0% found this document useful (0 votes)
6 views

EPC-Data-Sheet

The Eurotherm EPC3000 is a range of programmable single loop process and temperature controllers designed for precision control in various industrial applications, featuring enhanced cybersecurity and user-friendly configuration. It offers fast and accurate process inputs, exceptional thermal stability, and a highly visible display, making it suitable for demanding environments. The controllers support multiple communication protocols and are certified for robust cybersecurity, ensuring efficient and secure operations in production settings.

Uploaded by

Samuel Bhukya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

EPC-Data-Sheet

The Eurotherm EPC3000 is a range of programmable single loop process and temperature controllers designed for precision control in various industrial applications, featuring enhanced cybersecurity and user-friendly configuration. It offers fast and accurate process inputs, exceptional thermal stability, and a highly visible display, making it suitable for demanding environments. The controllers support multiple communication protocols and are certified for robust cybersecurity, ensuring efficient and secure operations in production settings.

Uploaded by

Samuel Bhukya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Helping deliver an efficient and secure process

Eurotherm EPC3000 programmable controllers


Maintain the high standards of production
quality and ease your cybersecurity worries

Product at a glance • Precision furnace control


The EPC3000 range of programmable single loop process and temperature • Atmosphere control
controllers maximizes efficiency and repeatability and is certified for • Industrial ovens
cybersecurity communications robustness.
• Crystal growing
The controllers combine industry leading control and measurement performance
with simplicity of use while remaining highly flexible. • Composite materials processing
A simple “Quick Start” configuration code, enables fast commissioning “Out • Heat exchangers
of the Box” using just the instrument HMI. For applications requiring additional
• Automotive paint drying
processing, user function block wiring provides a full range of math, logic,
totalizer and specialized functions. • Baking ovens
A highly visible three-color display with natural language status and alarm
indications is easy and clear for operators to use. • Precision single loop controller with
EPC3000 is highly durable, with a battery-free design and extended service life. cybersecurity function
Accuracy and repeatability • Precise (0.1%) universal inputs with 50ms
Process inputs are fast and accurate, with exceptional thermal stability, aiding sample rate
precise and consistent control over long periods without calibration drift. • Thermocouples, resistance thermometer, mA,
Recalibration and user calibration correction functions are available to further mV, volts, zirconia
improve accuracy.
• Exceptional thermal stability
The industry leading Eurotherm PID algorithm delivers fast reacting and
repeatable control and has been enhanced for EPC3000 to further reduce • Fast PID response with minimal overshoot and
overshoot. Rapid rise to operating temperature and low oscillation aids high oscillation
process throughput at low scrap rates. Different PID settings may be applied in • Multi-programmer function with up to 10
different process operating regions for optimum performance. programs of 24 steps
Connectivity and cybersecurity • Direct Ethernet RJ45 Connection certified to
The EPC3000 Ethernet enabled controller range is Eurotherm’s first to be Achilles® CRT Level 1
designed and certified to meet the stringent cybersecurity requirements
• High visibility customizable display
of Achilles® Communications Robustness Testing Level 1. Ethernet
communications are supported via a standard RJ45 connector, providing fast • Quick code setup with application templates
access to process and diagnostic information as well as connectivity to external • User function block wiring including math, logic
PLC or plant SCADA.
and totalizer
Modbus RTU serial communications is also supported.
• Extensive range of international approvals
A free PC based backup and configuration tool uses a USB connection, powering
the instrument from the USB interface for convenient desktop configuration.
EPC3000 Data Sheet eurotherm.com/epc3000 2

Specification
General
Controller function Single loop panel mount PID controller range with autotune, on/off, valve positioning (no slidewire required).
Zirconia probe atmosphere control. Single loop profile/program up to 10 profiles of 24 segments. Mains and
24VDC options.
Measurement inputs 1 or 2 inputs. Accuracy ±0.1% reading (refer to detailed specification).
PID control 2 PID sets are available (Separate proportional band for heat and cool). Enhanced Autotuning control with
cutback to minimize overshoot and oscillation. Fast reacting precision control to setpoint changes or after process
disturbances. Enhanced valve positioning (unbounded) algorithm. Gain scheduling allows PID selection for a wide
range of operating situations, including deviation from setpoint, absolute temperature, output level and others. AC
supply voltage monitoring for feedforward. PV and SP feedforward functions.
Program/profiler
Up to 10 profiles of 24 steps. Options for 1x8, 1x24 and 10x24.
Holdback (“guaranteed soak”), event outputs, time to target, ramp rate, dwell, step and call segment types.
Communications compatible with Eurotherm 2400 programmer.
Additional timer functions available.

User function block wiring Optional totalizer, math, logic and multiplexing, BCD conversion, counter/timer and many other special function
blocks available including zirconia and switchover.
Additional functions Digital and analog retransmission functions. CT Input - Monitor partial load failure, load short and open circuit;
Dual input functions including switchover, redundant sensor, average, min, max, Zirconia. 6 Freely configurable
alarms with manual, automatic, non-latching and event types plus alarm delay function and blocking. Alarms
may be inhibited in standby. 5 Recipes with 40 freely selectable parameters switchable from front panel or digital
input. Scrolling parameter help and user messages displayed on event. USB backup lead and free configuration
software.
Backup and configuration tools Free Eurotherm iTools software for backup and configuration. USB Backup lead available for convenient desktop
configuration and back up; powers the instrument with or without a sleeve. iTools also connects using Ethernet and
serial Modbus RTU.
Ethernet Certified to Achilles® communications robustness testing level 1.

3008/3004 Isolation 3016 Isolation


300V ac 300V ac
300V ac 300V ac
Double Double
Double Double
Serial/Ethernet
Serial/Ethernet Comms or
Comms Remote Setpoint
Rectification Power Rectification
Power
Power Power
All logic inputs and
Supply Supply
outputs Circuits
Circuits All logic inputs and
outputs
300V ac
Double µP & µP &
system 300V ac
system
Secondary PV circuits Primary PV Double circuits
input Input
300V ac Relays & Triacs Micro mounted
Double PV Input

Relays & Triacs CT Measurement 300V ac


Double
300V ac 300V ac
Double Double 0-20mA/0-10V
CT Measurement
Isolated Modules
0-20mA/0-10V
Transmitter PSU
Isolated Modules
EPC3000 Data Sheet eurotherm.com/epc3000 3

Environmental specifications, standards approvals and certifications


Operating temperature 0 to 55°C
Storage temperature -20 to +70°C
Operating/storage humidity 5% to 90% RH non condensing
Atmosphere Non-corrosive, non-explosive
Altitude <2000 Meters
Vibration and Shock EN61131-2 (5 to 11.9Hz @ 7mm peak to peak displacement, 11.9-150Hz @ 2g, 0.5 octave min.)
EN60068-2-6 Test FC, Vibration. EN60068-2-27 Test Ea and guidance, Shock.
Front of panel sealing protection Standard bezel: EN60529 IP65, UL50E Type 12 (equivalent to NEMA12)
Washdown bezel: EN60529 IP66, UL50E Type 4X (indoor use) (equivalent to NEMA4X)
Rear of panel protection EN60529 IP10
Flammability of plastic materials UL746C-V0
Electromagnetic Emissions HV PSU units to EN61326-1 Class B – Light industrial
compatibility (EMC) LV PSU units to EN61326-1 Class A – Heavy industrial
Immunity BS EN61326-1 Industrial
Approvals and Europe CE (EN61326), RoHS (EN50581), REACH, WEEE, EN14597 pending
certification USA, Canada UL, cUL
Russia EAC (CUTR) pending
China RoHS, CCC: Exempt (Product not listed in catalogue of products subject to China Compulsory
Certification)
Global
When subject to the necessary field calibration, EPC3000 series controllers manufactured by Eurotherm
are suitable for use in Nadcap applications in all furnace classes, as defined in AMS2750E clause 3.3.1.

Meets accuracy requirements of CQI-9


Achilles® Level 1 CRT Cyber Security Assessment
Schneider Electric Green Premium

Electrical safety EN61010-1 (installation category II, pollution degree 2)

Mechanical Details
3008 3004
48mm (1.89”)
+ 1mm (0.04”) 96mm (3.78”) 101mm (3.97”)
+ 1mm (0.05”) 3016
90mm (3.54”)

48mm (1.89”) 101mm (3.97”)


+ 1mm (0.04”)
+ 2mm (0.08”)

90mm (3.54”)
+ 1mm (0.04”)

96mm (3.78”)
96mm (3.78”)

+ 1mm (0.04”)
48mm (1.89”)

Panel cut out and weight


3008 3004 3016
Panel dimension 92mm (-0.0 +0.8) x 45mm (-0.0 +0.6) 92mm (-0.0 +0.8) x 92mm (-0.0 +0.8) 45mm (-0.0 +0.6) x 45mm (-0.0 +0.6)
3.62” (-0.0 +0.03”) x 1.77” (-0.0 +0.02) 3.62” (-0.0 +0.03”) x 3.62” (-0.0 +0.03) 1.77” (-0.0 +0.02”) x 1.77” (-0.0 +0.02)
Weight 350g 420g 250g
12.34oz 14.81oz 8.81oz
EPC3000 Data Sheet eurotherm.com/epc3000 4

Inputs and outputs


I/O and communication types
I/O and comms 3016 3008/3004
Analog inputs 1 universal input 20Hz 1 or 2 (option) universal input 20Hz
1 auxilliary input 4-20mA, 0-10V 4Hz (option)
Optional I/O modules: Up to 2, freely selectable: Up to 3, freely selectable:
Form A relay output
Logic I/O
DC analog output
TRIAC output
Form C relay output 1 1
Contact closure logic input 1 (option) 2
Logic I/O (open collector) – 4 or 8 (option)
Current transformer 1 (option) 1
24V transmitter PSU – 1
1 of the following options:
Communications 2 of the following options: RS485 Modbus (or EI Bisynch)
RS485, RS422, RS232, Modbus RTU slave (EI and Ethernet Modbus TCP (option).
Bisynch available with serial comms), Ethernet
TCP.

I/O specifications
Universal process inputs
Input types Thermocouples, PT100/PT1000 RTD, 4-20mA, 0-20mA, 10V, 2V, 0.8V, 80mV, 40mV, zirconia (oxygen probe),
pyrometers. For other input types, contact your Eurotherm supplier for advice.
Accuracy ±0.1% reading. When subject to the necessary field calibration, 3000 series controllers manufactured
by Eurotherm are suitable for use in Nadcap applications in all furnace classes as defined in AMS2750E clause
3.3.1.
Sample time Process Inputs 50ms (20Hz). Thermocouple 62.5ms (16Hz). RTD. Automatic cycle time selection 100ms (10Hz).
Mains rejection Series mode rejection 48-62Hz >80dB. Common mode rejection >150dB
Sensor break AC sensor break. Break detected within 3 seconds worst case.
Input filtering OFF to 60 seconds filter time constant.
User calibration User 2 point input adjust (offset/gradient), transducer scaling.
Thermocouple K, J, N, R, S, B, L, T as standard, plus 2 downloadable custom curves
Linearization accuracy
CJ calibration accuracy: <±1.0ºC at 25ºC ambient
CJ ambient rejection ratio: better than 40:1 from 25ºC ambient
CJ automatic (internal), variable (external fixed 0, 45, 50ºC)
CJ external (measured) for 3004/3008 only
EPC3000 Data Sheet eurotherm.com/epc3000 5

Inputs and outputs

RTD (PT100/
Input Ranges 40mV 80mV 0.8V 2V 10V mA
PT1000)

Range
Min -40mV -80mV -800mV -2V -10V 0Ω (-200ºC) -32mA

400Ω /4000Ω
Max +40mV +80mV +800mV +2V +10V +32mA
(850ºC)
Thermal stability from 25ºC ±0.4μV/ºC ±0.4μV/ºC ±0.4μV/ºC ±0.4μV/ºC ±0.8μV/ºC ±0.01ºC/ºC ±0.16μA/ºC
ambient ±13ppm/ºC ±13ppm/ºC ±13ppm/ºC ±13ppm/ºC ±70ppm/ºC ±25ppm/ºC ±113ppm/ºC
Resolution 1.0μV unfiltered 1.6μV 16μV 41μV 250μV 0.05 ºC 0.6μA
Electrical noise (peak to peak
0.8μV 3.2μV 32μV 82μV 250μV 0.05ºC 1.3μA
with 1.6s input filter)
Linearity accuracy (best fit
straight line) 0.003% 0.003% 0.003% 0.003% 0.007% 0.033% 0.003%

Calibration accuracy @25ºC ±4.6μV ±7.5μV ±75μV ±420μV ±1.5mV ±0.31ºC ±3μA
ambient ±0.053% ±0.052% ±0.052% ±0.044% ±0.063% ±0.023% ±1.052%
2.49Ω (1%
Input resistance 100MΩ 100MΩ 100MΩ 100MΩ 57kΩ –
Shunt)
Bulb current -– -– -– -– -– 190μA/ 180μA -–

Remote setpoint auxilliary analog input (3016 Only)


Range 0 to 10V and 4 to 20mA. Max ranges -1V to 11V and 3.36mA to 20.96mA
Accuracy <±0.25% of reading ± 1LSD, 14 Bits
Sample rate 4Hz (250ms)
Functions Remote setpoint input
Auxiliary analog input
Thermal stability 100ppm (typical) < 150ppm (worst case)
Mains rejection Common Mode 48-62Hz > 120db, Series Mode > 90db
Input impedance Voltage 223kΩ. Current 2.49Ω

Current transformer input


Input range 0-50mA RMS, 48-62Hz
10Ω burden resistor fitted inside module
Measurement scaling 10, 25, 50 or 100 Amps
Calibration accuracy <1% of reading (typical) <4% of reading (worst case)
Input functions Partial load failure. SSR open or short circuit. Other functions including power usage totalization available using
soft wiring.

Contact closure logic inputs


Thresholds Open > 600Ω, Closed < 300Ω
Input functions Auto/Manual select, SP2 select, Integral hold, Control inhibit, Program run functions, Keylock, Recipe select,
PID select, BCD bit, Autotune enable, Standby, PV select plus other functions available using soft wiring.
EPC3000 Data Sheet eurotherm.com/epc3000 6

Inputs and outputs


Logic I/O modules
Output rating ON 12V DC 44mA max. Minimum control cycle time 50ms (auto)
Output functions Time proportioned heat, time proportioned cool. SSR drive alarm and event outputs, interlock outputs, other
functions available using soft wiring.
Contact closure (input) Open > 500Ω, Closed < 150Ω
Input functions Auto/Manual select, SP2 select, Integral hold, Control inhibit, Program run functions, Keylock, Recipe select,
PID select, BCD bit, Autotune enable, Standby, PV select plus other functions available using soft wiring.

Logic I/O open collector type (3004/3008 only)


External DC PSU 15V to 35V DC
Output limit Maximum current sinking 40mA
Output functions Alarm and event outputs, interlock outputs, other functions available using soft wiring. Cannot be used as a
control output.
Voltage sensing input OFF < 1V, ON > 4V. Max 35V, Min -1V
Contact closure input OFF > 28KΩ, ON < 100Ω
Input functions Auto/Manual select, SP2 select, Integral hold, Control inhibit, Program run functions, Keylock, Recipe select,
PID select, BCD bit, Autotune enable, Standby, PV select plus other functions available using soft wiring.

Relays (Form A modules and form C built in)


Types Form A (normally open)
Form C (changeover)
Output functions Time proportioned heat, time proportioned cool. SSR Drive. Direct valve raise/lower. Alarm and event outputs,
interlock outputs, other functions available using soft wiring.
Rating Min 100mA @ 12V, Max 2A @ 264V AC resistive. External snubber recommended.

TRIAC module
Rating Min 40mA, 30V RMS, Max 0.75A @ 264V AC resistive.
Output functions Time proportioned heat, Time proportioned cool. SSR drive alarm and event outputs, interlock outputs, other
functions available using soft wiring.
Surge rating Max current surge 30A (<10ms) Max continuous operating voltage 540V peak, 385V RMS. Max surge voltage
800V peak, 565V RMS (< 10ms).

Isolated DC analog output module


Current output Voltage output
Range 0-20mA 0-10V
Load resistence <550Ω >450Ω
Calibration accuracy < ±(0.5% of reading + 100uA offset) < ±(0.5% of reading + 50mV offset)
Resolution 13.5 bits resolution 13.5 bits resolution
Output functions SCR/Power control drive. Proportional valve. Retransmission to chart recorder or other
instrumentation. Other functions using soft wiring.
EPC3000 Data Sheet eurotherm.com/epc3000 7

Power, communications and operator interface


Power and transmitter PSU
Power supply, AC supply measurement and transmitter power supply
Instrument supply voltage 100-230Vac +/- 15%, 48 to 62Hz or 24Vac +10/-15%, 48 to 62Hz 24Vdc +20/-15%, max 5% ripple voltage.
PSU rating EPC3016 6W
EPC3008/3004 9W
Power supply measurement Only available in 100-230Vac powered instruments. Measures direct from power supply (no additional
connections. Uncalibrated. Electrical noise 0.5V filtered, used by the PID function for power feedforward.
Transmitter PSU 24Vdc. 2 to 28mA load. Isolated from system (300V AC double isolation) (3004/3008 only)

Communications
Communications
Ethernet Shielded grounded RJ45 connection supporting 10/100BASE-T auto sensing. Fixed IP address or DHCP
Serial RS485 Half duplex
RS422/RS232 Full duplex
Baud rates 9600, 19200
Modbus RTU 8 data bits, odd/even/no parity selectable
EI-Bisynch 7 data bits even parity fixed

Operator interface
Display and operation
Type High visibility LCD with backlight. Flat “washdown” membrane bezel with superior panel sealing, or sculpted
bezel with fully tactile keys.
Keyboard 100,000 operations typical
Main PV 3016 4 digits, 3DP; 3008 4.5 digits, 4DP; 3004 5 digits, 4DP; green/red bicolor (red in alarm)
Second line (3004/3008 only) 5 character 16 segment text or numeric
Third line 16 segment scrolling text or numeric display
Text character sets Roman, simplified cyrillic
Additional display functions Program status “crowsfoot” indicator. Output indicators. Alarm indication. Units. Bar graph (3004/3008 only).
Communications activity indicator.
HMI functions Configurable display contents. Configurable scroll lists for operator/supervisor. Configurable scrolling event
messages. Passcode level protection with lockout period. 2 Programmable function keys (3004/3008 only)
EPC3000 Data Sheet eurotherm.com/epc3000 8

Rear Terminals
3016

{
+ + 1A 3A
IO(1)
- - 1B 3B OP(3) Form C relay

+ + 2A Option 3C
IO(2) slot
- - see
2B VI
below
+ + +
AC supply 100-230Vac +/-15%, 48 to 62Hz L V+
2.49Ω
Low voltage supply 24Vac +10/-15%, 48 to 62Hz N V-
24Vdc +20/-15%, max 5% ripple voltage - - -
T/C Pt100 mA mV/V
Pt1000
Digital communications
RS232
RS485
RS422
Remote setpoint IP
Ethernet

CT CT NC HA CT E

C C RX+ HB C C

LA LA RX- HC LA LA

CMN HD CMN HD CMN HD 0-10V HD

RX HE A(+) HE TX+ HE 4-20mA HE

TX HF B(–) HF TX- HF CMN HF

RS232 RS485 RS422 RSP INPUT ETHERNET


CT INPUT CT INPUT CT INPUT DIGITAL INPUT
DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT

Key to symbols used in wiring diagrams

+
Logic output (SSR drive) Relay output Contact input
-

+ 0-10V/0-20mA
Triac output Current transformer input
analog output
-
EPC3000 Data Sheet eurotherm.com/epc3000 9

{
Rear Terminals
3004 / 3008
+ + 1A 3A
IO(1)
- - 1B 3B OP(3) Form C relay

+ + 2A 3C
IO(2)

{
- - CMN
2B HD

LB HE A (+) Digital
communications
B (–) EIA485
LC HF
Options
+ + 4A CT
IO(4)
- -
4B C

5A LA
+

24V
– 5B VI
AC supply + + +
100-230Vac +/-15%, 48 to 62Hz L V+
Low voltage supply 2.49Ω
24Vac +10/-15%, 48 to 62Hz N V-
- - -
24Vdc +20/-15%, T/C Pt100 mA mV/V
max 5% ripple voltage
Pt1000

DIO D1 DIO D1

DIO D2 DIO D2

DIO D3 DIO D3

DIO D4 DIO D4

DIO D5 CMN DC

DIO D6 E

DIO D7

DIO D8

Secondary CMN DC Secondary


sensor sensor
input SI input SI

+ + + + + +
S+ S+
2.49Ω 2.49Ω
S- S-
- - - - - -
mV/V mA Pt100 T/C mV/V mA Pt100 T/C
Pt1000 Pt1000

PV INPUT PV INPUT
8 x DIGITAL IN / OUT ETHERNET
4 x DIGITAL IN / OUT

Key to symbols used in wiring diagrams

+
Logic output (SSR drive) Relay output Contact input
-

+ 0-10V/0-20mA
Triac output Current transformer input
analog output
-
EPC3000 Data Sheet eurotherm.com/epc3000 10

Order Codes EPC3016


1 2 3 4 5 6 7 8 9 10 11 12

Note 1. Basic EPC3016 Model includes one Form C Relay


13 14 15

Model (see Note 1) 3 I/O 1 6 Future 11 Future


EPC3016 1/16 DIN Controller XX Not Fitted XX Future XXX Future
L2 Logic
R1 Relay Output (without 7 Serial Comms Protocol 12 Bezel
1 Type snubber)
CC Controller only R2 Relay (supplied with XX MODBUS (Default) ST Standard
CP 1 x 8 Segment Basic external snubber) EI EI Bisynch WD Washdown
Programmer D1 DC Output
P1 1 x 24 Segment T1 Triac (without snubber) Ethernet, Comms & 13 Labels
Advanced Programmer T2 Triac (supplied with 8
Remote SP XXXX None (Default)
P10 10 x 24 Segment snubber)
XX None (Default) Fnnnn Custom Label
Advanced Programmer
C1 CT Input, Dig In, and
4 I/O 2 RS232 14 Specials
2 Supply Voltage XX Not Fitted C2 CT Input, Dig In, and
XXXX None (Default)
VH 100 - 230Vac +/-15% L2 Logic RS485 (3 wire)
(48 to 62Hz) R1 Relay Output (without C3 RS422 only (5 wire)
VL 24Vac +10%, -15% (48 snubber) CR CT Input, Dig In, RSP 15 Future
to 62 Hz); 24Vdc +20, R2 Relay (supplied with Input XX Future
-15%; 5% ripple external snubber) CE Digital Input, Ethernet
D1 DC Output
T1 Triac (without snubber) 9 Future
T2 Triac (supplied with
external snubber) XX Future

5 Future 10 Tool Kit Blocks


X Not fitted XX None (Default 50 wires)
TK Enabled (includes 200
wires)

Quick Start Codes EPC3016


16 17 18 19 20 21 22 23 24 25 26 27

Note 1 Requires purchase of Communications Option (Field 8) with “Dig In”


28

16 Application 18 Input 1 Range 20 Future 23 Future


X None (Default) X Not required XX Future XX Future
1 Heat only F Full range
2 Heat/Cool 1 0 to 100°C or 32 to 212°F or
21 CT Input Range 24 Future
V VPU 273 to 373K
2 0 to 200°C or 32 to 392°F or X Not Used XX Future
273 to 473K 1 10A
17 Input 1 Sensor Type 2 25A
3 0 to 400°C or 32 to 752°F or 25 Units
X Not required 273 to 673K 5 50A
M Linear 0 to 80mVdc 6 100A X Not used (Default)
4 0 to 600°C or 32 to 1112°F
V Linear 0 to 10Vdc 7 1000A C Degrees Celsius (Default)
or 273 to 873K
2 Linear 0 to 20mA F Degrees Fahrenheit
5 0 to 800°C or 32 to 1472°F
4 Linear 4 to 20mA K Kelvin
or 273 to 1073K Digital Input A Function
B Type B Thermocouple 6 0 to 1000°C or 32 to 1832°F 22
(see Note 1)
J Type J Thermocouple or 273 to 1273K 26 Future
X Not Used
K Type K Thermocouple 7 0 to 1200°C or 32 to 2192°F
W Alarm Acknowledge XX Future
L Type L Thermocouple or 273 to 1473K
M Auto/Manual
N Type N Thermocouple 8 0 to 1300°C or 32 to 2552°F
R Programmer Run/Hold 27 Warranty
R Type R Thermocouple or 273 to 1573K
L Keylock
S Type S Thermocouple 9 0 to 1600°C or 32 to 2912°F XX Standard warranty
K Loop Track
T Type T Thermocouple or 273 to 1873K
P Local Setpoint Select
P PT100 A 0 to 1800°C or 32 to 3272°F
T Programmer Reset 28 Certificate of Conformity
W PT1000 or 273 to 2073K
U Remote Setpoint Select
XX None required
V Recipe Select
19 Future CERT1 Supplied with Certificate
of Conformity
XX Future
EPC3000 Data Sheet eurotherm.com/epc3000 11

Order Codes EPC3008 / EPC3004


1 2 3 4 5 6 7 8 9 10 11 12

Note 1. Base EPC3008/4 Model includes RS485 Modbus RTU Slave communications, 1 Form C Relay, 2x Contact Closure
13 14 15
Digital inputs, 1 Current Transformer Input, and 24V Transducer Power Supply

Note 2. Digital I/O on I8/IE cannot be used for PID control output

Model (see Note 1) 3 I/O 1 6 Future 11 Future


EPC3008 1/8 DIN Controller XX Not fitted XX Future XXX 50 Wires (Default)
EPC3004 1/4 DIN Controller L2 Logic
R1 Relay Output (without
snubber) 7 RS485 Function 12 Bezel
R2 Relay (supplied with
1 Type external snubber) XX MODBUS (Default) ST Standard
CC Controller only D1 DC Output EI EI Bisynch WD Washdown
CP 1 x 8 Segment Basic T1 Triac (without snubber)
Programmer T2 Triac (supplied with
P1 1 x 24 Segment external snubber) Ethernet, 2nd Input & 13 Labels
8
Advanced Programmer Option I/O XXXX None (Default)
P10 10 x 24 Segment
XX None (Default) Fnnnn Custom Label
Advanced Programmer 4 I/O 2 I8 Second PV Input; 8
XX Not Fitted Digital Input/Outputs:
L2 Logic IE Second PV 14 Specials
2 Supply Voltage R1 Relay Output (without (see Input;Ethernet
Note 2) (MODBUS TCP slave) + XXXX None (Default)
VH 100 - 230Vac +/-15% snubber)
(48 to 62Hz) R2 Relay Output (supplied 4 x Digital I/O
VL 24Vac +10%, -15% (48 with external snubber)
to 62 Hz); 24Vdc +20, D1 DC Output 15 Future
-15%; 5% ripple T1 Triac (without snubber) 9 Future XX Future
T2 Triac (supplied with
external snubber) XX Future

5 I/O 4 10 Tool Kit Blocks

XX Not Fitted XX None (Default 50 wires)


L2 Logic TK Enabled (includes 200
R1 Relay Output (without wires)
snubber)
R2 Relay Output (supplied
with external snubber)
D1 DC Output
T1 Triac (without snubber)
T2 Triac (supplied with
external snubber)
EPC3000 Data Sheet eurotherm.com/epc3000 12

Quick Start Codes EPC3008 / EPC3004


16 17 18 19 20 21 22 23 24 25 26 27

Note 1. Requires purchase of 2nd Input (Field 8)


28

Note 2. Requires purchase of Option I/O (Field 8)

16 Application Input 2 Sensor Type 23 Digital Input B Function 25 Units


19
(see Note 1)
X None (Default) X Not Used X Not used (Default)
1 Heat only X Not fitted W Alarm Acknowledge C Degrees Celsius (Default)
2 Heat/ Cool M Linear 0 to 80mVdc M Auto/Manual F Degrees Fahrenheit
V VPU V Linear 0 to 10Vdc R Programmer Run/Hold K Kelvin
C Carbon Potential 2 Linear 0 to 20mA L Keylock
Controller (requires PV2 4 Linear 4 to 20mA K Loop Track 26 Future
and Zirconia) B Type B Thermocouple P Local Setpoint Select
D Dew Point Controller J Type J Thermocouple T Programmer Reset XX Future
(requires PV2 and K Type K Thermocouple U Remote Setpoint Select
Zirconia) L Type L Thermocouple V Recipe Select 27 Warranty
N Type N Thermocouple
R Type R Thermocouple XX Standard warranty
17 Input 1 Sensor Type Programmer I/O
S Type S Thermocouple 24
X Not required Configuration (see Note 2)
T Type T Thermocouple 28 Certificate of Conformity
M Linear 0 to 80mVdc P PT100 X Not Used/fitted
V Linear 0 to 10Vdc XX None required
W PT1000
2 Linear 0 to 20mA CERT1 Supplied with Certificate
Z Zirconia (HiZ) 1 D1 to D8 Programmer Event
4 Linear 4 to 20mA of Conformity
Outputs 1 to 8
B Type B Thermocouple
20 Input 2 Range (see Note 1)
J Type J Thermocouple 2 D1 to D4 = Programmer
K Type K Thermocouple X Not required Event Outputs 1 to 4, D5 to
L Type L Thermocouple F Full range D7 = BCD Inputs 1 t o3, D8
N Type N Thermocouple 1 0 to 100°C or 32 to 212°F or = Programmer Run/Hold.
R Type R Thermocouple 273 to 373K BCD Output to Program
S Type S Thermocouple 2 0 to 200°C or 32 to 392°F or Number
T Type T Thermocouple 273 to 473K
P PT100 3 0 to 400°C or 32 to 752°F or 3 D1 to D4 = Programmer
W PT1000 273 to 673K Event outputs 1 to 4, D5
4 0 to 600°C or 32 to 1112°F to D8 Programmer Run,
or 273 to 873K Hold, Reset, Advance
18 Input 1 Range
5 0 to 800°C or 32 to 1472°F respectively
X
F
Not required
Full range 6
or 273 to 1073K
0 to 1000°C or 32 to 1832°F 4 D1 to D4 = Programmer
Accessory
1 0 to 100°C or 32 to 212°F or
273 to 373K 7
or 273 to 1273K
0 to 1200°C or 32 to 2192°F
Event inputs 1 to 4, D5
to D7 Programmer Run/ Order Codes
2 0 to 200°C or 32 to 392°F or or 273 to 1473K Hold, Reset, Advance
273 to 473K 8 0 to 1300°C or 32 to 2552°F respectively, D8 Not Used.
3 0 to 400°C or 32 to 752°F or BCD Output to Program 1
or 273 to 1573K
273 to 673K 9 0 to 1600°C or 32 to 2912°F Number
4 0 to 600°C or 32 to 1112°F or 273 to 1873K
or 273 to 873K A 0 to 1800°C or 32 to 3272°F 5 D1 to D8 = BCD Inputs 1
5 0 to 800°C or 32 to 1472°F or 273 to 2073K to 8. BCD Output to Recipe
or 273 to 1073K Recall
6 0 to 1000°C or 32 to 1832°F
21 CT Input Range Model
or 273 to 1273K 6 D1 to D4 = BCD Inputs 1 to
7 0 to 1200°C or 32 to 2192°F X Not Used 4, D5 - D8 = Not used. BCD EPCACC EPC Accessories
or 273 to 1473K 1 10A Output to Recipe Recall
8 0 to 1300°C or 32 to 2552°F 2 25A 1 Accessories
or 273 to 1573K 5 50A 7 D1 to D4 Programmer
Run, Hold, Reset, Advance RES2R9 2.49 Ohm Resistor
9 0 to 1600°C or 32 to 2912°F 6 100A
RES250 250 Ohm Resistor
or 273 to 1873K 7 1000A respectively, D5 - D8 = Not
used RES500 500 Ohm Resistor
A 0 to 1800°C or 32 to 3272°F SNUBBER RC SNUBBER
or 273 to 2073K 22 Digital Input A Function USBCONF USB Backup lead
8 D1 to D3 Programmer Run,
X Not Used Hold, Reset respectively, D4 CTR10A Current transformer
W Alarm Acknowledge - D8 = Not Used 10A Primary
M Auto/Manual CTR25A Current transformer
R Programmer Run/Hold 9 D1 to D4 = Programmer 25A Primary
L Keylock Event Outputs, D5 to D8 = CTR50A Current transformer
K Loop Track Not Used 50A Primary
P Local Setpoint Select CTR100A Current transformer
T Programmer Reset 100A Primary
U Remote Setpoint Select ITOOLS Itools configuration
V Recipe Select Software

Eurotherm USA
44621 Guilford Drive, Suite 100
Ashburn, VA 20147
Phone: +1-703-724-7300
Phone: +1-703-724-7301
www.eurotherm.com

Document Number HA032952USA Issue 4 © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.