Synchronous-Motor
Synchronous-Motor
Synchronous Motor
Page 2 of 14
11-Synchronous Motor
Before considering as to what goes on inside a synchronous motor, it is worthwhile to refer briefly
to the DC motors. We have seen (Art. 27.3) that when a DC motor is running on a supply of, say, V volts
then, on rotating, a back emf Eb is set up in its armature conductors. The resultant voltage across the
armature is (V-Eb) and it causes an armature current Ia=(V-Eb)/Ra to flow where Ra is armature resistance.
The value of Eb depends, among other factors, on the speed of the rotating armature. The mechanical
power developed in armature depends on EbIa (Eb and Ia being in opposition to each other).
Similarly in a synchronous machine, a back emf Eb is set up in the armature (stator) by the rotor
flux which opposes the applied voltage V. This back emf depends on rotor excitation only (and not on
speed as in DC motors). The net voltage in armature (stator) is the vector difference (not arithmetical, as
in DC motors) of V and Eb. Armature current is obtained by dividing this vector difference of voltages by
armature impedance (not resistance as in DC machines).
Fig. 36.6 shows the condition when the motor (properly synchronized to the supply) is running on
no-load and has no losses and is having fixed excitation which makes Eb=V. It is seen that vector
difference of Eb and V is zero and so is the armature current. Motor intake is zero, as there is neither load
nor losses to be met by it. In other words, the motor just floats.
If motor is on no-load, but it has losses, then the vector for Eb falls back (vectors are rotating anti-
clockwise) by a certain angle α (Fig. 36.7), so that a resultant voltage ER and hence current Ia is brought
into existence, which supplies losses.
If, now, the motor is loaded, then its rotor will further fall back in phase by a greater value of
angle α-called the load angle or coupling angle (corresponding to the twist in the shaft of the pulleys).
The resultant voltage ER is increased and motor draws an increased armature current (Fig. 36.8), though
at a slightly decreased power factor.
E bV
∴ Pin = 3 sin α
XS
- for three phase
Since Stator Cu losses
have been neglected, Pin also
represents the gross mechanical
power (Pm) developed by the
motor.
3E V
∴ Pm = b sin α
XS
The gross torque developed by
the motor is Tg=9.55Pm/NS N-m
-NS in rpm.
The gross torque developed by the motor is Tg=9.55Pm/NS N-m -NS in rpm.
P 9.55 × 3E bV E V sin α
∴ Tg = 9.55 m = sin α = 28.65 b N-m.
NS NS X S NS X S
Example 36.1 A 75 kW, 3-phase, Y-connected, 50 Hz, 440 V cylindrical rotor synchronous motor
operates at rated condition with 0.8 power factor leading. The motor efficiency excluding field and stator
losses, is 95% and XS=2.5 ohm. Calculate: (i) mechanical power developed, (ii) armature current, (iii)
back emf, (iv) power angle, and (v) maximum or pull-out torque of the motor.
Solution: NS= 120×50/4= 1500 rpm = 25 rps.
(i) Pin = Pm = Pout / η = 75 × 103 / 0.95 = 78,950 W
(ii) Since power input is know, we know that
∴ 3V L I a cos φ = 3 × 440 × I a × 0.8 = 78,950
78,950
Ia = = 129 A
3 × 440 × 0.8
(iii) Applied voltage/phase= 3 × 440 = 254 V. Let V = 254∠0°
as shown in Fig. 36.11.
Now, V = E b + jIX S and φ = cos −1 (0.8) = 36.9° or
E b = V − jIX S = 254∠0° − 129∠36.9° × 2.5∠90° = 516∠ − 30°
(iv) ∴α = −30°
(v) Maximum or Full-out torque occurs when α = 90°
3E V 3 × 254 × 516
Maximum Pm = b sin α = sin 90° = 157,276.8
XS 2.5
W
∴Pull-out torque=9.55×157,276.8/1500=1001.328 N-m
On the other hand, if DC field excitation is such that Eb>V, then motor is said to be over-excited
and draws a leading current as shown in Fig. 36.13(a). There will be some value of excitation for which
Page 5 of 14
11-Synchronous Motor
armature current will be in phase with V, so that power factor will become unity, as shown in Fig.
36.13(b).
The value of α and back emf Eb can be found with the help of vector diagrams for various power
factors, shown in Fig. 36.14.
(i) Lagging Power Factor: As seen from Fig. 36.14(a)
AC 2 = AB 2 + BC 2 = [V − E R cos(θ − φ)] 2 + [ E R sin(θ − φ)] 2
E b = AC = [V − I a Z S cos(θ − φ)] 2 + [ I a Z S sin(θ − φ)] 2
⎛ BC ⎞ −1 ⎛ I a Z S sin(θ − φ) ⎞
Load angle α = tan −1 ⎜ ⎟ = tan ⎜⎜ ⎟⎟
⎝ AB ⎠ ⎝ V − I a Z S cos(θ − φ) ⎠
Fig. 36.14
Page 6 of 14
11-Synchronous Motor
(ii) Under-excitation
As shown in Fig. 36.17, with a small
load and hence, small torque angle α1, Ia1 lags
behind V by a large phase angle φ1 which
means poor power factor. Unlike normal
excitation, a much larger armature current
must flow for developing the same power
because of poor power factor. That is why Ia1
of Fig. 36.17 is larger than Ia1 of Fig. 36.15(a).
As load increases, ER1 increases to ER2,
consequently Ia1 increases to Ia2 and power
factor angle decreases from φ1 to φ2. Due to
increase both in Ia and power factor, power
generated by the armature increases to meet
the increased load. As seen, in this case,
change in power factor is more than the
change in Ia.
(iii) Over-excitation
When running on light load, α1
is small, but Ia1 is comparatively
larger and leads V by a larger angle
φ1. Like the under excited motor, as
motor load is applied, the power
factor improves and approaches unity.
The armature current also increases
thereby producing the necessary
armature power to meet the increased
load (Fig. 36.18). However, it should
be noted that in this case, power
factor angle φ decreases (or power
factor increases) at a faster rate than
the armature current thereby
producing the necessary increased
power to meet the increased load
applied to the motor.
The main points regarding the above three cases can be summarized as under:
1. As load on the motor increases, Ia increases regardless of excitation.
Page 7 of 14
11-Synchronous Motor
2. For under- and over-excited motors, power factor tends to approach unity with increase in
load.
3. Both with under- and over-excitation, change in power factor is greater than Ia with increase in
load.
4. With normal excitation, when load is increased change in Ia is greater than in power factor
which tends to become increasingly lagging.
Page 8 of 14
11-Synchronous Motor
Page 9 of 14
11-Synchronous Motor
Page 10 of 14
11-Synchronous Motor
Hence, they now supply only the active component of the load current. When used in this ways, a
synchronous motor is called a synchronous capacitor, because it draws, like a capacitor, leading current
from the line. Most synchronous capacitors are rated between 20 MVAR and 200 MVAR and many are
hydrogen-cooled.
Example 36.31 A synchronous motor absorbing 60 kW is connected in parallel with a factory load of 240
kW having a lagging power factor of 0.8. If the combined load has a power factor of 0.9, what is the value
of the leading kVAR supplied by the motor and what power factor is it working?
Solution: Load connections and phase relationships are shown in Fig. 36.53.
Total load= 240+60 = 300 kW; combined power factor =0.9 (lag);
φ=25,8o; tanφ=0.4834; combined kVAR=300×0.4834=145 (lag)
Factory Load:
cosφL=0.8; φL=36.9o; tanφL=0.75; load kVAR=240×0.75=180 (lag)
[or load kVA=240/0.8=300, kVVAR=300×sinφφL=300×0.6=180]
∴leading kVAR supplied by synchronous motor =180-145=35
For Synchronous Motor:
kW= 60; leading kVAR=35; tanφm=35/60; φm=30.3o; cos30.3o=0.863
∴ Motor power factor=0.863 (leading).
Incidentally, motor kVA= 60 2 + 35 2 = 69.5
Page 11 of 14
11-Synchronous Motor
2. The synchronous motor can be operated over a wide range of power factors, both lagging and
leading, but induction motor always runs with a lagging power factor which may become very low
at light loads.
3. A synchronous motors is inherently not self-starting but induction motor is self-starting.
4. The changes in applied voltage do not affect synchronous motor torque as much as they affect the
induction motor torque.
5. The breakdown torque of a synchronous motor varies approximately as the first power of applied
voltage whereas that of an induction motor depends on the square of this voltage.
6. A DC excitation is required be synchronous motor but not by induction motor.
7. Synchronous motor are usually more costly and complicated than induction motors, but they are
particularly attractive for low speed drives (below 300 rpm) because their power factor can always
be adjusted to 1.0 and their efficiency is high. However, induction motors are excellent for speeds
over 600 rpm.
8. Synchronous motor can be run at ultra-low speeds by using high power electronics converters
which generated very low frequencies. Such motors of 10 MW range are used fro driving crusher,
rotary kilns and variable speed ball mills etc.
Page 12 of 14
11-Synchronous Motor
Reference
[1] B.L.Theraja, A.K.Theraja,: A textbook of Electrical Technology, Volume- II, S. Chand & company
Ltd.
[2] Jack Rosenblat and M. Harold Friedman, Direct and Alternating Current Machinery, Second and
latest Edition, CBS Publishers and Distributors.
[3] Irving L. Kosow, Electrical Machinery and Transformers, Second Edition, Prentice –Hall India Pvt.
Limited.
Kiln: A large oven for baking clay and bricks, drying wood and grain etc.
Page 13 of 14
11-Synchronous Motor
Page 14 of 14