global capacity (C10) of a battery refers to the battery's total energy storage
capacity when discharged over a 10-hour period. In this context, "C10" indicates
the amount of energy in ampere-hours (Ah), the battery can supply continuously
for 10 hours before its voltage drops below a specified threshold. This value
helps characterize the battery's performance under a moderate discharge rate,
commonly used for evaluating storage systems.

PVsyst SA – Grid Connected Systems – User’s manual Page 35


• Stored energy at 80% depth of discharge (DOD) refers to the amount of energy
that can be drawn from a battery when it is discharged to 80% of its total
capacity. In this context, the term highlights the battery's usable energy when
80% of its capacity is utilized, leaving 20% as reserve. The state of Charge (SOC)
can be defined in the next window. If you change the Minimum discharge (OFF)
from the default value of 20%, the DOD in the storage pack window will adapt
accordingly. For Lithium-Ion batteries the charging cycle should never be 100% DOD, since
a deep discharge or an overcharge reduce the battery lifetime or can even cause
irreversible damage.
• The total weight is also displayed for information, to give a rough idea of the
physical size of the battery.
• The next line shows the number of cycles that can be performed at 50% Depth of
Discharge, before the battery reaches the end of its life.
• Finally you can read off the total energy that can be stored over the battery
lifetime.
In the bottom left box, you can choose the battery operating temperature that will be
used in the simulation. The battery temperature is used in the aging model of the battery.
An increase of 10°C in the operating temperature reduces the "static" battery life by a
factor of two. In the System information box, you find additional information about your
defined system as well as some estimation about the behaviour of the battery pack.
7.1 Self-consumption with storage
The self-consumption strategy with storage has the objective to increase self-
consumption by storing excess energy, that can be consumed when the production is
not enough to fulfill the users need. Excess energy from PV generators can also be
injected into the grid when the batteries are fully charged, but in this strategy, the energy
in the batteries will only be for self-consumption and will never be injected into the grid.
The load profile must be defined beforehand, and the battery charging will start as soon
as there is an excess PV generation.
By default, PVsyst set up the battery state of charge thresholds for maximum charging
and minimum charging such that when the battery attains 95 percent of his capacity, we
will stop charging and we will discharge, after 20 percent of his capacity, we will stop
discharging.
In Operating conditions, we can read an explanation on how batteries will be charged
and discharged. Also, you have the option to allow or not to inject solar energy to the grid.
In Battery input charger, PVsyst suggests a default value of the maximum charging power
based on the possible charging power at maximum irradiance value and charging time
during full sun conditions. Increasing the Maximum charging power will reduce the time
of full charge duration. The battery should not charge too fast: for Lithium-Ion batteries,
a full charge in 1 hour is the minimum reasonable to not compromise the lifetime of the
battery. The possible excess power will be injected into the grid. By default, PVsyst sets
the maximum discharge power based on the load profile predefined in self-
consumption. In order to optimize the lifetime of the battery, please refer to the
datasheet to know the adequate discharge time without damaging the battery. If you for

PVsyst SA – Grid Connected Systems – User’s manual Page 36


instance reduce your discharging power and increase the discharge duration of the
batteries, when you need more power, your system will take it from the grid.

7.2 Peak shaving


If the grid operator limits the power that can be injected into the grid, a battery pack can
store energy during periods of overproduction and inject it at a time when the PV
generation drops below the injection limit. The Peak shaving strategy cannot be used in
combination with a self-consumption profile.
In the Operating condition you must define a Grid power limit and a discharging strategy,
you can choose between 4 options:
• The first option, which is also the default, is “As soon as power is needed”. With
this option selected, the battery will start injecting energy to the grid as soon as
the generated AC power is less than the grid power limit
• The second option is “after sunset”. Here, the grid injection only starts when the
PV generation has dropped to zero at the end of the day.
• The third option is “from a specified hour”. If you select this option, a field will
appear, allowing you to input an hour of the day. Injection from the battery to the
grid will only happen from that hour onwards

PVsyst SA – Grid Connected Systems – User’s manual Page 37


• The fourth and last option is “during a specified hourly period”. With this option
two fields will appear, allowing you to input specific hours of the day. The battery
discharging will only be possible between these two values.

7.3 Weak grid islanding


This option concerns regions where the grid is not reliable (numerous cuts due to load
shedding). This strategy requires the definition of a consumption profile and of a
schedule of grid unavailability.
The PV energy is stored in a battery and returned to the user when the grid is unavailable.
Technologically, this is far from being simple, as the usual solar inverters for feeding the
grid require the presence of the grid for working. There may be several ways for avoiding
this problem.
For the energy fluxes
• When the sun power is sufficient for feeding the user's needs, the rest is used for
charging the battery. If the battery is full the excess will be injected into the grid if
this is allowed, otherwise this energy will be lost (i.e. the inverter will operate at
reduced energy level).

PVsyst SA – Grid Connected Systems – User’s manual Page 38


• When the sun is not sufficient (or during night) the user may be fed by the battery.
However we should keep a storage reserve for the case of grid unavailability.
Therefore we have to define a limit DOD for using the energy in any case, and
another one for supplementing the grid when it is down.
• In case of grid failure, the switch should immediately open, and the user will be
fed by the sun's energy + battery through the SA inverter.
• The control device should be able to limit the solar inverter's power if the injection
into the grid is not allowed.
You have first to define the grid unavailability. This may be done:
• either by specifying the unavailability fraction of time, the number of periods and
the minimum / maximum duration of each period. Then the program can propose
a random distribution of unavailability periods along the year.
• or define an hourly sequence of unavailability for the whole year in a CSV
(msExcel) l file.

The battery pack capacity is closely related to the user's needs. Ideally, the remaining
energy below the SOC higher level should allow to cover the maximum needs for the
longer unavailability period. You can obviously diminish this capacity, at the risk of
feeding failure.

PVsyst SA – Grid Connected Systems – User’s manual Page 39


You can choose to define the unavailability as random periods or by reading a file. By
clicking on "Show graph," you can visualize the unavailability periods throughout the
year.

8 Horizon
The horizon profile is suited for shading objects that are located sufficiently far away from
your PV system, so that the shadings may be considered global on your array. This is the
case when the distance of the shading object is more than about 10 times the PV system
size. The Horizon Profile is a curve that is defined by a set of (Height, Azimuth) points.
The Far Shadings operate in an ON/OFF mode: i.e., at a given time, the sun is or is not
present on the field. When the sun is behind the horizon, the beam component becomes
null. The effect on the diffuse component will be explained below.
Clicking the "Horizon" button will open a graph of the sun paths for the site of the project.

The horizon profile may be defined manually by a set of (Azimuth/Height) points in


degrees. These may be from on-site measurements (using land-surveyors instruments
like compass and inclinometer). They can be imported from several sources, either as a

file or from web sources by clicking:


A PVsyst internal file is a horizon line already saved in your workspace. A standard CSV
can be any text file containing properly structured data. PVsyst will recognize files as
valid horizon profiles if they meet following characteristics:
• File with text or CSV format, containing columns separated with comma,
semicolon, tabulation or space.
• Header/comments:
- All lines containing text are considered comment lines

PVsyst SA – Grid Connected Systems – User’s manual Page 40


- Comment line containing text such as "Latitude 25.3°, Longitude 44.1°" will be
used as a comment for the generated horizon. This comment can later be
manually edited.
• Data:
- One line per defined point. Each point defined as an Azimuth and
a Height value, expressed in degrees.
• Before import, you can define the angular reference for your file with the Direction
of rotation of azimuth as Clockwise or Counterclockwise and the North azimuth
angle.
• The Meteonorm software produces Horizon profiles, which you can also import in
PVsyst. The file name of these profiles holds the exact coordinates of the site
evaluated.
The horizon line can also be imported from web sources directly (with an active internet
connection):
• The free service PVGIS provides worldwide horizons. This service is completely
integrated in PVsyst, manually downloading the profile from the web page is not
necessary. Simply choose "PVGIS Horizon From WEB" and press the Import from
web button.
• The included Meteonorm web service for horizon profiles provides worldwide
horizons.

For horizon profiles established using a geo-reference grid (like PVGIS and Meteonorm),
the exact location should be carefully defined. You can edit the latitude and longitude in

PVsyst SA – Grid Connected Systems – User’s manual Page 41


this window to be as precise as possible: keep in mind that a degree in latitude is 111 km,
the second decimal is 1.1km and the 4th decimal is 11m. The 4th decimal can still have
a big impact in places with high slope.

9 Near shading
The "Near Shading" window is the main dialog providing access to the 3D editor for
constructing scenes representing nearby shading. This functionality is essential for
simulating the shading impact on photovoltaic (PV) modules, thereby calculating the
resulting energy losses.
The "Construction/Perspective" button is the key element for accessing the 3D scene
editor. This allows defining surrounding objects that may create shading, such as
buildings, trees, or other obstacles, to accurately model the PV modules' environment.

It is important to note that the primary objective of near shading is to precisely represent
irradiance losses due to nearby objects and to help optimize the solar panel installation
to minimize these losses. When defining objects that may create shading, as well as the
topography, it is advised not to get too detailed and avoid spending time drawing every
object precisely. The more detailed the 3D scene, the longer the software will take to
calculate shading on the PV scene. Therefore, it is preferable to keep the drawing simple
and representative of the project to ensure efficient calculations.

PVsyst SA – Grid Connected Systems – User’s manual Page 42


9.1 Compatibility between the 3D Scene and System-Orientation
Once the 3D scene is constructed, the program will check this construction’s
compatibility with the previously defined PV system parameters, such as the orientation
and layout of the modules. This ensures a consistent and reliable simulation of losses
due to near shading.
In this section, several important pieces of information allow control over compatibility
between the 3D scene and the system definition, as well as orientation.

First, there is a dropdown list for the different existing orientations. Next, information
about the number of sub-fields, the surface area of existing PV modules, and, finally, the
total number of PV modules is displayed.
Matching orientation between the 3D scene and the orientation definition is mandatory.
If an incompatibility is detected, the program will ask if you want to update the orientation
definition to match the 3D scene.
Regarding the PV modules' surface area, the software accepts a tolerance for differences
between the system definition and the 3D scene. This tolerance accounts for slight
variations that may occur during scene construction while ensuring consistent surface
areas.
Finally, the total number of PV modules should be close between the system definition
and the 3D scene, with a small tolerance accepted.

PVsyst SA – Grid Connected Systems – User’s manual Page 43


9.2 Simulation Parameter
Three parameters calculate shading-related losses:

Linear Shading
This mode only considers the irradiance deficit on the PV field without electrical effect.
It represents a lower limit of total shading losses. You can run this simulation quickly (by
interpolating values from the shading factors table at each step) or more accurately but
slower, calculating the complete shading factor at each simulation step.
By Module String
While creating the 3D scene, you can group the modules into distinct strings. With this
option, a shading factor is calculated for each string, and the electrical losses related to
shading on each string are estimated individually. This provides a more detailed estimate
of the electrical effects than a simple linear shading calculation.

PVsyst SA – Grid Connected Systems – User’s manual Page 44


For a more precise result, you can specify the electrical effect fraction from "pure linear"
calculation (fraction for electric effect of 0%) to full electrical effect (fraction for electric
effect of 100%).
The partition model estimates electrical loss but does not account for module bypass
diodes.
Detailed Electrical Calculation (acc. To module layout)
Finally, after specifying a detailed configuration of the "module arrangement" in the 3D
scene, you can perform shadow calculations based on detailed electrical losses. The
“module layout” tool is designed for precise mismatch shadow loss calculations.
This simulation type requires a precise description of each PV module's position in the
3D scene and the interconnection of modules into strings according to the inverters
defined in the "System" section. This allows highly accurate modeling of shading effects
on each module, including losses due to current mismatches between strings.
The advantage of this model is that it calculates shading on inverter-connected strings
and considers bypass diodes, which circumvent shaded zones and thus reduce power
losses. This model allows for a more precise shading-related electrical loss calculation
than the partition model.

PVsyst SA – Grid Connected Systems – User’s manual Page 45


9.3 Orientations, table, graph buttons
Orientations
The "Orientation" button opens the orientation management window without having to
leave this window, enabling additional orientation management operations.

Table
The Table button enables you to build the shading factor table, which calculates the
shading factor for different directions from which sunlight comes.
This process calculates the diffuse and albedo attenuation factors, which remain the
same throughout the year.
Following this, you can view the Iso-shading diagram and start the simulation.
If you set up a partition in module strings when building your 3D model, two tables will be
generated at the same time: one for the standard "irradiance" or "linear" shading factor,
and another based on the module strings.

PVsyst SA – Grid Connected Systems – User’s manual Page 46


The Shading Factor represents the proportion of the PV field that is shaded relative to its
total sensitive area, for a specific sun orientation (where 0 means no shading and 1
means completely shaded).
Calculating this at every step of the simulation could be time-consuming. To address
this, the program creates tables with pre-calculated Shading Factor values at intervals
of 10° for sun height and 20° for azimuth. These tables allow quick interpolation to
determine the Shading Factor for any direction of sunlight, a method known as "Fast
calculation" mode.
It’s possible to calculate the Shading Factor at every step of the simulation to avoid errors
from interpolation, referred to as "Slow calculation" mode. In this scenario, the pre-
calculated tables are not used for determining the shading on the beam and circumsolar
components.
Graph
The iso-shading diagram visually represents the shading factor table. It displays contour
lines for specific shading factors, overlaid on the paths that the sun takes through the
sky.

PVsyst SA – Grid Connected Systems – User’s manual Page 47


Blue lines on the diagram mark the points where the sun’s rays are parallel to the surface.
This diagram provides a concise overview of how shading varies with the seasons and
times of day throughout the year.
The irregular look of the lines is due to the interpolations across discrete calculation
points.
Remember that this loss factor applies to the beam component reaching the PV plane.
When the incident angle is high, even high loss factors will act on very low irradiance
component, giving rise to reasonable effects on the overall efficiency.

9.4 Construction/Perspective, 3D scene


Clicking on the "Construction/Perspective" button opens a new window where the 3D
scene is located.

PVsyst SA – Grid Connected Systems – User’s manual Page 48


To begin, there are several strategies for creating a 3D scene in PV.

First Strategy: You can create your PV tables as well as objects that will cast shadows
on the PV tables.

Second Strategy: You can import a 3D scene created with another software. The
following formats are supported for import:
3DS, DAE, PVC, H2P.

PVsyst SA – Grid Connected Systems – User’s manual Page 49


More information can be found in the tutorial "Exporting 3D Scene to PVsyst."

Third Strategy: This involves combining the first and second strategies. You can import
a PV scene and then modify it in PVsyst by adding additional objects that may create
shading.
It is also possible to import a topography with a satellite image of your site specified in
the "Project" section.

File menu
Several actions are available:
New Scene: Allows you to create a new
scene by clearing the previous one.
Read Scene: Loads a previously
exported scene using the "Export Scene"
function.
Read Building: Loads a building
exported with the "Export Selected
Element" function.
Read Object: Loads an object exported
with the "Export Selected Element"
function.

PVsyst SA – Grid Connected Systems – User’s manual Page 50


Export Scene: Allows exporting the
entire scene to save it for future projects.
Export Selected Objects: Exports the
selected object for later re-import.
Save Scene View: Saves the scene view
to record it as an image.
Print: Prints the 3D scene.

9.5 Create Menu


The "Create" menu is divided into two main sections:

Object Creation
The first section is dedicated to creating different scene objects. PVsyst allows creating
a variety of 2D and 3D objects to represent elements like buildings, trees, roofs, and other
architectural obstacles. You can choose from a library of basic objects (2D and 3D
shapes, construction elements) and assemble them to build more complex objects. It's
also possible to customize the terrain topography by creating specific ground objects.
Created objects can be adjusted in terms of dimensions and position to fit your PV
installation layout.
In the shape type, several models are available:
First, there are surface models, which are simple, elementary 2D shapes, and surface
models, which are elementary 3D models.

PVsyst SA – Grid Connected Systems – User’s manual Page 51


In this list, the construction objects are basic, with trees being a useful model example.
Lastly, there are special shapes like a wind turbine

and an electric pylon.

PVsyst SA – Grid Connected Systems – User’s manual Page 52


PV Element Creation
The second part of the "Create" menu concerns creating photovoltaic elements. This
includes creating different types of PV fields, such as:

Single PV Table: A rectangular area intended to host PV modules.


Tracker Row: One or more tables that follow the sun to maximize irradiance reception.
Table Row: Multiple tables placed one behind the other, commonly used in ground
installations.
Dome Row: Groups of tables in an East-West opposing configuration.

PVsyst SA – Grid Connected Systems – User’s manual Page 53


Sunshade Row: Vertically aligned tables, suitable for facades.
Rectangular PV Plane (single or multiple): Frame-less sensitive rectangles that can be
created in multiple instances within the same plane.
Polygonal PV Plane: A field of any shape drawn with the mouse, allowing maximum
flexibility.
For each PV field type, you can define specific parameters like orientation, the number
of tables, layout, spacing between tables, etc. These parameters can be adjusted to
meet your installation’s needs and optimize energy production.
The created objects and PV fields can then be integrated into the 3D scene to simulate
shading effects and other environmental factors on your installation accurately.
9.6 Edit Menu
In the "Edit" menu, several tools allow you to manipulate a scene object.

Undo: Reverses actions, can be done with


"CTRL+Z".
Redo: Reapplies an action that was undone, can
be done with "CTRL+Y".
Copy: Copies an element, can be done with the
"CTRL+C" shortcut.
Paste: Pastes a copied element, can be done with
the "CTRL+V" shortcut.
Edit an Object: Allows modifying a scene object
by double-clicking on it.
Delete the Selected Object: Deletes the
selected object, can be done with the "DEL"
shortcut.
Move Selection: Moves the selected item, also accessible from the main menu.
Rotate Selection: Rotates the selected item, also accessible from the main menu.
Rotate whole scene: Applies azimuth rotation to all scene objects.
Modify selected objects: Opens the "List and Object Management" window for grouped
modifications, accessible with "CTRL+G."
Set Auto Altitude: Sets an object’s automatic altitude based on another object, useful
for automatically setting a PV object's altitude on a surface.

9.7 Transform Menu


The transform menu allows changing an object's surface into a PV surface.

PVsyst SA – Grid Connected Systems – User’s manual Page 54


Transform to PV Faces: Selected faces can be transformed into a PV surface.
Transform to Objects: Converts PV surfaces to non-PV objects.
Convert Fixed Tables to Trackers: Converts the selected PV table into a tracker.
Transform Selected PV Tables to arrays of tables: Converts a single PV table into a PV
table field.
Transform Selected PV Tables to a Single array of table: Converts multiple single PV
tables into a single table row.
Transform to Ground Object: Converts an object into a ground object.

9.8 Tools Menu


Orientation understanding educational
tool: This tool opens an educational
resource to understand the orientation of PV
tables.

PVsyst SA – Grid Connected Systems – User’s manual Page 55


In the Base slope tab, users can view a PV table with an initial orientation and apply a
base inclination, such as ground slope, to see the resulting tilt and azimuth. Users can
experiment by inputting a "Nominal Inclination," "Nominal Azimuth," and adjusting the
"Base Inclination," potentially representing terrain slope, to observe the final tilt and
azimuth after applying the base inclination.

The Angle Between Planes tab helps users understand the angle value between the
normal of two PV table planes by adjusting their orientations. Users can experiment to
see the angle difference between two PV planes, which appears in the "Angle Between
Planes" area.

PVsyst SA – Grid Connected Systems – User’s manual Page 56


Thin objects shading analysis:
This tool demonstrates the effect of fine shading on a PV surface. Users can input
variables like the width of a narrow object, the distance from the object to the PV surface,
and the PV cell's size. This tool calculates and shows the maximum shading percentage
on a PV cell based on these parameters.

PVsyst SA – Grid Connected Systems – User’s manual Page 57


Trackers diffuse shading definition:
Dedicated to PV field trackers, this tool defines the contribution of diffuse light on PV
tables. Users can set up a representative tracker to calculate shading factors for use in
simulations, reducing diffuse shading computation time compared to using all trackers.
Options include:
• select the central tracker in the scene
• select manually a tracker
• select all trackers

PVsyst SA – Grid Connected Systems – User’s manual Page 58


Shading Scene Summary:
Opens an informative window listing all objects in the project scene.

PVsyst SA – Grid Connected Systems – User’s manual Page 59


List and Management of object (Ctrl+G):
Opens a window listing all scene objects for easy modification.

Automatic Altitude: Opens a tool to place PV objects above other objects automatically.

Orientation Management (Ctrl+Shift+O):


The Orientation Management window lets users view a list of scene orientations and
check for consistency between the 3D scene and system definition. Users can review the
matching PV surfaces and module count between the definitions, reassign existing
orientations to new ones, and see orphan orientations to reassign.

Backtracking Management
PVsyst’s backtracking management tool optimizes the backtracking strategy to minimize
mutual shading between PV trackers. It identifies two reference trackers to calculate the
backtracking angle for all scene trackers. This tool is accessible in the PVsyst 3D editor,

PVsyst SA – Grid Connected Systems – User’s manual Page 60


helping users select optimal parameters based on distances between trackers,
supporting irregular configurations, and minimizing electrical losses from shading.

When defining a backtracking strategy, PVsyst identifies two reference trackers to


establish the backtracking relationship (tracker width and distance). During simulation,
the same backtracking angle applies to all trackers based on this reference.

In 3D scenes, trackers are often defined independently in external CAD software, but
PVsyst groups them into tables, making it necessary to identify a reference tracker pair
for full backtracking calculations.

This tool lists distances between neighbouring trackers in descending order. Selecting a
tracker with the highest ground coverage ratio (GCR) allows for a recommended
neighbour tracker (highlighted in orange) to associate with. Users can set backtracking
reference parameters automatically or select specific tracker fields in the list.

PVsyst SA – Grid Connected Systems – User’s manual Page 61


The selected tracker series appears in green, both in the scene and in the list.

PVsyst SA – Grid Connected Systems – User’s manual Page 62


Check Scene Validity: Verifies the validity of the 3D scene.
Disable Field Interpretation Check: Sometimes, objects touch PV surfaces in the
scene, despite minimal spacing, such as a roof and PV module. PVsyst flags this as a 3D
interpenetration error, which can be ignored by disabling this setting. Use caution as
shading calculations may be impacted.
Use Partial Shading Calculations: Calculates shading on an entire scene over a small
selected PV area. This reduces computation time for large, resource-heavy scenes and
is useful for homogeneous shading scenes.
9.9 Main Menu
This chapter explains the main menu visible on the 3D scene window.

History: Actions like creating, selecting, or modifying objects are logged,


allowing undo/redo.
• Undo : Ctrl+Z
• Redo : Ctrl+Y

Selection:
• Default Selection: Press Esc to deselect an object.
• Click any object to select it; click edges in technical view to select an object.
• Rectangle Selection: Shift+Ctrl+R
o Click and drag to draw a selection rectangle.
o You can specify whether you wish to select all objects touching the
rectangle, or only those inside it.
• Lasso Selection: Ctrl+L
o Click and drag to draw a selection area.
o You can specify whether you wish to select all objects touching the area,
or only those insides.
• Add to Selection: Hold Shift
• Remove from Selection: Hold Ctrl
• Select All: Ctrl+A

Point of view

PVsyst SA – Grid Connected Systems – User’s manual Page 63


Move View: Click and drag to move the viewpoint.
Rotate Camera: Click and drag to rotate around the current target.
Perspective View**: F2
Top View: F3
Front View: F4
Side View: F5
Sun View: F6 - Aligns the view to the current sun position; adjust in the right-side "Tool"

tab.

Zoom Options
Zoom In: F7
Zoom Out: F8
Zoom by Rectangle: Click and drag to define the viewing area.
Fit Zoom: Ctrl+F - Zooms to see all selected objects.
All these tools are also accessible in the View menu.

PVsyst SA – Grid Connected Systems – User’s manual Page 64


Additional Tools

Observer Position: Opens the "tools" tab on


the right, allowing a precise observer viewpoint.

Center on Selected Object: Centers the view on a selected object.

Back to Default View: Resets the observer to the default


position, looking towards the scene origin (X=0; Y=0; Z=0).

PVsyst SA – Grid Connected Systems – User’s manual Page 65


Rendering Options
Technical View/Realistic View:
• Technical View:
o Displays objects in wireframe; selectable by edges only. Colours are
defined by object type and selection state, without real-time lighting or
shadows.
• Realistic View:
o Objects appear more realistic; selectable on any visible part. Colors are
customizable for each object, with real-time lighting.
• Perspective / Orthogonal Projection
o Orthogonal Projection: This is the default and is recommended when
constructing the scene.
o Perspective Projection: Provides a more realistic view of the scene, useful
for creating shadow videos or reports.

Module Chains: Displays the module chains defined in the module layout.

PVsyst SA – Grid Connected Systems – User’s manual Page 66


Other Rendering Options

In the "View / Rendering Options" menu, you can enable/disable the following:
• Enable anti-aliasing: Smooths object edges. Availability may depend on your
hardware and could reduce performance.
• Enable real-time shadows: Enables real-time shadow viewing. Activating this
option may reduce performance.
• Enable camera animation: Animates the transition when switching views.
Activating this option may slightly reduce performance.
• Show backfaces: Shows or hides the back faces of objects, meaning those not
oriented toward the viewpoint. Hiding them increases performance.

Measure
Measure a Distance: Ctrl+L - Click to set the starting point, then click again to set the
end point. Hold Ctrl to snap to an object vertex.
Measure an Angle: Ctrl+K - Click to set the vertex, then points #1 and #2. Hold Ctrl to
snap to an object vertex.

Modify
Edit Objects: Ctrl+M
Move Objects: Ctrl+B

PVsyst SA – Grid Connected Systems – User’s manual Page 67


Rotate Objects: Ctrl+R
Rotate Entire Scene: Ctrl+Alt+R

Additional Tools

Drawing: Draw objects with the mouse


The freehand drawing tool allows you to create objects directly in the scene using the
mouse. This tool currently allows drawing the following objects:
• Triangle
• Parallelepiped
• House
• Tree
• Cable
• Extruded Polygon (by defining the 2D outline
and height)
• Rectangular PV Table
To start, click the button to open the object selection menu and choose the desired
object type. Then follow the instructions in the tooltip for each object.

Field zones: In the shading scene, you can define areas that will be filled with PV
tables. These zones are defined on the X-Y plane as drawn on the ground, with tables
dynamically placed in the scene. The tables are positioned based on the objects they lie
on, so if a zone is drawn on a roof, tables will be positioned accordingly at the correct
altitude. This also applies to zones on topographies. You can specify if you want the
tables to automatically tilt according to the object they are on.
Creating Zones: To create or edit zones, click the **Zone tool**, then find the "Zone
Editing" section on the right side of the window

PVsyst SA – Grid Connected Systems – User’s manual Page 68


The button to create a rectangular
zone allows you to define the upper-left and
lower-right corners of the rectangle in the scene.

The button to create a polygonal zone


lets you define new points by left clicking in the
scene. To end the zone definition, right-click.

The button to draw a freeform zone lets


you click and drag the mouse. Right-click to
finish defining the zone.

This button
opens the table field editing dialog to define
parameters for the tables generated within the
zone.

PVsyst SA – Grid Connected Systems – User’s manual Page 69


Basic Settings Tab: The initial tab allows the following adjustments:

• Description: Sets a custom label for the zone.


• Global table sizes: Summarizes the table’s dimensions.
• Orientation: Choose the orientation for table generation.
Table size tab: The Table size tab includes a dedicated area for photovoltaic modules.
When setting up a field, specify the associated PV module. A table can only hold PV
modules of the same size.

PVsyst SA – Grid Connected Systems – User’s manual Page 70


Sizes definition:
• By Modules: This recommended option defines an area exactly suited for the
desired module count with specific spacing.
• By Sensitive Area: Specify the desired PV table size without constraints initially.
Later, retrieve the exact size for your modules by selecting "By Modules."
Both options can be adjusted by dragging red points with the mouse, with modules filling
the available space as sizes are modified.

PVsyst SA – Grid Connected Systems – User’s manual Page 71


Section “by modules” shows information
regarding the PV module chosen in the
system definition.
It allows you to select the orientation of the
module by “Landscape” or “Portrait”.
It also lets you define the number of modules
the PV table will contain, as well as their
spacing.

After completing this setup, return to the Zone Editing section:


Pitch: Distance between the bases of tables in
consecutive rows.
Table Spacing: Distance between
consecutive tables in the same row.
Align tables: Defines table alignment in each
row within the defined zone.
Distance from ground: Defines the height of
the PV planes relative to the ground.
Automatic Tilt: Enabling this option overrides
the tilt parameter, letting tables adopt the tilt
of the surface they’re on.
Automatic Length: Enabling this option
overrides the length parameter, extending a
single table in each row to fit the zone.
Create Trackers: When enabled, fills the area
with trackers.

The "Fill Zone"


button calculates the required space for PV
tables based on the specified parameters.

After positioning the tables, the following buttons allow further


modifications:

Select all tables.

PVsyst SA – Grid Connected Systems – User’s manual Page 72


Add or remove tables.

Move tables along their axis.

Exclusion Zone: Finally, it is possible to define exclusion zones where tables won’t be

added. These zones can be drawn as previously


described.

Ground Image: Reopens a section allowing image scaling and opacity


adjustments.

PVsyst SA – Grid Connected Systems – User’s manual Page 73


Geographic/Building Reference:
To ease complex system construction, you can build within a reference framework linked
to the building, where coordinates (X, Y, Z) match the architectural plan. This framework
enables scene rotation according to geographic coordinates, and you can toggle
between coordinate systems using dedicated 3D editor toolbar buttons.
The construction reference includes the following section:

This tool modifies the azimuth of the entire


scene.

Global Reference Orientations


The global reference system for the shading scene aligns with cardinal points:
Northern Hemisphere: X-direction is west, Y-direction is south, and Z points upward
(zenith). PV field azimuths are defined relative to the south (OY) and are positively
oriented clockwise toward the west.
Southern Hemisphere: X points east, Y north. Azimuths are measured from north (OY)
and oriented positively counterclockwise toward the west.

PVsyst SA – Grid Connected Systems – User’s manual Page 74


In the 3D scene window, the right section contains two tabs:

Scene Objects: View scene objects, existing


orientations, and created groups, allowing
zone selection.

Tools: Access various tools previously


mentioned.

PVsyst SA – Grid Connected Systems – User’s manual Page 75


Shading animation:
This tool displays the shadow animation in the scene for a given date. By default, it is set
to December 21, the day of the lowest sun height in the Northern Hemisphere. The
interval can be adjusted for a more precise shadow result.

Clicking this icon starts the shadow animation.

For example, the linear shading on PV module surfaces on December 21 is 16.3%.

PVsyst SA – Grid Connected Systems – User’s manual Page 76


The sun icon locks the view to the sun's position, and the horizontal scroll bar lets
you navigate the hours of the day, adjusting the sun’s position simultaneously. The save

icon enables video creation of the animation that can be saved.

10 Energy management
In PVsyst, energy management encompasses functions related to the inverter
temperature, power factor, grid power limitation, and P50/P90 energy yield analysis.
These features collectively aid users in optimizing and managing the energy performance
of photovoltaic systems in PVsyst.
10.1 Inverter Temperature
Inverters are responsible for converting the direct current (DC) electricity generated by
solar panels into alternating current (AC) electricity for use in the grid. Inverter efficiency
decreases as its temperature rises. Higher temperatures can result in increased losses
during the conversion process, leading to lower AC power output. By precisely choosing
the temperature model approach for the simulation of the inverter temperature, you can
more accurately estimate and evaluate the inverter's efficiency, system performance,
safety and reliability. The inverter’s temperature profil and evalauation for limits can be
found in the PVsyst inverter file (.OND file) under Output parameters tab.

In the simulation, by default the inverter temperature is the external ambient


temperature (outdoor installation). This strategy can be modified in Inverter Temperature
page in the Energy management.

PVsyst SA – Grid Connected Systems – User’s manual Page 77


The reference inverter temperature may be specified in the output system parameters
by:
• Ambient external temperature, the usual parameter admitted by manufacturers
for outdoor installation.
• Ambient external temperature + specified shift
• Fixed temperature + linear increase proportional to the power (represented by the
incident irradiance). This could be used for indoor inverters and not perfect
cooling installation.

10.2 Power Factor


Power factor control in PV systems is a critical aspect of modern grid management, as it
helps optimize the interaction between solar energy production and grid stability.
In alternating current (AC) circuits, power can be understood in three distinct forms:
active power, reactive power, and apparent power.
• Active Power (𝑃𝑎𝑐𝑡𝑖𝑣𝑒 ): This is the real power that performs useful work, such as
producing movement or heat. It is the power that directly translates into energy
consumption, measured in kilowatts (kW). In an AC circuit, active power is
calculated by multiplying the effective values of voltage and current, and then
multiplying by the cosine of the phase angle (φ) between them:
𝑃𝑎𝑐𝑡𝑖𝑣𝑒 = 𝑈𝑒𝑓𝑓 ∗ 𝐼𝑒𝑓𝑓 ∗ 𝑐𝑜𝑠(φ)
• Reactive Power (𝑃𝑟𝑒𝑎𝑐𝑡𝑖𝑣𝑒 ): This is "virtual" power, representing the energy
temporarily stored and released by inductive (motors, transformers) or
capacitive devices. Reactive power, expressed in kilovolt-amperes reactive
(kVAr), does not contribute to actual energy consumption (no heat or movement
is produced). It is calculated using the sine of the phase angle (φ):
𝑃𝑟𝑒𝑎𝑐𝑡𝑖𝑣𝑒 = 𝑈𝑒𝑓𝑓 ∗ 𝐼𝑒𝑓𝑓 ∗ 𝑠𝑖𝑛(φ)
• Apparent Power (𝑃𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡 ): This is the combined effect of both active and
reactive power. It represents the total power flowing in the circuit, measured in

PVsyst SA – Grid Connected Systems – User’s manual Page 78


kilovolt-amperes (kVA), and is the product of voltage and current, irrespective of
their phase difference:
𝑃𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡 = 𝑈𝑒𝑓𝑓 ∗ 𝐼𝑒𝑓𝑓

The relationship between active and apparent power is quantified by the power factor
(PF), which is simply the cosine of the phase angle (φ). Power factor is crucial because it
indicates how efficiently electrical power is being used:
𝑃𝑎𝑐𝑡𝑖𝑣𝑒
𝑃𝐹 = 𝑐𝑜𝑠(φ) =
𝑃𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡
In photovoltaic systems, inverters convert the direct current (DC) from solar panels into
alternating current (AC) for grid integration. With modern inverter technology is possible
to control the phase angle between voltage and current. This allows the inverter to
generate reactive power without additional energy consumption. By adjusting the phase
shift between voltage and current, PV systems can support grid needs for reactive power
without compromising their active energy production.
Reactive power plays an essential role in compensating for the reactive loads, typically
introduced by motors or transformers in the grid. This compensation is often a
requirement set by grid managers to maintain grid stability. By adjusting the phase angle
(φ), inverters can either "absorb" or "generate" reactive power, depending on the needs
of the grid:

Lagging reactive power: When the current lags behind the voltage, with a positive phase
angle, φ > 0. Defining a lagging PF in your inverter means the inverter will inject reactive
power into the grid to help compensate for reactive power demand of inductive loads
such as motors and transformers.
Leading reactive power: When the current leads the voltage, with a negative phase
angle, φ < 0. Defining a leading PF in your inverter means the inverter will absorb reactive
power from the grid (or “consume” it), helping to counterbalance the excess reactive
power generated by capacitive loads.
When inverters are required to produce reactive power, it does not affect the active
energy output directly. However, depending on whether the inverter’s nominal power
(PNom) is defined as active power (kW) or apparent power (kVA), the inverter’s capacity
to handle overloads may be affected. If PNom is based on apparent power, the maximum
available active power will be reduced by a factor of the power factor:
𝑃𝑁𝑜𝑚(𝑎𝑐𝑡𝑖𝑣𝑒) = 𝑃𝑁𝑜𝑚(𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡) ∗ cos ( φ)

PVsyst SA – Grid Connected Systems – User’s manual Page 79


Grid operators may impose power limits based on either active or apparent power. If the
limit is set on apparent power, PV systems will need to adjust the power factor to comply,
potentially reducing the amount of active energy delivered to the grid.
When the power factor decreases (i.e., more reactive power is produced), the current in
the system must increase to maintain the same level of active power. Since ohmic losses
in cables and transformers are proportional to the square of the current, this leads to
higher energy losses in the system:
𝐼𝑒𝑓𝑓(𝑎𝑐𝑡𝑖𝑣𝑒)
𝐼𝑒𝑓𝑓(𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡) =
cos (φ)

In PVsyst simulations, the power factor is an adjustable parameter, typically fixed for a
given period or specified monthly. The simulation results focus on active energy (in
kWh), but when a power factor is defined, the apparent energy (in kVAh) is also
calculated:
𝐸𝐺𝑟𝑖𝑑
𝐸𝐺𝑟𝑖𝑑𝐴𝑝𝑝 =
cos (φ)
The apparent energy will always be greater than the active energy due to the inclusion of
reactive power.

The nominal power rating of inverters may be an active power or apparent power:
• In the case of active power rating, reactive energy does not come at the cost of
active power.
• In the case of an apparent power rating, reactive energy may come at the cost of
active power, when close or at the maximum power threshold.

PVsyst SA – Grid Connected Systems – User’s manual Page 80


Force as apparent/active power" will force all inverters to operate under this
conditions. This means that inverters may not operate like in the datasheet anymore.
This has been kept here for compatibility with old versions < 7.3.3, and for possible
tests. It is not recommended.

10.3 Grid Power limitation


To maximize energy production, one strategy is to over-size the PV installation, accepting
some energy losses during peak production hours (peak-shaving). The grid limitation
feature in PVsyst allows you to set limits on the power that your PV system injects into
the grid, based on requirements from the grid manager. This is often needed when grid
operators request a maximum limit to prevent overloading.
The power limitation must occur at the inverter level by adjusting the operating point on
the PV array’s I/V curve to produce only the necessary power. The inverter will ensure that
the power output matches the grid’s required limit.

In the Power limitation dialog, you can define one value for the grid limitation that will be
applied throughout the year. The limitation may be defined:

PVsyst SA – Grid Connected Systems – User’s manual Page 81


• either at the inverter level: the inverter power is limited to the rated value, and the
power injected into the grid is further reduced by the losses defined after the
inverter (auxiliaries, AC wiring, transformer).
• or at the injection point level: the maximum power delivered to the grid is indeed
the rated limit, the inverter will have to deliver a higher power for compensating
the losses after the inverter.
This limitation may be required:
• either as active power (expressed in kW),
• or as apparent power [kVA]: in this case the effective active power [kW] is limited
at a lower value than the apparent power limit [kVA]. The Cos(Phi), specific for the
grid limitation, may be specified in yearly or monthly values.
The excess energy will be accounted as "Inverter loss over nominal power" or when
checking "Account as separate loss", the results will show separately the loss due to the
inverter limitation itself, and the loss (named EUnused) due to the additional condition
of grid limitation. This does not correspond exactly to the physical behavior of the
system, which will always clip at the inverter level, but it is meant to show explicitly the
part of the clipping losses due to the injection limitation.
10.4 P50 - P90 Estimation
The P50 - P90 evaluation is a probabilistic approach for the interpretation of the
simulation results over several years. This approach supposes that over several years of
operation, the distribution of the annual yields will follow a statistical law, which is
assumed to be the Gaussian (or "normal") distribution.
The normal/gaussian distribution describes the tendency for data to cluster around a
central value, this value is the mean. Some data will then fall below the mean and other
above the mean. The standard deviation Sigma describes the spread of the normal
distribution. The larger the Sigma, the more spread out the distribution will be. And the
contrary, with a smaller Sigma, the distribution is less spread out, accumulating more
data near the mean.

PVsyst SA – Grid Connected Systems – User’s manual Page 82


The P50-P90 evaluation of the energy yield potential of a site, represent a statistical level
of confidence for which the probability that the production of a particular year is over this
value is 50%, resp. 90%.
The annual variability will be dominated by the weather year-to-year variability. Several
weather data providers can now deliver multi-year weather data (sets of 15 to 25 years),
that you can directly import in PVsyst (for example SolarGIS, 3-Tiers Vortex, Soda-
Helioclim, or other). If you avail of such weather data for your site, you can calculate the
RMS of the annual GlobInc distribution. You have a tool for doing this in PVsyst: please
use "Databases > Compare Weather Data", and choose the corresponding .MET files for
different years. You have an option "Histo and Probabilities" which shows the gaussian
distribution, average and RMS.
If the data are representative of an average over several years (like monthly averages or
TMY), the result of the simulation can be considered as the average, and corresponds to
P50 (mean value of the Gaussian). If the data are for a specified year, these cannot be
considered as representative of the P50 value. In absence of further information you
cannot determine a reliable P50-P90 indicator. But if you have some information about
the usual average of the site, you can introduce an estimation of the deviation of this
particular year with respect to the average.
Additional uncertainties in the simulation process could eventually be taken into
account. These deviations should represent random variability of the uncertainty from
year to year, not absolute uncertainty.
The P50-P90 statistical estimations are based on yearly values. P90 for hourly or daily
values (or even for monthly accumulations) doesn't provide meaningful results due to
the high variability of short-term weather patterns.

PVsyst SA – Grid Connected Systems – User’s manual Page 83

You might also like