Novel_Transient-Energy-Based_Directional_Pilot_Protection_Method_for_HVDC_Line
Novel_Transient-Energy-Based_Directional_Pilot_Protection_Method_for_HVDC_Line
Abstract
This paper proposes a novel directional pilot protection method based on the transient energy for bipolar HVDC
line. Supposing the positive direction of current is from DC bus to the DC line, in the case of an internal line fault,
the transient energies detected on both sides of the line are all negative within a short time, which denotes the
positive direction fault; while for an external fault, the transient energy on one end is positive, which means a
negative direction fault, but the transient energy on the opposite end is negative, which indicates that the fault
direction is positive. According to these characteristics, an integration criterion identifying fault direction is
constructed. In addition, through setting a fixed energy threshold, the faulted line and lightning disturbance can
also be discriminated. Simulation results from UHVDC transmission system show the validity of the proposed
protection method.
Keywords: Transient energy, HVDC line, Directional pilot protection, Fault direction, Lightning stroke
© The Author(s). 2017 Open Access This article is distributed under the terms of the Creative Commons Attribution 4.0
International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and
reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to
the Creative Commons license, and indicate if changes were made.
Zou et al. Protection and Control of Modern Power Systems (2017) 2:15 Page 2 of 10
From (5) it can be seen that the variations of transient In (6) and (7), the polarities of Δum+ and Δim+ at the
power on each side of bipolar line are all negative and, rectifier side are the same, while those of Δun+ and Δin+
after the integral calculation, the transient energies are at the inverter side are opposite. Therefore, the transient
also negative. power variation ΔPm+ is positive, but ΔPn+ is negative
Based on the above analyses, the following conclusions and, thus the transient energy Sm+ is positive while Sn+
can be drawn: for an internal DC line fault, whatever it is negative.
is a single pole to earth fault or a pole to pole fault, the When a fault occurs on the converter valve or DC bus
power variations on both sides of the faulted line are of the inverter side, the corresponding fault superim-
always negative, as well as the transient energies. posed circuit is shown in Fig. 5a and b illustrates the
fault superimposed circuit for a fault occurring on the
2.1.4 Transient energy characteristics for external fault AC side.
For HVDC line, external faults include two types, one As shown in Fig. 5:
type occurs on the DC side, and the other type occurs
on the AC side. Actually, the influence generated by an Δumþ ¼ −Z eq Δimþ ð8Þ
AC side external fault on HVDC line protection is
similar to that generated by a DC side external fault, and Δunþ ¼ Z eq þ Z L Δinþ ð9Þ
the transient analyses for the external faults are dis-
cussed as follows. From (8) and (9) it can be seen that the polarities of
Δum+ and Δim+ at the rectifier side are opposite, while
2.1.4.1 Faults outside the positive pole line If a fault those of Δun+ and Δin+ at the inverter side are the same.
occurs on the converter valve or DC bus of the rectifier Therefore, the transient power variation ΔPm+ is nega-
side, the fault superimposed circuit is shown in Fig. 4a, tive, and ΔPn+ is positive, so the corresponding transient
where Zeq1 and Zeq2 are the equivalent impedances from energy Sm+ is negative while Sn+ is positive.
Zou et al. Protection and Control of Modern Power Systems (2017) 2:15 Page 4 of 10
X
j
S ηp ¼ Δt Δuηp ðk ÞΔiηp ðk Þ ð10Þ
1
without causing fault must be correctly identified by the Table 1 Simulation results for a fault at F1
protection. The sampling frequency of the proposed Location RF (Ω) Pole Rectifier side Inverter side Result
method is relatively low (10 kHz) and integral calcula- Sm Dir Sn Dir
tion is used in the algorithm, which can filter high F1 300 + −1.96 1 −1.91 1 Internal
frequency components to some extent. Moreover, the
- / / / / Normal
amplitude of lightning current for direct stroke line is
low [20, 21], and generally the transient energy
caused by lightning disturbance will not exceed the station. The frequency-dependent line model is utilized
fixed threshold. for accurate simulation. As shown in Fig. 6, the length of
For convenient analysis, a rule is defined here. The UHVDC line is 2190 km, the transmission capacity is up
logic value of a positive directional fault is 1, and that of to 8000 MW, and the rated current is 5 kA.
the negative directional fault is equal to −1, and 0 means In Fig. 6, extensive internal and external faults will
there is no fault. Therefore, the transient energy direc- be simulated, and the sampling frequency is 10 kHz.
tion Dir[Sηp] is expressed as follows: Practical operating experience shows the polarity of
8 lightning current is generally negative, so the lightning
< −1 S ηp ≥S set stroke mainly occurs on the positive pole line and a stand-
Dir S ηp ¼ 0 S ηp j< S set ð12Þ ard 2.6/50 μs lightning current is used in the simulation.
:
1 S ηp ≤−S set A multi-wave-impedance tower model, a flashover insula-
tor model and a nonlinear surge earth impedance model
The logic identifying fault is described as below: if the are included to evaluate the back-flashover accurately. For
logic values of fault direction detected on both sides of convenient analysis, the fault components of voltage and
HVDC line are equal to 1, an internal fault will be current, and the value of transient energy are all expressed
determined; if the logic value of fault direction on one in per unit value. Considering the lightning stroke inter-
side is 1, while that on the other side is −1, an external ference of 2 ~ 3 ms and the influence of fault resistance,
fault will be discriminated; otherwise, it is normal. the integral time is set as 5 ms, and the fixed threshold Sset
is set as 1 here.
3 Results and discussion
3.1 Simulation and analysis 3.1.2 Typical internal faults
3.1.1 Simulation model 3.1.2.1 Single-pole to earth fault When a fault occurs
To test the performance of the proposed protection on the positive pole line at F1 500 km from the rectifier
principle, using the actual parameters of ±800 kV Hami- station, and the fault ground resistance and fault initial
Zhengzhou HVDC transmission system in China, this instant are 300 Ω and 0 ms, respectively. The waveforms
paper constructs a simulation model of bipolar UHVDC of fault component voltage and fault component current,
system with a double 12-pulse valves at each converter
(a) (a)
(b) (b)
Fig. 7 Waveforms of fault components and transient energies Fig. 8 Waveforms of fault components and transient energies
detected on the positive pole line for a fault at F1. a Rectifier station. detected on the negative pole line for a fault at F2. a Rectifier
b Inverter station station. b Inverter station
Zou et al. Protection and Control of Modern Power Systems (2017) 2:15 Page 6 of 10
(a) (a)
(b) (b)
Table 3 Simulation results for a fault at F3 Table 4 Simulation results for a fault at F4
Location RF (Ω) Pole Rectifier side Inverter side Result Location RF (Ω) Pole Rectifier side Inverter side Result
Sm Dir Sn Dir Sm Dir Sn Dir
F3 0 + −27.41 1 −27.66 1 Internal F4 0 + 23.73 −1 −14.01 1 External
- −27.63 1 −27.72 1 Internal - 1.85 −1 −4.05 1 External
and current on two ends of the positive pole line rise at on the positive pole line, and the simulation results are
fault initial stage for a fault at F2, but the transient indicated in Table 4.
energies detected on both ends of the line don’t exceed From Fig. 12 and Table 4, it can be seen that the
the fixed threshold, thus the protection units at two ends transient energies detected on both ends of the positive
will not operate. Therefore, through setting a fixed pole line have obvious differences. The transient energy
threshold, a single pole to earth fault has no effect on detected on the rectifier side is positive while it is nega-
the fault identification of the normal line. tive on the inverter side. According to the fault identifi-
cation logic, the protection unit at the rectifier side
identifies a negative direction fault while the protection
3.1.2.3 Pole to pole fault at F3 For a pole to pole fault
unit at the inverter side identifies a positive direction
at F3 occurring on the middle of the bipolar line, Figs. 10
fault. Through analyzing the above results, an external
and 11 show the transient waveforms detected on both
fault is finally determined, and the same characteristic
ends of the bipolar line, and the simulation data are
exists in the negative pole line, so the identification
shown in Table 3.
results are all correct.
As shown in Figs. 10, 11 and Table 3, the transient
energies detected on the positive pole line and the
negative pole line exceed the fixed threshold, so the
3.1.3.2 External fault at F5 For a fault at F5 occurring
protection units at two ends of the bipolar line all
on the AC side of the inverter station, Figs. 13 and 14 il-
identify a positive direction fault. In combination with
lustrate the transient waveforms detected on the posi-
the results on the two sides, a fault inside both the posi-
tive pole line and the negative pole line, respectively,
tive pole line and the negative pole line is identified, and
and Table 5 lists the relevant simulation results.
the results are correct.
As shown in Figs. 13, 14, and Table 5, the polarities of
transient energies detected on both ends of the positive
3.1.3 Typical external faults line and the negative line are all opposite. Therefore, an
3.1.3.1 External fault at F4 Supposing a fault occurs at external fault will be identified and the discrimination
F4 on the DC bus of the positive pole line in the rectifier results are correct.
station, Fig. 12 shows the transient waveforms detected
(a) (a)
(b) (b)
Fig. 12 Waveforms of fault components and transient energies Fig. 13 Waveforms of fault components and transient energies
detected on the positive pole line for a fault at F4. a Rectifier station. detected on the positive pole line for a fault at F5. a Rectifier station.
b Inverter station b Inverter station
Zou et al. Protection and Control of Modern Power Systems (2017) 2:15 Page 8 of 10
Fig. 14 Waveforms of fault components and transient energies - −1.70 1 −1.71 1 Internal
detected on the negative pole line for a fault at F5. a Rectifier F3 (1000 km) 10 + −24.96 1 −25.01 1 Internal
station. b Inverter station
- −25.21 1 −25.09 1 Internal
200 + −8.13 1 −8.44 1 Internal
stroke on tower without causing back-flashover, the protec- protection criteria can effectively discriminate between
tion units will not start. lightning stroke disturbance and lightning stroke fault.
As shown in Table 9, for shielding failure and back-
flashover with different lightning current amplitudes and 4 Conclusions
lightning stroke locations, those faults can also be Using the characteristic differences of transient energy
correctly identified. Note that lightning stroke on tower on both sides of HVDC line after the fault, the paper
with the amplitude of 200 kA causes both the positive proposes a novel directional pilot protection method.
pole and negative pole insulators back-flashover, but for From the theoretical analysis and simulation results, the
lightning current of 120 kA, it only results in the insula- following conclusions can be obtained:
tor back-flashover of positive pole line. Therefore, the
1) Due to applying directional pilot protection principle
Table 9 Simulation results for lightning stroke causing faults and energy integral criteria, the proposed protection
Condition Pole Sm Sn Result method is rarely influenced by fault position, fault
Shielding failure 15 kA 1 km + −29.83 −9.14 Internal resistance and lightning stroke disturbance. For special
- −0.23 −2.13 Normal fault cases, such as close-up faults or high ground re-
500 km + −12.33 −8.77 Internal
sistance faults, the method can make a correct identifi-
cation, so it has absolute selectivity and high reliability.
- −0.10 −0.62 Normal
2) The proposed protection criteria can correctly
30 kA 300 km + −13.79 −8.48 Internal identify the faulted line for a single pole to earth
- 0.15 −0.84 Normal fault, so the method has good adaptability.
900 km + −10.84 −9.18 Internal 3) Because of only identifying the fault directions on
- −0.14 −0.27 Normal both sides of HVDC line, so the pilot protection
Back- flashover 120 kA 10 km + −38.95 −11.56 Internal
does not require the synchronous data.
- −0.34 −2.40 Normal Acknowledgements
This work was supported in part by National Natural Science Foundation of China
1200 km + −9.46 −12.06 Internal (51677109), and in part by National Key Research and Development Program of
- −0.57 0.88 Normal China (2016YFB0906003).
Competing interests 20. Azizi, S., Sanaye-Pasand, M., Abedini, M., et al. (2014). A Traveling-Wave-
The authors declare that they have no competing interests. Based Methodology for Wide-Area Fault Location in Multiterminal DC
Systems. IEEE Transactions on Power Delivery, 29(6), 2552–2560.
Author details 21. Nanayakkara, O. M. K. K., Rajapakse, A. D., & Wachal, R. (2012). Traveling-
1
Key Laboratory of Power System Intelligent Dispatch and Control of Ministry Wave-Based Line Fault Location in Star-Connected Multiterminal HVDC
of Education, Shandong University, Ji’nan, China. 2State Grid Weifang Electric Systems. IEEE Transactions on Power Delivery, 27(4), 2286–2294.
Power Company, Weifang 261021, China. 3State Grid Langfang Electric Power
Company, Langfang 065000, China.
References
1. Yang, J., Fletcher, J. E., & O’Reilly, J. (2010). Multiterminal dc wind farm
collection grid internal fault analysis and protection design. IEEE
Transactions on Power Delivery, 25(4), 2308–2318.
2. Bresesti, P., Kling, W. L., Hendriks, R. L., et al. (2007). HVDC connection of
offshore wind farms to the transmission system. IEEE Transactions on Energy
Conversion, 22(1), 37–43.
3. Andersen, B. R., & Lie, X. (2004). Hybrid HVDC system for power transmission
to island networks. IEEE Transactions on Power Delivery, 19(4), 1884–1890.
4. Zhang, S., & Li, Y. L. (2011). Simulation and analysis of HVDC line protection
under the single pole to ground fault with high transition resistance (Electric
Utility Deregulation and Restructuring and Power Technologies, 2011 4th
International Conference on, pp. 926–929).
5. Li, A. M., Cai, Z. X., Sun, Q. Z., et al. (2009). Study on the dynamic performance
characterisitcs of HVDC control and protections for the HVDC line fault (Power
& Energy Society General Meeting, p. 5).
6. Gao, S. P., Chu, X., Shen, Q. Y., et al. (2015). A novel whole-line quick-action
protection principle for HVDC transmission lines using one-end voltage.
International Journal of Electrical Power and Energy Systems, 65, 262–270.
7. Kong, F., Hao, Z. G., Zhang, S., et al. (2014). Development of a novel
protection device for bipolar HVDC transmission lines. IEEE Transactions on
Power Delivery, 29(5), 2270–2278.
8. Song, G. B., Chu, X., Gao, S. P., et al. (2015). A new whole-line quick-action
protection principle for HVDC transmission lines using one-end current. IEEE
Transactions on Power Delivery, 30(2), 599–607.
9. Liu, K. Z., Yu, J. L., Shu, H. C., et al. (2012). Study on electrical transient
protection for ±800kV UHVDC Transmission Lines. In:sia-Pacific Power and
Energy Engineering Conference.
10. Takeda, H., Ayakawa, H., Tsumenaga, M., et al. (2012). New protection
method for HVDC lines including cables. IEEE Transactions on Power Delivery,
10(4), 2035–2039.
11. Ha, H., Yu, Y., & Yi, R. (2010). Novel scheme of traveling wave based differential
protection for bipolar HVDC transmission lines (Proceedings of the
International Conference Power Systems, Technology, p. 5).
12. Zheng, X. D., Tai, T. N. L., Thorp, J. S., et al. (2001). A Transient Harmonic
Current Protection Scheme for HVDC Transmission Line. IEEE Transactions on
Power Delivery, 27(4), 2278–2285.
13. Han, K. L., Cai, Z. X., Liu, Y., et al. (2011). Study on protective performance
of HVDC transmission line protection with different types of line fault
(Electric utility deregulation and restructuring and power technologies
(DRPT), pp. 358–361).
14. Li, A. M., Cai, Z. X., Sun, Q. Z., et al. (2009). Study on the dynamic performance
characteristics of HVDC control and protections for the HVDC line fault (Power
& energy society general meeting, p. 5).
15. Zheng, X. D., Tai, N. L., Yang, G. L., et al. (2012). A transient protection scheme
for HVDC transmission line. IEEE Transactions on Power Delivery, 27(2), 718–724.
16. Liu, X. L., Osman, A. H., & Malik, O. P. (2009). Hybrid traveling wave/boundary
protection for monopolar HVDC line. IEEE Transactions on Power Delivery,
24(2), 569–578.
17. Kerf, K. D., Srivastava, K., Reza, M., et al. (2012). Wavelet-based protection
strategy for DC faults in multi-terminal VSC HVDC system. IET Generation
Transmission and Distribution, 5(4), 496–503.
18. Liu, X. L., Osman, A. H., & Malik, O. P. (2011). Real-time implementation of a
hybrid protection scheme for double-pole HVDC line using FPGA. IEEE
Transactions on Power Delivery, 26(1), 101–108.
19. Liang, Y. S., Wang, G., & Li, H. F. (2015). Time-Domain Fault-Location Method
on HVDC Transmission Lines Under Unsynchronized Two-End Measurement
and Uncertain Line Parameters. IEEE Transactions on Power Delivery, 30(3),
1031–1038.