Exercise Notes - Masonry Structures _2025!04!29_unlocked
Exercise Notes - Masonry Structures _2025!04!29_unlocked
FÜR
MASSIVBAU
EXERCISE NOTES -
MASONRY STRUCTURES
_2025_04_29
EXAMPLES
Third Edition
2025
Contents i
Contents
0 Building description ......................................................................................................... 1
1 Load determination.......................................................................................................... 3
2 Structural stability .......................................................................................................... 24
3 Simplified calculation method according to DIN EN 1996-3 /NA .................................... 45
4 Simplified calculation method according to DIN EN 1996-3 Annex A /NA ...................... 61
5 General verification method according to DIN EN 1996-1-1 .......................................... 67
6 Basement walls ........................................................................................................... 115
7 Non-loadbearing walls and special components .......................................................... 134
8 Structural fire design ................................................................................................... 146
List of tables
Table 1.1 Live loads of selected categories of use according DIN EN 1991-1-1/NA ........ 5
Table 1.2 Simplified peak velocity pressure for buildings with total height < 25 m [6] ...... 6
Table 1.3 External pressure coefficient for vertical construction elements [6] .................. 7
Table 1.4 External pressure coefficient for duo pitch roofs with wind direction 0° [6] ..... 10
Table 1.5 External pressure coefficient for duo pitch roofs with wind direction 90° [6] ... 10
Table 1.6 Characteristic value of snow load depending on the snow zone [5] ............... 12
Table 1.7 Snow load shape coefficients [5] ................................................................... 13
Table 1.8 Overview of all vertical acting dead and live loads on the building ................. 18
Table 1.9 Calculation of the load area for each construction element ............................ 20
Table 1.10 Vertical dead load summarized for each construction element, for each storey
and for the whole building from the top to the bottom of the wall of the 1 st floor
...................................................................................................................... 22
Table 1.11 Vertical live loads summarized for each construction element, for each storey
and for the whole building from the top to the bottom of the wall of the 1 st floor
...................................................................................................................... 23
Table 2-1: Calculation of cross-sectional values [Schneider Bautabellen für Ingenieure, 20.
Auflage (2012), page 4.28] ............................................................................ 30
Table 2-2: Cross-sectional values of the stiffening walls ................................................. 30
Table 2-3: Equation for the coordinates of the shear centre M of the stiffening walls
[Schneider Bautabellen für Ingenieure, 20. Auflage (2012), page 5.40] ......... 31
Table 2-4: Calculation of the shear centre of the bracing system .................................... 31
Table 2-5: Summary of the horizontal stiffening wall loads at the bottom of each wall .... 44
Table 3.1 Characteristic compressive strength fk in N/mm² of one-brick masonry made of
vertically perforated clay masonry units with type A perforation (type HLzA), type
B perforation (type HLzB) and type E perforation (type HLzE), type T1 clay
masonry units for masonry panels, perforated calcium silicate masonry units
and hollow calcium silicate masonry blocks with general purpose masonry
mortar ............................................................................................................ 46
Table 3.2 Factor ρ2 for determining the effective height hef in the simplified calculation
method [9] ..................................................................................................... 47
Table 3.3 Application requirements for the simplified calculation method according to DIN
EN 1996-3/NA ............................................................................................... 48
Table 3.4 Factor ρ2 for determining the effective height hef for walls in the simplified
calculation method [9] .................................................................................... 53
Table 4.1 comparison of the results of the simplified calculation methods according to DIN
EN 1996-3 / NA and DIN EN 1996-3 – Annex A / NA..................................... 63
Table 4.2 Comparison of the results of the simplified calculation methods according to DIN
EN 1996-3 / NA and DIN EN 1996-3 – Annex A / NA..................................... 66
Table 5.1 Values KE for the calculation of the modulus of elasticity of masonry [8] ........ 69
Table 5.2 Factor ρ2 for determining the buckling height hef in general calculation method
...................................................................................................................... 76
Table 5.3 Deformation characteristics of masonry according to [8] ................................ 79
Table 5.4 Critical slenderness depending on the final creep coefficient ......................... 80
Table 5.5 Comparison of the load-bearing resistance of IW-01 according to different
calculation methods ....................................................................................... 81
Table 5.6 Initial shear strength values fvk0 for masonry under zero compressive stress
according to [8]. ........................................................................................... 101
Table 5.7 Values of fst as a function of the compressive strength class according to [8]
.................................................................................................................... 106
Table 6.1 Maximum permissible values of the infill area of non-loadbearing exterior walls
according to DIN EN 1996-3/NA without calculation .................................... 135
TUD – Institut für Massivbau
Only for use in the context of the lecture MSCC. No further reproduction or distribution is permitted!
List of tables iii
Table 6.2 Maximum permissible values of the infill area of non-loadbearing exterior walls
according to DIN EN 1996-3/NA without calculation .................................... 137
Table 6.3 Limiting dimensions for walls supported on four edges without superimposed
vertical load2),3) and walls supported on three edges with a free vertical edge*)
according to [12] .......................................................................................... 140
Table 6.4 Limiting dimensions for walls supported on four edges with superimposed
vertical load2),3) and walls supported on three edges with a free vertical edge*)
according to [12] .......................................................................................... 140
Table 6.5 Limiting dimensions for walls supported on three edges and a free upper edge
(top of the wall) without superimposed vertical load2),3) according to [12] .... 141
Table 6.6 Limiting dimensions for walls supported on four edges without superimposed
vertical load2),3) and walls supported on three edges with a free vertical edge*)
according to [12] .......................................................................................... 141
Table 6.7 Limiting dimensions for walls supported on four edges without superimposed
vertical load2),3) and walls supported on three edges with a free vertical edge*)
according to [12] .......................................................................................... 145
Table 7.1 Fire protection according to MBO 2002 (Musterbauordnung – MBO)........... 146
Table 7.2 Factor ω to allow for different combinations of masonry units and mortar (Table
NA.1 in DIN EN 1996-1-2/NA) ..................................................................... 152
Table 7.3 Design values of the acting axial forces and the load-bearing resistance of IW-
01 according to different calculation methods .............................................. 155
Table 7.4 Design values of the acting axial forces of the exterior wall EW-02.1 (see section
5.2.1.1) ........................................................................................................ 161
Table 7.5 Design values of the acting axial forces of the exterior wall EW-02.1 in case of
fire ............................................................................................................... 162
Table 7.6 Design values of the acting moments of the exterior wall EW-02.1 in case of fire
.................................................................................................................... 163
Table 7.7 Eccentricities of the exteriror wall EW-02.1 under fire case.......................... 164
List of figures
Figure 1.1 Wind action on vertical construction elements [6] ............................................ 7
Figure 1.2 Horizontal wind loads acting in two perpendicular directions on the facade ..... 8
Figure 1.3 Wind action on duo pitch roofs [6] .................................................................... 9
Figure 1.4 Static system of the gable roof with dead and live loads ................................ 14
Figure 1.5 Graphically determined load areas for a regular storey .................................. 19
Figure 1.6 Load transfer from a concrete beam to the adjacent construction elements ... 20
Figure 2.1: Requirements for lengths and distances a of stiffening walls according to the
simplified check of structural stability according to Mann/ Müller [17] ............. 25
Figure 2.2: Stiffening walls for the analysis of structural stability ...................................... 27
Figure 2.3: Wind loads on the example building in the direction of letter-axis .................. 27
Figure 2.4: left: static system of the fassade; right: static system of the building bracing . 29
Figure 2.5: Shear center and center of the floor plan of the bracing system .................... 32
Figure 2.6: Equivalent hotizontal loads due to imperfections [7] ...................................... 34
Figure 2.7: Torsion and Translation in the bracing system ............................................... 35
Figure 2.8: Equilibrium of forces for a centric wind load ................................................... 40
Figure 2.9: Equilibrium of forces for an eccentric wind load ............................................. 43
Figure 2.10: Resulting loads at the bottom of a wall in the basement HEd and MEd ...... 44
Figure 3.1 Section of the first-floor plan showing IW-01 .................................................. 45
Figure 3.2 Section of the third-floor plan showing EW-02 ............................................... 51
Figure 3.3 Partially supported slab ................................................................................. 51
Figure 4.1 Section of the first-floor plan showing IW-01 .................................................. 61
Figure 4.2 Section of the third-floor plan showing EW-02 ............................................... 64
Figure 5.1 Section of the first-floor plan showing IW-01 .................................................. 67
Figure 5.2 Simplified frame diagram ............................................................................... 70
Figure 5.3 Load combinations for decisive eccentricities at the top and bottom of the wall
...................................................................................................................... 70
Figure 5.4 Bending moment of IW-01 for different load combinations ............................. 73
Figure 5.5 Reduced bending moment of IW-01 with different load combinations ............ 75
Figure 5.6 Moments from calculation of eccentricities [8] ................................................ 77
Figure 5.7 Section of the first-floor plan showing EW-02.1.............................................. 82
Figure 5.8 Wall-floor-junction of the exterior wall EW-02.1.............................................. 84
Figure 5.9 Bending moment of the weak axis (wind load with hinged supports) .............. 86
Figure 5.10 Bending moment of the weak axis (wind load with fixed supports) ................. 86
Figure 5.11 Offset of the wall EW-02.1 from the second to the first floor........................... 93
Figure 5.12 Comparison of the internal force lines according to the cantilever model and the
method according to Annex NA.K from DIN EN 1996-1-1/NA ........................ 95
Figure 5.13 Equilibrium of forces according to the bending moment distribution of Figure 5.9
...................................................................................................................... 99
Figure 5.14 Horizontal wind load acting on the façade.................................................... 100
Figure 5.15 Left (a): failure due to friction of the bed joints; right (b): tensile failure of the
bricks ........................................................................................................... 104
Figure 5.16 Shear stress distribution for left: short walls (parabolic distribution) and right:
long walls (constant distribution) .................................................................. 107
Figure 5.17 Failure due to compression and shear ......................................................... 109
Figure 5.18 Joint failure due to tilting of the individual bricks under shear load ............... 111
Figure 5.19 Limitation of the edge strain in shear walls [8] ............................................. 113
Figure 0.1 Basement wall ([26]) .................................................................................... 115
Figure 0.2 Conditions of a basement wall for using the verification according to DIN EN
1996-3/NA ([26]) .......................................................................................... 116
Figure 0.3 Position of the basement wall BW-01 .......................................................... 118
Figure 0.4 Position of the basement wall BW-01.02 and BW-01.03 .............................. 119
Figure 0.5 Frame system of a basement wall using joint analysis (Source: Mauerwerk 17
(2013), Heft 3) ............................................................................................. 123
Figure 0.6 Simplified frame system using joint analysis [8] ........................................... 124
Figure 0.7 Earth pressure on basement wall ([26]) ....................................................... 127
Figure 0.8 Basement wall according to DIN EN 1996-3 ([25]) ....................................... 131
Figure 0.9 Approach of arching action ([25]) ................................................................. 131
Figure 6.1 Non-loadbearing walls: exterior walls ([26]) ................................................. 135
Figure 6.2 Position of the gable wall GW-01 ................................................................. 136
Figure 6.3 Non-loadbearing walls: interior walls ([26]) .................................................. 138
Figure 6.4 Limitation of wall dimensions of non-loadbearing interior walls [26] ............. 139
Figure 6.5 Wall with one opening: left: type (a); right: type (d) ...................................... 139
Figure 6.6 Non-loadbearing masonry wall n-lb. mw-01 ................................................. 142
Figure 6.7 Non-loadbearing masonry wall n-lb. mw-01 with openings (1.0m x 2.0m) .... 143
Figure 7.1 Variation of the reduction factor 𝜼𝒇𝒊 with the load ration 𝑸𝒌, 𝟏/𝑮𝒌 ............... 151
Figure 7.2 Position of the exterior wall IW-01................................................................ 154
Figure 7.3 Position of the exterior wall EW-02.1 ........................................................... 160
Figure 7.4 Simplified frame diagram of the exterior wall EW-02.1 ................................. 162
References
[1] DGfM (Hrsg.) (2013): Merkblatt zur Abdichtung von Mauerwerk. Berlin: Deutsche
Gesellschaft für Mauerwerks- und Wohnungsbau e. V.
[11] Graubner, Glock, Jäger, Pflücke (2002): Knicksicherheit von Mauerwerk. In:
Mauerwerk-Kalender. Berlin: Ernst & Sohn GmbH, Seite 381-445
[12] Kirtschig, Anstötz (1986): Zur Tragfähigkeit von nichttragenden inneren Trennwänden
in Massivbauweise. In: Mauerwerk-Kalender. Berlin: Ernst & Sohn GmbH, Seite 697-
734
[14] Mann (1992): Zug- und Biegezugfestigkeit von Mauerwerk – theoretische Grundlagen
und Vergleich mit Versuchsergebnissen. In: Mauerwerk-Kalender. Berlin: Ernst & Sohn
GmbH, Seite 601-607
[15] Mann, Müller (1973): Bruchkriterien für querkraftbeanspruchtes Mauerwerk und ihre
Anwendung auf gemauerte Windscheiben. In: Die Bautechnik, Heft 12. Berlin
[21] Steinle, Hahn (1995): Bauen mit Betonfertigteilen im Hochbau. Berlin: Fachvereinigung
Deutscher Betonfertigteilbau e. V., Ernst & Sohn GmbH
[22] MIW- Masonry Institut of Washington: Pocket Guide to Brick and CMU Construction,
2012
[23] Böhme (2004): Ringanker und Ringbalken: Mauerwerk, Heft 1, 2004, Ernst & Sohn
GmbH
[24] DAfM (Hrsg.) (2020):Eurocode 6, DIN EN 1996 mit Nationalen Anhängen: Bemessung
und Konstruktion von Mauerwerksbauten, kommentierte Fassung, Beuth Verlag
GmbH, Ernst & Sohn Verlag GmbH
[26] Mauerwerk – Das Lehrportal” of the “DGfM – Deutsche Gesellschaft für Mauerwerks-
und Wohnungsbau e.V.“: Mauerwerksbaulehre - Lehre zum Mauerwerksbau
(mauerwerksbau-lehre.de)
0 Building description
1.1 Generals
The observed construction project is a four-storey residential building in Heppenheim
(Bergstraße). The main load-bearing structure consists of masonry walls, reinforced concrete
floor slabs and a wooden gable roof structure. The exterior walls are made of perforated clay
masonry units (t = 36.5 cm) with high thermal resistance. Therefore, no further thermal
insulation is necessary for the exterior walls. Also, the interior walls are made of perforated
clay masonry units with a wall thickness of t = 17.5 cm.
The residential building has three regular storeys for apartments (1st floor – 3rd floor), one
basement storey and one attic storey. The regular storeys are finished with light drywalls
partitions with a dead load of < 3.0 kN/m. The constructor orders photovoltaics on top of the
roof covering.
• Bracing system:
The building is braced by concrete floor slabs, that act as rigid diaphragms and by the
stiffening walls EW-01, EW-02, EW-03. EW-04 on the axis 1, 3, A and F. As a conservative
assumption the other walls are not considered for the bracing. The clamping plane is
assumed at the ground slab since the basement floor plan is similar to the floor plans
above.
• Foundations:
A ground slab transfers the building loads to the ground.
• The execution plans show the geometry and construction dimensions of the building.
• Construction materials:
On-site concrete: C 30/37
Reinforcing steel B 500 B
General-purpose mortar compressive strength class M5
Perforated clay masonry units:
Exterior walls t x l x h = 36.5 x 20.0 x 24.9 cm
compressive strength class 10
Interior walls t x l x h = 17.5 x 30.7 x 24.9 cm
compressive strength class 12
The following structural details show the structure of the slab and wall finishing.
2. Load determination
1.1 Preliminary remarks for the static analysis
Table 2.1 Live loads of selected categories of use according DIN EN 1991-1-1/NA
The category A2 for residential areas applies to all storeys of the considered building.
Therefore, the disposed live load is:
qk = 1.5 kN/m²
we = q p ( ze ) c pe
According to DIN EN 1991-1-4 Annex NA.B.3.2, the peak velocity pressure qp for structures
up to 25 m high can be chosen in a simplified way according to Table 2.2:
➔ qp(ze) = 0.65 kN/m²
Table 2.2 Simplified peak velocity pressure for buildings with total height < 25 m [6]
h 10 m 10 m < h 18 m 18 m < h 25 m
Table 2.3 External pressure coefficient for vertical construction elements [6]
In the following, the horizontal wind load is determined separately for the two directions of the
floor plan based on the building elevation. Either the load case wind parallel to the letter-axis
or the load case wind parallel to the number-axis acts on the building. Within each load case,
the wind pressure on the front-side and the wind suction on the back-side act simultaneously
(additive) on the vertical facade.
Figure 2.2 Horizontal wind loads acting in two perpendicular directions on the facade
kN kN
wind pressure: wD = qP ( ze ) c pe = 0.65 0.80 = 0.52
m² m²
kN kN
wind suction: wE = qP ( ze ) c pe = 0.65 (−0.52) = − 0.34
m² m²
kN kN
wind pressure: wD = qP ( ze ) c pe = 0.65 0.74 = 0.48
m² m²
kN kN
wind suction: wE = qP ( ze ) c pe = 0.65 (−0.37) = − 0.24
m² m²
Table 2.4 External pressure coefficient for duo pitch roofs with wind direction 0° [6]
Table 2.5 External pressure coefficient for duo pitch roofs with wind direction 90°
[6]
As a conservative approach the maximum/ minimum wind load zone is applied for the whole
roof area:
kN kN
wind pressure: wD = qP ( ze ) c pe = 0.65 0.57 = 0.37
m² m²
kN kN
wind suck: wE = qP ( ze ) c pe = 0.65 (−0.63) = − 0.41
m² m²
kN kN
wind pressure: wD = qP ( ze ) c pe = 0.65 0.00 = 0.00
m² m²
kN kN
wind suck: wE = qP ( ze ) c pe = 0.65 (−1.37) = − 0.89
m² m²
The load case wind pressure (on the roof) acts additively in the same direction as the other
dead and live loads of the building. Therefore, the wind pressure is the decisive load case for
the masonry walls. The load case wind suction (on the roof) acts in the opposite direction and
compensates the dead and live loads. However, the load case wind suction might be decisive
for the design of the wooden roof construction and the roof covering. Since this exercise is
focused on masonry constructions, the load case wind suction will not be considered here.
s = i sk
with
s characteristic snow load on the roof
i snow load shape coefficient
sk characteristic value of snow on the ground at the relevant site
Table 2.6 Characteristic value of snow load depending on the snow zone [5]
A + 140
2
1 sk = 0.19 + 0.91 0.65
760
A + 140
2
A + 140
2
2 sk = 0.25 + 1.91 0.85
760
A + 140
2
A + 140
2
31) sk = 0.31 + 2.91 1.10
760
A is the terrain height above sea level in m
1)
In Zone 3, for certain locations (e.g. Oberharz, high
altitudes of the Fichtelgebirge, Reit im Winkl,
Obernach/Walchensee) higher values than those according
to the above equation may be decisive. Information about
the snow load in these regions must be obtained from the
responsible authorities.
Heppenheim is located in the snow load zone 2. Therefore, the following is applied:
A + 140
2
kN
sk = 0.25 + 1.91 0.85
760 m²
1 0.8 0.80 ( 60 − ) 30 0
The shape coefficients apply if the snow is not prevented from sliding off the roof. If the snow
is prevented from sliding off (e.g. by snow fences, parapets, etc.), the shape coefficient must
be set at = 0.8.
1.3 Determination of the live and dead loads acting per storey
1.3.1 Gable roof (above-rafter insulation)
Dead loads:
Live loads:
In the following, the live loads are summed up without the consideration of load reduction
factors for the different combinations of action, since this simplifying assumption is a
conservative approach.
Figure 2.4 Static system of the gable roof with dead and live loads
2 2
M B : Av 4.5 = Ah 2.20 + g 5.77 5.18 + w 5.77 + s 5.18
2 2 2
Av = 9.87 kN / m
( Av, gk = 6.28 kN / m; Av,qk = 2.94 kN / m)
Symmetric system → support B gets loads from both sides of the gable roof:
Dead loads:
Live loads:
The influence of light unloaded partition walls (up to a maximum load of 5 kN/m) may be applied
as a uniformly distributed surcharge to the live load (Trennwandzuschlag).
The surcharge on the effective load must be at least 0.8 kN/m² for walls which, including the
plaster, provide a load of at most 3 kN/m, and at least 1.2 kN/m² for walls which provide a load
between 3 kN/m and 5 kN/m. This supplement is not required for live loads of 5 kN/m² and
more. Loads due to movable partitions must be treated as live loads.
1.3.3 Staircase
Dead loads:
Staircase and stair landing (load per m² plan projection) = 5.0 kN/m²
Live loads:
Dead loads
Exterior walls + plastering 3.0 m · (0.365 m · 6.88 kN/m³ + 0.3 kN/m²) = 8.43 kN/m
Interior walls + plastering 3.0 m · (0.175 m · 11.14 kN/m³ + 0.3 kN/m²) = 6.75 kN/m
The effective span of the slab has the ratio: lz / ly = 9.0 m / 5.0 m = 1.80. Since this ratio is
< 2.0, the floor slabs are considered as two-way slabs. The load areas for each construction
element are identified with the rules according to the lecture notes in chapter 4.2 and shown
in the following Figure 2.5.
The dead and live loads of the considered residential building are summarized in the following
table.
Table 2.8 Overview of all vertical acting dead and live loads on the building
1 2 3
9,365 m
4,50 m 4,50 m
EW-02
z
A
y
1,83 m
EW-02
5,34 m 45°
EW-01.1
EW-03.1
5,00 m
30°
MC-01
60
IW-01
°
CB-01
B
4,82 m 4,18 m
3,00 m
30°
EW-01.2
EW-03.2
2,62 m 2,45 m
6,00 m
EW-03
80 m
45°
IW-02.1 IW-02.2
C
60
°
60
2,00 m
°
25,333 m
EW-01.3
EW-03.3
IW-03
4,00 m
3,63 m
5,37 m
D
1,83 m
IW-04.1 IW-04.2
45°
2,99 m 64 cm 2,10 m
45° 30°
67cm
EW-01.4
EW-03.4
5,00 m
30° 30°
°
60
IW-05
60
4,82 m 4,18 m
°
E
CB-02
3,17 m
60
°
MC-01
60
30° 30°
5,00 m
EW-01.5
EW-03.5
45°
45°
5,34 m
1,83 m
45°
F
EW-04
Notes:
• The stairs have the static system of a simple beam, tensioned in the direction parallel
to the letter-axis.
• The stair landings have the static system of a simple beam, tensioned in the direction
parallel to the number-axis.
• The concrete beams have the static system of a simple beam and transfer the loads to
the adjacent walls/columns. In the table of the total vertical loads, these loads are
already assigned to the adjacent walls/columns. Figure 2.6 shows the load transfer
from the concrete beam CB-01 to the wall IW-01 and EW-03 as well as to the masonry
column MC-01. The half of each beam span (= 0.88 m) is transferred into the adjacent
construction elements.
Figure 2.6 Load transfer from a concrete beam to the adjacent construction elements
Table 2.9 shows the calculation of the load area A for each construction element and is
recorded from the above-shown floor plan with the graphical load areas.
Table 2.9 Calculation of the load area for each construction element
The calculation of the load area A of the interior wall IW-01 is shown exemplary in detail:
IW-01 (A-B) → trapezoid load area between axis A and B:
lz = (4.82 + 2.99) / 2 = 3.91 m; ly = 3.17 m; A = lz · ly = 12.38 m²
IW-01 (B-C) a → trapezoid load area between axis B and C:
lz = (4.82 + 2.62) / 2 = 3.72 m; ly = 3.00 m; A = lz · ly = 11.16 m²
IW-01 (B-C) b → triangular load area between axis B and C:
lz = 2.62 m; ly = 0.80 m; A = lz · ly · 0.5 = 01.05 m²
Total load area IW-01: A = 24.59 m²
The following table shows the dead load of each construction element for each storey. The resulting values refers to the load sum at the bottom of the wall of the first floor.
Table 2.10 Vertical dead load summarized for each construction element, for each storey and for the whole building from the top to the bottom of the wall of the 1st floor
Dead loads Exterior wall Exterior wall Exterior wall Exterior wall Interior wall Interior wall Interior wall Interior wall Interior wall Masonry column Masonry column sum
GEK EW-01 EW-02 EW-03 EW-04 IW-01 IW-02 IW-03 IW-04 IW-05 MC-01 MC-02 [kN]
area/ area/ area/ area/ area/ area/ area/ area/ area/ area/ area/
Gek Gek Gek Gek Gek Gek Gek Gek Gek Gek Gek
length length length length length length length length length length length
[kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN]
slab over actions [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m]
3rd floor slab gk [kN/m²] 7.34 20.33 149.19 13.12 96.31 28.88 212.02 13.12 96.31 29.05 213.24 24.01 176.21 2.32 17.03 21.55 158.20 27.32 200.55 11.41 83.75 10.68 78.40
roof Bv,gk gk [kN/m] 9.26 - - 2.50 23.14 - - 2.50 23.14 5.50 50.92 5.00 46.29 - - 4.50 41.66 5.00 46.29 - - - -
ext. wall gk [kN/m] 8.43 25.00 210.75 9.00 75.87 25.00 210.75 9.00 75.87 - - - - - - - - - - - - - -
int. wall gk [kN/m] 6.75 - - - - - - - - 4.64 31.29 8.64 58.32 3.83 25.85 8.64 58.32 4.64 31.29 0.50 3.38 0.50 3.38
CB gk [kN/m] 1.75 - - - - 1.76 3.08 - - 0.88 1.54 - - - - - - 0.88 1.54 2.25 3.94 2.25 3.94
Sum 3rd floor 516.85 249.68 582.76 249.68 296.98 305.52 42.88 282.88 279.66 91.06 85.71 2983.67
2rd floor slab gk [kN/m²] 7.34 20.33 149.19 13.12 96.31 28.88 212.02 13.12 96.31 29.05 213.24 24.01 176.21 2.32 17.03 21.55 158.20 27.32 200.55 11.41 83.75 10.68 78.40
ext. wall gk [kN/m] 8.43 25.00 210.75 9.00 75.87 25.00 210.75 9.00 75.87 - - - - - - - - - - - - - -
int. wall gk [kN/m] 6.75 - - - - - - - - 4.64 31.29 8.64 58.32 3.83 25.85 8.64 58.32 4.64 31.29 0.50 3.38 0.50 3.38
CB gk [kN/m] 1.75 - - - - 1.76 3.08 - - 0.88 1.54 - - - - - - 0.88 1.54 2.25 3.94 2.25 3.94
Sum 2rd floor 359.94 172.18 425.85 172.18 246.07 259.23 42.88 241.22 233.38 91.06 85.71 2329.68
1st floor slab gk [kN/m²] 7.34 20.33 149.19 13.12 96.31 28.88 212.02 13.12 96.31 29.05 213.24 24.01 176.21 2.32 17.03 21.55 158.20 27.32 200.55 11.41 83.75 10.68 78.40
ext. wall gk [kN/m] 8.43 25.00 210.75 5.00 42.15 25.00 210.75 5.00 42.15 - - - - - - - - - - - - - -
int. wall gk [kN/m] 6.75 - - - - - - - - 4.64 31.29 8.64 58.32 3.83 25.85 8.64 58.32 4.64 31.29 0.50 3.38 0.50 3.38
CB gk [kN/m] 1.75 - - 4.00 7.00 1.76 3.08 4.00 7.00 0.88 1.54 - - - - - - 0.88 1.54 2.25 3.94 2.25 3.94
Sum 1st floor (1x) 359.94 145.46 425.85 145.46 246.07 259.23 42.88 241.22 233.38 91.06 85.71 2276.24
1236.72 567.32 1434.45 567.32 789.11 823.97 128.64 765.32 746.42 273.17 257.14 7589.60
sum at the bottom of the wall of the 1st floor
The following table shows the live load of each construction element for each storey. The resulting value refers to the load sum at the bottom of the wall of the first floor.
Table 2.11 Vertical live loads summarized for each construction element, for each storey and for the whole building from the top to the bottom of the wall of the 1st floor
area/ area/ area/ area/ area/ area/ area/ area/ area/ area/ area/
Gek Gek Gek Gek Gek Gek Gek Gek Gek Gek Gek
length length length length length length length length length length length
[kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN] [kN]
[m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m] [m²]/[m]
slab over actions
3rd floor 20.33 46.75 13.12 30.18 28.88 66.44 13.12 30.18 29.05 66.82 24.01 55.21 2.32 5.34 21.55 49.57 27.32 62.84 11.41 26.24 10.68 24.57
slab qk [kN/m²] 2.30
stairs qk [kN/m²] 3.00 - - - - - - - - - - 10.74 32.22 - - 10.74 32.22 - - - - - -
roof Bv,qk qk [kN/m] 5.01 - - 2.50 23.14 - - 2.50 23.14 5.50 27.53 5.00 25.03 - - 4.50 22.52 5.00 25.03 - - - -
Sum 3rd floor 203.66 53.32 223.35 53.32 94.35 112.46 5.34 104.32 87.87 26.24 24.57 988.70
2rd floor 20.33 46.75 13.12 30.18 28.88 66.44 13.12 30.18 29.05 66.82 24.01 55.21 2.32 5.34 21.55 49.57 27.30 62.84 11.41 26.24 10.68 24.57
slab qk [kN/m²] 2.30
/ 1st floor
stairs 3.00 - - - - - - - - - - 10.74 32.22 - - 10.74 32.22 - - - - - -
qk [kN/m²]
Sum 2rd floor / 1st floor (2x) 46.75 30.18 66.44 30.18 66.82 87.43 5.34 81.79 62.84 26.24 24.57 528.48
3. Structural stability
3.1 Preliminary remarks for the analysis of structural stability
The analysis of the structural stability of a building ensures, that the global structure of the
building will not collapse due to horizontal loads (wind, imperfections, earthquakes, earth
pressure). Therefore, stiffening walls or building cores with an adequate cross-section, that
rest on the foundations, are required to brace the building. The analysis of structural stability
includes the following steps:
- Definition of the bracing system
- Definition of the acting horizontal loads
- Structural analysis of the bracing system with calculating the horizontal loads and the
bending moment around the strong axis for each stiffening element.
According to the German National Annex of DIN EN 1996-1-1, chapter 5.5.3 the analysis of
the structural stability ist not required if the following is fulfilled:
(NA.12) “An analysis of the structural stability of a building is not required if adequate
stiffness is provided by floors designed as rigid diaphragms, or by ring beams, and there
are sufficiently long shear walls that are located in both directions of the building and rest
on the foundations, provided that the cross-section of the wall does not undergo any
major changes.”
(NA.13) “For masonry made of high-precision elements designed with an overlap lol of
less than 0,4 hu, any reduction in the shear resistance under high surcharges shall be
taken into account unless the structural stability of the building is analysed as specified
in (NA.12).”
According to DIN EN 1996-3, chapter 4.1 and the corresponding Germany National Annex the
following applies:
4.1 (1) “The overall stability of a building, of which the wall forms a part, shall be verified.”
NDP re 4.1(1) “An analysis of the structural stability is not required if adequate stiffness
is provided by floors designed as rigid diaphragms or by adequately designed ring beams
and if there is a sufficient number of shear walls that are located in both directions of the
building and ultimately rest on the foundations, provided that the cross-section of such
walls does not undergo any major changes.
Where there is uncertainty as to whether adequate stiffness of the structure is ensured,
the shear resistance shall be verified by calculation in accordance with the detailed
method described in DIN EN 1996-1-1:2010-12, 6.2, in conjunction with the relevant
National Annex.”
3.2 Simplified check of the structural stability according to Mann/ Müller (1985) [17]
General Information
On the basis of detailed experimental research Mann and Müller (1985) [17] give a
reccomandation for the evaluation of the adequate stiffness of a masonry building for the
omission of the analysis of structural stability. According to [17] this analysis is not required if:
- Building height < 20,0 m (for saddle-roofs: mean value of the height of the eaves and
the ridge purlin).
- Slabs act like rigid diaphragms / adequate ring beams are provided.
- In longitudinal and traverse direction an abviously sufficient number of walls is
arranged.
- The walls are frictionally connected with traverse walls and form I-Profiles (this is the
common construction practice).
- The number of walls can be assumed sufficient if for one row of stiffening walls the wall
length is l ≥ 7,0 m and for two rows of stiffening walls the wall length is l ≥ 3,5 m and
the distance between two parallel walls according to Figure 3.1 is:
For bricks of compressive strength class 2:
o a < 35 · t for all storeys in three-storey buildings and for the
three upper storeys of a four storey building and for the
two upper storeys of a seven-storey building
o a < 20 · t for all other storeys in four – seven – storey buildings
For bricks of compressive strength class 4 and 6:
o a < 35 · t for all storeys building smaller than 20,0 m
For bricks of higher compressive strength classes:
o a < 40 · t for all storeys building smaller than 20,0 m
These criteria count for masonry with and without mortared butt joints.
Figure 3.1: Requirements for lengths and distances a of stiffening walls according to
the simplified check of structural stability according to Mann/ Müller [17]
TUD – Institut für Massivbau
Only for use in the context of the lecture MSCC. No further reproduction or distribution is permitted!
2 Structural stability 26
According to the simplified check in the direction of the letter-axis there must be a stiffening
wall with a length equal or larger than 7,0 m with a maximum traverse distance to the next
stiffening wall of 7,0 m. This requirement is not fulfilled.
So even if on the first view it seems like there is a great number of stiffening walls in this
building, the analysis of the structural stability has to be executed and cannot be omitted.
For the bracing system only long walls, that do not have any major openings and offsets and
that go continiously from the top till the foundations are considered. The engineer is free to
chose which elements are taken into account for the analysis of structural stability. The more
walls are considered in the calculation the higher are the stiffness and the load bearing capacity
of the bracing system. In Figure 3.2 the walls which are considered as stiffening elements are
marked in blue.
Figure 3.3: Wind loads on the example building in the direction of letter-axis
All stiffening elements together creates the stiffness of the “building cross section” with the
shear centre “M” (see Figure 3.2). In vertical direction the bracing system is supposed a
cantilever, which transfers the horizontal loads till the clamping plane.
This vertical static system of the building for determining the bracing loads can be applied in
different ways depending on the stiffness of the basement box. The following representations
are chosen as examples:
2.OG
1.OG
Highly stiffened
basement EG
UG
M V
2.OG
Stiffened 1.OG
UG
M V
2.OG
M V
Since the basement storey has the same floor plan as the storeys above the clamping level is
defined at the foundation level (see Figure 3.4, right).
Figure 3.4: left: static system of the fassade; right: static system of the building
bracing
The left part of Figure 3.4 shows the static system of the fassade of the building. The wind
loads which act on the outside of the building are transfered vertically to the slabs by the
exterior walls. The reinforced concrete slabs act like rigid diaphragms. The slabs transfer the
load to the stiffening elements. All stiffening elements act together as one single cross section
of the vertical cantilever (see left part of Figure 3.4) which transfers the horizontal loads to the
foundations.
As a conservative and common approach the stiffness of the walls around the weak axis is
neglected for this calculation and therefore assumed to be equal to zero. Only the stiffness
around the strong axis is considered. The following table shows the cross-sectional values of
the individual stiffening components.
Table 3-3: Equation for the coordinates of the shear centre M of the stiffening walls
[Schneider Bautabellen für Ingenieure, 20. Auflage (2012), page 5.40]
The centrifugal moment of area Iyz,I of all stiffening elements is equal to zero. Therefore, the
simplified equations can be employed.
Ei I y ,i yi Ei I z ,i zi
yM = zM =
Ei I y Ei I z
yi, zi Distance of an optional point to the shear centre of a stiffening element. The distances
have to be inserted with their correct sign. For this example, the intersection point A/1
is chosen as reference point and orgin of the coordinate system.
Stiffening wall Iy [m4] yi [m] Iy*yi [m5] Iz[m4] zi [m] Iz*zi [m5]
EW-01.1 0.00 5.64 0.00 39.44 0.00 0.00
EW-01.2 0.00 19.87 0.00 29.56 0.00 0.00
EW-02.1 0.59 0.00 0.00 0.00 1.34 0.00
EW-02.2 0.59 0.00 0.00 0.00 7.84 0.00
EW-03 0.00 12.50 0.00 267.25 9.00 2405.29
EW-04.1 0.59 24.97 14.67 0.00 1.34 0.00
EW-04.2 0.59 24.97 14.67 0.00 7.84 0.00
IW-02 9.39 11.00 103.28 0.00 4.50 0.00
IW-04 9.39 15.00 140.84 0.00 4.50 0.00
∑ 21.13 273.46 336.26 2405.29
273.46 m5
yM = = 12.94m
21,13m4
Coordinates of the shear centre:
2405.29m5
zM = = 7.15m
336.26 m4
25.00 m
yS = = 12.50 m
2
Coordinates of the centre of the floor plan:
9.00 m
zS = = 4.50 m
2
Figure 3.5: Shear center and center of the floor plan of the bracing system
The distance from the shear center to the center of the floor plan is:
cy = 0.44 m; cz = 2.65 m
N Ed 0.6 for n 4
htot
EI 0.2 + 0.1 n for 1 n 4
Where:
htot is the total height of the structure from the top of the foundation;
NEd is the design value of the vertical load (at the bottom of the building) for service
loads (1.0 · NGk + 1.0 · NQk)
∑ EI is the sum of the bending stiffnesses of all vertical stiffening building elements in
the relevant direction;
n is the number of storeys.
NOTE: Openings in vertical stiffening elements of less than 2 m2 with heights not
exceeding 0,6 h may be neglected.
For the calculation the loads can be extracted from Table 2.10 and Table 2.11. These tables
do not include the loads for the basement floor. Since the basement floor is very similar to the
first floor, these loads for the basement floor are assumed here to be equal to the loads of the
first floor in a simplified approach.
NGk = 7589.60 kN + 2276.24 kN = 9865.84 kN
NQk = 2045.95 kN + 528.57 kN = 2574.52 kN
NEd = 1.0 · NGk + 1.0 · NQk = 12440.36 kN
For the calculation of ∑ EI for the wind load parallel to the letter-axis, ∑ EIy is used.
∑ Iy = 21.13 m4 (see Table 3-4)
E = KE · fk
KE =1100 (for clay bricks according to DIN EN 1996-1-1, chapter 3.7.2, table NA.13)
fk = 5.0 MN/m² (see chapter 3.1.2)
E = 1100 · 5.0 = 5500 MN/m²
∑ EI = 5500 · 21.13 = 116215 MNm²
htot = 16.0 m
12.440
16 = 0.166 0.6 for n = 5 ✓
116215
Second oder effects do not have to be considered for the analysis of structural stability.
The inclination angle causes in combination with a vertical load an equvalent horizontal load
as it can be seen in Figure 3.6: ΔH = ν · NEd.
The total vertical loads per storey can be extracted from Table 2.10 and Table 2.11:
Figure 3.7 shows the real situation of the acting loads (left), the translation-part (middle) and
the torsion-part (right). Under the figures the equations for the calculation of the load
distribution of each stiffening wall are given.
Ei I z ,i Ei I z ,i zi*
H y ,i = H y , Ed H y ,i = −TEd
EI z ,i ( Ei I zi zi*2 + Ei I yi yi*2 )
Ei I y ,i Ei I y ,i yi*
H z ,i = H z , Ed H z ,i = TEd
EI y ,i ( Ei I zi zi*2 + Ei I yi yi*2 )
Ei I y ,i
H z ,i = H z , Ed
EI y ,i
All stiffening elements consist out of the same brick type, therefore Ei can be eliminated in the
equation.
9.39
H z ,1−load , IW −02 = H z ,1−load , IW −04 = 1
= 0, 444
21.13
→ IW-02, IW-04 gets 44.4 % of the acting horizontal load in z-direction
All stiffening elements consist out of the same brick type, therefore Ei be cutted out in the
equation. The signs of TEd in the equation above assume a positive torsion-moment in
clockwise direction. If TEd acts counterclockwise it must be inserted as a negative value.
7.60
H z ,1−load , EW −02.1 = 1, 0 = 0, 0016
441.89 + 4442.27
7.60
H z ,1−load , EW −02.2 = 1, 0 = 0, 0016
441.89 + 4442.27
−7.06
H z ,1−load , EW −04.1 = 1, 0 = −0, 0014
441.89 + 4442.27
−7.06
H z ,1−load , EW −04.2 = 1, 0 = −0, 0014
441.89 + 4442.27
18.24
H z ,1−load , IW −02 = 1, 0 = 0, 0037
441.89 + 4442.27
−19.32
H z ,1−load , IW −04 = 1, 0 = −0, 0040
441.89 + 4442.27
Wind loads for the load case full wind parallel to the letter-axis:
wz,voll = wD + wE = 0.52 kN/m² + 0.34 kN/m² = 0.86 kN/m²
efull wind distance between the load center of the wind load and the shear center of the bracing
system
efull wind = yM – ywind full = 0.44 m
Note: The full centric wind load acts in the center of the floor plan.
eimp distance between the load center of the floor plan and the shear center of the bracing
system
eimp = yM – yimp= 12.94 – 12.50 = 0.44 m
The loads in the stiffening walls are calculated by multiplying the factors H z ,1−load ,i and
H z ,1−load ,i with the value of the total load Hz,Ed,full and TEd,full. Additionally, the bending moment
around the strong axis of each stiffening wall is calculated by multiplying the horizontal load
per storey with the storey height above the foundations.
H z , i = H z ,i + H z ,i
H z ,i = H z ,1−load ,i H z , Ed , full + H z ,1−load ,i TEd , full
H Ed , z ,i ,bottom = H z ,i ,base + H z ,i ,1st + H z ,i ,2 nd + H z ,i ,3rd
M Ed ,i ,bottom = H z ,i ,3rd 12.40m + H z ,i ,2 nd 9.20m + H z ,i ,1st 6.00m + H z ,i ,base 2.80m
H y ,i = H y ,i
H y ,i = H y ,1−load ,i TEd , full
H Ed , y ,i ,bottom = H y ,i ,base + H y ,i ,1st + H y ,i ,2 nd + H y ,i,3 rd
M Ed ,i ,bottom = H y ,i ,3rd 12.40m + H y ,i ,2 nd 9.20m + H y ,i ,1st 6.00m + H y ,i ,base 2.80m
Check of equilibrium:
Fy = 0: 19.86 kN - 11.37 kN – 8.52 = 0.0 kN
Fz = 0: 12.67 kN · 2 + 12.08 kN · 2 + 198.36 kN + 196.85 kN – 444.72 kN = 0.0 kN
MM = 0: 2 · 12.67 kN · 12.94 m + 198.36 kN · 1.94 m – 196.85 kN · 2.06 m
- 2 · 12.08 kN · 12.03 m + (11.37 kN + 8.52 kN) · 7.15 m + 19.89 kN · 1.85 m
- 196.83 kNm = -1.26 kNm ≈ 0 (rounding error)
Wind loads for the load case full wind parallel to the letter-axis:
wz,ecc = 0.5 · wD + wE = 0.5 0.52 kN/m² + 0.34 kN/m² = 0.60 kN/m²
eecc wind distance between the load center of the eccentric wind load and the shear center of
the bracing system
0.5 wD 1 25.0 + wE 1 25.0
yecc wind = 3 2
yecc wind = 0.5 wD + wE
yecc wind = 10.69 m
eecc wind = yM – yecc wind = 12.94 – 10 69 = 2.25 m
Note: The eccentric wind load is applied unfavourably with the maximum distance to the
shear center.
eimp distance between the load center of the floor plan and the shear center of the bracing
system
eimp = yM – yimp= 0.44 m
The loads in the stiffening walls are calculated by multiplying the factors H z ,1−load ,i and
H z ,1−load ,i with the value of the total load Hz,Ed,full and TEd,full. Additionally, the bending moment
around the strong axis of each stiffening walld is calculated by multiplying the horizontal load
per storey with the storey height above the foundations.
H z , i = H z ,i + H z ,i
H z ,i = H z ,1−load ,i H z , Ed , full + H z ,1−load ,i TEd , full
H Ed , z ,i ,bottom = H z ,i ,base + H z ,i ,1st + H z ,i ,2 nd + H z ,i ,3rd
M Ed ,i ,bottom = H z ,i ,3rd 12.40m + H z ,i ,2 nd 9.20m + H z ,i ,1st 6.00m + H z ,i ,base 2.80m
H y ,i = H y ,i
H y ,i = H y ,1−load ,i TEd , full
H Ed , y ,i ,bottom = H y ,i ,base + H y ,i ,1st + H y ,i ,2 nd + H y ,i,3 rd
M Ed ,i ,bottom = H y ,i ,3rd 12.40m + H y ,i ,2 nd 9.20m + H y ,i ,1st 6.00m + H y ,i ,base 2.80m
Check of equilibrium:
Fy = 0: 66.72 kN – 28.58 kN – 38.14 kN = 0.0 kN
Fz = 0: 10.15 kN · 2 + 8.17 kN · 2 + 148.29 kN + 143.21 kN – 328.14 kN = 0.0 kN
MM = 0: 2 · 10.15 kN · 12.94 m + 148.29 kN · 1.94 m – 143.21 kN · 2.06 m
- 2 · 8.17 kN · 12.03 m + (38.14 kN + 28.58 kN) · 7.15 m + 66.72 kN · 1.85 m
- 660.16 kNm = -0.89 kNm ≈ 0 (rounding error)
Table 3-5: Summary of the horizontal stiffening wall loads at the bottom of each wall
imperfections + wind in z
shear wall full wind load ecc. wind load
The following sketch illustrates the resulting loads HEd and MEd in the table.
Figure 3.10: Resulting loads at the bottom of a wall in the basement HEd and MEd
Geometry
t = 0.175 m
b = 4.635 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 12
Compressive fk N/mm²
strength
class of units M 2.5 M5 M 10 M 20
4 2.1 2.4 2.9 -
6 2.1 3.1 3.7 -
8 3.1 3.9a 4.4a -
a a
10 3.5 4.5 5.0 5.6
12 3.9 5.0a 5.6a 6.3
16 4.6 5.9a 6.6a 7.4
20 5.3 6.7a 7.5a 8.4
28 5.3 6.7 9.2 10.3
36 5.3 6.7 10.6 11.9
48 5.3 6.7 12.5 14.1
60 5.3 6.7 14.3 16.0
a
vertically perforated clay masonry units with type E perforation only for compressive
strength class 8 till 20 and mortar class M 5 and M 10.
hef = n h
with
hef effective height
h clear storey height
ρn reduction coefficient according to Table 4.2
Table 4.2 Factor ρ2 for determining the effective height hef in the simplified
calculation method [9]
Wall thickness Reduction coefficient Required minimum support depth of the ceiling
t ρ2 a
[cm] [cm]
≤ 17.5 0.75 a=t
17.5 < t < 24 0.90 a=t
24 ≤ t ≤ 25 0.90 a ≥ 17.5
> 25 1.00 -
The slab support width is equal to the wall thickness (a/t = 1.0)
Having t = 0.175m, the reduction coefficient is given by:
➔ ρ2 = 0.75
➔ hef = 0.75 · 3.0 = 2.25 m
Slenderness λ
for the permanent residence of people. As load-bearing wall framed with a veneer wall and for double-leaf
walls used for house partition up to a maximum of two full storeys plus developed attic storey; bracing cross
walls at a distance b ≤ 4.50 m or edge distance from an opening b' ≤ 2.0 m (see Figure NA.2).
b Characteristic live load including surcharge for non-load-bearing internal partition walls q ≤ 3.0 kN/m2 .
k
c For characteristic compressive strengths masonry f < 1.8 N/mm2 footnote a need to be applied.
k
d Application requirements:
lf a a
1 = 1.6 − 0.9
6 t t
with
a/t ratio of slab support width a to wall thickness t; with fully supported slab, a/t = 1.0
lf the span length of the adjacent floor slab in m, for two-way slabs with 0.5 ≤ l1 /l2 ≤ 2.0,
0.85 times the shorter span may be used for lf, the span starts and ends at the load
centre of the slab support.
a / t = 1.0
slab axis A-B: span = min(9.0 m; 5.0 m) = 5.0 m → lf = 0.85 · 5.0 m = 4.25 m
slab axis B-C: span = min(9.0 m; 6.0 m) = 6.0 m → lf = 0.85 · 6.0 m = 5.10 m
As a conservative approach lf = 5.10 m applies for the following calculation.
5.1
1 = 1.6 − 1.0 0.9 1.0
6
1 = 0.75 0.9
1 = 0.75
2
2.25
2 = 0.85 1.0 − 0.0011
0.175
2 = 0.67
3.1.6 Verification
3.1.6.1 Maximum load
NRd = Φ · A · fd ≥ NEd
Geometry
t = 0.365 m; a = 2/3 · 0.365 m = 24.3 m
b = 9.36 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 10
1 h
hef = 2 h for 4 1
h
2
b
1 + 4 2
b
b h
hef = 4 1
2 4 b
with
ρ2 reduction coefficient according to Table 4.2
h wall height
b centre-to-centre distance of the bracing walls according to chapter 5
4 modification factor to take into account the properties of high precision masonry
elements with reduced overlap. For small and medium-sized masonry the modification
factor is 4 = 1.0.
Table 4.4 Factor ρ2 for determining the effective height hef for walls in the simplified
calculation method [9]
Wall thickness Reduction coefficient Required minimum support depth of the ceiling
t ρ2 a
[cm] [cm]
≤ 17.5 0.75 a=t
17.5 < t < 24 0.90 a=t
24 ≤ t ≤ 25 0.90 a ≥ 17.5
> 25 1.00 -
➔ ρ2 = 1.00
h 3.00
➔ 4 = 1.0 = 0.33 1.00
b 9.00
1
hef = 1.0 3.0 = 2.70
1.0 3.0
2
1 + 1.0
9.0
Slenderness λ
a / t = 2/3
2
1,top = 0.4 = 0.27
3
1,top = 0.27
Equation for capacity reduction factor at the bottom of the wall for fk ≥ 1.80 N/mm²:
lf a a
1,bottom = 1.6 − 0.9
6 t t
with
a/t ratio of slab support width a to wall thickness t; with fully supported slab, a/t = 1.0
lf the span length of the adjacent floor slab in m, for two-way slabs with 0.5 ≤ l1 /l2 ≤ 2.0,
0.85 times the shorter span may be used for lf, the span starts and ends at the load
centre of the slab support.
a / t = 2/3
span = min(9.0 m; 5.0 m) = 5.0 m → lf = 0.85 · 5.0 m = 4.25 m
4.25 2 2
1,bottom = 1.6 − 0.9
6 3 3
1,bottom = 0.59 0.6
1,bottom = 0.59
3.2.6 Verification
3.2.6.1 Maximum load
NRd = Φ · A · fd ≥ NEd
3 qEwd h2 b
N Ed ,min = 1,0 NGk
h
16 a −
300
with
NGk characteristic value of permanent actions at the mid-height of the wall
h clear wall height
qEwd characteristic wind load according to chapter 1.2.3
b the action width of the wind load (wall length)
a ceiling support depth (with fully supported ceiling, set a = t)
The verification must be carried out at the mid height of the wall, so that the dead weight of
half of the wall plus plaster may also be considered. If this verification is not fulfilled, the walls
or wall sections in question can be designed and constructed conservatively as non-load-
bearing exterior walls according to chapter 7.
Geometry
t = 0.175 m
b = 0.50 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 12
hef = n h
The reduction coefficient ρn applies according to Table 4.2 and the slab support width is equal
to the wall thickness (a/t = 1.0).
➔ ρ2 = 0.75
➔ hef = 0.75 · 3.0 = 2.25 m
Slenderness λ
TUD – Institut für Massivbau
Only for use in the context of the lecture MSCC. No further reproduction or distribution is permitted!
3 Simplified calculation method – DIN EN 1996 -3 59
lf a a
1 = 1.6 − 0.9
6 t t
a / t = 1.0
lf = 0.85 · 6.0 m = 5.1 m
(for two-way slabs with 0.5 ≤ l1 /l2 ≤ 2.0, 0.85 times the shorter span may be used for lf)
5.1
1 = 1.6 − 1.0 0.9 1.0
6
1 = 0.75 0.9
1 = 0.75
3.3.6 Verification
NRd = Φ · A · fd ≥ NEd
This example illustrates that the design of masonry columns with high loads gets difficult with
an increasing number of storeys. One of the following measures must be applied to fulfil the
verification:
o Masonry with a higher compressive strength
o Construction of the column with reinforced concrete instead of masonry
Even with a general-purpose mortar of compressive strength class M20 and a masonry unit of
compressive strength class 60, this verification is not fulfilled. Therefore, a reinforced concrete
column must be constructed.
Geometry
t = 0.175 m
b = 4.635 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 12
• the building does not exceed three storeys in height above the ground floor level ✓
• the walls are laterally restrained by the floors and roof in the horizontal direction at
right angles to the plane of the wall, either by the floors and roof themselves or by ✓
suitable methods, for example, ring beams with sufficient stiffness
• the floors and roof have a support width on the wall of at least 2/3 of the thickness
✓
of the wall but not less than 85 mm
• the clear storey height does not exceed 3.0 m ✓
For walls that support ceilings over a part of the wall thickness and
- fk ≥ 1.8 N/mm² and an effective span of the ceiling > 5 m or
- fk < 1.8 N/mm² and an effective span of the ceiling > 4 m as well as
generally, for walls as end supports on the uppermost storey, especially under roof ceilings,
the values for φ are to be multiplied by a/t.
18
a / t = 1.0
fk > 1.8 N/mm²
lf > 5.0 m
➔ Φ = 0.5
4.1.6 Verification
The verification of the absorbable normal force is carried out analogous to the simplified
procedure.
NRd = Φ · A · fd ≥ NEd
NRd = 0.5 · 0.175 · 4.635 · 2.83 = 1147.74 kN < NEd,u = 1407.28 kN
➔ The verifications with the simplified calculation method according to DIN EN 1996-3
Annex A for the interior wall IW-01 are not fulfilled!
Geometry
t = 0.365 m
b = 9.36 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 10
generally, for walls as end supports on the uppermost storey, especially under roof ceilings,
the values for φ are to be multiplied by a/t.
a/t=2/3
fk > 1.8 N/mm²
lf > 5.0 m
➔ Φ = 0.33 · 2 / 3 = 0.22
4.2.6 Verification
The verification of the absorbable normal force is carried out analogous to the simplified
procedure.
NRd = Φ · A · fd ≥ NEd
NRd = 0.22 · 0.365 · 9.365 · 2.55 = 1917.62 kN > NEd,u = 384.07 kN ✓
➔ The wall EW-02 can be verified with the simplified calculation method according to DIN
EN 1996-3 Annex A!
Geometry
t = 0.175 m
b = 4.635 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 12
Internal forces
5.1.1.1 Normal forces
The vertical loads of all construction elements are calculated in chap. 1.4 and summarized in
Table 1-10 and Table 1-11. (Pdf page 32)
n1 E1 I1
h1 q3 l32 q4 l42
M1 = −
n1 E1 I1 n2 E2 I 2 n3 E3 I 3 n4 E4 I 4 ( n3 − 1) 4 ( n4 − 1)
+ + +
h1 h2 l3 l4
n2 E2 I 2
h2 q3 l32 q4 l42
M2 = −
n1 E1 I1 n2 E2 I 2 n3 E3 I 3 n4 E4 I 4 ( n3 − 1) 4 ( n4 − 1)
+ + +
h1 h2 l3 l4
with
ni stiffness factor of members; it is taken as 4 for members fixed at both ends and
otherwise 3;
Ei modulus of elasticity of member i, the values of E for masonry are defined with:
E = KE · fk (or KE see Table 5.1)
Ii second moment of area of member i;
h1 clear height of member 1;
h2 clear height of member 2;
l3 clear span of member 3, the longer slab span
l4 clear span of member 4, the shorter slab span
Note for l3 und l4:
According to DIN EN 1996-1-1 Annex NA.C for two-way slabs a reduced value applies
for the spans, which is 2/3 of the shorter span.
q3 design uniformly distributed load on member 3, using the partial factors from EN 1990
for unfavourable actions;
q4 design uniformly distributed load on member 4, using the partial factors from EN 1990
for unfavourable actions
Table 5.1 Values KE for the calculation of the modulus of elasticity of masonry [8]
Two different load combinations can be decisive for the determination of the eccentricity at the
top and bottom of the wall. According to DIN EN 1996-1-1 / NA, section 2.4.2 half the imposed
load may be taken as permanent. Therefore, the load combinations shown in Figure 5.3 are
possible.
Load combination A Load combination B
Figure 5.3 Load combinations for decisive eccentricities at the top and bottom of the
wall
Load combination A
junction at the top of the wall: q3 = 1.35 ·7.34 + 0.5 · 1.5 · 2.30 = 11.63 kN/m²
q4 = 1.35 ·7.34 + 1.5 · 2.30 = 13.36 kN/m²
junction at the bottom of the wall: q3 = 13.36 kN/m²
q4 = 11.63 kN/m²
4 5500 0.000447
3.00 11.63 3.882 13.36 3.152
M1 = −
4 5500 0.000447 4 5500 0.000447 4 33000 0.000667 3 33000 0.000667
+ + + 4 ( 4.0 − 1) 4 ( 3.0 − 1)
3.00 3.00 3.88 3.15
3.278
M1 = 14.590 − 16.571
3.278 + 3.278 + 22.692 + 20.963
M1 = −0.129 kNm / m
4 5500 0.000447
3.00 13.36 3.882 11.63 3.152
M2 =− −
4 5500 0.000447 4 5500 0.000447 4 33000 0.000667 3 33000 0.000667
+ + + 4 ( 4.0 − 1) 4 ( 3.0 − 1)
2.60 3.00 3.88 3.15
3.278
M2 = − 16.761 − 14.425
3.782 + 3.278 + 22.692 + 20.963
M 2 = −0.151 kNm / m
Load combination B
junction at the top of the wall: q3 = 13.36 kN/m²
q4 = 11.63 kN/m²
junction at the bottom of the wall: q3 = 11.63 kN/m²
q4 = 13.36 kN/m²
4 5500 0.000447
3.00 13.36 3.882 11.63 3.152
M1 = −
4 5500 0.000447 4 5500 0.000447 4 33000 0.000667 3 33000 0.000667
+ + + 4 ( 4.0 − 1) 4 ( 3.0 − 1)
3.00 3.00 3.88 3.15
3.278
M1 = 16.761 − 14.425
3.278 + 3.278 + 22.692 + 20.963
M1 = 0.153 kNm / m
4 5500 0.000447
3.00 11.63 3.882 13.36 3.152
M2 = − −
4 5500 0.000447 4 5500 0.000447 4 33000 0.000667 3 33000 0.000667
+ + + 4 ( 4.0 − 1) 4 ( 3.0 − 1)
2.60 3.00 5.825 4.730
3.278
M2 = − 14.590 − 16.571
3.782 + 3.278 + 22.692 + 20.963
M 2 = 0.128 kNm / m
The following figure illustrates that load combination A produces the decisive moment at the
bottom of the wall and load combination B produces the decisive moment at the top of the wall.
In each decisive load case the slab with the longest span is charged with the higher load at the
top or respective at the bottom of the wall.
Load combination B
Load combination A
Since IW-01 is an interior wall, wind loads do not affect the distribution of the bending moment
around the weak axis of the wall.
These bending moments may be reduced by multiplication with the factor η, as the theoretical
rigidity of the floor-wall junction may not be achieved due to crack formation:
E3,o I 3,o E I
n3,o l + n4,o 4,o 4,o
l4,o
o = 1 − 0, 25 min 3,o
;2,0
n1,o E1,o I1,o + n2,o E2,o I 2,o
h1,o h2,o
E3,u I 3,u E I
n3,u l + n4,u 4,u 4,u
l4,u
u = 1 − 0, 25 min 3,o
;2,0
n1,u E1,u I1,u + n2,u E2,u I 2,u
h1,u h2,u
with
ni stiffness factor of the considered member i
n = 4 for restrained support at the distal end (e.g. outer wall)
n = 3 for hinged support at the distal end (e.g. inner wall)
Ei modulus of elasticity of the considered bar i
Ii moment of inertia of the bar under consideration i
In the case of cavity walls with an air layer, where only one wall shell is loaded, only
the moment of inertia of the loaded wall shell may be assumed for Ii. In most cases, the
effective width of the slab and the width of the wall are equal, i.e. b B/bD = 1. If wall
openings or slab openings are arranged near the edge, the widths of the slab and wall
can be different. The moment of inertia of the walls has to be determined with a wall
thickness equal to the actual support depth of the ceiling (t = a).
h1 clear height of the bar 1
h2 clear height of the bar 2
l3 clear span of member 3, the longer slab span
l4 clear span of member 4, the shorter slab span
Note for l3 und l4:
According to DIN EN 1996-1-1 Annex NA.C for two-way slabs a reduced value applies
for the spans, which is 2/3 of the shorter span.
q3 uniformly distributed design load of member 3 when applying the partial safety factors
for unfavourable action
q4 uniformly distributed design load of member 4 when applying the partial safety factors
for unfavourable action
o, u index for the top (o) or bottom (u) of the wall
The values of the bending moment according to Figure 5.4 are reduced by the factors ηo at the
top of the wall and ηu at the bottom of the wall. The reduced bending moments are shown in
Figure 5.5.
Load combination A Load combination B
Figure 5.5 Reduced bending moment of IW-01 with different load combinations
e ≤ t/6 0.75
e ≥ t/3 1.0
Intermediate values may be obtained by linear interpolation
e is the eccentricity of the design axial load acting on the top of the wall (without allowing
for any accidental eccentricity)
A reduction in the effective height using ρ2 < 1.0 is only permitted if the bearing height a of
the floor on the wall complies with the following values:
t ≥ 12.5 cm a ≥ 2/3 - t
5.1.3.3 Slenderness
Slenderness λ = hef / t = 2.25 / 0.175 = 12.86 < 27
According to DIN EN 1996-1-1, section 5.5.1.4 the slenderness ratio of the masonry wall
should not be greater than 27 when subjected to mainly vertical loading.
with
ei eccentricity at the top or the bottom of the wall
Mid design value of the bending moment at the top or bottom of the wall resulting from the
eccentricity of the floor load at the support (see Figure 5.6)
Nid design value of the vertical load at the top or bottom of the wall;
ehe eccentricity at the top or bottom of the wall, if any, resulting from horizontal loads (for
example, wind);
einit initial eccentricity with a sign that increases the absolute value of ei
t thickness of the wall
The eccentricity due to horizontal loads ehe is 0 (no horizontal loads act on IW-01)
The unplanned eccentricity einit is equal to zero at the top and bottom of the wall, since
imperfections are already covered by the minimum eccentricity of 0.05 · t.
einit, top = einit, bottom = 0
0.077
etop = + 0 + 0 = 0.00026 m 0.05 0.175= 0.00875 m
1365.04 4.635
0.00875
top = 1− 2 = 0.9
0.175
0.076
ebottom = + 0 + 0 = 0.00025 m 0.05 0.175= 0.00875 m
1407.28 4.635
0.00875
bottom = 1− 2 = 0.9
0.175
with
emk eccentricity at the middle height of the wall, calculated as follows:
emk = em + ek ≥ 0.05 · t
M md
em = + ehe + einit 0.05 t
N md
The eccentricity due to creep ek can be neglected if the critical slenderness according to
Table 5.4 is not exceeded. For the determination of the critical slenderness the final creep
coefficient - depending on the masonry unit and mortar - can be applied according to Table
5.3.
Table 5.3 Deformation characteristics of masonry according to [8]
Final value of the Coefficient of
Final creep
moisture thermal E-Modulus
coefficient a
expansion b expansion
Masonry N/mm2
Unit type Φ∞
mortar type mm/m αt 10-6 / K
General
purpose
masonry
0.5 -
mortar / thin- 1.0
1.5 -0.1c 950 -
layer
Clay masonry 0 - 6 5-7 1100 - fk 1250
mortar +0.3 - fk
Lightweight
1.0 -
masonry 2.0
3.0
mortar
General
purpose
masonry 800 -
Calcium 1.0 - -0.3
mortar / thin- 1.5 -0.2 8 7-9 950 - fk 1250
silicate 2.0 -- 0.1
layer - fk
masonry
mortar
General 2050
Aggregate purpose -0.3 -
1.0 - -0.2 10 2400 - fk
concrete masonry -- 0.1 2700
mortar - fk
General 8 -
purpose -0.6 12
-0.4
Lightweight masonry -- 0.2 800 -
mortar 1.5 - d
aggregate 2.0 10; 8 950 - fk 1100
2.5
concrete Lightweight - fk
-0.6
masonry -0.5
-- 0.3
mortar
a Final creep coefficient φ∞ = ε∞ / εel , where εc∞ is the final creep strain and εel = σ/E.
b Final value of moisture expansion is given negatively for shortening and positively for expansion.
c For masonry units < 2 DF the limit value - 0.2 mm/m applies.
Final creep coefficient for clay masonry units and for general purpose mortar: Φ∞ = 1.0
ek = 0
For the eccentricity resulting from horizontal loads ehe at mid-height applies ehe = 0 since
there are no horizontal loads acting on IW-01.
For the unplanned eccentricity einit,mid at the mid-height of the wall applies according to DIN
EN 1996-1-1, section 5.5.1.1:
einit,mid = hef / 450 = 2.25 / 450 = 0.005 m
M md
em = + ehe + einit 0.05 t
N md
0.071
em = + 0 + 0.005 = 0.00524 m 0.05 0.175= 0.00875 m
1386.16 4.635
emk = em + ek
emk = 0.00875 + 0.0 = 0.00875 m
Geometry
t = 0.365 m; a = 2/3 · 0.365 m = 24.3 m
b = 2.68 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 10
Normal force at the bottom of EW-02.1 at the level of the 1st floor:
Ngk,u = 567.32 kN / 2 = 283.66 kN; Nqk,u = 113.68 kN / 2 = 56.84 kN
NEd,u = 1.35 · Ngk,u + 1.50 · Nqk,u = 468.20 kN
Normal force at the top of EW-02.1 at the level of the 1st floor:
Ngk,o = Ngk,u – gk,interior,wall · l = 283.66 kN – 8.43 kN/m · 2.68 m = 261.07 kN
Nqk,o = 56.84 kN
NEd,o = 1.35 · Ngk,o + 1.50 · Nqk,o = 437.70 kN
Normal force at the mid-height of EW-02.1 at the level of the 1st floor:
Ngk,m = Ngk,u – 0,5 · gk,interior,wall · l = 283.66 kN – 0.5 · 8.43 kN/m · 2.68 m = 272.36 kN
Nqk,m = 56.84 kN
NEd,m = (NEd,u + NEd,o) / 2 = 452.95 kN
n1 E1 I1
h1 q3 l32 q4 l42
M1 = −
n1 E1 I1
+
n2 E2 I 2
+
n3 E3 I 3
+
n4 E4 I 4 ( n3 − 1) 4 ( n4 − 1)
h1 h2 h3 h4
n2 E2 I 2
h2 q3 l32 q4 l42
M2 = −
n1 E1 I1
+
n2 E2 I 2
+
n3 E3 I 3
+
n4 E4 I 4 ( n3 − 1) 4 ( n4 − 1)
h1 h2 h3 h4
4 4950 0.001201
3.00 13.36 3.152
M1 = 0−
4 4950 0.001201 4 4950 0.001201 4 33000 0.000667
4 ( 4.0 − 1)
+ +0+
3.00 3.00 3.15
7.927
M1 = 0 − 11.05
7.927 + 7.927 + 0 + 27.950
M 1 = −2.00 kNm / m
4 4950 0.001201
2−
13.36 3.15
M2 = − 3.00 0 −
4 4950 0.001201 4 4950 0.001201 4 33000 0.000667 4 ( 4.0 − 1)
+ +0+
2.60 3.00 3.15
7.927
M2 = − −11.05
9.146 + 7.927 + 0 + 27.950
M 2 = 1.946 kNm / m
These results may be reduced by multiplication with the factor ηo and ηu, as the theoretical
rigidity of the floor-wall junction may not be achieved due to crack formation. As a conservative
approach this reduction of the bending moments is relinquished here.
For the bending moments due to wind loads that are acting on the facade, the engineer is free
to choose a static system to determine the internal forces. Either a simple beam with hinged
supports at the top and bottom of the wall can be used, or a beam with fixed supports at the
top and bottom of the wall (see Figure 5.9 and Figure 5.10). For each assumption, it is
important that the internal forces can be taken up by the structure.
The decisive wind load at the facade results from wind suction:
we = cpe,10,A · qp = -1.2 · 0.65 kN/m² = - 0.78 kN/m²
wd = γQ · we = 1.50 · - 0.78 = - 1.17 kN/m²
The following figures illustrate the bending moment due to the restraint of the slab and due to
wind. The resulting bending moment around the weak axis is the addition of both. The
assumption of hinged supports for the wind load is shown in Figure 5.9 and the assumption of
fixed supports is shown in Figure 5.10.
+ =
Figure 5.9 Bending moment of the weak axis (wind load with hinged supports)
+ =
Figure 5.10 Bending moment of the weak axis (wind load with fixed supports)
The following calculation uses the bending moment according to Figure 5.9.
5.2.3.2 Capacity reduction factors at the top and bottom of the wall
The verification and the capacity reduction factor at the top and bottom of the wall refers to the
ideational cross-section with the wall thickness a (a = 2/3 · t).
ei
z ,i = 1 − 2
a
M id
ei = + ehe + einit 0.05 a
Nid
with
ei eccentricity at the top or the bottom of the wall
Mid design value of the bending moment at the top or bottom of the wall resulting from the
eccentricity of the floor load at the support
Nid design value of the vertical load at the top or bottom of the wall;
ehe eccentricity at the top or bottom of the wall, if any, resulting from horizontal loads (for
example, wind);
einit initial eccentricity with a sign that increases the absolute value of ei
a support depth of the slab on top of the wall
The eccentricity due to horizontal loads ehe is already included in Mid / Nid (see chapter
5.2.1.2).
The unplanned eccentricity einit is equal to zero at the top and bottom of the wall, since
imperfections are already covered by the minimum eccentricity of 0.05 · t.
einit, top = einit, bottom = 0
1.95
ebottom = + 0 + 0 = 0.0112 m 0.05 2 0.365= 0.01217 m
468.20 2.68 3
0.01217
z ,bottom = 1− 2 = 0.90
2 0.365
3
1
hef = 2 h 0.3 h
h
2
1 + 3 2
3 b '
1
hef = 0.75 3.00 = 2.06 0.3 h = 0.9
0.75 3.00
2
1 + 1.0
3 2.50
hef = 2.06 m
Slenderness
Slenderness λ = hef / t = 2.06 / 0.365 = 5.64 < 27
According to DIN EN 1996-1-1, section 5.5.1.4 the slenderness ratio of the masonry wall
should not be greater than 27 when subjected to mainly vertical loading.
The capacity reduction factor has to be calculated according to the equation given by DIN EN
1996-1-1/NA - Annex NA.G:
with
emk eccentricity at the middle height of the wall, calculated as follows:
emk = em + ek ≥ 0.05 · t
M md
em = + ehe + einit
Nmd
ehm eccentricity at mid-height resulting from horizontal loads (for example, wind);
NOTE The inclusion of ehm depends on the load combination being used for the
verification; its sign relative to that of Mmd/Nmd should be taken into account.
einit initial eccentricity with a sign that increases the absolute value of em
hef effective height
tef effective thickness of the wall
ek eccentricity due to creep, calculated from the following equation:
hef
ek = 0.002 t em
tef
Φ∞ final creep coefficient
The eccentricity due to creep ek can be neglected if the critical slenderness according to
Table 5.4 is not exceeded. For the determination of the critical slenderness the final creep
coefficient - depending on the masonry unit and mortar - can be applied according to Table
5.3.
Infinite creep coefficient for clay masonry units and general purpose mortar: Φ∞ = 1.0
Slenderness λ = 5.64 ≤ 15 (critical slenderness) ✓
ek = 0
The eccentricity due to horizontal loads ehe is already included in Mid / Nid (see chapter
5.2.1.2).
For the unplanned eccentricity einit,mid at the mid-height of the wall applies according to DIN
EN 1996-1-1, section 5.5.1.1:
einit, mid = hef / 450 = 2.06 / 450 = 0.0046 m
The verification and the capacity reduction factor at the centre of the wall refers to the real
cross-section with the wall thickness t. Since the load eccentricities are calculated with the
ideational cross-section with the wall thickness a (see chapter 5.2.1.2), the eccentricity at the
wall centre increases about (t – a) / 2.
M md t − a
em = + + ehe + einit
N md 2
emk = em + ek 0.05 t
emk = 0.0734 + 0.0 0.05 0.365 = 0.0183 m
emk = 0.0734 m
H3,Ed = 4.39 kN
H2,Ed = 3.26 kN
H1,Ed = 3.25 kN
H0,Ed = 1.77 kN
∑HEd = 12.67 kN
Figure 5.11 Offset of the wall EW-02.1 from the second to the first floor
The concrete beam CB-03 is considered as a simple beam and therefore half of its load is
transferred to the wall EW-02.1. The length of the line-load of EW-02 in the second storey, that
is transferred to EW-02.1 is ltotal = 2.68 m + 4.00 m / 2 = 4.68 m. The partial load Ncent. goes
centrically into EW-02.1 and the partial load Neccent. is transferred into EW-02.1 at its edge. The
eccentricity eo,offset of the total load Ntotal due to the offset is calculated as follows:
For the calculation of the eccentricity due to horizontal loads the combination factors ψ0 of
simultaneous acting live loads are neglected as a conservative approach. Therefore, only two
load combinations need to be observed. The horizontal loads and the corresponding lever are
taken from chapter 5.2.4.2.
LC 1 Minimal normal force and maximum bending moment from horizontal loads
Verification: min NEd = 1.0 NGk ≤ NRd = Φmin · A · fd
Top: MEd,o = H3,Ed · 6.40 m + H2,Ed · 3.2 m = 38.53 kNm
NEd,min,o = 1.0 NGk = 261.07 kN
ew,LC1,o = eo,offset + MEd,o / NEd,min,o = 0.573 m + 38.53 kNm / 261.07 kN
ew,LC1,o = 0.72 m
Mid-height: MEd,m = H3,Ed · 8.00 m + H2,Ed · 4.8 m + H1,Ed · 1.60 m = 55.97 kNm
NEd,min,m = 1.0 NGk = 272.36 kN/m
ew,LC1,m = eo,offset + MEd,o / NEd,min,o = 0.573 m + 55.97 kN / 272.36 kNm
ew,LC1,m = 0.78 m
Bottom: MEd,u = H3,Ed · 9.60 m + H2,Ed · 6.40 m + H1,Ed · 3.20 m = 73.41 kNm
NEd,min,u = 1.0 NGk = 283.66 kN
ew,LC1,u = eo,offset + MEd,o / NEd,min,o = 0.573 m + 73.41 kNm / 283.66 kN
ew,LC1,u = 0.83 m
Cantilever model
according to DIN EN
1996-1-1/NA
Consideration of
positive effects from
restraint as well as
restoring forces
according to DIN EN
1996-1-1/NA Annex
NA. K
Figure 5.12 Comparison of the internal force lines according to the cantilever model
and the method according to Annex NA.K from DIN EN 1996-1-1/NA
When determining the load-bearing capacity of a masonry slab according to DIN EN 1996-1-
1, NCL Annex NA.K.2 (1), the favourably acting restraint of the wall plates in the adjacent slabs
can be considered for the determination of the acting internal forces. The resulting back-
rotating moments at the slab edge may be applied and the wall may be considered storey by
storey.
The spring stiffness of the restraint of the wall plates in the adjacent slabs must be determined
for each stiffening wall in each storey separately. For the calculation of each spring stiffness
the engineer needs to consider a complex static system. Therefore, the internal forces for the
verification with Annex NA.K are regularly determined with FEM-Software.
Since the method according to Annex NA.K is hardly used in practice, the following exercise
focuses on the widespread cantilever method and omits the method according to Annex NA.K.
ew
y ,i = 1 − 2
l
with
ew eccentricity of the vertical load in the longitudinal direction of the wall: ew = MEwd / NEd
MEwd design value of the moment acting in the longitudinal direction of the wall, taking into
account the partial safety factor γQ, sup = 1.5, MEwwd = VEd · h
NEd design value of the decisive vertical load (min NEd or max NEd)
l length of the stiffening wall
with
VEd design value of the acting shear force in the respective combinations of action
NEd design value of the acting vertical load in the respective combinations of action
v = · h / l shear slenderness of the wall according to Annex K of DIN EN 1996-1-1/NA
factor to describe the distribution of moments over the height of the shear wall
Since the method according to Annex NA.K is hardly used in practice, the following exercise
focuses on the widespread cantilever method and omits the method according to Annex NA.K.
Verification for vertical load and combined bending (out-of-plane and in-plane)
In the case of a combined load from bending about the strong axis y and bending about the
weak axis z, the verification of combined bending must be carried out at the relevant point.
According to DIN EN 1996-1-1/NA chap. 6.1.2.2 for the sake of simplification, the reduction
factors Φ may be combined by multiplying one by the other. Thus, the design value of the
normal force that can be absorbed is given by:
N Rd = y z A f d (5.2)
with
Φz capacity reduction factor for bending around the weak axis. Differentiation has to be
made according to the relevant points of verification.
Φy capacity reduction factor for bending around the strong axis
A total area of the cross-section
fd design value of the masonry compressive strength
with
tc,cal calculated value of the compressed wall thickness; the calculated wall thickness tcal
increases in the case of short-term effects due to wind tcal = 1.25 · tc,lin; in all other cases
tcal = tc,lin
l wall length, in case of simultaneous shear loading in both directions (out-of-plane and
in-plane), the compressed wall length l = lc,lin should be considered
fvd design value of shear strength with fvd = fvk / M according to chapter 3.1.6 and M = 1,5
c factor for the shear stress distribution; c = 1.5 for shear perpendicular to the wall plane
h2
− wd − M Ed ,o − M Ed ,u
M o : VEd ,u = 2
h
2
3.0
−1.17 − 2.00 − 1.95
M o : VEd ,u = 2 = −3.072 kN / m
h
h2
wd − M Ed ,o − M Ed ,u
M u : VEd ,o = 2
h
2
3.0
1.17 − 2.00 − 1.95
M u : VEd ,o = 2 = 0.438 kN / m
h
Right next to the exterior wall EW-02.1 there is a big window opening with a width of 4.00 m
(see Figure 5.14). As a conservative approach for the verification of lateral shear loads it is
assumed that the window transfers all the wind loads horizontally to the walls EW-02.1 and
EW-02.2.
The resulting maximum out-of-plane shear force acting on EW-02.1 is:
➔ VEd,o · lload = = 3.072 kN/m · (2.68 m + 4.00 m / 2) = 14.38 kN
3 e
tc ,lin = 1 − 2 t t
2 t
with
tc,lin compressed wall thickness based on linear-elastic material behaviour
e eccentricity of the weak axis of the acting vertical load
Shear forces can only be absorbed by the compressed part of the cross-section. Therefore, a
high vertical load acts favourable for the shear resistance. The decisive verification point with
the lowest vertical load and the highest eccentricity is at the top of the wall.
𝑀𝐸𝑑,𝑜 2.00
𝑒𝑡𝑜𝑝 = = = 0.01224 𝑚
𝑁𝐸𝑑,𝑜 437.70/2,68
The eccentricity of the weak axis at the top of the wall etop is referred to the ideational cross-
section with the wall-thickness a. Therefore, the wall thickness t is replaced by the support
depth a in the following equation.
3 e
lc,lin = 1 − 2 w,max l l
2 l
with
lc,lin compressed wall length based on linear-elastic material behaviour
ew,max maximum eccentricity of the strong axis, see chapter 5.2.4.3
3 0.83
lc ,lin = 1 − 2 2.68 2.68
2 2.68
lc ,lin = 1.53 m
2
fvlt1 = fvk 0 + 0.6 Dd
3
with
fvk0 initial shear strength according to Table 5.6
σDd design value of the associated compressive stress at the location of the maximum
shear stress. For rectangular cross-sections, σDd = NEd / (tc,lin · lc,lin); the minimum action
NEd = 1.0 · NGk generally applies.
Table 5.6 Initial shear strength values fvk0 for masonry under zero compressive
stress according to [8].
fvk0 [N/mm²]
VRdlt VEd
5.2.9.2 Failure due to friction in bed joints and tensile failure of the bricks
Figure 5.15 Left (a): failure due to friction of the bed joints; right (b): tensile failure of
the bricks
The shear resistance of the two failure modes due to friction in the bed joints and tensile failure
of the bricks is calculated according to DIN EN 1996-1-1, section 6.2 as follows:
1
VRdlt = lcal t f vd
c
with
lcal calculated value of the compressed length
t wall thickness, in case of simultaneous shear loading in both directions (out-of-plane
and in-plane), compressed wall thickness tc,lin should be considered
fvd design value of shear strength
c factor for the shear stress distribution: c = 1.0 for h / l 1.0 and c = 1.5 for h / l ≥ 2.0,
intermediate values may be linearly interpolated in both cases.
h/l ratio of the clear height of the wall to the wall length, if the internal forces are determined
according to the cantilever model
Characteristic value of the shear strength according to DIN EN 1996-1-1, section 3.6.2:
fvk = min fvlt1; fvlt 2
with
fvlt1 characteristic shear strength in case of failure due to friction of the bed joints
fvlt2 characteristic shear strength in case of tensile failure of the bricks
f vk
fvd = with M = 1.5
M
Characteristic value of the shear strength for failure due to friction in bed joints fvlt1
According to DIN EN 1996-1-1, section 3.6.2 the stone tilting reduces the friction coefficient for
shear loads in-plane. Therefore, it is assumed with μ = 0.4 for shear loads in-plane. The shear
strength is calculated with the conservative assumption of non-mortared bed joints as follows:
with
fvk0 initial shear strength according to Table 5.6
σDd design value of the associated compressive stress at the point of the maximum shear
stress. For rectangular cross-sections σDd = NEd / A, with A = lc,lin · t; the minimum action
NEd = 1.0 · NGk generally applies.
lc,lin compressed wall length with linear-elastic material behaviour approach
t wall thickness, in case of simultaneous shear loading in both directions (out-of-plane
and in-plane), compressed wall thickness tc,lin should be considered
Compressed wall length under consideration of the maximum in-plane eccentricity at the
bottom of the wall, linear-elastic material behaviour may be assumed:
3 e
lc,lin = 1 − 2 w,max l l
2 l
with
lc,lin compressed wall length based on linear-elastic material behaviour
ew,max maximum eccentricity of the strong axis, see chapter 5.2.4.3
3 0.83
lc ,lin = 1 − 2 2.68 2.68
2 2.68
lc ,lin = 1.53 m
The compressed wall thickness tc,lin (see chapter 5.2.8.1): tc,lin = 0.24 m
N Ed ,min 283.66
Dd = = = 0.772 N / mm²
lc ,lin tc ,lin 1.53 0.24
Characteristic value of the shear strength for tensile failure of the bricks fvlt2
Dd
f vlt 2 = 0.45 fbt ,cal 1 +
fbt ,cal
with
fvk0 initial shear strength according to Table 5.6
fbt,cal characteristic tensile strength of the units with
fbt,cal= 0.020 ∙ fst for hollow masonry blocks (Hohlblocksteine)
fbt,cal= 0.026 ∙ fst for vertically perforated clay masonry units (Hochlochsteine) or
units with grip holes (Grifflöcher) or handling recesses
(Grifftaschen)
fbt,cal= 0.032 ∙ fst for solid units of height ≥ 248mm without grip holes
handling recesses
fst converted mean compressive strength of the unit according to Table 5.7
σDd design value of the associated compressive stress at the point of the maximum shear
stress. For rectangular cross-sections σDd = NEd / A, with A = lc,lin · tc,lin; the minimum
action NEd = 1.0 · NGk generally applies.
Table 5.7 Values of fst as a function of the compressive strength class according to
[8]
Compressive
strength
class of the
masonry
units and
2 4 6 8 10 12 16 20 28 36 48 60
high-
precision
elements
Converted
mean
compressive 2.5 5.0 7.5 10.0 12.5 15.0 20.0 25.0 35.0 45.0 60.0 75.0
strength fst
[N/mm²]
Bricks: vertically perforated clay masonry units with compressive strength class 10
➔ fst = 12.5 N/mm²
➔ fbt,cal = 0.026 · fst = 0.325 N/mm²
0.772
f vlt 2 = 0.45 0.325 1 +
0.325
f vlt 2 = 0.269 N / mm²
Design value of the shear strength for failure due to friction of the bed joints and tensile
failure of the bricks
Design value of the decisive shear strength:
f vk
fvd = = 0.179 N / mm² with M = 1,5
M
Figure 5.16 Shear stress distribution for left: short walls (parabolic distribution) and
right: long walls (constant distribution)
Verification for failure due to friction of the bed joints and tensile failure of the bricks
1
VRdlt = 2.04 0.243 0.179
1.06
VRdlt = 83.71 kN
Verification fulfilled! ✓
This verification only needs to be checked in special cases with special design variants of high-
precision masonry elements with lol / hu < 0.40. For the exterior wall EW-01.2 with
lol = 0.5 · (20.00 – 1.00) = 9.50 cm and therefore lol / hu = 9.50 cm / 24.90 cm = 0.381 < 0.40
this verification can not be omitted.
The corresponding shear bearing capacity is given by DIN EN 1996-1-1, section 6.2 NA.13 as
follows:
1 f l
VRdlt = lc t k − max N Ed ol
c M hu
with
c factor for the shear stress distribution: c = 1.0 for h / l 1.0 and c = 1.5 for h / l 2
Intermediate values may be linearly interpolated in both cases.
lc compressed wall length with rigid-plastic stress distribution
t wall thickness, in case of simultaneous shear loading in both directions (out-of-plane
and in-plane), compressed wall thickness tc,lin should be considered
fk characteristic value of the masonry compressive strength
γM partial safety factor for masonry, γM = 1.5
NEd design value of the acting vertical load
lol overlap
hu height of the stone
Compressed wall length lc under the consideration of the maximum in-plane eccentricity at the
bottom of the wall. Since the maximum vertical load (load combination 2, LC2) is decisive for
this verification, rigid-plastic material behaviour may be assumed:
ew, LC 2
lc = 1 − 2 l l
l
with
lc compressed wall length based on rigid-plastic material behaviour
ew,LC2 maximum eccentricity of the strong axis for the load case 2, see chapter 5.2.4.3
0.73
lc = 1 − 2 2.68 2.68
2.68
lc = 1.22 m
Verification fulfilled! ✓
Figure 5.18 Joint failure due to tilting of the individual bricks under shear load
This verification only needs to be checked in special cases with high precision masonry
elements with height-to-length ratio of the elements lu < hu and non-mortared perpend joints.
For the exterior wall EW-01.2 with lu = 20.00 cm and hu = 24.90 cm the verification for this
failure mode can not be omitted.
Failure of the joints shall be verified at the mid-height of the wall. The corresponding shear
bearing capacity is given by DIN EN 1996-1-1, section 6.2 NA.14 as follows:
2 1 l l
VRdlt = u + u min N Ed
3 M hu h
with
γM partial safety factor for masonry, γM = 1.5
lu length of the stone
hu height of the stone
h clear height of the stiffening wall (for one storey)
min NEd design value of the minimum acting vertical load
Design value of the minimum acting vertical load in the mid-height of the wall NEd,m:
NEd,m = 272.36 kN/m
Verification fulfilled! ✓
D
R 10−4
D
D =
E
a lc,lin
l
D l
R = − 1 10 −4
1000 f k l
c ,lin
D
D =
1000 f k
with
εR calculated edge strain
εD calculated edge compressive strain
σD compressive stress based on a linear-elastic constitutive relation
l wall length
lc,lin compressed wall length with linear-elastic stress distribution
fk characteristic value of the masonry compressive strength
2 N Ed
D =
lc ,lin t
with
NEd design value of the acting vertical load in the characteristic design situation
lc,lin compressed wall length with linear-elastic stress distribution
t wall thickness, in case of simultaneous shear loading in both directions (out-of-plane
and in-plane), compressed wall thickness tc,lin should be considered
Design value of the internal forces for the characteristic design situation
Vertical load NEd = 1.0 · NGk + 1.0 · NQk = 283.66 kN + 56.84 kN = 340.50 kN
The design value of the bending moment at the bottom of the wall for the characteristic design
situation MEd is calculated approximativly by dividing the design bending moment of chapter
5.2.4.3 (ultimate limit state) with a mean partial safety factor γQ = 1.4:
Bending moment: MEd = 108.94 kNm / 1.4 = 77.81 kNm
Compressed wall length lc,lin under consideration of the in-plane eccentricity ew,SLS at the bottom
of the wall, linear-elastic material behaviour may be assumed:
3 𝑒𝑤,𝑆𝐿𝑆
𝑙𝑐,𝑙𝑖𝑛 = 2 ⋅ (1 − 2 ⋅ 𝑙
)⋅𝑙 ≤𝑙
3 0.80
𝑙𝑐,𝑙𝑖𝑛 = ⋅ (1 − 2 ⋅ ) ⋅ 2.68 ≤ 2.68
2 2.68
𝑙𝑐,𝑙𝑖𝑛 = 1.62 𝑚
2 N Ed 2 340.50
D = =
lc ,lin t 1.32 0.243
D = 2.12 N / mm²
2.12 2.68
R = − 1 = 4.85 10−4 10−4
1000 4.5 1.32
6. Basement walls
For the dimensioning of basement walls, one of the verifications shown in the following can be
used:
rigid diaphragm
t ≥ 240 mm
Figure 6.2 Conditions of a basement wall for using the verification according to DIN
EN 1996-3/NA ([26])
For the verification of the load-bearing capacity under lateral earth pressure, the arch action
approach is assumed:
➢ A minimum value for the acting axial force at the mid height of the fill 𝒏𝑬𝒅,𝒎𝒊𝒏 should
be verified.
𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2
𝑛𝐸𝑑,𝑚𝑖𝑛 ≥ [𝑘𝑁/𝑚]
𝛽∙𝑡
with
𝜌𝑒 Self−weight of the backfill
ℎ Clear height of the basement wall
➢ A maximum design value of the axial force (dead weight and live loads) at the mid
height of the fill 𝒏𝑬𝒅,𝒎𝒂𝒙 also should be verified.
𝑡 ∙ 𝑓𝑑
𝑛𝐸𝑑,𝑚𝑎𝑥 ≤ [𝑘𝑁/𝑚]
3
with
𝑡 Wall thickness
➢ The verification of the shear force capacity (out-of-plane) is also included and
considered as fulfilled.
➢ The simplified calculation method is based on an earth pressure coefficient of ≤ 1/3.
Otherwise, use of the general method according to DIN EN 1996-1-1/NA!
t = 36.5 cm
h = 2.8 – 0.2 = 2.6 m (clear height of the basement wall)
bc = 6.0m for BW-01.2 (located at axis 1/B-C)
bc = 4.0 m for BW-01.3 (located at axis 1/C-D, direct above the basement wall there is
a great opening at the first floor)
a = 2/3 ∙ 0.365 m = 24.3 m
perforated clay masonry wall γ = 6.88 kN/m³
compressive strength class 10 and general purpose masonry mortar M5
Fill material: 𝜌𝑒 = 20 kN/m³, flat ground level (𝛿 = 0) and frictional angle of soil 𝜑 = 35𝑜
𝜑
𝑘𝑎 = 𝑘𝑎𝑔ℎ = 𝑡𝑎𝑛2 (45𝑜 − ) = 0.27
𝛼 = 𝛽 = 𝛿 = 0: { 2 → 𝑘𝑖 = 0.35
𝑘0 = 𝑘𝑜𝑔ℎ = 1 − 𝑠𝑖𝑛𝜑 = 0.43
BW-01.02
BW-01.03
(71.18 + 63.87)
𝑛𝐺𝑘,𝑚𝑖𝑑 = = 67.53 𝑘𝑁/𝑚
2
𝑘𝑁
𝑛𝑄𝑘 = 2.94 + (2.30 𝑘𝑁/𝑚² ∙ 6.60𝑚2 ) ∙ 4 / 6.0𝑚 = 13.06𝑘𝑁/𝑚
𝑚
Design values of the internal axial forces:
𝑛𝐸𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 = 1.35 ∙ 71.18 + 1.50 ∙ 13.06 = 115.68𝑘𝑁/𝑚
(115.68 + 105.81)
𝑛𝐸𝑑,𝑚𝑖𝑑 = = 110.75 𝑘𝑁/𝑚
2
For BW-01.03:
Direct above the basement wall BW-01.03, there is a great opening as door at the first floor.
The floors slab (or stair landing 4.0m x 1.2m) above the basement is located not only on the
interior walls IW-02 and IW-04, but also on the basement wall. Thus, the axial forces can be
determined by:
𝑘𝑁 1.2𝑚 𝑘𝑁
𝑛𝐺𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 5.0 2
∙( ) + 7.31 = 10.31 𝑘𝑁/𝑚
𝑚 2 𝑚
𝑛𝐺𝑘,𝑡𝑜𝑝 = 10.31 − 7.31 = 3.00 𝑘𝑁/𝑚
(10.31 + 3.00)
𝑛𝐺𝑘,𝑚𝑖𝑑 = = 6.66 𝑘𝑁/𝑚
2
𝑘𝑁 1.2𝑚
𝑛𝑄𝑘 = 3.0 ∙( ) = 1.8 𝑘𝑁/𝑚
𝑚2 2
(16.62 + 6.75)
𝑛𝐸𝑑,𝑚𝑖𝑑 = = 11.69 𝑘𝑁/𝑚
2
6.1.1.3 Check the conditions for using the simplified method according to DIN EN 1996-
3/NA
For designing basement walls subject to lateral earth pressure providing the following
conditions are fulfilled:
6.1.1.4 Determination of the minimum value for the acting axial force at the mid height
of the fill
The minimum value for the acting axial force at the mid height of the fill can be determinated
using the equation:
𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2
𝑛𝐸𝑑,𝑚𝑖𝑛 ≥ [𝑘𝑁 / 𝑚]
𝛽∙𝑡
For BW-01.2:
bc = 6.0 m
𝑏𝑐 6.0
→ = = 2.31 → 𝛽 = 20
ℎ 2.6
𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2 20 𝑘𝑁/𝑚³ ∙ 2.6𝑚 ∙ (2.6𝑚)2
𝑛𝐸𝑑,𝑚𝑖𝑛 ≥ = = 48.15𝑘𝑁/𝑚
𝛽∙𝑡 20 ∙ 0.365𝑚
𝑛𝐺𝑘,𝑚𝑖𝑑 = 64.17 𝑘𝑁/𝑚
For BW-01.3:
bc = 4.0 m
𝑏𝑐 4.0
→ = = 1.54 → 𝛽 = 60 − 20 ∙ 1.54 = 29.2
ℎ 2.6
𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2 20 𝑘𝑁/𝑚³ ∙ 2.6𝑚 ∙ (2.6𝑚)2
𝑛𝐸𝑑,𝑚𝑖𝑛 ≥ = = 32.98 𝑘𝑁/𝑚
𝛽∙𝑡 29.2 ∙ 0.365𝑚
𝑛𝐺𝑘,𝑚𝑖𝑑 = 6.66 𝑘𝑁/𝑚
➔ Not fulfilled
Using a cross wall having a length greater than 0.2h to reduce bc, so that bc / h ≤ 1
→ 𝛽 = 40
𝑘𝑁 2
𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2 20 𝑚3 ∙ 2.6𝑚 ∙ (2.6𝑚)
𝑛𝐸𝑑,𝑚𝑖𝑛 = 6.66 𝑘𝑁/𝑚 ≥ = = 24.08 𝑘𝑁/𝑚
𝛽∙𝑡 40 ∙ 0.365𝑚
➔ Still not fulfilled
➔ Use a reinforced concrete wall for this section BW-01.03
Note: In some cases, the verification will be fulfilled, by using the general method according to
DIN EN 1996-1-1/NA and using additional cross wall to reduce the distance bc to a value bc ≤ h
for a two-way load transfer. The minimum required value for the acting axial force can be
1
determined by using: 𝑏 ≤ ℎ: 𝑛1,𝐸𝑑,𝑖𝑛𝑓 ≥ ∙ 𝑛1,𝑙𝑖𝑚,𝑑 (see section NA.5 in DIN EN 1996-1-1/NA).
2
6.1.1.5 Determination of the maximum design value of the axial force at the mid height
of the fill
𝑡 ∙ 𝑓𝑑
𝑛𝐸𝑑,𝑚𝑎𝑥 ≤ [𝑘𝑁 / 𝑚]
3
For BW-01.2:
𝑡 ∙ 𝑓𝑑 0.365𝑚 ∙ 2.83𝑀𝑁/𝑚²
𝑛𝐸𝑑,𝑚𝑎𝑥 ≤ = = 344 𝑘𝑁/𝑚
3 3
𝑛𝐸𝑑,𝑚𝑖𝑑 = 110.75 𝑘𝑁/𝑚
For BW-01.3:
𝑛𝐸𝑑,𝑚𝑖𝑑 = 11.69 𝑘𝑁/𝑚
Note:
If the verification for the minimum design value is fulfilled, but the maximum not, it means, the
basement wall is overcompressed highly. In this case, a joint analysis should be taken into
account and the verification should be considered using approach according to DIN EN 1996-
1-1, section 6.1.2.1. The equations to determine the moment in appendix NA.C can not be
used for this case with earth pressure (column 1b in Figure 6.6 is not applied with lateral loads).
Thus, a static program should be used to calculate the internal forces.
with:
ki Relevant earth pressure coefficient
• k0 in case of at-rest earth pressure component
• ka for the horizontal active earth pressure component
• kp in case of passive earth pressure.
If the basement wall is stiffened by cross walls or or other structural elements at a distance b
so that a two-way load transfer is possible, the lower value n1,lim d may be reduced as follows
(intermediate values may be interpolated):
1
𝑛1,𝐸𝑑,𝑖𝑛𝑓 ≥ 𝑛 [𝑘𝑁/𝑚] 𝑓𝑜𝑟 𝑏 ≤ ℎ
2 1,𝑙𝑖𝑚,𝑑
𝑛1,𝐸𝑑,𝑖𝑛𝑓 ≥ 𝑛1,𝑙𝑖𝑚,𝑑 [𝑘𝑁/𝑚] 𝑓𝑜𝑟 𝑏 ≥ 2ℎ
𝑛𝑄𝑘 = 13.06𝑘𝑁/𝑚
vEd,top
he
vEd,bottom
6.2.1.3 Check the conditions for using the general method according to DIN EN 1996-
1-1/NA
For the basement wall BW-01.02, which is subjected to lateral earth pressure, the given
conditions to use the general method according to DIN EN 1996-1-1/NA are fulfilled, see also
section 6.1.1.3.
6.2.1.4 Determination of the lower value for the acting axial force at the mid height of
the fill
Lower design values of the axial load acting on the wall at the mid height of the fill can be
calculated using the equation:
𝑘𝑖 ∙ 𝜌𝑒 ∙ ℎ ∙ ℎ𝑒2
𝑛1,𝑑,𝑖𝑛𝑓 ≥ 𝑛1,𝑙𝑖𝑚,𝑑 = [𝑘𝑁 / 𝑚]
7.8 ∙ 𝑡
6.2.1.5 Determination of the upper value for the acting axial force at the mid height of
the fill
Upper design value of the wall axial load acting on the wall at the mid height of the fill can
be calculated using the equation:
𝑛1,𝐸𝑑,𝑠𝑢𝑝 ≤ 𝑛1,𝑅𝑑 = 0.33 ∙ 𝑓𝑑 ∙ 𝑡 [𝑘𝑁/𝑚]
6.3 Verification of basement walls using the approach of the arching action
According to [25], an approach of the arch action can be described as follows:
𝑀𝐸𝑑
min 𝑁𝐸𝑑,𝑏𝑒𝑛𝑑𝑖𝑛𝑔 =
𝑓
whereby, f is rise of an arch due to the arching action, see also Figure 6.9.
The verification can be determined using the equation:
1 1 ℎ 𝑁𝐸𝑑
𝑀𝐸𝑑 ≤ 𝑀𝑅𝑑 = ∙ 𝑁𝐸𝑑 ∙ 𝑓 = ∙ 𝑁𝐸𝑑 ∙ (𝑡 − − )
𝛾𝑀𝑜𝑑 𝛾𝑀𝑜𝑑 450 𝑙 ∙ 𝑓𝑑
The solution of the equation above for 𝑁𝐸𝑑 can be rewrited as:
2
1 𝜆 1 𝜆 𝛾𝑀𝑜𝑑 ∙ 𝑀𝐸𝑑
min 𝑁𝐺𝑘,𝑏𝑒𝑛𝑑𝑖𝑛𝑔 = 𝑡 ∙ 𝑙 ∙ 𝑓𝑑 ∙ [ ∙ (1 − )− √ ∙( − 1) − 2 ]
2 450 4 450 𝑡 ∙ 𝑙 ∙ 𝑓𝑑
or
2
1 𝜆 1 𝜆 𝛾𝑀𝑜𝑑 ∙ 𝑚𝐸𝑑
min 𝑛𝐺𝑘,𝑏𝑒𝑛𝑑𝑖𝑛𝑔 = 𝑡 ∙ 𝑓𝑑 ∙ [ ∙ (1 − )−√ ∙( − 1) − ]
2 450 4 450 𝑡 2 ∙ 𝑓𝑑
whereas,
ℎ
𝜆= 𝑎𝑠 𝑠𝑙𝑒𝑛𝑑𝑒𝑟𝑛𝑒𝑠𝑠
𝑡
𝛾𝑀𝑜𝑑 = 1.1
Here, also the lateral shear loading needs to check, using the equation:
𝛾𝑀 ∙ 𝑐 ∙ 𝑣𝐸𝑑 𝛾𝑀 . 𝑣𝐸𝑑
min 𝑁𝐺𝑘,𝑠ℎ𝑒𝑎𝑟 = ≤
𝑓 𝜇
𝜇 + 1.5 ∙ 1.25 ∙ 𝑣𝑘0
𝑓𝑘
where:
𝑐 factor for the shear stress distribution; c = 1.5 for shear perpendicular to the wall plane
𝜇=0.6 friction coefficient for lateral shear loads, because a rotating of the masonry units (in
comparison to shear load (in-plane)) does not occur here
The verification is fulfilled, if the minimum axial loading is greater than both axial forces due to
bending and shear:
min 𝑛𝐺𝑘,𝑏𝑒𝑛𝑑𝑖𝑛𝑔
𝑚𝑖𝑛 𝑛𝐸𝑑 = 𝑛𝐺𝑘 ≥ {
min 𝑛𝐺𝑘,𝑠ℎ𝑒𝑎𝑟
thrust linie
water
level
hydrostatic earth
pressure pressure
𝑛𝑄𝑘 = 13.06𝑘𝑁/𝑚
2
1 7.12 1 7.12 1.1 ∙ 13.14
= 0.365 ∙ 2.83 ∙ 103 [ ∙ (1 − )−√ ∙( − 1) − ]
2 450 4 450 0.3652 ∙ 2.83 ∙ 103
= 41.97 𝑘𝑁/𝑚
𝑛𝐺𝑘,𝑚𝑖𝑑 = 67.53 𝑘𝑁/𝑚
Table 7.1 Maximum permissible values of the infill area of non-loadbearing exterior
walls according to DIN EN 1996-3/NA without calculation
1 2 3 4 5
1), 2)
Maximum permissible values of the infill area in m² for
a height above ground level of
Wall
thickness 0 m to 8 m 8 m to 20 m3)
t h/l ≥ 2.0
h/l ≥ 2.0
[mm] h/l = 1.0 or h/l = 1.0 or
h/l ≤ 0.5
h/l ≤ 0.5
1153), 4) 12 8 - -
1504) 12 8 8 5
175 20 14 13 9
240 36 25 23 16
≥ 300 50 33 35 23
1)
For aspect ratios 0.5 < h/l <1.0 and 1.0 < h/l < 2.0,
Intermediate values of the infill areas can be interpolated linearly.
2)
The values given above is applied to general purpose masonry mortar of at least
group M5 and thin-layer masonry mortar
3)
In WLZ 4 only permitted inland.
4)
When using masonry units of strength classes ≥ 12, the values of the infill areas
can be enlarged by about 33% (it means increasing by 1/3 more).
7.1.1.1 Check the conditions for using the simplified method according to DIN EN 1996-
3/NA – Annex C
For designing non-loadbearing exterior walls the following conditions must be fulfilled:
➢ Masonry units: at least the compression strength class 4 of the masonry unit ✓
➢ Overlap of masonry units lol ≥ 0.4 ∙ hu is required for masonry of high precision ✓
masonry elements
7.1.1.2 Verification
𝑡 = 0.365𝑚
ℎ = 3.50𝑚
Exterior walls: compressive strength class 10
General-purpose mortar: compressive strength class M5
Infill area of a trapezoidal shape is given by:
(10.67 − 9.80) + (13.20 − 9.8)
𝐴1 = 𝐴2 = ∙ 4.50 = 9.6𝑚²
2
Height above ground level
𝐻𝑡𝑜𝑝 + 𝐻𝑏𝑜𝑡𝑡𝑜𝑚 13.20 + 9.80
𝐻= = = 11.5𝑚
2 2
Ratio
ℎ 3.50
= = 0.78
𝑙 4.50
➔ Maximum permissible value of the infill area = 29.72 m² (interpolated) > 9.6m² ✓
Note: When using masonry units of strength classes ≥ 12, the values of the infill areas can be
enlarged by about 33% (it means increasing by 1/3 more).
Table 7.2 Maximum permissible values of the infill area of non-loadbearing exterior
walls according to DIN EN 1996-3/NA without calculation
1 2 3 4 5
1), 2)
Maximum permissible values of the infill area in m² for
a height above ground level of
Wall
thickness 0 m to 8 m 8 m to 20 m3)
t h/l ≥ 2.0
h/l ≥ 2.0
[mm] h/l = 1.0 or h/l = 1.0 or
h/l ≤ 0.5
h/l ≤ 0.5
1153), 4) 12 8 - -
1504) 12 8 8 5
175 20 14 13 9
240 36 25 23 16
≥ 300 50 33 35 23
Limiting height and length to thickness ratios of non-loadbearing internal walls under limited
horizontal loading
• Type (b): Wall restrained at the bottom, the top and one vertical edge
• Type (c): Wall restrained at the edges, the bottom, but not the top
• Type (d): Wall restrained only at the top and bottom edge
Figure 7.4 Limitation of wall dimensions of non-loadbearing interior walls [26]
Figure 7.5 Wall with one opening: left: type (a); right: type (d)
Table 7.4 Limiting dimensions for walls supported on four edges with
superimposed vertical load2),3) and walls supported on three edges with a
free vertical edge*) according to [12]
Max. Wall length in m in installation area I (upper value)/ installation area II (lower value)
Wall Wall height in m
thickness cm
2.5 3.0 3.5 4.0 4.5 6.0
5.5 6.0 6.5 - - -
5.01)
2.5 3.0 3.5 - - -
6.0 6.5 7.0 - - -
6.01)
4.0 4.5 5.0 - - -
1) 8.0 8.5 9.0 9.5 - -
7.0
5.5 6.0 6.5 7.0 7.5 -
1) 12.0 12.0 12.0 12.0 12.0 -
9.0
7.0 7.5 8.0 8.5 9.0 -
12.0 12.0 12.0 12.0 12.0 -
10.01)
8.0 8.5 9.0 9.5 10.0 -
12.0 12.0 12.0 12.0 12.0 -
11.5/15.0
12.0 12.0 12.0 12.0 12.0 -
12.0 12.0 12.0 12.0 12.0 12.0
≥ 17.5
12.0 12.0 12.0 12.0 12.0 12.0
1) For calcium silicate units (dry units must be pre-moistened), the specified values apply when using
general purpose masonry mortar M 10 or thin-layer masonry mortar for wall thicknesses < 11.5 cm. For
wall thicknesses ≥ 11.5 cm, use at least general-purpose masonry mortar M 5 or thin-layer masonry
mortar.
2) For autoclaved aerated concrete blocks, the specified values apply when using general purpose mortar
M 10 or thin-layer mortar. For wall thicknesses < 17.5 cm and use of M 2.5 or M 5, the values for the
permissible wall lengths must be halved.
3) The mortaring of perpend joints can be dispensed with under certain conditions. For walls without
perpend joint mortaring with l/h < 2, only a half of the values from this table is used.
*) For walls restrained top and bottom and stiffened on one vertical edge with the other vertical edge
free, only a half of the values in table is applied
Table 7.5 Limiting dimensions for walls supported on three edges and a free upper
edge (top of the wall) without superimposed vertical load2),3) according to
[12]
Max. Wall length in m in installation area I (upper value)/ installation area II (lower value)
Wall
thickness Wall height in m
cm 2.00 2.25 2.50 3.00 3.50 4.00 4.50 ≤ 6.00
3.0 3.5 4.0 5.0 6.0 - - -
5.01)
1.5 2.0 2.5 - - - - -
5.0 5.5 6.0 7.0 8.0 9.0 - -
6.01) 2.5 2.5 3.0 3.5 4.0 - - -
7.0 7.5 8.0 9.0 10.0 10.0 10.0 -
7.01)
3.5 3.5 4.0 4.5 5.0 6.0 7.0 -
8.0 8.5 9.0 10.0 10.0 12.0 12.0 -
9.01) 4.0 4.0 5.0 6.0 7.0 8.0 9.0 -
8.0 9.0 10.0 12.0 12.0 12.0 12.0 -
10.01)
5.0 5.0 6.0 7.0 8.0 9.0 10.0 -
11.5 8.0 9.0 10.0 12.0 12.0 12.0 12.0 -
15.0 6.0 6.0 7.0 8.0 9.0 10.0 10.0 -
12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
≥ 17.5
8.0 9.0 10.0 12.0 12.0 12.0 12.0 12.0
1) For calcium silicate units (dry units must be pre-moistened), the specified values apply when using general
purpose masonry mortar M 10 or thin-layer masonry mortar for wall thicknesses < 11.5 cm. For wall
thicknesses ≥ 11.5 cm, use at least general-purpose masonry mortar M 5 or thin-layer masonry mortar.
2) For autoclaved aerated concrete blocks, the specified values apply when using general purpose mortar
M 10 or thin-layer mortar. For wall thicknesses < 17.5 cm and use of M 2.5 or M 5, the values for the
permissible wall lengths must be halved.
3) The mortaring of perpend joints can be dispensed with under certain conditions
Table 7.6 Limiting dimensions for walls supported on four edges without
superimposed vertical load2),3) and walls supported on three edges with a
free vertical edge*) according to [12]
Max. Wall length in m in installation area I (upper value) / installation area II (lower value)
Wall Wall height in m
thickness cm
2.5 3.0 3.5 4.0 4.5 6.0
3.0 3.5 4.0 - - -
5.01)
1.5 2.0 2.5 - - -
4.0 4.5 5.0 5.5 - -
6.01)
2.5 3.0 3.5 - - -
5.0 5.5 6.0 6.5 7.0 -
7.01)
3.0 3.5 4.0 4.5 5.0 -
6.0 6.5 7.0 7.5 8.0 -
9.01)
3.5 4.0 4.5 5.0 5.5 -
7.0 7.5 8.0 8.5 9.0 -
10.01)
5.0 5.5 6.0 6.5 7.0 -
10.0 10.0 10.0 10.0 10.0 -
11.5
6.0 6.5 7.0 7.5 8.0 -
12.0 12.0 12.0 12.0 12.0 12.0
17.5
12.0 12.0 12.0 12.0 12.0 12.0
12.0 12.0 12.0 12.0 12.0 12.0
24.0
12.0 12.0 12.0 12.0 12.0 12.0
Figure 7.7 Non-loadbearing masonry wall n-lb. mw-01 with openings (1.0m x 2.0m)
7.2.1.1 Check the conditions for using the simplified method according to DIN EN 1996-
3/NA – Annex B
For designing non-loadbearing interior walls the following conditions must be fulfilled:
➢ The wall should not have any vertical effects other than its own weight ✓
➢ The wall is not used as a support for heavy objects such as furniture, sanitary or ✓
heating equipment
➢ Effects of openings (Aopening > 0.025 ∙ Awall ) should be taken into account ✓
➢ The largest area of a single opening is not greater than 0.1 m² and the length or
width of a single opening is not greater than 0.5 m
➔ Wall type (a) with opening shall be considered as wall type (b), where l is the
greater of l1 and l2 see Figure 7.5.
7.2.1.2 Verification
𝑡 = 0.115𝑚
ℎ = 3.0𝑚
Interior walls: compressive strength class 12; perforated clay masonry units
General-purpose mortar: compressive strength class M5
Wall type (b): walls supported on three edges with a free vertical edge), where l is the greater
of l1 and l2 see Figure 7.5.:
𝑙1 = 2.10𝑚 + 0.50𝑚 = 2.60 𝑚
𝑙2 = 1.20𝑚 + 0.50𝑚 = 1.70 𝑚
𝑙 = max(2.60𝑚; 1.70𝑚) = 2.60𝑚
For the middle part of the wall if l3 ≥ 2/3 ∙ l and l3 ≥ 2/3 ∙ h, it needs to consider as wall type (d),
but in this case, no consideration is needed, since:
2 2 2
𝑙3 = 0.52𝑚 < ∙ 𝑙 = ∙ (0.52 + 0.5 + 0.5) = 1.0𝑚 𝑎𝑛𝑑 𝑙3 < ∙ 3.0𝑚 = 2.0𝑚
3 3 3
Ratio
𝑙 2.60
= = 22.6
𝑡 0.115
ℎ
𝑡
= 67 → ℎ𝑚𝑎𝑥 = 7.71𝑚 > ℎ = 3.0𝑚 ✓
Alternative:
Table 7.7 Limiting dimensions for walls supported on four edges without
superimposed vertical load2),3) and walls supported on three edges with a
free vertical edge*) according to [12]
Max. Wall length in m in installation area I (upper value) / installation area II (lower value)
Wall Wall height in m
thickness cm
2.5 3.0 3.5 4.0 4.5 6.0
3.0 3.5 4.0 - - -
5.01)
1.5 2.0 2.5 - - -
4.0 4.5 5.0 5.5 - -
6.01)
2.5 3.0 3.5 - - -
5.0 5.5 6.0 6.5 7.0 -
7.01)
3.0 3.5 4.0 4.5 5.0 -
6.0 6.5 7.0 7.5 8.0 -
9.01)
3.5 4.0 4.5 5.0 5.5 -
7.0 7.5 8.0 8.5 9.0 -
10.01)
5.0 5.5 6.0 6.5 7.0 -
10.0 10.0 10.0 10.0 10.0 -
11.5
6.0 6.5 7.0 7.5 8.0 -
12.0 12.0 12.0 12.0 12.0 12.0
17.5
12.0 12.0 12.0 12.0 12.0 12.0
12.0 12.0 12.0 12.0 12.0 12.0
24.0
12.0 12.0 12.0 12.0 12.0 12.0
For walls restrained top and bottom and stiffened on one vertical edge with the other vertical
edge free, only a half of the values in table is applied. Therefore,
10
➔ 𝑙𝑚𝑎𝑥. 𝑝𝑒𝑟𝑚𝑖𝑠𝑠𝑖𝑏𝑙𝑒 = 2
= 5.0𝑚 > 𝑙 = 2.60𝑚 ✓
1 2 3 4 5
detached detached not detached other building OKF ≤ 13m and 13m<OKF ≤ 22m
used for OKF ≤ OKF ≤ 7m and OKF ≤ 7m ≤ 400 m² each unit or
agriculture 7m and ≤ 2 units (NE) (Nutzungseinheit – > 400 m² each
or forestry ≤ 2 units and NE) unit
(NE) and ≤ 400 m² in total
≤ 400 m²
in total
Example: Calcium-silicate masonry with the REI-M requirement is listed in section NA.B.2 in
table NA.B.2.5. An interpolation of the minimum wallthicknesses between the different
utilisation factors is not permissible.
The design eccentricity in case of fire is always to be limited to 𝑒𝑚𝑘,𝑓𝑖 ≤ 𝑡𝑓 /6 since the tests
that the table values are based on always consider a fully compressed cross-section. For
eccentricities 𝑒𝑚𝑘,𝑓𝑖 > 𝑡𝑓 /6 (or equivalent to 𝑎/𝑡 > 2/3), the constructional detailing should be
such that there is central loading.
According to DIN EN 1996-1-2/NA, for all type of masonry, the loading level in fire can be
determined as follows.
ℎ𝑒𝑓
For 10 ≤ 𝑡
≤ 25:
15 𝑁𝐸𝑑,𝑓𝑖
𝛼6,𝑓𝑖 = 𝜔 ∙ ∙ 𝑒𝑚𝑘,𝑓𝑖
ℎ𝑒𝑓 𝑓𝑘
25 − 𝑡 𝑙 ∙ 𝑡 ∙ 𝑘 ∙ (1 − 2 ∙ 𝑡 )
0
ℎ𝑒𝑓
For 𝑡
< 10:
𝑁𝐸𝑑,𝑓𝑖
𝛼6,𝑓𝑖 = 𝜔 ∙ 𝑒𝑚𝑘,𝑓𝑖
𝑓𝑘
𝑙 ∙ 𝑡 ∙ ∙ (1 − 2 ∙ 𝑡 )
𝑘0
𝜔 factor to allow for different types of masonry unit in accordance with Table NA.1; it is
based on fire tests (see Table 8.2 below)
𝑙 the wall length
𝑡 the wall thickness
𝑁𝐸𝑑,𝑓𝑖 the design value of the acting vertical load in fire
ℎ𝑒𝑓 the buckling length of the wall, or also called the effective length of the wall
In case of calcium silicate masonry, an alternative to define the loading level in fire is given.
If lines 1.4 and 1.5 of Table NA.B.2.2, line 2.4 of Table NA.B.2.3 and lines 1.3.1 to 1.3.4 of
Table B.2.4 are used, the loading level 𝛼𝑓𝑖 is determined by:
𝑁𝐸𝑑,𝑓𝑖
𝛼𝑓𝑖 =
𝑁𝑅𝑑
where
𝑁𝐸𝑑,𝑓𝑖 the design value of the acting vertical load in fire
𝑁𝐸𝑑 the design value of the applied vertical load in accordance with DIN EN 1996-1-1 or
DIN EN 1996-3, for normal temperature design, or also called “in the cold case”
𝜂𝑓𝑖 the reduction factor for the design value of the actions in fire
with 𝜂𝑓𝑖 = 0.7 being valid as a simplification without more precise verification of the
reduction factor for the design value of the actions in fire
𝑁𝑅𝑑 the design value of the loadbearing capacity in the cold case. The loadbearing capacity
both according to DIN EN 1996-1-1/NA and also according to DIN EN 1996-3/NA may
be used.
Instead of the simplified assumption of a reduction factor 𝜂𝑓𝑖 = 0.7 for the design load in fire,
more precise determination is also permissible. For this purpose, DIN EN 1996-1-2 provides a
calculation equation that may be used for the reduction factor:
𝐺𝑘 + 𝜓𝑓𝑖 ∙ 𝑄𝑘,1
𝜂𝑓𝑖 =
𝛾𝐺 ∙ 𝐺𝑘 + 𝛾𝑄,1 ∙ 𝑄𝑘,1
with
𝐺𝑘 the characteristic value of a permanent action
𝑄𝑘,1 the principal variable load;
𝛾𝐺 , 𝛾𝑄,1 the partial factor for permanent actions & for variable action 1 respectively
𝜓𝑓𝑖 the combination factor for frequent values, given in function of either 𝜓1,1 or 𝜓2,1. For
the combination factor 𝜓𝑓𝑖 , the value for the frequent combination of actions 𝜓1 should
be used to be on the safe side. Accordingly, 𝜓𝑓𝑖 = 0.5 according to DIN EN 1990/NA,
Tab. NA.1.1 is to be used for live loads in residential and office buildings.
The equation above can also be used without concern if in the determination of the “cold”
effects of actions at the ultimate limit state, the acting vertical load has been determined
according to DIN EN 1996-1-1/NA, Abs. 2.4.2 (NA.2) without consideration of a combination
factor. In this way, depending on the ratio of live and permanent loads, a significant decrease
of the reduction factor for the design value of the actions in fire is possible, as shown in Figure
8.1 below.
Figure 8.1 Variation of the reduction factor 𝜼𝒇𝒊 with the load ration 𝑸𝒌,𝟏 /𝑮𝒌
Table 8.2 Factor ω to allow for different combinations of masonry units and mortar
(Table NA.1 in DIN EN 1996-1-2/NA)
Relevant table in
DIN EN 1996-1-
Line Material properties Mortar 1/NA:2012-05 or ω
DIN EN 1996-
3/NA:2012-01
Vertically perforated clay masonry
units of types HLzA and HLzB
Clay masonry units for masonry NA.4
1 panels of type T1 NM 2.2
NA.D.1
Perforated calcium-silicate masonry
units & calcium-silicate hollow blocks
NA.10
9 Autoclaved aerated concrete units DM 2.1
NA.D.9
a
ω = 2.6 for high-precision masonry elements and solid high-precision masonry units of
compressive strength class 28 or higher.
b
ω = 3.0 for solid or perforated lightweight concrete units of compressive strength classes
6 and 8 and for type LM 21 lightweight masonry mortar.
The four-storey residential building in Heppenheim has each unit (Nutzungseinheit) smaller
than 400 m² and the top of concrete floor of the attic < 13.0 m, therefore it belongs to building
category 4 (GK 4), which should be a highly fire-retardant according to fire protection in MBO
2002 (Musterbauordnung – MBO). Thus, the fire resistance duration of building components
must be at least 60 minutes.
IW-01 is a loadbearing internal wall with non-separating functions
➔ Criterion R 60 (Table NA.B.1.3) in DIN EN 1996-1-2/NA: clay masonry - loadbearing,
non-separating single-leaf wall with fire from all sides
The interior wall IW-01 is located at axis B / 1-2. The slab is fully supported over the whole wall
thickness t of IW-01 and therefore it transfers the load centrically into the wall.
Geometry
ℎ = 3.0 𝑚 (clear height)
𝑡 = 0.175 𝑚
𝑙 = 4.63 𝑚
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 12
8.2.1.1 Internal forces of the interior wall “in the cold case”
According to Table 5.5 in section 5, the design values of the acting axial forces and the load-
bearing resistance of IW-01 according to different calculation methods are given by:
Table 8.3 Design values of the acting axial forces and the load-bearing resistance
of IW-01 according to different calculation methods
DIN EN 1996-3 –
Vertical load DIN EN 1996-3 / NA DIN EN 1996-1-1
Annex A / NA
𝜙 = 0.75 𝜙 = 0.9
𝑁𝐸𝑑,𝑡𝑜𝑝
𝑁𝑅𝑑,𝑡𝑜𝑝 𝑁𝑅𝑑,𝑡𝑜𝑝
= 1365.04 𝑘𝑁
= 1723.47 𝑘𝑁 = 2068.16 𝑘𝑁
𝜙 = 0.67 𝜙 = 0.72
𝑁𝐸𝑑,𝑚𝑖𝑑 𝜙 = 0.5
𝑁𝑅𝑑,𝑚𝑖𝑑 𝑁𝑅𝑑,𝑚𝑖𝑑
= 1386.16 𝑘𝑁 𝑁𝑅𝑑 = 1148.98 𝑘𝑁
= 1539.63 𝑘𝑁 = 1631.55 𝑘𝑁
𝜙 = 0.75 𝜙 = 0.9
𝑁𝐸𝑑,𝑏𝑜𝑡𝑡𝑜𝑚
𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚
= 1407.28 𝑘𝑁
= 1723.47 𝑘𝑁 = 2068.16 𝑘𝑁
(see Table 5.5 in chapter 5.1.5)
The details of the design values of the acting axial force are shown in section 3.1.1.They are
based on the following components:
𝑁𝑔𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 789.11 𝑘𝑁
𝑁𝑞𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 227.99 𝑘𝑁
𝑁𝐸𝑑 the design value of the applied vertical load in accordance with DIN EN 1996-1-1 or
DIN EN 1996-3
𝜂𝑓𝑖 the reduction factor for the design value of the actions in fire; 𝜂𝑓𝑖 = 0.7 unless a detailed
analysis is performed
Therefore, according to simplified assumption, the design acting axial force is given by:
𝑁𝐸𝑑,𝑓𝑖,𝑡𝑜𝑝 = 𝜂𝑓𝑖 ∙ 𝑁𝐸𝑑,𝑡𝑜𝑝 = 0.7 ∙ 1365.04 = 955.53 𝑘𝑁
Axial force at the bottom of IW-01 at the 1st floor are based on the following components:
𝑁𝑔𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 789.11 𝑘𝑁
𝑁𝑞𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 227.99 𝑘𝑁
𝜓1,1 = 0.5 according to DIN EN 1990/NA, Tab. NA.1.1 is to be used for live loads in residential
buildings.
Thus, the reduction factor for the design value of the actions in fire can be determined using
the diagram:
𝜂𝑓𝑖 = 0.65
In comparison to the exact calculation below using the formula, the value using the diagram is
slightly different due to the accuracy of the readability according to the diagram.
with
𝛾𝑔 = 1.0
𝛾𝑞,1 = 1.0
The design value of the acting axial force can be calculated by:
𝑁𝐸𝑑,𝑓𝑖,𝑏𝑜𝑡𝑡𝑜𝑚 = 1.0 ∙ 𝑁𝑔𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 + 1.0 ∙ 0.5 ∙ 𝑁𝑞𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 1.0 ∙ 789.11 + 1.0 ∙ 0.5 ∙ 227.99
= 903.11 𝑘𝑁 ≈ 914.73 𝑘𝑁
Both cases, using 𝜂𝑓𝑖 = 0.7 or performing a detailed analysis give a small difference of the
acting force in fire 985.10 𝑘𝑁 and 903.11 𝑘𝑁, respectively. The deviation of the results is
around 10%.
TUD – Institut für Massivbau
Only for use in the context of the lecture MSCC. No further reproduction or distribution is permitted!
8 Structural fire design 157
8.2.1.3 Slenderness
From section 2.1.3, the slenderness is given by:
ℎ𝑒𝑓 2.25
𝜆= = = 12.86
𝑡 0.175
whereas, ℎ𝑒𝑓 = 0.75 ∙ 3.0 = 2.25 𝑚
15 𝑁𝐸𝑑,𝑓𝑖
𝛼6,𝑓𝑖 = 𝜔 ∙ ∙ 𝑒𝑚𝑘,𝑓𝑖
ℎ𝑒𝑓 𝑓𝑘
25 − 𝑡 𝑙 ∙ 𝑡 ∙ 𝑘 ∙ (1 − 2 ∙ 𝑡 )
0
whereas,
𝑁𝐸𝑑,𝑓𝑖 = 𝑁𝐸𝑑,𝑓𝑖,𝑏𝑜𝑡𝑡𝑜𝑚 = 985.10 𝑘𝑁
𝜔 = 2.2 since masonry is made of perforated clay masonry units, see also Table 4.1 in section
3 above, which is actually from DIN EN 1996-3/NA, Table NA.D.1.
ℎ𝑒𝑓 = 2.25 𝑚
𝑡 = 0.175 𝑚
𝑙 = 4.63 𝑚
The characteristic compressive strength is given with:
𝑓𝑘 = 5.0 𝑁/𝑚𝑚, see section 3.1.2
𝑘0 = 1.0 , since wall cross-sectional area equals to 𝐴 = 0.175 ∙ 4.63 = 0.810 > 0.1𝑚²
For the interior wall IW-01 on the 1st floor, in the cold case, the simplified methods according
to DIN EN 1996-3/NA are used. And the verification is fulfilled. Therefore, for this wall, having
floor supported over the full thickness of the wall, the eccentricity can be set to be zero. Thus,
𝑒𝑚𝑘,𝑓𝑖 = 0
IW-01 is a loadbearing internal wall with non-separating functions. According to DIN EN 1996-
1-2/NA, Table NA.B.1.3, for perforated clay masonry units HLz using general-purpose mortar
M5, the minimum wall thickness (mm) 𝒕𝑭 for fire resistance classification R for 𝒕𝒇𝒊,𝒅 =
𝟔𝟎 𝒎𝒊𝒏𝒔 is given by:
From line 1.3 in the table: 𝑡𝐹 = 115 𝑚𝑚 < 𝑡 = 175 𝑚𝑚
➔ The structural fire design is checked!
According to DIN EN 1996-3/NA Annex A, see also Table 8.3, the design values of the capacity
is given by:
𝑁𝑅𝑑 = 1148.98 𝑘𝑁
Thus,
𝑁𝐸𝑑,𝑓𝑖 985.10
𝛼𝑓𝑖 = = = 0.86 > 0.70
𝑁𝑅𝑑 1148.98
➔ In this case, using the result of the capacity from the simplified method with Annex A,
the verification can not be made.
According to DIN EN 1996-3/NA, see also Table 8.3, the design values of the axial force
capacity can be determined as:
𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 = 1723.47 𝑘𝑁
Therefore,
𝑁𝐸𝑑,𝑓𝑖 985.10
𝛼𝑓𝑖 = = = 0.57 < 0.7
𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 1723.47
➔ By using the result according to the simplified method, the verification of the structure
in case of fire can be made now.
The loading level can even be more precisely, using the results of the capacity according to
DIN EN 1996-1-1/NA, see also Table 8.3, with
𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 = 2068.16 𝑘𝑁
and performing a detailed analysis of the acting force in fire, see section 8.2.1.2.2:
𝑁𝐸𝑑,𝑓𝑖,𝑏𝑜𝑡𝑡𝑜𝑚 = 903.11 𝑘𝑁
Thus,
𝑁𝐸𝑑,𝑓𝑖 903.11
𝛼𝑓𝑖 = = = 0.44
𝑁𝑅𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 2068.16
➔ For 𝛼𝑓𝑖 , there is only the limitation 0.7 used. Not like with 𝛼6,𝑓𝑖 , the requirement of the
minimum wall thickness in fire can be reduced in some cases if 𝛼6,𝑓𝑖 ≤ 0.42!
Note: The calculation of the loading level 𝛼𝑓𝑖 is not necessary in practice if the requirement for
case with 𝛼𝑓𝑖 ≤ 0.7 in the corresponding tables according to Annex B is met. In this case the
following applies:
𝑁𝐸𝑑,𝑓𝑖
𝛼𝑓𝑖 =
𝑁𝑅𝑑
Whereas, 𝑁𝐸𝑑,𝑓𝑖 = 𝜂𝑓𝑖 ∙ 𝑁𝐸𝑑 = 0.7 ∙ 𝑁𝐸𝑑
𝑁𝐸𝑑,𝑓𝑖 0.7 ∙ 𝑁𝐸𝑑
𝛼𝑓𝑖 = =
𝑁𝑅𝑑 𝑁𝑅𝑑
Since 𝑁𝐸𝑑 /𝑁𝑅𝑑 ≤ 1.0 must always be verified for the design in the cold case, the general result
is 𝛼𝑓𝑖 ≤ 0.7. The utilisation factor 𝛼𝑓𝑖 can therefore not be greater than 0.7. The minimum wall
thickness required for the respective fire resistance class can therefore be read off directly
from the relevant tables in Annex B for the brick-mortar-combinations mentioned.
The exterior wall EW-02.1 is located at axis A / 1-2. The slab is supported over 2/3 of the wall
thickness t of EW-02.1 and therefore, it transfers the load eccentric into the wall.
Geometry
t = 0.365 m; a = 2/3 · 0.365 m = 24.3 m
b = 2.68 m
h = 3.00 m (clear height)
Construction materials
General-purpose mortar compressive strength class M5
Perforated clay masonry units: compressive strength class 10
In this example the exterior wall EW-02.1 is verified with the general method according to
DIN EN 1996-1-1. In this case, to determine the loading level 𝛼6,𝑓𝑖 the eccentricity 𝑒𝑚𝑘,𝑓𝑖 in
case of fire needs to be calculated.
8.2.2.1 Internal forces of the exterior wall EW-02.1 in the cold case
The vertical loads of all construction elements are calculated in chap. 1.4 and summarized in
Table 1-10 and Table 1-11.
Table 8.4 Design values of the acting axial forces of the exterior wall EW-02.1 (see
section 5.2.1.1)
𝑁𝐸𝑑,𝑡𝑜𝑝 = 310.53 𝑘𝑁
𝑁𝐸𝑑,𝑚𝑖𝑑 = 363.79 𝑘𝑁
𝑁𝐸𝑑,𝑏𝑜𝑡𝑡𝑜𝑚 = 417.05 𝑘𝑁
The details of the design values of the acting axial force are shown in section 5.1.1.1.They are
based on the following components:
𝑁𝑔𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 249.68 𝑘𝑁
𝑁𝑞𝑘,𝑏𝑜𝑡𝑡𝑜𝑚 = 53.32 𝑘𝑁
8.2.2.2 Slenderness
The slenderness is given by:
ℎ𝑒𝑓 2.70
𝜆= = = 7.40
𝑡 0.365
whereas, ℎ𝑒𝑓 = 2.70 𝑚, see also section 4.2.3.
For simplification, the acting normal force NEd,fi according to DIN EN 1996-1-2/NA may be
assumed to be 70% of the value in the cold case, which corresponds approximately to a
superposition of the characteristic values of the actions due to dead weight and live load
(𝛾𝑔 = 𝛾𝑞,1 = 1.0 and 𝜓1,1 = 0.5), whereby wind loads are neglected (𝜓2,𝑖 = 0.0).
Table 8.5 Design values of the acting axial forces of the exterior wall EW-02.1 in
case of fire
Given:
I1 = I2 = 1.0 m · a3 / 12 = 1.0 m · (2/3 · 0.365 m)3 / 12 = 0.001201 m4
I4 = 1.0 m · h3 / 12 = 1.0 m · (0.20 m)3 / 12 = 0.000667 m4
E1 = E2 = KE · fk = 1100 · 4.5 = 4950 N/mm² (see Table 5.1)
E4 = 33000 N/mm² (concrete C30/37)
According to section NA.C (2) in DIN EN 199-1-1/NA, for a two-way slab (span ratios to up
1:2), the shorter span is used and a reduction of 2/3 can be applied on it:
l4 = 2/3 (5.0 m – 0.175 / 2 – 0.365 / 2) = 2/3 x 4.730 = 3.15 m
at the top of the wall: h1 = h2 = 3.00 m
4 4950 0.001201
3.00 9.35 3.152
M1 = 0−
4 4950 0.001201 4 4950 0.001201 4 33000 0.000667
4 ( 4.0 − 1)
+ +0+
3.00 3.00 3.15
7.927
M1 = 0 − 7.731 = −1.40 kNm / m
7.927 + 7.927 + 0 + 27.950
4 4950 0.001201
2−
9.35 3.15
M2 = − 3.00 0 −
4 4950 0.001201 4 4950 0.001201 4 33000 0.000667 4 ( 4.0 − 1)
+ +0+
2.60 3.00 3.15
7.927
M2 = − −7.731 = 1.36 kNm / m
9.146 + 7.927 + 0 + 27.950
Table 8.6 Design values of the acting moments of the exterior wall EW-02.1 in case
of fire
Table 8.7 Eccentricities of the exteriror wall EW-02.1 under fire case
M md
em = + ehe + einit 0.05 t
N md
The eccentricity due to creep ek can be neglected if the critical slenderness according to
Table 5.4 is not exceeded. Slenderness λ = 5.64 ≤ 15 (critical slenderness) → ek = 0
The eccentricity due to horizontal loads ehe = 0 as the combination factor for wind
𝜓2,𝑖 = 0.0 in the considered load combination.
For the unplanned eccentricity einit,mid at the mid-height of the wall applies according to DIN
EN 1996-1-1, section 5.5.1.1:
einit, mid = hef / 450 = 2.06 / 450 = 0.0046 m
The verification and the capacity reduction factor at the centre of the wall refers to the real
cross-section with the wall thickness t. Since the load eccentricities are calculated with the
ideational cross-section with the wall thickness a (see chapter 5.2.1.2), the eccentricity at the
wall centre increases about (t – a) / 2.
M Ed , fi ,mid t −a
em, fi = + + ehe + einit + ek 0.05 t
N Ed , fi ,mid 2
0.365 − 2 0.365
em, fi = 0.00008 + 3 + 0 + 0.0046 + 0 = 0.065 m 0.05 0.365 = 0.0183
2
𝑒𝑚𝑘,𝑓𝑖 = 0.065 ≤
𝑡𝑓
6
=
0.365
6
= 0.061 ↯
➔ For eccentricities 𝑒𝑚𝑘,𝑓𝑖 greater than 𝑡𝑓 /6 or the partially supported wall with 𝑎/𝑡 ≥ 2/3,
the constructional detailing should be such that there is central loading.
➔ A centring strip is installed, so that the vertical load applies central the partial slab
support has no effect anymore. The moment due to the joint analysis will be equal to
zero due to the hinged support of the centring strip.
M Ed , fi ,mid
em, fi = + ehe + einit + ek 0.05 t
N Ed , fi ,mid
em, fi = 0 + 0 + 0.0046 + 0 = 0.0046m 0.05 0.365 = 0.0183m
𝑡𝑓
✓
0.365
𝑒𝑚𝑘,𝑓𝑖 = 0.0183 ≤ 6
= 6
= 0.061
𝑁𝐸𝑑,𝑓𝑖
𝛼6,𝑓𝑖 = 𝜔 ∙ 𝑒𝑚𝑘,𝑓𝑖
𝑓𝑘
𝑙∙𝑡∙ ∙ (1 − 2 ∙ 𝑡 )
𝑘0
whereas,
𝑁𝐸𝑑,𝑓𝑖 = 𝑁𝐸𝑑,𝑓𝑖,𝑏𝑜𝑡𝑡𝑜𝑚 = 291.94 𝑘𝑁
𝜔 = 2.2 since masonry is made of perforated clay masonry units, see also Table 4.1 in section
3 above, which is actually from DIN EN 1996-3/NA, Table NA.D.1.
ℎ𝑒𝑓 = 2.70 𝑚
𝑡 = 0.365 𝑚
𝑙 = 2.68 𝑚
The characteristic compressive strength is given with:
𝑓𝑘 = 4.5 𝑁/𝑚𝑚, see section 3.1.2 for M5 and clay class 10
𝑘0 = 1.0 , since wall cross-sectional area equals to 𝐴 = 0.365 ∙ 2.68 = 0.978 > 0.1𝑚²
𝑁𝐸𝑑,𝑓𝑖 0.29194
𝛼6,𝑓𝑖 = 𝜔 ∙ = 2.2 ∙ = 0.16 = 16%
𝑓 4.5 0.0183
𝑙 ∙ 𝑡 ∙ 𝑘 ∙ 𝑎/𝑡 2.68 ∙ 0.365 ∙ 1.0 ∙ (1 − 2 ∙
0.365
)
𝑘0
Note: In Table NA.B.1.2 only values in brackets are available: Plaster finish on both sides (min
15mm P IV inside/ min 15mm P II outside according to technical approval of the product)
The structural fire design is checked.
Perforation: HLz W,
HLzT2, HLzT3 and
HLzT4
Density class ≥ 0,8
Mortar: General purpose
masonry mortar,
lightweight masonry
mortar
3.1 Loading level 6,fi 0,42
3.1.1 240 (240) (240) (240) (240) (365)
3.1.2 300 (175) (175) (175) (240) (240)
3.1.3 365 (175) (175) (175) (240) (240)
3.2 Loading level 6,fi 0,70
3.2.1 240 (240) (240) (300) (365) (365)
3.2.2 300 (240) (240) (240) (240) (300)
3.2.3 365 (240) (240) (240) (240) (240)
The values in brackets apply to walls with a plaster finish on both side in accordance with
4.2 (1).
a
If solid clay masonry units are used.
b
The minimum length is lF > 1,0 m. External walls should therefore be designed as
separating walls with according to Table NA.B.2 or otherwise as non-separating walls
according to Table NA.B.3.
Table NA.B.1.6 – Clay masonry – Minimum thickness of each leaf of loadbearing cavity
walls with one leaf loaded (criteria REI) for fire resistance classifications
The values given in Table NA.B.1. 2 apply.
Table NA.B.3. 4 – Dense and lightweight aggregate concrete masonry – Minimum length
of non-separating loadbearing columns or single-leaf walls < 1,0 m in length (criterion
R) for fire resistance classifications