CS-3200 Inverter l
CS-3200 Inverter l
2、Installation……………………………………………………………………………………………5
2-1、demount and remount front cover………………………………………………………………5
2-2、Take down and reinstall numeric keypad………………………………………………………6
2-3、Select the place to install the inverter……………………………………………………6
2-4、The installation space to choose………………………………………………………………7
3、Wiring…………………………………………………………………………………………………8
3-1、Perphearl device and wiring the arbitrary option………………………………………9
3-2、wiring diagram…………………………………………………………………………………10
3-3、Wiring of main loop……………………………………………………………………………12
3-4、Grounding ………………………………………………………………………………………16
3-5、Wiring of control circuit……………………………………………………………………17
3-6、wire check………………………………………………………………………………………19
4、Operation ……………………………………………………………………………………………19
4-1、Select the operation mode ……………………………………………………………………19
4-2、The check before test operation………………………………………………………………20
4-3、trial operation…………………………………………………………………………………20
4-4、Operating check…………………………………………………………………………………21
7、Failure recovery……………………………………………………………………………………61
7-1 Faulty diagnose and correction measure…………………………………………………………62
7-2 Warning display and explain…………………………………………………………………………63
7-3 The motor faulty and correction measure…………………………………………………………64
8、Quality Guarantees…………………………………………………………………………………66
Appendix1 technical norm………………………………………………………………………………68
Appendix2 function parameter catalog………………………………………………………………70
Appendix3 shape dimension………………………………………………………………………… …84
Appendix4 kinds of rating output amperemeter type…………………………………………… 85
Appendix5 routine maintenance and check……………………………………………………………88
Appendix6 RS-485 communication agreement…………………………………………………………91
Appendix7 auxiliary instrction for CS3200 series inverter in use to
Injection machine reforming ………………………………………………………………94
9、Option…………………………………………………………………………………………………97
1
Notice transaction for safe operating
The notice transation about safe operation can be classified to “warning”or “attention”
Warning
z While installing or operating, should observe the guidance of instruction
z Verify the inverter rating voltage should be consistented with the AC power supply
voltage
Not to observe the waring, might lead to injury or catch fire
z Do not made AC loop supply power and output terminal U,V and W connected.
While in connecting, the inverter will be mangled, and maintenance bond will
invalidation
z Only after install the panel can connect the input power supply,while electrify ,don’t
remove the outside cover.
If not observe might lead to electric shock
z Do not touch the high pressure terminal inside the inverter
If not observe might lead to electric shock
z After break the main loop power supply, only finish affirmed can maintenancce and check
Capacitor inside machine with charge, is very dangerous, should waiting at least
5mintues,till finished discharge of the DC bus bar capacitor.
z While electricity do not connect or break the guide line and the connection
If not observe will lead to body injured.
z Controlling PCB panel should use CMOS ICS, do not touch CMOS element
CMSO element is easy to disturbed with static
z The inverter can mot be in pressurization test.
It could cause the damage of the inverter inners semicon component
2
1、Check and accept
Caution
z Do not install and operate the inverter which has been damaged or has the blunder
component otherwise it will hurt person or destroy the facility.
This chapter introduces the check method of the inverter used by the user.
1-1、check
1-1-1、
This table is check item
Check item Explain
Does the inverter type agree with the Check the type in flank data plate of the
indent inverter.
Does this have the damage of the Check the appearance by eyeballing and assure
component? no damage while transiting
Take off the front cover of the inverter.use the
Is the component screw up safely or not suitable tool to check the entire eyeable
component.
Receive the instruction or not?
Instruction certificate of qualification and
Receive the certificate of qualification
maintenance of inverter
and maintenance card
If do not satisfied with any check item above.please contact with our company.
Dataplate data
Specification MODEL:CS3200-G1R5 T4
Input specification INPUT:AC 3PH 380V ±15% 50/60Hz
3
Data dataplate
type instruction
CS3200 G 1R5 T4
inverter series
2、Installation
Caution
●Stock bed lift the machine,do not take front cover lift when move the inverter
Otherwise.main body may drop out cause damage.
● when put the setting into the ark,can install a fan or other cooling facility,at
the same time assure the air entrance temperature under 45℃.
Overheat will burn or setting damage.
This charper introduce the formation and setting environment and space while
4
Ecumenic install,it’s no need to take off the front cover and numeric keypad.The keypad
contact with the inner circuit with the electric cable.When loading and unloading must
be careful.Pull out the electric cable first then take down the keypad and front plat,or
may make the plug damaged.
★ Avoid meet the sunlight directly.Do not use in the openair directly.
★ Install the filter unit when there are some metal powder and silk fribe in the air.
★ Must take reduce tempreture measure,when the using environment is over 45℃.
★ Too cool and hot will make the setting fault.the suggestion tempreture range is-10
℃~40℃
★ Far from the power supply yawp. Such as the electric welder and the large power
facility.
5
2-4、The installation space to chose
CS3200 series inverter should have enough radiating space for cooling when install
vertically.
大于150mm
>150mm
Air outlet出风口
> >
100mm
大于 FWD REV JOG LCL RUN FLT
大于
mm MON NEG Hz S % A
mm
MODE
△ ENTER
FWD
△ >>
REV JOG
STOP
RUN RESET
CAUTION
-Read the instruction manual
-Do not open the terminal cover
while power is applied or for 10
minutes after power has been removed.
★ notice
1、 The space needed by the top/button and the both sides are the same for the open
framework type(IP00) and the close hang type (IP55).
2、 The top and underpart area should leave enough heat dissipation space; in order to
pass in and out the frequency inverter air can be unobstructed.
6
3、Wiring
Warning
● Only after affirming the power supply be turned off can be connected.
If not abide the warning will lead to electric attack or catch fire.
● All the down-lead pressurization shoud as same grade as the converser voltage.
If not abide the warning will lead to body injured
Caution
● Verify the inverter rating voltage should be consistented with the AC power supply
voltage
If not abide the warning will lead to body injured or catch fire.
This charper introduce CS3200 series inverter’s wiring of main loop and control
circuit.
fluctuate frequency:±5%
7
Less than 18.5KW standard:
R S T P+ N- B E U V W
18.5KW-75KW standard:
R S T P+ N- E U V W
93KW-132KW standard:
R S T P1 P+ N- E U V W
P+ R S T U V W N-
sign function
R AC Power supply input
S Single-phase or three-phase200 - 230V AC(220V unit),three-phase
T 380-460V AC(400V unit)
U
V Three-phase output terminal connecting the machine
W
P+ Positive DC generatrix terminal
P1 DC generatrix reactor connecting terminal (between P+)
B dynamic brake resistance connecting terminal(between P+)
N- Negative DC generatrix terminal
Chassis grounding (according to different types,the grounding
E
terminal can be on the radiator not always on the terminal line.
8
Three-phase Outside setting Explain
and options
power supply To cut off the faulty
current celerity and
No-fuse breaker prevent the power
MCCB fault which is lead
by inverter and the
line fault.
While happened
inverter fault, to cut
Magnetic
off the main power
contactor
and to prevent the
MC
power –fail and
re-start after fault
* To use in
AC Reactor betterment
ACL inputting power
factor, reduce
higher harmonic
and to restrain
power surge.
CS3200 *Wireless noise
Use in reducing the
filter
radio jamming
Coursed by inverter
NF
*Resuscitate While the braking
braking moment can’t
resister RB satisfied requiring,
suits in big inertia
Resuscitate loading and
braking unit frequent braking or
UB quick-close state.
* To betterment
DC reactor power factor,
DCL restrain top of
current
* Wireless noise
To reduce the radio
filter
jamming of inverter
NF
3-2、Wiring diagram
The wiring diagram of main loop and controlling loop is shown in the below.while to use
numieric keypad, the motor will run as long as connect the main loop.
9
Dynamic brake
(selectable) 3
DB resistance
P N B1 B2
DC Bus reactor DB resistance
Potentiometer screen
power supply of sp Multi-function output relay 1
(1 KΩ, 1/2W) TA1
eed signal: lless than AC250V, 1A
V10 + 10V, 10mA less than DC30V, 1A
TC1 factory setting: ‘Run’
10
* V2,I2 can not input at the same time , VF,IF can not input at the same time ,
★ Attention
1.Control connector, frequency setting and scout instrument request to use screening
line or twin screening lines.
2.The input voltage or current which is afforded to the basic frequency can be choosed
by constant 01-01.
3.The most output current of control circuit connector VIO is 50mA
4.The output muiti-function analogy quantity is used to scout screening (For example
the output frequency meter, ammeter),but it can not be used to feedback control system.
Warning
The safty grouding connector has been put to earth.
The 200V rank grouding connection resistance:100 ohm or less
The 400V rank grouding connection resistance:10ohm or less
The 660V rank grouding connection resistance:5ohm or less
If not obey to the warning,it causes electric shock or fire
Caution
Do not made AC loop supply power and output terminal
11
(c)The installation of electromagnetism contactor
Inverter mains side has not installed electromagnetism (MC) , it also can be used.
The electromagnetism (MC) can substitute breaker(MCCB) be cut for the main circuit
Current order,but when the electromagnetism be cut by one side once,and can’t be trigged
any more , and the electromotor slide stop.
When one side close /cut, the electromagnetism contactor can made load run /stop. But
open/close frequently will cause inverter accident , please pay more attention.
When use trig resistor unit, it can across the release junction of over loading
Relay,do the order control.
(e)AC reactor
When a inverter is connected to a large capacity power supply transformer(600KVA or
more),or when across/cut a posture and location advanced capacitor(power factor
Compensator),it makes a large peak value current when input current circuit,and
Break the part of the commute convertor .In this case, install a DC (direct current)
Reactor (option) to the inverter,or add a DC (direct current) reactor to the
Input channel. To install a reactor can improve the frequency factor of the mains side
effectly.
(f)Surge absorber
If geist load (electromagnetism, relay, magnetic valve, electromagnetic brake)
Is connected to the adjacent inverter,and use a surge suppresser at the same time.
wiring example 1:please use the special yawp filter of the inverter.
Other equipment
12
The main loop output connection matters need attention
(b) Forbidden absolutely (connect the input power supply with output connector U V W)
Don’t connect input power supply to the output connector U, V and W
(d)forbid to connect the posture and location advanced capacitor or LC/RC yawp filter
Don’t connect the posture and location advanced capacitor or LC/RC yawp filter
To output circuit.
Disturbing noise :
Because the electromagnetism disturbs,and noise modulate in the signal wire,it cause
the control to produce error action.
Wireless noise : If the inverter reality or cable emit high frequency,and made
13
(h)The countermeasure to the interfere niose
In order to control the interfere noise of the output end,besides use the yawp filter,make
the connection line whole penetrate the grounding metallic conduit.Devide with signal
wire to 30cm or more,the effect of interfere noise reduce.
The frequency of the signal carrier can be established by the constant 01-26.
The table of wiring distance between frequency inverter and motor
wiring distance between The longest The longest
More than 100m
frequency inverter and motor Is 50m Is 100m
Carrrier frequency(the 8Khz or the 5KHz or the 3KHz or the
parameter01-26 of set value) lower lower lower
380V grade main loop mix line and need related ancillary equipment consult the form
14
CS3200-G093T4 93 172
350 250
CS3200-G110T4 110 M10 202
90
CS3200-G132T4 132 400 240
400
CS3200-G160T4 160 120 500 290
CS3200-G185T4 185 150 600 600 340
M12
CS3200-G200T4 200 180 362
600
CS3200-G220T4 220 240 415
600
CS3200-G250T4 250 470
270 800
CS3200-G280T4 280 530
CS3200-G315T4 315 1000 1000 600
350
CS3200-G400T4 400 M16 1500 1500 780
CS3200-G450T4 450
CS3200-G500T4 500 500 2000 2000 1000
CS3200-G630T4 630
3-4、Grounding
Grounding resistance:
200V gradation:100Ω or the less
400V gradation:10Ω or the less
660V gradation: 5Ω or the less
Don’t make CS3200 series inverter and electric welder or other large current eletric
equipment communal grounding.Ensure the whole grounding wire of canal and large current
electric equipment lead to pave apart.
z Use the regulation standard grounding wire, and make the length as shorter as possible.
z When use several CS3200 series inverter side by side,ground the equipment following the
picture (a),don’t follow the (c) to make grounding wire to form loop.
z Please follow the picture (d) to conect the CS3200 series inverter and electric motor
grounding.
15
(d)correct (e)not commend
V10 V2 I2 VF IF GND FM D6 D5 D4 D3 D2 D1 REV COM FWD SP1 SP2 +24 TC1 TA1 TC2 TB2 TA2
16
When close
D5 Free parking
effective
When close
D6 Fault reset
reset
Multi-function
COM Input common
connector
+10V
+10V output the largest
V10 Ananolg statement +10V current
current permission
Analogue current20mA
quantity input Analog input 0~ +10V/100% 0~ +10V(20KΩ)
V2
signal voltage
03-19 set
Analog input 0/4 ~ 0/4~20mA(250Ω)
I2
current 20mA/100% *
Analog input 0~ +10V/100% 03-23 set
VF 0~ +10V(20KΩ)
voltage
Analog input 0/4 ~
IF 0/4~20mA(250Ω)
current 20mA/100%
Analog signal 0V
GND
common ground
Multifunction When overload
Open set
output signal SP1 prewarning (03-06=15)
electric pole 1 The largest output
conduction
48V
When under
Open set 50mA
SP2 voltage (03-07=18)
electric pole 2
conduction
Open set
electric pole
COM
output common
ground
Between com can
Digit signal
24V input DC24V,the
current
largest 200mA
TA1 Operating Connection point
Multifunction
signal(normal content
When operating connection
open 250VAC,1An or
TC1 stop point output
connection smaller
(03-08=1)
point) 30VDC , 2A or
TA2 Fault When fault ,the Multifunction smaller
connection Connector TA2 connection
TB2
17
point output And TC2 close , point output
(normal Connector TB2 (03-09=2)
open/normal And TC cut
TC2
close
connection
point)
The frequency Multifunction
FM
Analog output meter output 0~ Analog Output 0~+10V
signal +10V/frequency quantity Load 2mA or
Analog signal
GND Fmax monitor smaller
common ground
(03-30)
RS-485 When it is in the
Communication communication terminal ,connect
signal positive JP485 linker to
signal the TER side.
SG+,SG-
RS-485
communication
negative
signal
3-6、wireing check
After finishing the installation and connection check the following items.
18
4、Operate
Warning
●Only after fixing the front cover connect the input current.when electrifying ,don’t
unload the outside cover.
If not obey the warning , it causes the electric shock.
●When choose retry function (02-07) ,don’t close to the inverter or load,because it
will suddenly restart as soon as stop.(Even the inverter restart,the other machine
system must ensure the person safety.)
If not obey the warning ,it causes the person injury.
●The setting function cause the stop button inert,so must install a single instant stop
button.
If not obey the warning ,it causes the person injury.
Caution
●Mustn’t touch the radiator or resistor,because of the high temperature.
If not obey the caution, it will burn out the body.
●Because it easily made the low speed to be high speed runned,so check the safetywork
area of electromotor and machine equipment before operate.
。If not obey the caution ,it causes person injury and equipment break down.
The frequency setting method is set by frequency set choices 01-03, the frequency set method
19
1 and frequency set method 2 form all kinds of combination.When the chioce 01-03 is frequency
set method 1, follow the table.
Frequency set Function code 01-01
Front panel set 0
Exterior set V2(I2) 1
Exterior set VF(IF) 2
Front panel potential device(with 3
the potential device type)
Ascending and descending control 4
RS-485 set 5
4-3、Trial operation
When the system is ready,put though the current,and check the inverter whether it is normal.
When it put though the current ,the numeric keypad display the light
If discover the problem.must cut off the power supply.
4-4、Operation examination
z Whether the state LED indicated light and the show of digit exerciser is correc
20
5、Front panel operation
功能码选择
Function code selection and data add-substract
数据加减设定
setting and frequency add-substract setting when
键盘频率给定时,频率加减设定
the front panel frequency was given.
Indicated lamp
RUN: The inverter is working,the indicated lamp light
JOG: To indicate nonce to be adjusting microinching method of operation,switch by the JOG
button.
LCL: To indicate nonce to be front panel method of operation and front panel frequency set
method,decide by PO100 and PO101.
FWD: Forward indicate.Indicate the current operation statement to be forward direction.
When operating,it light.When stopping, it flash.
REV: Reverse indicate.Indicate the current operation statement to be negnative direction.
When operating,it light.When stopping, it flash.
FLT: Fault indicate.When the inverter fault,the lamp light.
MON: Indicate nonce to be method of operation monitor.
NEG: Indicate nonce to show data to be negative value,only when run the method of operation
monitor.
Hz: Hertz S: Sec %: Percentage A: Ampere
21
5-2、The display modes of inverter
Operate method of monitor
(When operate method of monitor,if press △,the ▽ button enter the frequency set mode
.)
( When operate method of monitor,if appear the fault and alarm, it display the fault
protection method E or alarm method.)
Parameter set mode P
Parameter set mode U ENTER Frequency set mode
△,▽,button change the mode
Or delay 8 seconds
△,▽button
ENTER
MODE
MODE
Parameter set mode P
22
MODE
Exit the frequency set mode, return to the operation monitor mode,
When operate the frequency set mode, can not press ENTER button,only to wait 8 seconds
When operate and stop ,it can change the set value of frequency.
Fault monitor
z When operation monitoe mode,and appear fault and alarm,it will display fault and alarm
message.
z If the inverter FLT indicated lamp light, it show the coming fault.
z If the fault disappear,press the reset button RESET/STOP to reset the fault.
z If it show the serious fault, only to cut off the electricity and reset.
z If the fault has not reset or the screem has not cleaned,the front panel will display
the fault code all the time(refer to the fault diagnosis).The consumer can press ENTER
button to clean the screem,but the fault has not reset.If have not pressed any buttons
23
Parameter set mode
Set the inverter parameter and check the operating situation of inverter,then
set and check P and U parameter at the same time.In order to make the system operate
the best state,it must adjust some parameter value.
1. Press the MODE button to choose parameter set mode P or parameter set mode
U.
5. Press ENTER button to keyboard the data,and display the parameter code,such
as after press ENTER button ,AL1 indicates the set is wrong,the data have not
despoisted.
Watch out: When it is in the following cases,it can not change the data.
1. Press MODE button to choose parameter set mode P or parameter set mode U.
3. Press ENTER button to display the data,now the cursor do not fla
4. Press ENTER or MODE button again,quit the data show ,display the parameter
code.
24
The following example is the acceleration time 01-05 change from 015.0 to 016.1.
25
6、Function introdution
Output frequency
Machine rotate speed = × machine speed modulus
The largest output frequency
26
6-1-3、Selfset display function choice 1(10-03)
When set operation monitor mode c ,it displays the parameter serial number.
For example : The set value of 10-03 is 0001 ,and the parameter 00-01 represent
output frequency.So when selfset function display c, it represent output
frequency.
When set operation monitor mode y,it displays the parameter serial number.
FWD REV D6 D5 D4 D3 D2 D1
27
6-2、The set of basic parameter
Output voltage
The largest output voltage
Output voltage
Output voltage
100%
100%
Output
frequency Output
Basic frequency
requency Basic frequency
V/F mode: linearity
V/F mode: square
0: Linear V/F mode, relatively suitable for pulling the voltage of outputting
to keep invariable permanent torque load compared with ones that output
frequency. Such as the conveyor belt, bicycle parking equipment,etc..
1: The square V/F mode, the ones that are relatively suitable for pulling the
voltage of outputting with frequency of outputting, than for the turning into
torque load of shape of the parabola. Such as the fan, pump equipment,etc..
2: It is self-defining V/F mode,occasion not special use user can the wanton to
last voltage of outputting with outputting frequency than.
As the increase of the voltage of V/f mode will make the motor torque increase ,
but too much increase will cause the following situations :
z Make the work of the frequency inverter abnormal because the motor passes
the excitation
z The motor is overheated or vibration is too big.
z While increasing the voltage, increase the voltage step by step while
examining the electronic electromechanics and flowing.
29
6-2-2、Frequency limit(01-07,01-08)
(a)The upper limit frequency (01-07), set the upper limit value of frequency
order.
(b)The lower limit frequency (01-08), set the lower limit value of frequency
order.
output
frequency Moderate time 1(01-06)
Accelerate time 1 Accelerate time 2(01-31) Moderate
time 2(01-32)
(01-05)
Moderate time
1(01-06)
Time
ON
Add and moderate time to switch over
(sub D1-D6 of end is chosen)
When stop mode to choose “moderate time”(02-16=0).
Time
Time
Time
Accelera Desceler
Accelera Desceler
31
Output frequency
Output frequency
Time Tim e
S type = 1 S type = 2
6-3、Running statement
(a) Set 01-01=1,V2 input voltage signal(0~10V), input resistance is 20K Ohm。
I2 input current signal,input resistance is 250 Ohm。
(b) Set 01-01=2,VF input voltage signal(0~10V),input resistance is 20K Ohm
IF input current signal,input resistance is 250 Ohm。
(c) Anolog frequency set value is limited by the maximum of frequency(01-10)、
the upper limit frequency(01-07) 、the lower limit frequency(01-08)。
(d) 0~100.0% anolog frequency set value correspond to 0~ the upper limit
frequency(01-10)。
(e)Set 01-01=3, input front panel potentiometer (with potentiometer)。
32
02-21 set explaination
0 Can reverse running
1 Can’t reverse running
01-19
Positive /nagetive running order OFF,the motor will speed-down and stop by
setting.If the speed-down time is short or loading inertance is great,it will
have the overvoltage(ou)faulty.And in this case,can add spped-down time ,
installate brake risistance ,or break unit (choose device )
DC brake frequency (01-21)should not be too high,or will infact the DC brake.
Output frequency
6-4、output fuction
6-4-1、output simalation
34
(b) simalation set up (03-31)
、(03-32)
Used for adjusting analog quantity to export and gain and setover。
FM
Simulation
FM +
03-31 exporting
FM
and
gaining
GND
Simulation
exporting
the largest output frequency
Press for the direct current of 10V when and
200% Specified electric
100% is exported electric current ,etc.
current ,etc.
35
12 Counting device reaches the introduction for the counter
largest value
13 Timer function Timer device output 43
When the feedbacking value is
VF(IF)losing the feedback reduced to and is smaller than the
14
signal voltage of measuring , output a
contact signal。
15 The overload of the
The overload of the electrical
electrical machinery is
machinery is predicted alertly
predicted alertly
16 OL the electron is predicted The overload percentage of the
alertly in hot year electrical machinery exceeds 50%
50%
17 The trouble reports to the The trouble reports to the police
police while resetting while resetting automatically and
automatically exports
18 Owe the voltage
6-4-3、frequency check(03-10,03-11)
While multifunction terminal outputting select is setting to “frequency
check”(set as 5,6,or 7),it is in effect.
(a) Reach to frequency check (set as”5”)
frequency checking base(03-12)–frequency checking range(03-11)≤outputting
frequency≤frequency checking base
(03-10)+ frequency checking range (03-11)]
ON ON
36
(b)bigger than frequency check (outputting frequency≥frequency checking base)
(set as“6”)
Release width
frequency checking base ( 03-10 ) frequency checking
range(03-11)
outputting frequency
ON
Frequency checking signal
ON ON
Setting frequency
Frequency checking
range
6-5、Input function
6-5-1、Analogue input
03-17 ~ 03-20 is to difine the analogue signal and the setting value for
thecontrolling terminal V2-GND(0~10V)and I2-GND(0~20mA)inputting.
★Note: While I2-GND input the current signal, 20mA corresponded 100% input
value, V2-GND input voltage signal,10V corresponded 100% input value.
37
Output frequency Output frequency Hz
fp2 fp1
50.0
fp1 fp2
Min analogue input value refer to the minimal value of the input voltage or
current, as picture of having shows Vmin or Imin。
Analogue input setting bias refers to the min anglogue value input the corrospond
setting data rate. as picture of having shows fp1。(03-18)
The max input value refers to the biggest value of inputting voltage or the
current,as the picture shows Vmax or Imax。
Analogue input setting gain refers to the correspond setting rate of the max
analogue value,as the picture shows fp2。(03-17)
★notice:
1、cording to 03-17 ~03-18,Can define two kinds of typical introduction and
output the characteristic,as picture shows the action and reaction, these two
characteristic can be used flexibly in control system with different feedback
characteristic.
2 、 In the closed loop control system that consist with the inverter and
controller,must assure the systems action and reaction first then choose the
output frequency characteristic of the inverter correctly.
3、When analog signals use ing the frequency set. 100% correspond to the max
output frequency.when analog signals use in given PI or feedback,100%
corresponds to the max feedback value.
Example:While the signle inputing is V2 with 0~10V outside ,the adjust frequency
range is 0.00Hz-60.00Hz,the max frequency input can be (01-10)=60.0Hz,the upper
limit frequency (01-07)=60.0Hz,and the analog inputting type (03-19)=0,
FWD/STOP FWD“open”
:stop,
“close”:Running
0:two-wire(1)
rotation REV“open”
:stop,
“close”:Reversal forward/stop
REV/STOP reverse/stop
COM
RUN/STOP
FWD“open” :stop,“close”:Running
1:two-wire(2)
FWD/REV REV “ open ”: positive rotation ,
running/stop
“close”:Negative rotation
reverse/forwa
COM
STOP RUN
FWD (“close”:running)
Three-wire type running ratain
3: three-wire(2)
FWD/REV (“open”:stop)
REV ( positive/negative rotation
select)
COM “open”:positive running,
“close”nagetive running
39
6-5-3、eletrify disposal terminal running select (02-19)
6-5-5、crawl frequency(01-50)
Terminal crawl running select:
Establish the multi-functional input end son (D1-D6 ) in order to click and move
and operate choosing.crawl running could accord the crawl frequency and second
speed –down time . while more speed given and the crawl running choose input
in the same time ,the crawl mode have the priopity.if adopt the terminal running
mode ,while FWD terminal connected are for the positive crawl running .
Front panel running mode can chose the adjusting direction with the buttonFWD/REV
And press RUN adjusting running ,speed-down and stop while off the button.
Key board crawl running select:press JOG button can turn the running
mode to crawl running,at the same time ,the JOG indication light on.
40
JOG Button is efficency in running inspect mode only while the
inverter stopped ,other wise will be inefficiency
Reference
set Name explain
page
0 no Inefficacy input
1 Casade speed terminal one Casade speed input order
2 Casade speed terminal two Casade speed input order
46
3 Casade speed terminal Casade speed input order
three
4 Upper frequency order Increase output frequency while closing
44
5 Down frequency order Reduce output frequency while closing
6 Faulty reset frequency Inverter fault while closing
Abnormity outside, Inverter stop for fault while outside
7 ordinary open terminal fault signal input close. If the output
input N.O break, numeric operate show “EF”.
8 Abnormity outside, Inverter stop for fault while outside
ordinary open terminal fault signal input close. If the output
input N.C break, numeric operate show “EF”
9 Secondly select time for Speed-up time choose 31
speed-up and speed -down
Free stopping order Inverter stop output while closing, the
10
machine stop itself.
11 Crawl running sekect Choose adjusting running mode while 42
closing.
12 Three-wire running Three-wire running keep input 41
control
13 Rigister input terminal Exterior counter output teminal 45
14 Eliminate rigister Counter count value reset
15 Timer input Exterior timer input 43
16 Program run pause Program operate pause operating input
17 Forbid speed-up or Inverter output frequency donot change 44
speed-down order
18 REF1/REF2 frequency Choose REF2 frequency setting while
41
change closing
19 Front panel run order choose front panel operating mode while
closing
20 PI control cancel Cancel PIcontrolling mode while closing
Other Reserve
Time input
close close close close close close close close
time output
closed closed
Output frequence
Time
Forbid speed-up-down
FWD
6-5-9. UP/DOWNorder(setting:03-00,03-01,03-02,03-03,03-04,03-05=4,5)
While input the positive (negative) running order, the terminal input UP/DOWN
42
can change the frequent order.make it running in expecting speed.
Set D5 as UP(03-04=4)
,D6 as DOWN(03-05=5)
。
Curcuit controlling Close Open open close
terminal D5 (UP order)
Curcuit controlling Open Close Open Close
terminal D6 (DOWN order)
Running state Speed-up Speed-down Retain Retain
Positive running
Up order D5
DOWN order D6
★ notice:
To choose orderUP/DOWN,the outputting of inverter are limited by upper-limit
frequency .
03-13 Set the timer setting value, 03-14 set the max value of counter.
This parameter set the inside tally value of CS3200, outside rminal
te which on
the controlling loop can be the tigger terminal for counter.while count value
reach to 03-13setting value, the appoint signal “counter reach to setting value
RELAY outoput”connectting action.
While count value from 01 up to the max value of 03-14 counter, the corrspond
“counter to the max RELAY output”multifunction output terminal tipper action.
The parameter can be used afer the counter finishing, and before stop, the output
signal can make inverter in low speed till stopped.
43
Sequence stoped as follows:
Show value
0 1 2 3 4 5 1 2
44
01-39
Frequency
01-40 01-43
01-44
01-42
01-41 01-45
main frequency
main frequency main frequency
ON ON ON ON time
Cascade speed terminal one
ON ON ON ON
Cascade speed terminal two
ON ON ON ON
Cascade speed terminal three
Running order ON
OFF
6-6-2、Process running
Process running is running frequency, running time, running direction, speed-up
and speed down time, and the running model can programme cascade speed timing
running.
2: Process running sopped after one circle 3:after one circle, running in last
speed.
The application of this parameter can be controlled as general small-scale
machinery , food processing machinery , working procedure washing the
equipment.can replace the conventional relay switch and timer controlling line;
Relevant parameters establish a lot of while using this function, the mistake
that every detail can't , please consult the following explanation carefully.
The setting time of seven parametr is to work in process running ,and the max
value of parameter is6000.0 seconds..
★Explain in particular:
If the setting value is 0.0(o second), Representing this stage will operate
and will be omitted and jumped to the next stage and carried out automatically.
Though CS3200 series offer to can is it run to programme seven sections of speed,
user can to use need that pay still, reducing the procedure and operating it for
five stages, three stages, etc., the stage that the choice of movements will not
only want to carry out sets as 0. 0 (0 seconds) can use it freely.
46
frequnecy 01-42
60Hz
01-43
50Hz
01-41
40Hz
01-44
30Hz
01-40
20Hz 01-45
15Hz
10Hz
01-39
0Hz time
04-04 04-05 04-06 04-07 04-08 04-09 04-10
Running
indication
Finish
indication
01-39=10Hz 04-04=10
01-40=20Hz 03-08=22 04-05=08
01-41=40Hz 03-06=23 04-06=15
01-42=60Hz* 04-07=15
01-43=50Hz 04-00=3 04-08=18
01-44=30Hz 04-09=20
01-45=15Hz 04-10=10
Action explain:
Left pursueing to show, as the operation order of the procedure is reached, the
frequency inverter runs according to the settlement of every parameter, get back
to first section of tempo more and continue running in circulation until the
seventh section is finished, until procedure operation order OFF did not stop.
47
Frequency 01-42
60Hz
01-43
50Hz
01-41
40Hz
01-44
30Hz
20Hz 01-40 01-40
01-45
15Hz
10Hz
01-39 01-39
0Hz
04-04 04-05 04-06 04-07 04-08 04-09 04-10 04-04 04-05
Running indication
Finish indication
01-39=10Hz 04-04=10
01-40=20Hz 03-08=22 04-05=10
01-41=40Hz 03-06=23 04-06=15
01-42=60Hz* 04-07=15
01-43=50Hz 04-00=1 04-08=15
01-44=30Hz 04-09=20
01-45=15Hz 04-10=22
48
Frequency 01-42
60Hz
01-43
50Hz
01-41
40Hz
20Hz 01-45
15Hz
10Hz 01-39
Positive rotation
0Hz
time
04-04 04-05 04-06 04-07 04-08 04-09 04-10
20Hz
01-44
30Hz
running
order
procedure
running indication
phase
running indication
Step indication
Finish indication
01-39=10Hz 04-04=10
01-40= -20Hz 03-08=22 04-05=20
01-41=40Hz 03-06=23 04-06=20
01-42=60Hz 04-07=15
01-43=50Hz 04-08=10
01-44= -30Hz 04-00=2 04-09=17
01-45=15Hz 04-10=17
49
6-6-3 Wobbulate running
Wobbulate running mode is fit for spin printing and dyeing.
wobbulate mode(04-18) 0:Inefficacy 1:efficacy
wobbulate amplitude value f h(04-19)
difference frequency△f(04-20)
risetimeT1(04-21), droptimeT2(04-22)
according to T1,T2 parameter to count the speed-up and down time ,setting
frequency shoule higher than f h .
Output Δf
Frequenc
fh
Setting frequency
T2 T1
Time
RUN
Running picture
Given value
Gain
50.0
0.0
-10.0 2.0 10.0 V2 input voltage signal
50
6-7-2、Outside IF feedback value(03-21,03-22)
While PI feedback signal choose(05-04)=2,using feedback IF outside.
If IF oiutside is 4mA,the pressure is -10.0%;if IF is 2omA,the pressure is 50.0%.
Setting 03-22= -10.0, 03-21= 50.0,any two points correspound to one line.
GAIN
50.0
4mA
6-03 20mA
-10.0
6-8、protect parameter
DC generatrix voltage
Time
Output frequency
When the inverter running in the irritated reduce the speed station, may happen
over-voltage or over-current. The phenomena may happen easily when the load
inertia is large raletively.when the DC generatrix voltage exceed a certain value
that checked in the inner, the output brake signal achieve the dynamic braking
through the external connection braking resistor. The consumer can choose the
machine type that has the braking function to apply this function.
When AVR function is effective, input voltage fluctuate to some extent, can is
it output voltage keep for the setting for value basically to make, make
electrical machinery work in the original state.
6-8-4、Current limiting(01-27)
Over-current lose speed set (01d-28),setting range: 20~180%.
When the frequency inverter is carried out and accelerated , because it is too
fast to accelerate or the motor is too big in load, the frequency inverter will
rise rapidly if the frequency inverter exports the electric current, exceed the
establishing value of 01-28 (cross the stall of the electric current and click ),
52
the frequency inverter will stop accelerating (keep regular to output frequency),
when the electric current should lower than the establishing value, the frequency
inverter continues accelerating
If frequency inverter in running constantly, output electric current exceed
01-28 (pass electric current stall a bit) when the person who establish, the
frequency inverter will reduce the frequency of outputting, avoid the stall of
the motor. If it is lower than 01-28 establishing value to export the electric
current, then the frequency inverter accelerates to establishing frequency again.
Percentage is established to establish the unit and output the electric current
(100% ) with the amount of the frequency inverter.
Output current output current
Output output
Frequency frequency
Time Time
In accelerating, over current Constant speed running, over
current lose speed prevent function. lose speed prevent function.
time
Multifunction ON ON
connection output signal
06-02 06-02
Over torque checking signal
53
(a)over torque checking function for choose(06-00)
Set Explaination
0 no checking (factory setting )
1 Checking betwwen constant speed running, and continued running after
checking.
2 Checking between running ,and go on running after checking
3 Checking while in constant speed, inverter output stopped while over torque.
4 Checking while running, inverter output stopped while over torque.
1、Setting to 2 or 4 to check over torque while speed-up or speed –down.
2、To continue running after checking over torque,the exerciser display “oL3”
warning (blink) while set as 1 or 2.
3、To stop inverter outputting while over torque,set as 3 or 4,will the exerciser
display“oL3”(blink).
6-8-6、Machine protection
Machine overloading checking
Can protect the machine by using the electron inside inverter,exact setting as
follows:
(a)Thermal overloading protecting level can be set by rating current of machine
and inverter.
(b)Machine overloading protection for chooseinfg(01-24)
time
Electron theral
Set 1min
character
0 No protect
Standard machine
1
(factory setting)
2 Convertion machine
0 100 200 current
The electron overloading protecting function is according to the inverter output
54
current 、 frecuency and the analog time to scout the temperature of
elctormotor,protect the elctormotor to be overheat,while be the overloading
relay action,display “ oL ” faulty signal,to cut off the inverter
outputting,prevent elctormotor to be overheat .while inverter connected to run
with a elctormotor, no need with an outside hot relay.while one inverter running
for several elctormotor s,a hot relay should be installed in every
elctormotor,and in this case,set the constant 01-24 as 0.
Heat overloading
Cooling effection Chracter
electron
In low speed running, While continuous running
Standard at commercial powe
course the motor in 100% loading low speed
electron r 50/60Hz running will
temperture rising should will be the heat
motor be effect in cooling.
limited the load. overloading pretection.
In 100% loading, 50/60HZ
Inverter Even in lower speed To be running in low or the lower speed
special (about 6Hz) running speed,use the inverter running continous,the
motor will be cooling. motor. electron heat over load
protection do not act.
55
6-9、other function
Running order ON
min base blank time or the longer time
speed selecting
This function would forbid or “skip”crirical frecuency, turn away the resonance
evocabled by machine system in running the motor.the function will have no effect
56
while setting value is 0.0HZ
Output frequency
Skip
frequency
Skip frequency range (01-49)
01-46
The torque requirement of the motor changes according to the load situation, but
according to the voltage of load torque requirement automatic V/f way. The necessary
torque is calculated by the frequency inverter, this has guaranteed that can not trip
to operate
(V)voltage
f frequency
57
along,and the been controlled respond to it,the main controlling and the been
controlled device to transmitted signal.so should should assign the address NO.
( 08-00 ) to every controlled device previously ,and the main controlling
transmitted according the address.the controlled device received the main
control order and perform the function ,and return answer to the main control.
1 … 31
Define the device adress.while on line do not allow two devices to use the same
adress ,and the adress 0 is broadcast adress. 1 … 31
6-10-2、conmunacation spec
Interface: RS-485
Transfers parameter
58
7、Faulty remove.
Warning
● Do not touch high voltage terminal inside inverter
If not obey will lead to electric shock.
● should install all the protect cover over again before the current electrify
If not observe, might lead to electric shock.
● After the loop cut off, can maintenance and check after discharged.
Electricity full in capasity ,will lead to danger.
z In running scout mode, while happed fault and warning ,will display the
z If happened the serious fault, should cut off power and reset.
z If fault haven’t reset or clear up the screen, the keyset will display
z Users can pressENTER to clean up the screen, and the fault haven’t reset.
z Notice! If the fault sttil in within press in 10 mins, the fault code will
Press kye-press reset, and can set the multifunction data input terminal to
be the fault reset, and connected the terminal, or to use RS485 communacation,
the fault can be reset after power cut.
59
7-1、Fault diagnose and correct measure
Display
Instruction Detail Put right
fault
Lack of DC main loop voltage
in running period.
Check level:
。Check the power line
lack of voltage in 200V step about 190VDC or
main loop(PUV) Lower.
。 Correct the lead-in
400Vstep about 380VDC or
voltage
lower
660V step about700VDC lower
。 Check motor loop
resistance
。Delay the time speed up
Output current exceed theOC and down
over current(OC)
Value. 。 Check insulation of
motor
。Check within
universal meter
Main loop DC current exceed
setting value.
Delayed the time speed
Check level
over voltage(OV) down, and add to brake
200V step: about 400VDC
resistance
400V step: about 800VDC
660V step: about 1300VDC
。 Check having bad of
Output grounding current of insulation or not
Ground fault(Grd) inverter overrun the 50% 。Check if have broken
rating current connection between
inverter and motor
radiator temperture ≥ oh Check the air blower and
Over-heat of check value(about 80℃,come environment temperature
radiator (oh) from temperture swtich) radiator and ventilate
radiator Over-heat radiator temperture ≥ oht the state, remove the
(oht) check value(about 90℃) dirt
motor over loading inverter output exceed the Reduce loaging
(oL) motor over loading value
inverter over Inverter output greater Reduce loaging, and
loading (oL2) than overloading valur delay the time speed up
over torque Output current exceed the Reduce the loading,
checking (oL3) checking value of torque delay the speed up time.
loading curreent 。Check the motor loop
Inverter output (loading)
short circuit resistance
short circuit
(oCP) 。Check motor insulation
60
exterior fault Trouble that the outside 。Check current exterior
(EF) control circuit produces control
61
7-2、 Warning display and explain
Waring would not stop runnig, and have no output action, and after clear up the
fault can be the inverter back to the running state again.
The vatious different warning explain as followes
62
Motor accident and corrective measure :
accident Check signal Corrective measure
Open the power ;
Chose the power and through
Whether the voltage of the
again;
power adds in the end son of
check the voltage of the
R、S、T?
power ;
make sure the end of scree
has firmed 。
Measure sub U of output end
with the rectification type Chose the power and through
voltmeter, V, is the voltage again
of W correct
The motor can’t running Makesure whether the
Reduce load and get rid of
overload, the motor is
locking.
locked?
Whether show on the operating Check the trouble according
device display that cranky? to the fault dictionary
To or reverse operation order
Check wiring
input?
Whether it has introduction
Correct wiring,frequency
that frequency establishes
and establish the voltage
the voltage?
Whether the settlement of the makesure input and
operation way is correct? establish is correctly
The motor changes With motor lead wire U, V,
Sub U of end, V, the wiring of
direction oppositly the looks preface of W is
W is correct?
wired correspondingly
Makesure whether operation
input signal that FWD or REV Check wiring
join is correct?
Frequency is given definitely
is the wiring of the circuit Check wiring
correct?
The motor is rotated but
makesure whether the
can't change speed Using the exerciser to check
settlement of the operation
the choose of running model
way is correct?
Whether load is too big? Reduce load
The rotational speed of Motor specified for value
Check the motor data plate
the motor (rotates / (count very much, voltage)
technical data
divides ) is too high or the correct
too low It is correct that gear Check and change speed in
wheel,etc. are added / the organization (gear
moderated the gear ratio? wheel,etc.)
63
It is correct that the most
Check and output the
greatly to output the
frequency establishing
frequency establishing
value the most greatly
value?
It is too many to be with
rectification voltmeter Check V/f characteristic
check motor end son voltage value
lower?
Is the load is big ? Reduce the load
Reduce the change of load
Is the load change too big? Increase the capacity of the
Motor while operating The
frequency inverter motor
rotational speed (rotates
Use three phases or the Whether the wiring which
/ divides ) is unstable
single-phase power? Whether checks the three-phase
lack the looks in the power lacks the looks。
three-phase power?
8、Quality guarantees
The quality assurance of this product is handled in accordance with the following
regulations:
8-2、When the export (does not include domestically abroad), responsible for
guaranteeing the repair free of charge buying in six months after producing the
goods.
8-3、No matter when, where use our company products of brand, is it serve all
the life while being paid to enjoy.
8-4、Our company in all parts of the country is selling, is produced , act for
the unit to offer the after-sale service to this product, its service condition
is:
8-4-1、Check and serve " tertiarily " in this unit site(include the trouble
clearing).
8-4-2 、 Is it relate to sell the contract content that the agent signs the
responsibility standard of the after-sale service in accordance with our company
to need.
8-4-3、Can paid to to is it act for unit ask after-sale service of acting as to
64
sell each our company (no matter whether guarantee to keep it. in good repair).
8-6、 In order to produce 15 months from goods date in guarantee period of this
product.
8-9、The machine if because buyer pay off the payment for goods or the left fund
close paying on time , the ownership of this machine still belongs to the
supply unit, does not also bear above-mentioned responsibility , the buyer
can't have objections
65
Appendix 1:technical regulation
66
Overloading voltage,under volt age,overloading electric current,fuse
Inverter break , grounding faulty , over heating of inverter , overheating of
p
r protection machine , Over loading protection, faulty outside1,2,message error,
o
t
e speed order losing hardware faulty, selecting mistake edc.
c
t Stifled and shift defending, overloading warning, temperature sensor
Inverter warning
i
o
n faulty
Instant break the less than 15 milliseconds: Continuous duty
electricity greater than 15 milliseconds: Allow to reset automatically
Workin
outputting frequency , outputting electric current, outputting
g
d voltage ,setting frequency ,working speed,Dcvoltage.
Key single
i
s
p
l
a board Error
y While in faulty protection working state, remain 3 faulty history
inform
information.
ation
Ambient
-10 ℃ ~ 40 ℃
C
i temperature
Storage
r
-20 ℃ ~ 65 ℃
c
u
temperature
m
s
t
Ambient humidity (maximal 90 % RH .(non dew)
a
n
c
Heighet/vibrat less than 1,000 m,5.9m/seconds
e
Apply place Have no corroded the gas , flammable gas , oil fog or dust and other
Cooling way Forcible wind cooling
67
Appendix2:function parameter catalog
Function Least Factory Referen
name Setting range Modification
number unit data ce page
0.00 ~ greatest outputting
Key board frequency
00-00 frequency Hz 10.00 ○
setting
be the same as function 01-04
00-01 outputting frequency Hz
Setting frequency
00-02 Hz
indication
Outputting electric
00-03 A
current
00-04 Outputting current rate %
00-05 DC bus bar voltage V
00-06 Outputting voltage V
Frequency order data
00-07 Hz
indication
00-08 Register &data 1 45
(0.00~99.99)electrify
00-09 hour
cumulative operation time
Cumulative operation time
00-10 Hour
(0.00~99.99)
Cumulative operation time 100
00-11
(0000~9999)* 100hours Hours
Inputting terminal break
00-12
on sate
28
outputting terminal break
00-13
on state
00-14 outputting frequency p(kW) 0.1KW
00-15 Outputting torque (remain) 0.1%
00-16 PI controlling given value 0.1%
PI controlling feedback
00-17 0.1%
value
0.0~100.0%,alike function
00-18 PI digital given value 0.1% 100.0 ○
05-13
00-19 radiator temperature 0.1℃
00-20 V2(I2)inputting value 0.1%
00-21 VF(IF)inputting value 0.1%
00-22 option VX inputting value 0.1%
V2(I2) setting data
00-23 0.1%
(after transfer)
VF(IF)setting data (after
00-24 0.1%
transfer)
68
Function Least Factory Referen
name Setting range Modification
number unit data ce page
options VX setting data
00-25 0.1%
(after transfer)
00-26 cumulating output kW.h 0.1k
00-27 cumulating output kW.h 1000k
00-28 achine speed indication
Machine timing speed of
00-29 1rpm
rotation
Overloading cumulating
00-30 0.1%
rate
inverter rated outputting
00-31 0.1A
current
Inverter rated outputting
00-32 V
voltage
Overloading ability 0:G type 150%overloading
00-33
display 1:P type 120%overloading
00-34 Software edition 1.00
0: key board operating
01-00 Working order for chose 1: Terminal operating 1 0 × 20
2:RS-485operating
0: digital key board
1: erminal V2(I2)
2:terminal VF(IF)
01-01 Frequency setting mode 1 3:front panel potential device 1 0 × 20
( with potential device type
69
Function Least Factory Referen
name Setting range Modification
number unit data ce page
0:Frequency setting 1
1:Frequency setting 2
2:Terminal chose frequency
setting1&frequency
setting 2
3 : frequency setting 1+
frequency setting 2
4 : frequency setting 1-
frequency setting for
01-03 frequency setting 2 1 0 ×
chose
5 : frequency setting 1 ×
frequency setting 2
6 : frequency setting 1/
frequency setting 2
7:min(frequency setting 1,
frequency setting 2)
8:max(frequency setting 1,
frequency setting 2)
front panel frequency 0.00~greatest outputting 10.00
01-04 0.01Hz ○
setting frequency Hz
01-05 Speed –up time 1 0.1s~6000.0s 0.1s 10.0s ○
31
01-06 Speed –down time 1 0.1s~6000.0s 0.1s 10.0s ○
01-07 lower limit frequency~
upper limit frequency 0.01Hz 50.00Hz ×
greatest frequency
31
01-08 0.00Hz~upper limit
Lower limit frequency 0.01Hz 0.00Hz ×
frequency
01-09 the mini outputting
0.00~greatest frequency 0.01Hz 0.50Hz ×
frequency
greatest outputting 50.00
01-10 10.00~300.0Hz 0.01 ×
frequency Hz
32
50.00
01-11 Basic frequency setting 10.00~300.0 Hz 0.01 ×
Hz
01-12 Outputting voltage rate 0.0~110.0% 0.1% 100.0% ×
01-13 torque compensation 0.0~30.0% 0.1% 2.0% ×
01-14 Auto torque compensation 0:no 1:yes 1 0 × 26
0: Line shape
1:Square
01-15 V/f mode pattern 1 0 × 27
2: Self setting V/f mode
(remain)
0: Inefficiency
01-16 AVR elect 1 1 × 53
1: efficiency
70
Function Least Factory Refern
Name Setting range Modification
number unit data ce page
0~1100V 220V
Reted input voltage of
01-17 Set rated voltage of power 1V 1* ×
power supply
supply 380V
DC brake section when
01-18 0:No 1:Yes 1 0 ×
starting
01-19 DC brake time when starting 0.0~60.0s 0.1s 2.0s × 34
01-20 DC brake voltage 0.0~30.0% 0.1% 5.0% ×
DC brake frequency when
01-21 0.00~300.0Hz 0.01Hz 0.50Hz × 35
stopping
01-22 DC brake time when stopping 0.0~60.0s 0.1s 0.0s ×
01-23 Slip compensation gain 0~150% (invalid when 0) 1% 0 × 35
0:No
Motor overload protection
01-24 1:Standard motor 1 1 ×
model
2:conversion motor 55
Motor overload protection
01-25 0~110 1% 100% ×
level
Factory
value
01-26 Carrier frequency 1~9 KHz 1 kHz accordi ○ 33
ng to
power
Current limitation
01-27 0:Invalid 1:Vvalid 1 0 ×
selection
G model
53
150.0
01-28 Current limiting value 20.0~180.0% 0.1% ×
P model
120.0
Over voltage stalling
01-29 0:Invalid 1:Valid 1 1 × 52
prevent selection
Auto energy-saving run
01-30 0:Invalid 1:Valid 1 0 × 58
selection
01-31 Acceleration time 2 0.1s~6000.0s 0.1s 15.0s ○
31
01-32 Deceleration time 2 0.1s~6000.0s 0.1s 15.0s ○
01-33 Acceleration time 3 0.1s~6000.0s 0.1s 20.0s ○
01-34 Deceleration time 3 0.1s~6000.0s 0.1s 20.0s ○
01-35 Acceleration time 4 0.1s~6000.0s 0.1s 30.0s ○
01-36 Deceleration time 4 0.1s~6000.0s 0.1s 30.0s ○
0:linearity
Acceleration and 1:S curve(begin)
01-37 1 0 × 32
deceleration S curve 2:S curve(end)
3:S curve(all)
71
Function Least Factory Refern
Name Setting range Modification
number unit data ce page
01-39 Lower limiting frequency~
First stage speed 0.01Hz 10.00Hz ○
upper limiting frequency
01-40 Lower limiting frequency~
Second stage speed 0.01Hz 20.00Hz ○
upper limiting frequency
01-41 Lower limiting frequency~
Third stage speed 0.01Hz 30.00Hz ○
upper limiting frequency
01-42 Lower limiting frequency~
Fourth stage speed 0.01Hz 40.00Hz ○ 46
upper limiting frequency
01-43 Lower limiting frequency~
Fifth stage speed 0.01Hz 50.00Hz ○
upper limiting frequency
01-44 Lower limiting frequency~
Sixth stage speed 0.01Hz 6.00Hz ○
upper limiting frequency
01-45 Lower limiting frequency~
Seventh stage speed 0.01Hz 7.00Hz ○
upper limiting frequency
01-46 Skipping frequency 1 0.00~300.0Hz 0.01Hz 0.00Hz ○
01-47 Skipping frequency 2 0.00~300.0Hz 0.01Hz 0.00Hz ○
57
01-48 Skipping frequency 3 0.00~300.0Hz 0.01Hz 0.00Hz ○
01-49 Skipping frequency range 0.00~50.00Hz 0.01Hz 2.00Hz ○
01-50 Adjusting frequency 0.00~50.00Hz 0.01Hz 5.00Hz ○ 42
01-51 Lower frequency selection 0:Run 1:Stop 1 0 0 98
220V
0~1100V
02-00 Motor rated voltage 1V 1* ×
Setted motor rated voltage
380V
Inverte
0.0~900.0A rrated
02-01 Motor rated voltage 0.1A ×
Setted motor rated current curren
t
10.00~300.0 Hz 50.00
02-02 Motor rated frequency 0.01 Hz ×
Setted motor rated frequency Hz
0~9000RPM
Motor rated rotational
02-03 Setted motorrated 1RPM 1425 ×
speed
rotational speed
2~12
02-04 Motor phase num. 2 4 ×
Setted motor phase Num
02-05 (Remain)
72
Function Least Factory Refern
Name Setting range Modification
number unit data ce page
0:Recovery from malefaction
Malfunction relay action
relay non-action
02-10 when reseted from 1 0 ×
1:Recovery from malfunction
malfunctiona
relay action
0:No start
Instant power off
02-11 1:Resetand run after 1 0 ×
restarting selection 57
voltage recovery
02-12 Allowed max.cut-off time 0.0~60.0s 0.1s 10.0s ×
0:Tracing start after
malfunction
02-13 Trace start ways 1 0 × 57
1:Tracing start all time
2:Invalid tracing start
Speed trace against
02-14 0.1~20.0s 0.1s 2.0s ×
deceleration time
Speed trace against
02-15 10~100% 1% 100% ×
voltageproportion
0:Deceleration stop
02-16 Stop way 1 0 × 34
1:Free stop
0:Two lines control mode 1
1:Two lines control mode 2
Control ways of terminal 2:Three lines control mode
02-17 1 0 × 40
running 1
3:Three lines control mode
2
0:Invalid when on terminal
Front panel stop key running way
02-18 1 0 ×
selection 1:Stop key valid when on
terminal running way
0:Deal upper valid terminal
Electric deal way on instruction
02-19 1 0 × 41
terminal running 1:Deal no upper valid
terminal instruction
0:Deal reset valid terminal
Reset and restart ways instruction
02-20 1 0 × 41
selection 1: Not deal reset valid
terminal instruction
0:Allow inversion running
02-21 Inversion prohibited 1:not allow inversion 1 0 × 33
running
73
Function Least Factory Refern
Name Setting range Modification
number unit data ce page
D1 Terminal designed as:
0:Invalid
1:Multi-stage speed
terminal first.
2:Multi-stage speed
terminal second.
3:Multi-stage speed
terminal third.
4:Rising frequency
instruction
5:Falling frequency
instruction
6:Malfuction reset
instruction
7:EF,out unnormal,NO
contact point input N.O
8:EF,out unnormal,,
NCcontact point input Multi
Multi-function input
03-00 N.C 1 stage ○ 44
terminal D1
9:Sencon add-and-subtract speed 1
speed time selection
10:Free stop instruction
11:Adjusting selection
12:Three line run maitenance
13:Counter import terminal
14:Clear counter
15:Timer input
16:Program runing pause
17:Prohibit add-subtract
instruction
18:REF1/REF2 frequecy
switching
19:Front panel operation
instruction
20:PI control cancel
other:remain
Multi
Multi-function input
03-01 D2 Terminal set same as 03-00 2 stage ○
terminal D2
speed2
44
Multi
Multi-function input D3 Terminal set same as
03-02 3 stage ○
terminal D3 03-00
speed 3
74
Function Least Factory Refern
Name Setting range Modification
number unit data ce page
03-03 Multi-function iput Add-sub
D4Terminal set same as 03-00 9 ○
erminal D4 tract 2
03-04 Multi-function input
D5 Terminal set same as 03-00 10 FREE ○
terminal D5
03-05 Multi-function input
D6 Termianl set same as 03-00 6 RESET ○
terminal D6
(Open collector output 1)
0~30
0:No output
1:Running (have run
instruction)
2:Malfaction instruction
3:Zero-speed (Motor
rotating speed is Zero)
4:Running frequency reach
setted frequency
5:Reach frequency level
measuring value
6:Greater than frequency
level measuring value
7:Less than frequency level
measuring value
8:Running frequency equal
low limiting frequency
9:Running fquency equal
upper frequency
Open collector output 10:Inversion running
03-06 1 15 ○ 36
selection 1 11:Counter reach setted
value
12:Counter reach Max.value
13:Timer output
14:VF(IF)Singal lost
15:Motor overload warning
16:electric thermal
overload pre-warnig
(Overload accumulating
percent greater than 50%)
17:Malfunction auto-reset
18:Under-voltage
19:Out malfunction
20:Inverter running
prepared
21:V2(I2)Signal lost
22:PLC stage running
compeleted
23:PLC Circle cycle
completed
Other:reserve
75
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
Open collector output 2
03-07 Open collector output 2 1 18 ○
(SP2),0~30 same as 03-06
Output relay1(TA1,TC1)
03-08 Relay 1 output selection 1 1 ○ 36
0~30,same as 03-06
Output relay 2(TA2,TB2,TC2)
03-09 Relay2 output selection 1 2 ○
0~30,same as 03-06
Frequency level measuring
03-10 0.00~300.0Hz 0.01Hz 30.00Hz ○
value 38
03-11 Frequency measuring range 0.00~10.00Hz 0.01Hz 1.00Hz ○
Overload warning current
03-12 0.0~150.0% 0.1% 100.0% ○
level
03-13 Counter setting value 1~Counter Max. 1 50 ○ 45
1 ~ 9000 , Counter reach
03-14 Counter Max. 1 100 ○
Max.,then back to 1
03-15 Timing time when close 0.0~6000.0s 0.1s 2.0s ○
43
03-16 Timing time when break 0.0~6000.0s 0.1s 2.0s ○
03-17 V2(I2) Input signal gain -500.0~500.0% 0.1% 100.0% ○
03-18 V2(I2)Input signal bias -500.0~500.0% 0.1% 0.0% ○
0:0~10V(0~20mA)
1:2~10V(4~20mA)
03-19 V2(I2) Input signal type 2:2~10V(4~20mA) With 1 0 ○ 39
signal lost protection
3:-10V~10V(preserve)
V2 ( I2 ) Output filtering
03-20 0.00~10.00s 0.01s 0.50 s ○
time constant
03-21 VF(IF)Input signal gain -500.0~500.0% 0.1% 100.0% ○
03-22 VF(IF)Input signal bias -500.0~500.0% 0.1% 0.0% ○
0:0~10V(0~20mA)
1:2~10V(4~20mA)
03-23 VF(IF)Input sighal type 2 : 2 ~ 10V ( 4 ~ 20mA ) With 1 0 ○ 51-52
signal lost protection
3:-10V~10V(preserve)
VF(IF)Input filtering time
03-24 0.00~10.00s 0.01s 0.50 s ○
constant
Option VX Output signal
03-25 -500.0~500.0% 0.1% 100.0% ○
gain
03-26 Option VX Input signal bias -500.0~500.0% 0.1% 0.0% ○
0:0~10V(0~20mA)
Option VX Input signal type
1:2~10V(4~20mA)
Note: With potentiometer
03-27 2 : 2 ~ 10V ( 4 ~ 20mA ) With 1 0 ○
model corresponding
signal lost protection
parameter
3:-10V~10V
76
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
Option VX Input
03-28 0.00~10.00s 0.01s 0.50 s ○
filteringtime constant
0:Negative is Zero
frequency!
Negative frequency set as 1:Input signal correspond to
03-29 1 0 × 40
inversion straight
linefrequency,negative
frequency is inversion
0:No simulation meter output
1:Frequency output
(Max.frequency
correspond to 10V)
2 : Output current ( 200%
Simulatin meter output
03-30 correspond to 10V) 1 1 ○ 35
selection
3 : DC main line voltaga
(1000V correspond to 10V)
4 : Output voltage ( Motor
rated voltage correspond
to10V)
Simulatin meter gain Use to correct simulation
03-31 0.1% 100.0% ○ 36
regulatin meter -200.0~200.0%
Use to correct simulation
Simulatin meter bias
03-32 meter 0.1% 0.0% ○ 36
regulation
-200.0~200.0%
Simulation meter output
03-33 0.00~10.00s 0.01s 1.00 s ○
filtering time constant
77
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
0:Program running invalid
1 : Program running
circulating running
2 : Program running stop
04-00 Program running ways 1 0 ×
after a week
3:Program running after a
cycle,running on last
stage
04-01 Program ruuning stage digit
1
diplay
04-02 Program running stage time 47
0.1s
display
04-03 Program running stage
0.1s
residual time display
04-04 First stage time 0~6000.0 s 0.1s 20.0s ○
04-05 Second stage time 0~6000.0 s 0.1s 20.0s ○
04-06 Third stage time 0~6000.0 s 0.1s 20.0s ○
04-07 Fouth stage time 0~6000.0 s 0.1s 20.0s ○
04-08 Fifth stage time 0~6000.0 s 0.1s 20.0s ○
04-09 Sixth stage time 0~6000.0 s 0.1s 20.0s ○
04-10 Seventh stage time 0~6000.0 s 0.1s 20.0s ○
04-11 One stage running
add-substractspeed time 1~4 1 1 ○
selection
04-12 Two stage running
add-substact speed time 1~4 1 1 ○
selection
04-13 Three stage ruuning
add-substrac speed time 1~4 1 1 ○
selection
04-14 Four stage running
add-substract time 1~4 1 1 ○ 48
selection
04-15 Five stage running
add-substract time 1~4 1 1 ○
selection
04-16 Six stage running
add-substract speed time 1~4 1 1 ○
selection
04-17 Seven stage running
add-substract speed time 1~4 1 1 ○
selection
78
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
0:Wobbulate running invalid
04-18 Wobbulate running ways 1 0 ×
1:Wobbulate running valid
Wobbulate running
04-19 0.10-50.00Hz 0.01Hz 5.00 Hz ×
amplitude value FH
Wobbulate running 51
04-20 0.00-5.00Hz 0.01Hz 1.00 Hz ×
difference frequency△f
Wobbulate running rising
04-21 0.1-6000s 0.1s 20.0 s ○
time T1
Wobbulate running
04-22 0.1-6000s 0.1s 20.0 s ○
fallingtime T2
79
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
0:Over the torque and
does not measure
1:Over the torque
measureduring during
constant speed
running,after torque
measureduring it will
warning
2:Over the torque
measureduring during
constant speed
06-00 Over torque protection ways 1 0 ○
running,after torque
measureduring it will
54
warning
3:Over the torque
measureduring during
constant speed running,
it is fault
4:Over the torque
measureduring during
constant speed running,
it is fault
06-01 Cross the torque protection
50.0~150.0% 0.1% 150.0% ○
current
06-02 Over the torque
0.0~100.0s 0.1s 1.0s ○
protectiontime
0:Not control,full control
1:According running
instruction to control
Cooling fan action
06-03 running 1 1 ○
selection
2:Automatically control
running according to
radiator
Motor lack phase protection 0:No protection
06-04 1 0 ○
selection 1:Lack phase protection
DC voltage waving 0:Not protection
06-05 1 0 ○
protection selection 1:Protection
Energy saving brake 0:No 1:Safty model
06-06 1 0 × 53
selection 2:Generally type
80
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
06-09 V2 ( I2 ) Input over-high
0.0~100.0% (0) 0.1% 0.0% ○
measuring level
06-10 V2(I2)Measuring protection
0.0~10.0s 0.1s 1.0s ○
time
Present trouble
07-00
information
The last trouble
07-01
information
Trouble information two
07-02
times recently
Trouble information
07-03
three times recently
Remove the historical
07-04 0:Invalid 1:Clear 1 0
record of the trouble
0:Invalid
1:Clear accumulating
Clear accumulative
07-05 running time 1 0
running data
2:Clear accumulating kW*h
table
Output frequency at the
07-06 Hz
time of the last trouble
Establish frequency at
07-07 the time of the last Hz
trouble
Export the electric
07-08 current at the time of A
the last trouble
Voltage of bus bar of direct
07-09 current at the time of the V
last trouble
Output the voltage at
07-10 the time of the last V
trouble
81
Function Factory Refern
Name Setting range Min unit Modification
code value ce page
08-00 RS-485 Mailing address 1~31 1 1 ×
0:1200 1:2400
Communication Potter
08-01 2:4800 3:9600 1 2 ×
rate
4:19200 5:38400
59
08-02 Detection time for
0.1~60.0s 0.1s 0.0s ×
transmission interrupt
Transmit the mistake to 0:Alarm
08-03 1 0 ×
deal with 1:Stop
1*: Dispatched from the factory the establishing value and divided into 200V grade and
400V grade . 2: ○Show the parameter that the frequency inverter can be revised while
operating
3: ×Show the parameter that the frequency inverter can't be revised while operating,
revise under stopping the state.
82
Appendix 3: External dimension
45KW and below type(without vector contol)externality:
45KW and below type(without vector 45KW and below type(without vector contol)size:
contol)externality:
Specificatio
W W1 H H1 H2 D D1 D3 d d1
n
G1R5T4
G2R2T4 150 135 260 245 230 150 121 80 5.5
G3R7T4
G5R5T4
214 140 320 305 299 150 97 80 7
G7R5T4
G011T4
G015T4 260 200 394 378 352 205 133 164 7 10
G018T4
G022T4
295 200 495 475 460 253 165 215 10 10
G030T4
G037T4
350 240 594 570 550 280 184 215 10 10
G045T4
83
45KW and below type(with vector contol)size:
Note:
1.Above machine externality and size take the type of G for example.The type of
P and ZS is about equal to the sample. For more accurate understanding of it,please
consultation agent or manufacturer.
2.Our company maybe change the externality and siz in the process of product improve,
above chart maybe is different with actual, please consultation agent or manufacturer.
84
Appendix4:Every type rated output ampere meter
Rated output
Tyep Rated voltage Rated voltage Adapter motor
current
CS3200-G1R5T4 380-415v 1.5kW 3.7A 1.5kW
CS3200-G2R2T4 380-415v 2.2kW 5A 2.2kW
CS3200-G3R7T4 380-415v 3.7kW 8A 3.7kW
CS3200-G5R5T4 380-415v 5.5kW 13A 5.5kW
CS3200-G7R5T4 380-415v 7.5kW 16A 7.5kW
CS3200-G011T4 380-415v 11kW 25A 11kW
CS3200-G015T4 380-415v 15kW 32A 15kW
CS3200-G018T4 380-415v 18.5kW 38A 18.5kW
CS3200-G022T4 380-415v 22kW 45A 22kW
CS3200-G030T4 380-415v 30kW 60A 30kW
CS3200-G037T4 380-415v 37kW 75A 37kW
CS3200-G045T4 380-415v 45kW 90A 45kW
CS3200-G055T4 380-415v 55kW 110A 55kW
CS3200-G075T4 380-415v 75kW 150A 75kW
CS3200-G090T4 380-415v 90kW 170A 90kW
CS3200-G110T4 380-415v 110kW 210A 110kW
CS3200-G132T4 380-415v 132kW 250A 132kW
CS3200-G160T4 380-415v 160kW 300A 160kW
CS3200-G185T4 380-415v 185kW 340A 185kW
CS3200-G200T4 380-415v 200kW 380A 200kW
CS3200-G220T4 380-415v 220kW 415A 220kW
CS3200-G250T4 380-415v 250kW 470A 250kW
CS3200-G280T4 380-415v 280kW 540A 280kW
CS3200-G315T4 380-415v 315kW 600A 315kW
CS3200-G375T4 380-415v 375kW 710A 375kW
CS3200-G400T4 380-415v 400KW 750A 400KW
CS3200-G450T4 380-415v 450KW 850A 450KW
CS3200-G500T4 380-415v 500kW 930A 500kW
CS3200-G630T4 380-415v 630kw 1170A 630kw
Rated output
Tyep Rated voltage Rated voltage Adapter motor
current
CS3200-G1R5T2 200-230v 1.5kW 7A 1.5kW
CS3200-G2R2T2 200-230v 2.2kW 10A 2.2kW
CS3200-G3R7T2 200-230v 3.7kW 16A 3.7kW
CS3200-G5R5T2 200-230v 5.5kW 20A 5.5kW
CS3200-G7R5T2 200-230v 7.5kW 30A 7.5kW
CS3200-G011T2 200-230v 11kW 42A 11kW
CS3200-G015T2 200-230v 15kW 55A 15kW
CS3200-G018T2 200-230v 18.5kW 70A 18.5kW
85
CS3200-G022T2 200-230v 22kW 80A 22kW
CS3200-G030T2 200-230v 30kW 110A 30kW
CS3200-G037T2 200-230v 37kW 130A 37kW
CS3200-G045T2 200-230v 45kW 160A 45kW
Rated output
Tyep Rated voltage Rated voltage Adapter motor
current
CS3200-G022T6 660-690v 22kW 28A 22kW
CS3200-G030T6 660-690v 30kW 35A 30kW
CS3200-G037T6 660-690v 37kW 45A 37kW
CS3200-G045T6 660-690v 45kW 52A 45kW
CS3200-G055T6 660-690v 55kW 63A 55kW
CS3200-G075T6 660-690v 75kW 86A 75kW
CS3200-G090T6 660-690v 90kW 98A 90kW
CS3200-G110T6 660-690v 110kW 121A 110kW
CS3200-G132T6 660-690v 132kW 150A 132kW
CS3200-G160T6 660-690v 160kW 175A 160kW
CS3200-G185T6 660-690v 185kW 198A 185kW
CS3200-G200T6 660-690v 200kW 218A 200kW
CS3200-G220T6 660-690v 220kW 240A 220kW
CS3200-G250T6 660-690v 250kW 270A 250kW
CS3200-G300T6 660-690v 300kW 340A 280-315kW
CS3200-G350T6 660-690v 350kW 390A 350kW
CS3200-G400T6 660-690v 400kW 430A 375-430kW
CS3200-G500T6 660-690v 500kW 540A 500kW
CS3200-G600T6 660-690v 600kW 600A 600kW
86
Appendis5:Safeguard and check regularly
87
Whether there is The naked eye is No fault Capacitor
liquid that is checked. Exceed rated measurem
Measure by the capacitor capacity ent
oozed out
measurement equipment 85% equipmen
train Whether the safe t
√
waves hole is
√
Conden outstanding?
ser Whether have found
the inflation of
the electric
capacity
If there is noise and Hear and check No fault
shake while The naked eye
Relay operating? √ checking.
Whether the
contact is damaged
Whether the No fault Digitmult
insulation of the The naked eye The error i-meter/
resistance is checking.. must Less Simulati
Resista damaged Disconnect one and than 10% of on
√ measure by instrument
nce Whether wire is resistance measurin
damaged between value g
resistance (open displayed apparatu
circuit) s
P Whether every phase Measure ourput terminal For 200V Digitmult
of output voltage between U,V,W ( 400V ), i-mete/Co
r C
o o
t
uneven? Short and open inverter Voltage of rrection
e n
c t
r
There is no mistake in output circuit every phase voltermet
t
Running
i o
√
o l
check circuit after carry can not er
n c
u
out order protection exceed4V(8V
c i
i c
r u
)
c i
u t
i
t
88
Appendix 6 CS3200’ S RS-485 Communication agreement
4、Digit format
11 bit form
5、Error-correcting method:
Adding checksum after information, checksum is equal to the last byte in
the sum of all bytes.
D3D2D1D0:Remove the parameter value of the decimal point, 16 systems of the four
bytes are counted altogether, send the high bit firstly, and then send the bottom
bit . (see " establishing value range " of every parameter of " parameter table
" in the decimal point position. )
89
S:Check the word with school.S is sum of bit in hexadecimal number(A+K+P+ D3+D2+D1+D0)
get last bit 7—bit0)Value。
The definition of K、P、D3D2D1D0 as fellows:
K P D3D2D1D0
K=0:preserve
K=1:preserve
K=2:send running P:1=STOP/RESET,2=FW
No means
instruction D,3=REV
Host machince sent
P:No means
K=3:
Sub-machine reply P: No means
Check running state
1=STOP,2=FWD,3=REV,
4=BRK
P:1=Given frequency
Remove decimal point of setted
while running(two
value
K=4: bit valid dicimal )
Set running parameter P:7=Given PI when
Remove decimal point of setted
running (one bite
value
valid decimal )
K=6: Remove the actual settlement
P: Parameter mark
set function parameter value of the decimal point
The host computer sends :
K=7: Pointless Sub computer reply:
P: Parameter mark
Check function parameter Remove the present actual
value of the decimal point
K=8:Preserve
K P D3D2D1D0
K=F0H:
The host computer
received orders when the
sub computer is unable to
carry out,sub computer
reply K=F0H
K=FCH:
Host computer sent
invalid parametr,
sub-computer reply K=FCH
K=FDH:
Pointless Pointless
Host computer sent
parameter exceed limit,
sub-computer reply ,
K=FDH
K=FEH:
Setted parameter of host
computer was locked,sub
computer reply K=FEH
K=FFH:
Sub-computer reply and
check the mistake
90
*Note 1:If regarded as correct available value from host computer when the host computer
sends all establishment data bags , reply the data received。
*Note 2:From K =F0H reaches K =FFH is it inform one-way message of host computer to
go back from host computer (frequency inverter ), the host computer does not
send this kind of information , if when the host computer picks up and finds
the mistake of byte of check-up , can send again an original information ,
and does not send K =FFH information.
*Note 4:The information value of the trouble is expressed as follows:
00:There is no trouble
25 : The main return circuit is
insufficient in voltage(PUV)
01:Over current(OC)
04:Over voltage(OV)
19:Ground fault(Grd)
03:Over heat of radiator(oh)
28:Over heat of raditor(oht)
07:Over load of motor(oL)
26 : Over load of frequency
convertor(oL2)
29:Over torque check(oL3)
02:Load short circuit(oCP)
08:External fault(EF)
30:The direct current of bus bar
is fluctuated too big(SPi)
23:Output lack phase(SPo)
12:Under voltage protection(LL)
22:EEPROM fault(EEP)
11:Parameter setting fault(ErP)
31:RS-485 Communication trouble
(cE)
14:V2(I2) Signal lost Lo2
15:VF(IF) Signal lost LoF
16:Options VX signal lost(Lo3)
20:Inner circuit trouble(Er5)
24:Motor rated current setted is
too big(Er6)
32 : Front panel communication
trouble (oPr1)
7、Interval between A(bit) and K(bit) <20ms,and interval among other bit<10ms,
The time of dealing after recived a data bag is less than 80ms。
92
Appendix7:Auxiliary instruction of CS3200 series inverter used
Wiring graph of saving power device of intelligent cabinet type injection machine
R S T E U V W
machine
For direct start and stop injection machine the oil pump motor
Circuit breaker electromagnet switch motor protection device oil pump motor
When transforming, fetch the power wire from hot protector of motor to the power
input end of frequency convertor( or intelligence power saving control cabinet), and
connect the wire of oil motor to output end of frequency convertor(or intelligence
power saving control cabinet)..
For injection machine with reduced voltage starting oil punp motor, circuit as
fellows
Circuit breaker Reduce voltage starting device circuit oil pump motor
When transforming, fetch the power wire of front-end of reduce voltage starting
device or after-end of circuit breaker to power input end of frequency conveter(or
93
intelligence power saving control cabinet), contect the output-end of frequency
inverter(or intelligence power saving control cabinet) to main circuit input end of
reduce voltage starting.
User can connect the G1, S1 to control circuit of proportion flow valve seriesly and
connect the G2,S2 to control circuit of proportion pressure valve according to the way
of current circuit. For reducing the interference of change board from outside, user
can add wave filter in the joint of G1,S1,G2,S2. And if there is mechanical arm in the
injection machine, user should add the wave filter near the change board.
The corresponding relation between change board and input end of frequency
conveter.
Proportional flow signal G1/S1 Signal change board V2
(V2 is the treating signal of proportional flow)
Proportional pressure signal G2/S2 Signal change board VF
(VF is the treating signal of proportional pressure)
94
Main parameter regulation
Code No. Function Recommend value
P0100 0:Front panel running 1:Terminal running 1
P0101 1
* P0102 1
* P0103 1(Single circuit) or8( Double circuit)
P0105 accelerating time 1.0 (Sec.) (According to situation)
P0106 Decelerating time 1.0 (Sec.) (According to situation)
P0137 Acceleating and decelerating curve 0 ((According to situation)
P0207 Times of auto-reset from fault 10
P0208 Delay of auto-restart 2.0 (Sec.)
P0317 V2 input signal gain (Regulate according to situation)
P0318 V2 input signal bias (Regulate according to situation)
P0320 V2 Time constant of input wave filtering 0.00 (Sec.)
Regulate according to situation)
* P0321 VF input signal gain (Regulate according to situation)
* P0322 VF input singal bias (Regulate according to situation)
* P0324 VF Time constant of input wave filtering 0.00 (Sec.)
(Regulate according to situation)
P0329 Negative frequency set 0
P0151 Low limiting frequency selection 1
Mark * means the parameter need to change when two signal inputed in the same
time.
P0208Delay of auto-restart
The parameter con guarantee the production continuity when the frequency inverter
jump in case of fault.
P0317,P0318
Gain
80.0
0.0
-10.0 2.0 10.0 VFInput voltage signal
Bias
Analog input seting bias, means the percentage of setting value corresponding
to min alalog quantity input(0V) (03-18)。
Analog input setting bias,means the percentage of setting value corresponding
to max alalog quantity input(10V)(03-17)。
When analog signal used in frequency setting, 100% correspond to Max.input
frequency.
For example : When use outside 0~10V output signal V2,the range of frequency
regulating is 0.00Hz-50.00Hz,it can set the largest frequency(01-10)=50.0Hz,
the upper limit frequency(01-07)=50.0Hz,
Simulation inputs the type(03-19)=0,
Simulation inputting and setovering(03-18)=0.0%, The simulation input signal
gaining(03-17)=100.0%。
For example : When use outside 2~8V input signal,the range of frequency
regulating is 0.00Hz-50.00Hz,it can set the largest frequency(01-10)=50.0Hz,
the upper limit frequency(01-07)=50.0Hz,
Simulation inputs the type(03-19)=0,
Simulation inputting and setovering(03-18)= -33.3%,The simulation input signal
gaining(03-17)=113.3%。
Control connector VF-GND(0~10V)and IF-GND(0~20mA) are the same。
P0319,P0323
P0320,P0324
Simulation inputs and strains the wave time constant,the set range :0.01~10.00s
As to be strained waves to deal with by the simulation voltage or electric current
signal that V2-GND and I2-GND inputting, in order to prevent frequently jumping
the influence on the system of interfering signal changed. But strain wave time
too long , will influence the sensitivity regulated .
Can choose :0.00 – 0.20 seconds.
96
P0329
P0151
Set 0: When frequency establishes the signal and is less than the establishing
value of lower limit frequency (01-08 ), the frequency inverter still outputs
lower limit frequency, the electrical machinery operates in accordance with lower
limit frequency.
Set 1: When frequency establishes the signal and is less than the establishing
value of lower limit frequency (01-08 ), the frequency inverter stops exporting,
the electrical machinery stops operating.
When the moulding plastics machine is used, when the flow signal is minimum ,
the electrical machinery still operates at a low speed, can't stop , at this moment ,
can establish the frequency value of lower limit (01-08 ) and choose (01-51)=1,
then the electrical machinery can stop rotating .
9 Options
This series of products can be installed the ancillary equipment additional by the user
because of the service condition different from ones that require
9.1 AC reactor:
1、AC reactor can suppress frequency inverter input high times of in harmony wave of
electric current, obviously improve the power factor of the frequency inverter. Propose
using and exchanging the reactor in case of the following.
2、More than 10:1 that the frequency inverter is in a ratio of the capacity of power
of its place being used and capacity of frequency inverter.
3、Connect with silicon controlled rectifier load or the factor of power with control
and compensate the device on the same power.
4、The uneven degree of voltage of the three-phase power is relatively large.(≥3%)。
97
AC reactor of the daily specification
98
DC reactor
Three-phase and three line radio noise wave filter in commonly used
Wave filter main parameter
Volta Motor Voltg Motor power
Wave filter Common mode input Differential mode
ge power e
model loss dB input loss dB
(V) (kW) (V) (kW)
0.1MHz 1MHz 30MHz 0.1MHz 1MHz 30MHz
Occasion of using of expecting much and demanding to accord with CE , UL , CSA standard
in preventing radio interference, or there are equipment of anti-interference with
insufficient ability ,etc. under the situation around the frequency inverter, should
use this wave filter . Should notice wiring is it shorten to try one's best when the
installation, wave filter should try one's best close to the frequency inverter also.
99
9.4. Remote operation board
Design exquisite operation plates easy to use on the panel of this serial frequency
inverters. If user need to guide operation board to other place can buy additional
line only need to propose while ordering. Operate record with adopt serial
communication way by host computer , so user can operate record move to from place
within the host computer 10m, if need larger distance , can buy remote operation board
from the supplier or our company and operate one .
100
9.6 Leakage protector
Because the static capacity to ground exsited in the output and input leading wire
and inside frequency inverter and motor and the and because the inverter is low noise
type and load wave frequency is high, so the leakage current is much higher expecially
to large capacity type and even more will lead to misoperation in protection circuit.
If you meet this kind of problem, you can low the load wave frequency, short leading
wire, and install leakage protector. And when using leakage protector, should note:
z Leakage protector should install by the input of frequency protector and it is
better to install after MCCB( without fuse circuit breaker).
z The operating current of leakage protector should be 10 fold larger than the
leakage current( total of cuicuit,radio noise filter,motor etc.) of the circuit without
using conveter.
101