The BKP Series Panel User Guide provides detailed instructions on the operation and settings of the control panel, including features such as voltage and current settings, automatic testing, and fault recording. It outlines the menu navigation, settings adjustments, and safety protections against dry operation and current fluctuations. Additionally, it includes connection diagrams for various pump configurations and technical specifications.

Uploaded by

Mohamed Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views18 pages

BKP USER GUIDE

The BKP Series Panel User Guide provides detailed instructions on the operation and settings of the control panel, including features such as voltage and current settings, automatic testing, and fault recording. It outlines the menu navigation, settings adjustments, and safety protections against dry operation and current fluctuations. Additionally, it includes connection diagrams for various pump configurations and technical specifications.

Uploaded by

Mohamed Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

BKP SERIES PANEL

USER GUIDE

MADE IN
TÜRKİYE
ATTENTION PLEASE!

1
2
3
4
5
16 B t m crocontroller des gned.
48Mhz runn ng frequency.
2X16 character LCD (L qu d Crystal D splay).
Auto test feature.
Auto test seleno d valve output.
3-phase voltage read ng and d splay on LCD.
Voltage protect on, poss b l ty to enter the lower and upper sett ngs.
Pump current read ng and d splay on LCD.
Current protect on, poss b l ty to enter the lower and upper sett ngs.
Pump c rcu t,fault and ready to see the status scrren.
Recogn t on mode to calculate the pump current.
Poss b l ty to l m t te engagement number of the pumps 1 hour.
Ab l ty to determ ne the reset t me at automat c resett ng.
Ab l ty to reset automat cally n error cases and to set the reset number.
Automat c-manuel select on.
Manuel operat on when press ng the test button at manuel.
Protect on aga ns dry operat on w thout floater ans SSR control.
Protect on aga ns dry operat on w thout moment control.
Screen to see all the error cond t ons.
Pressure transm tter nput and use.
Pressure transm tter to mon tor the measured value LCD.
To adjust the set pressure value.
Track ng the operat on t me of each pump.
The actual run t me depends on te co-ag ng.
All pumps belong ng to the PTC protect on.
Waste water to be used as panel (menu opt on).
Waste water panel water leak term nal.
Password protect on aga nst unauthor zed nterference.
Fault record ng 20 takes memory.

6
S1 S2 S3 9
A1 A2 A3 10
BKP-3 P-1 P-2 P-3
Control Panel

2 Auto-1 Auto-2 Auto-3


6
AT AT AT
4 MN MN MN 7

5 TEST TEST TEST 8


Pump-1 Pump-2 Pump-3
3

1 : 2x16 LCD screen.


2 : Up arrow key to move up n the menu ont ma n screen and prov des pag ng
3 : Down arrow key to move down nthe menu prov des.
4 : Set key to enter the menu and used the changes made n the menu.
5 : ESC key to to return to the menu and the menu before a transacton s allowed r se.
6 : Automat c run led.
7 : Auto - Manuel select button.
8 : Manuel Run button.
9 : L ghts when pressure sw tch s start.
10: Error l hgt.

7
SETTINGS MENU

press the button to enter the menu.

Voltage Sett ngs


H gh Volt=250V

The Voltage Sett ngs menu appears. When we press the set button once, the above screen appears.
The upper voltage text starts to flash. In th s case, the value can be changed w th the help of the arrow
keys. Press the Set button and save the H gh Voltage set, and the follow ng screen appears automat cally.

Voltage Sett ngs


Low Voltaj=180V

When we press the Lower Voltage Sett ng set button, the Lower Voltage sett ng starts to flash, n th s case
the arrow keysThe value can be changed w th the help of Press the SET key, save the lower voltage set
and return to the menu page.

Current Sett ngs


P.1 H gh =15.0A

In order to change the current sett ngs, press the set button and the current sett ngs appear. Press the
set button. P.1 saves the upper current sett ng by sett ng, and the follow ng screen appears automat cally.

Current Sett ngs


P.1 Low =01.0A

When the Sub-Stream sett ng set button s pressed, the P.1 subt tle starts to flash. In th s case, the value
can be changed w th the help of the arrow keys. Press the set key, save the P.1 Sub stream set and
return to the menu page.

8
SETTINGS MENU

H story Fault
01= H gh Current

From the h stor cal fault nformat on sett ngs menu, w th the help of the set button, the past fault nformat on
s h ghl ghted, and by press ng the down arrow button, the most recent fault of the dev ce always moves to t
he first place. A total of 20 records are stored n memory.

Language Select
Engl sh

Language select on s pressed, set button s pressed, Language Select on s h ghl ghted w th the help of the
arrow button n the sett ngs menu, and the menu s entered by press ng the set button. The des red language
s selected w th the help of the arrow keys and automat cally saved by press ng the set key.

Operat ng T me
P1=0h / 0S
P2=0h / 0S
Press the Work ng Hours set button, and n the sett ngs menu, use the arrow key to scroll to the Work ng
T mes. By press ng the set button, the menu s entered. The operat ng t me of the pumps s d splayed n
hours.

Enter Password

A password s requ red by the system to enter the general sett ngs. When the set button s pressed, a 4-d g t
password s requested. If the password s ncorrect, the system automat cally d scards t from the menu.
When the password s entered, the screen on the next page appears.

9
SETTINGS MENU

General Sett ngs


Voltage On = 05

Press the Set button n the General Sett ngs menu, the text Voltage On starts to flash and the value next
to t can be changed w th the help of the arrow keys, after the change s completed, by press ng the set
button.value s memor zed. Arrow keys are used to find the parameter we want to change and when the
parameter s hovered, the set key s pressed and the text starts to flash, n th s case the value s changed.

Voltage On = It s the voltage-on t me sett ng. Wa t ng t me for automat c reset when the voltage values
measured when the system s n fault state due to voltage error aga n w th n the des red l m ts.

Voltage off = It s the voltage error tr pp ng t me sett ng. When the measured voltage values go out of the
set values, t s the wa t ng t me to turn off. It s necessary n order not to take the pump off frequently n
case of nstantaneous fluctuat ons.

SSR On = It s the l qu d level (SSR) reset t me sett ng. It s the wa t ng t me sett ng for automat c reset
when the water comes back when the system s n a malfunct on state due to dehydrat on.

SSR Off = It s the l qu d level error tr pp ng t me sett ng. When the water n the tank or well runs out, t s
the t me to wa t for the c rcu t to go out.

Demerage = Inrush current t me sett ng. Dur ng the per od set here, the currents drawn from the moment
the pump starts up for the first t me cannot be compared w th the set values.

Current Delay = Current fault tr p t me sett ng. When the lower or upper current goes out of the set value,
the t me sett ng for stopp ng the motor s set n seconds.

Start Delay = When the s gnal comes from the pressure sw tch, the pumps are act vated as late as the
set t me for the t me set here.

Stop Delay = When the s gnal from the pressure sw tch s lost, t turns off the pumps w th n the set t me.

Reset T me = Reset t me sett ng allows us to set how long t wa ts for the system to be act vated aga n
when t fa ls due to current error. The sett ng s n seconds.

Reset-2 = It s the reset number sett ng.

Salt = Ab l ty to l m t the number of pumps on and off n 1 hour.

Pump Change = It s the changeover t me sett ng for pumps operat ng n c rculat on mode.

10
SETTINGS MENU
Auto Test Sett ngs
Test = Act ve

The automat c test sett ng s pressed, the set button s pressed, the test factory sett ng s pass ve, when
we press the set button, the Test text starts to flash. appears as a clock. The run t me sett ng allows us to
set how long (seconds) the pump w ll run. Pump operat on act ve or pass ve opt on s selected by press ng
the arrow key and the set key s pressed, t automat cally saves.

Transm tter Set


There s Sensor

Transm tter Sett ng s adjusted w th the help of arrow keys wh le the text "Sensor ava lable or No sensor"
s flash ng, and t s stored by press ng the Set key. If the sensor s selected, the system now works w th
the transm tter and does not read the pressure sw tch nput.

Max mum = Pressure transm tter max mum (label) value, enter 16 bar for 16 bar transm tter.

Set Value = Pump stop set pressure value.

Hys Value = Pressure hysteres s adjustment. For example, f our set pressure s 8.0 bar hysteres s 1.0,
then 1 pump works at 7.0 bar, 2 pumps work at 6.0 bar, and 3 pumps at 5.0 bar.

Operat on Mode Select


Hydrophore

Operat on Mode Select on, operat on select on s made w th the help of arrow keys accord ng to the pump
used. Press the set button and t w ll save automat cally.

Hydrophore = Standart h drofor motorlarında bu mod seç lmel d r.

Hydrophore + Ptc = If there s PTC protect on n booster pumps, th s mode should be selected.
Otherw se, PTC protect on w ll not do..

P + Joker = It s the cho ce of 1 ma n and 1 w ldcard n fire systems.

Waste Water = Th s mode should be selected for wastewater pumps. When th s mode s selected, water
leakage and Ptc nputs are act ve.

Waste Water Stop Flt = In the select on of waste water w th stop floater, water leakage and Ptc nputs
become act ve and the system stops accord ng to the stop floater.

11
Floater / SSR Sec m
Floater

Floater / SSR select on s the float or SSR electrode protect on select on sett ng of the dev ce. Select on
s made w th the help of the arrow key and saved by press ng the set key.

CONNECTION DIAGRAM

BKP-1 CONTROL PANEL

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
SELENOID
COM

ERR

MAIN L1
380V AC L2
50-60Hz. L3
N

FLOATER

U V W
X Y Z

PRESSURE
SWITCH

F gure-1: 1 Pump Booster Connect on D agram

12
CONNECTION DIAGRAM
BKP-2 CONTROL PANEL

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

SELENOID
COM

ERR
MAIN L1
380V AC L2
50-60Hz. L3
N

FLOATER

U V W U V W
X Y Z X Y Z

PRESSURE
SWITCH

F gure-2: 2 Pump Booster Connect on D agram

BKP-3 CONTROL PANEL

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
SELENOID
COM

ERR

MAIN L1
380V AC L2
50-60Hz. L3
N

FLOATER

U V W U V W U V W
X Y Z X Y Z X Y Z

PRESSURE
SWITCH

F gure-3: 3 Pump Booster Connect on D agram

13
14
TECHNICAL DETAILS

15
16
BKP SERIES PANEL
USER GUIDE