The Shimaden Digital Controller Series SR80 offers high accuracy temperature and humidity control with features such as auto tuning, multiple output options, and robust communication interfaces. It includes models SR82, SR83, and SR84, each with varying display sizes and functionalities, including PID control and optional event outputs. The controllers are designed for durability with an IP66 rating and a wide range of customizable features to meet various application needs.

Uploaded by

xaxorad579
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views

Brochure

The Shimaden Digital Controller Series SR80 offers high accuracy temperature and humidity control with features such as auto tuning, multiple output options, and robust communication interfaces. It includes models SR82, SR83, and SR84, each with varying display sizes and functionalities, including PID control and optional event outputs. The controllers are designed for durability with an IP66 rating and a wide range of customizable features to meet various application needs.

Uploaded by

xaxorad579
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Shimaden, Temperature and Humidity Control Specialists

°C
Series SR80
%RH
SHIMADEN DIGITAL CONTROLLER

& ®

approved
C US

BASIC FEATURES

High accuracy: ± (0.25% FS + 1 digit)


Only SR83 (96 x 96) Large 20 mm bright display
Make reading from long distance and low light location
easier.
2-output heating and cooling control available for SR83 (96
x 96) and SR84 (48 x 96)
Auto tuning function for both heating and cooling outputs
in a high performance individual expert PID control
Both RS232C/RS485 and CC-Link are communication
interface ready. (CC-Link available only for SR83)
Dust and splash proof front panel Equivalent to IP66
A wide selection of additional functions (optional) is
available to suit various needs.
SPECIFICATIONS Series SR80

SR82 (72 x 72) DISPLAY


• LED display: Measured value (PV) display/
7-segment red LED 4 digits
Set value (SV) display/
7-segment green LED 4 digits
Display accuracy: ±(0.25% FS + 1 digit)
Range in which display
accuracy is maintained: 23˚C±5˚C
Display resolution: Depends on measuring range
(0.001, 0.01, 0.1, 1)
Sampling cycle: 250 msec. (0.25 sec.)
Action display/color: 11 types, LED lamp display
Control output: (OUT1, 2)/
green
¡ Wide range of optional features Event action (EV1, 2, 3)/
¡ Event output, Remote input, Analog output signal and orange
Communication interface Auto tuning action (AT)/green
Manual control action
¡ Others
(MAN)/green
Set value bias action
SR83 (96 x 96) (SV2/SB)/
Large 20 mm bright display (PV) green
Remote action (REM)/green
Stand-by action (STBY)/green
Communication status
(COM/RUN)/
green
SETTING
• Setting method: By front key switch operation
Setting range: Same as measuring range
(within setting limiter)
Setting limiter: Higher and lower limits separate
setting; free within measuring
range (Lower limit < higher limit)
Set value resolution: Depends on range and scaling
(0.001, 0.01, 0.1, 1)
Setting key type: 6 types - PARA (parameter
selection), UP, DOWN, AT, ENT
and DISP keys
¡ Wide range of optional features • Ramp control upon
¡ Event output, Remote input, Analog output signal and reaching set value: Ascending/descending ramp
Communication interface control
¡ For example Ramp setting range: OFF, 1~9999 Units
Selectable One control output type or Two control output Ramp unit time: /sec, /min switching by front key
type. operation and communication
¡ Others Ramp rate: x 1, x 0.1 switching by front key
operation and communication
SR84 (48 x 96) INPUT
• Thermocouple: B, R, S, K, E, J, T, N, PL II,
WRe5-26, {L, U (DIN43710)} K,
AuFe-Cr Kelvin unit input
Allowable external
resistance range: 100Ω maximum
Input impedance: 500k Ω minimum
Burnout function: Standard feature (up scale)
Cold junction
temperature
compensation accuracy: ±2˚C (within a range from 5 to
45˚C)
• R.T.D.: Pt100/JPt100
Amperage: Approx. 0.25mA
Allowable range of
lead wire resistance: 5Ω maximum/wire
• Voltage (multiple input): -10~10, 0~10, 0~20, 0~50,
10~50, 0~100mV DC, or -1~1,
¡ Wide range of optional features 0~1, 0~2, 0~5, 1~5, 0~10V DC
¡ Event output, Remote input, Analog output signal and Input impedance: 500k Ω minimum
Communication interface • Current: 0~20mA, 4~20mA DC
¡ For example Receiving impedance: 250Ω
Selectable One control output type or Two control output • Sampling cycle: 250 msec. (0.25 sec.)
type. • PV bias: -1999~1999 Units
¡ Others • PV filter: OFF, 1~100 sec.
SPECIFICATIONS Series SR80
• Cold junction Higher limit side: 0.1~100.0% on
temperature condition that lower limit value <
compensation higher limit value.
switching: INT (internal)/EXT (external) Separate setting for SB/SV2 is
switching by front key operation possible.
• Isolation: Insulated from various outputs Setting range is the same as the
[not insulated from system, DI one listed above.
(external switching input) and CT • Control output at time
input] of error
CONTROL (SR82: 1 output only) (individually for control
• Control system: One output operation: outputs 1 and 2): 0.0~100.0%
Expert PID control with auto • Control output type/
tuning function rating
RA (reverse action): (common to control
Heating action outputs 1 and 2): Contact (Y): 240V AC
DA (direct action): 2.5A/resistive load
Cooling action SSR drive voltage (P): 12V
Two output operation (option): ±1.5V
Expert PID + PID (control DC, load current 30mA maximum
outputs 1 and 2 individually in Current (I): 4~20mA DC, load
action) control with auto tuning resistance 600Ω maximum.
function Voltage (V): 0~10V DC, load
RA (reverse action): current 2mA maximum
Heating action (output 1 side) • Output resolution
and cooling (output 2 side) Control output 1: Approx. 0.0125% (1/8000)
DA (direct action): Control output 2: Approx. 0.5% (1/200)
2-stage heating action (by both • Sampling cycle: 250 msec. (0.25 sec.)
of control outputs 1 and 2) • Manual control
• PID Manual switching: Front key operation or DI
(Control outputs 1 and 2 individually) (external switching input) through
Control output 1: Proportional band (P); OFF, communication
0.1~999.9% (OFF=ON/OFF Manual control output: 0.0-100.0% (out of output limiter
action) range possible)
Integral time (I): OFF, 1~6000 Setting resolution: 0.1%
sec. (OFF=with manual reset) Manual ↔ automatic
Derivative time (D): control: Balanceless bumpless (within
OFF, 0~3600 sec. proportional band, though)
Manual reset: -50.0 to +50.0% • Isolation: Insulated between control output
(valid when I=OFF) and system and various inputs
ON/OFF hysteresis: 1~1000 unit (not insulated between control
(valid during ON/OFF action) output of current, voltage or SSR
Control output 2 (only and analog output)
when two output option
is added): Proportional band (P): OFF, EVENT OUTPUT (optional)
0.1~999.9% (OFF=ON/OFF • Number of event
action) outputs: SR82 - 2
Integral time (I): OFF, 1~6000 SR83 - 3 (2 when 2 output
sec. option is added)
Derivative time (D): SR84 - 3 (2 when
OFF, 0~3600 sec. communication option, analog
ON/OFF hysteresis: 1~1000 output option and/or 2 output
Units (valid during ON/OFF option are added)
action) (In case of 2 event outputs, EV2
Dead band: -1999~5000 Units and EV3 are common output
Separate setting for SV2 is with OR.)
possible. • Event type: Selectable from 8 types (7 types
Setting range is the same as the when heater break alarm option
one listed above. is not added)
• Proportional cycle: (for contact and SSR drive A_Hi: Higher limit absolute value
voltage output) alarm
Control output 1: 1~120 sec. A_Lo: Lower limit absolute value
Control output 2: 1~120 sec. alarm
• AT point setting: 0-5000 Units D_Hi: Higher limit deviation
• Control output value alarm
characteristics: RA (reverse action)/DA (direct D_Lo: Lower limit deviation value
action) switchable by front key alarm
operation or DI (external D_i: Higher/lower limit
switching input) through deviation value alarm
communication. (within range)
• Higher and lower limit D_o: Higher/lower limit
output limiter deviation value alarm (out
(individually for control of range)
outputs 1 and 2): Lower limit side: 0.0~99.9%, Sco: Scaleover (input trouble
alarm)
SPECIFICATIONS Series SR80
Hb: Heater break alarm • Alarm action: Heater amperage detected by
(selectable only when external CT (CT attached).
heater break alarm option Alarm output ON upon detection
is added) of heater break while control
• Event setting range Deviation value alarm output is ON.
Higher limit alarm: Alarm output ON upon detection
-1999~9999 Units of heater loop alarm while
Lower limit alarm: control output is OFF.
-1999~9999 Units • Current setting range: 0.1~50.0A (Alarm action stops
Higher/lower limit alarm: when OFF is set.)
0~9999 Units • Setting resolution: 0.1A
Absolute value alarm • Current display: 0.0~55.0A
Both higher and lower limits: • Display accuracy: Approx. 3% FS
Within measuring range (for 50Hz/60Hz sine wave)
Event setting system: By front key operation • Minimum time for
• Event action: ON/OFF action action confirmation: ON (OFF) time 250 msec.
• Event hysteresis: 1~1000 Units • Alarm output/rating: Contact 240V AC 1.0A
• Stand-by/nonstand-by (resistive load)
action: Selectable from 5 types • Alarm action display: ”Event” lamp lights during action.
Alarm action without stand-by • Alarm holding mode: Switchable between holding and
Alarm action with stand-by not holding on the setting
(When power is ON) screen.
Alarm action with stand-by • Sampling time: 500 msec. (0.5 sec.)
(When power is ON, when • Isolation: Insulated between CT input and
stand-by is switched to various outputs (not insulated
execution) from system and other inputs)
Alarm action with stand-by REMOTE (optional, not selectable together with heater
(When power is ON, when break alarm)
stand-by is switched to • Remote setting: By external analog signal
execution, including the time Switching to remote: By DI (external switching) input
when SV is changed) (valid only when DI option is
Control action added)
• Event action delay: OFF, 1~9999 sec. Remote/local switching function
• Event output/rating: Contact 240V AC 1.0A by remote signal
(resistive load) • Remote switching
• Output updating cycle: 250 msec. (0.25 sec.) point: OFF, 0.1~50.0%
ANALOG OUTPUT (optional, not selectable together with • Remote switching
communication type (1) and (2)) hysteresis: 0.1~10.0%
• The number of analog • Remote scaling: Within measuring range (inverted
output: 1 scaling possible)
• Output signal: Selectable from 5 types Accuracy of setting: ±(0.25% SF + 1 digit)
(3 types for instrument with one Setting signal: 0~10, 1~5V DC
output) (Input impedance: 500k Ω min.)
PV: Measured value 4~20mA DC
SV: Set value (Receiving impedance: 250Ω)
DEV: Deviation output • Remote bias: -1999~1999 units
OUT 1: Control output 1 • Remote filter: OFF, 1~100 sec.
OUT 2: Control output 2 • Sampling cycle: 500 msec. (0.5 sec.)
(selectable only when 2 • Isolation: Insulated between remote input
output option is added) and various outputs (not
• Output type/rating 0~10mV DC/FS Output insulated from system and
impedance: 10Ω various inputs)
0~10V DC/FS Load current: COMMUNICATION (optional, not selectable together with
2mA maximum analog output for SR82 and SR84)
4~20mA DC/FS Load resistance: • Communication type (1): RS-232C, RS-485
300Ω maximum • Communication system: RS-232C 3-line half duplex
• Output scaling PV/SV: Within measuring range system
(inverted scaling possible) RS-485 2-line half duplex
OUT1/OUT2: 0.0-100.0% multiple drop (bus) system
(inverted scaling possible) • Synchronization system: Start-stop synchronization
DEV: -100.0~100.0% (inverted system
scaling possible ) on condition • Communication
that Ao_L ≠ Ao_H distance: RS-232C maximum 15 m
• Output accuracy: ±0.3% FS (to displayed value) RS-485 maximum 500 m
• Output resolution: 0.01% FS (1/10000) (depending on conditions)
• Output updating cycle: 250 msec. (0.25 sec.) • Communication speed: 1200, 2400, 4800, 9600, 19200
• Isolation: Insulated from system and bps
various inputs (not insulated from
control outputs I, P and V)
HEATER BREAK ALARM (optional, not selectable together
with REM input)
• Current capacity: 30A or 50A CT to be specified
when order is placed.
SPECIFICATIONS Series SR80
• Data bit length: 7 bits, even parity, stop bit 1 Deviation value setting (SB)
7 bits, even parity, stop bit 2 • Setting range Absolute value setting:
7 bits, no parity, stop bit 1 Within measuring range
7 bits, no parity, stop bit 2 Deviation value setting:
8 bits, even parity, stop bit 1 -1999~5000 Units
8 bits, even parity, stop bit 2 SV2 allows PID and output limit
8 bits, no parity, stop bit 1 to be set.
8 bits, no parity, stop bit 2 OTHERS
• Communication • Data storage: By non-volatile memory
address: 1~99 (EEPROM)
• Communication • Ambient temperature/
memory mode: EEP/RAM/r_E humidity ranges for use: -10~+50˚C/below 90% RH (on
• Communication BCC: Add/Add two’s cmp/XOR/None condition that there is no dew
• Communication delay condensation)
time: OFF, 1~100 • Temperature
• Communication code: ASCII code for storage: Between -20 and +65˚C
• Communication • Power supply: 100V-240V AC±10% (50/60 Hz),
protocol: Shimaden standard protocol 24V AC±10% (50/ 60Hz),
• The number of 24V DC±10%.
instruments allowed to (One of the above to be
be connected: RS-232C 1 specified)
RS-485 32 maximum • Power consumption: 12V A maximum
(depending on • Input noise removal
conditions; host ratio: Normal mode 60 dB minimum
included) (50/60 Hz)
• Isolation: Insulated between Common mode 140 dB minimum
communication signal and (50/60 Hz)
various inputs/system/ • Applicable standards: Safety:
various outputs IEC1010-1 and EN61010-1
• Communication type (2): Conforming with Mitsubishi EMC:
Electric Company’s CC-Link EN50081-2: 1993
(only for SR83, simultaneous (EMI/Emission)
selection of analog output is not EN50082-2, 1995
possible) (EMS/Immunity)
• Transmission speed: 156K, 625K, 2.5M, 5M, 10Mbps • Insulation resistance: Between input/output terminals
• Private station: 1 and power terminal 500V DC
• Communication 20M Ω minimum
method: Polling method Between input/output terminals
• Synchoronization and protective conductor
method: Frame synchronous method terminal 500V DC 20M Ω
• Coding system: NRZI system minimum
• Transmission line: Bus (RS-485) • Dielectric strength: 1 minute at 2300V AC between
• Transmission format: Conforming with HDLC input/output terminals and power
DI (EXTERNAL SWITCHING) INPUT (optional) terminal
*DI stands for “Digital Input.” 1 minute at 1500V AC between
• Number of DI point: 2 power terminal and protective
• DI input type: Selectable from 8 types (7 types conductor terminal
if the remote option is not • Protective structure: Only front panel has simple dust-
added.) proof and drip-proof structure
NOP: No operation (equivalent to IP66)
STB: Execution/stand-by • Material of case: PPO resin molding (equivalent to
SB/SV2: Set value bias/set value UL94V-1)
2 • External dimensions: SR82
AT: Auto tuning H72 x W72 x D111 mm
MAN: Manual (Inside depth of panel: 100 mm)
STP: Ramp temporary stop SR83
DA: Direct action H96 x W96 x D111 mm
REM: Remote (selectable (Inside depth of panel: 100 mm)
only when remote SR84
option is added) H96 x W48 x D111 mm
• DI input rating: Nonvoltage contact, open (Inside depth of panel: 100 mm)
collector input (about 5V/2mA • Mounting: Push-in panel (one-touch mount)
impress) • Applicable panel
• Isolation: Insulated between DI input and thickness: 1.0~4.0 mm
various outputs (not insulated • Panel cutout size SR82: H68 x W68 mm
from system and various inputs) SR83: H92 x W92 mm
SET VALUE 2 (SV2)/Set Value Bias (SB) (optional) SR84: H92 x W45 mm
(DI option is prerequisite.) • Weight SR82: 300g
• Action input: Nonvoltage contact by SB/SV2 SR83: 420g
selection through DI (external SR84: 280g
switching) input (in action during
closed input)
• Selection of setting Absolute value setting (SV2)
ORDERING INFORMATION Series SR80

ITEMS CODE SPECIFICATIONS


MPU-Based Auto-Tuning PID Digital Controller
SERIES SR82-
DIN H72 × W72 mm
1 Thermocouple User-selectable inputs and ranges
2 R.T.D. User-selectable ranges
DC Voltage User-selectable 0~10, 10~50,
3 -10~10, 0~20, 0~50,
0~100mV DC linear inputs
INPUT
DC Current User-selectable 4~20, Programmable
4
0~20mA DC linear inputs Range
DC Voltage User-selectable 0~1,
6 1~5, -1~1, 0~2, 0~5,
0~10V DC linear inputs
Contact PB Cycle: 1~120 seconds, Contact Capacity:
Y- 240V AC 2.5A / resistive load,
1A / inductive load
Current 4~20mA DC
I-
CONTROL OUTPUT 1 Load resistance: 600 Ω Max.
SSR Voltage PB Cycle 1~120 seconds, Output rating:
P-
12V ±1.5V DC 30mA Max.
Voltage 0~10V DC
V-
Maximum load current: 2mA Max.
CONTROL OUTPUT 2 N- None
90- 100~240V AC ±10% 50/60Hz
POWER SUPPLY 10- 24V AC ±10% 50/60Hz
02- 24V DC ±10%
0 None
1 Contact output, Contact capacity: 240V AC 1A / resistive load
EVENT OUTPUT (2 points) Contact output + Heater break alarm Selectable
2
[OPTION] (with 30A CT) only for
Contact output + Heater break alarm Y or P
3
(with 50A CT) Control output
00 None
Current 4~20mA DC
14
REMOTE INPUT Receiving resistance: 250 Ω
(Not selectable together with Heater Voltage 1~5V DC Non-Isolated
15
break alarm function) [OPTION] Input resistance: 500k Ω Min. input
Voltage 0~10V DC
16
Input resistance: 500k Ω Min.
0 None
ANALOG OUTPUT
3 Voltage 0~10mV DC, Output resistance: 10 Ω
(Not selectable together with Interface
4 Current 4~20mA DC, Load resistance: 300 Ω Max.
function) [OPTION]
6 Voltage 0~10V DC, Load current: 2mA Max.
INTERFACE FUNCTION 0 None
(Not selectable together with Analog output 5 RS-485
function) [OPTION] 7 RS-232C
0 None
EXTERNAL INPUT CONTROL SIGNAL /
Control input 2 points, Non-voltage contact, Open collector
SET VALUE BIAS [OPTION] 1
input (about 5V / 2mA impress)
0 Without
REMARKS
9 With (Please consult before ordering.)
TERMINAL ARRANGEMENT Series SR80

• SR82

DI Analog Output/Interface Power Supply


A-output RS-232C RS-485
15 COM 8
L
8 24V DC
16 SG 16 SG 16 100-240V AC
1 DI 1 N 50/60Hz 12VA or
9 9 24V AC
17 SD 17 17 50/60Hz 9VA
2 DI 2
10 10
RD 18 18 GND GND

Control Output

I, V Output
Contact Output
SSR Drive Output

REM CT 1 15 8 12
12
3 3
2 16 9 13
13
4 4 14
3 17 10
4 18 11
Input 5 19 12
I•V TC RTD Event Output

5 5
A
5
6 20 13
COM 19
B
6 7 21 14 EV 1 20
B EV 2 21
7 7 7

EXTERNAL DIMENSIONS & PANEL CUTOUT

111
100min
72 11 100

OUT PV
EV1

EV2

EV3
SV ˚C
100min

AT REM

MAN STBY
72

SV2/SB COM
68+0.7

DISP
0

AT ENT
SR82 SHIMADEN

68+0.7
0

(Unit : mm)
ORDERING INFORMATION Series SR80

ITEMS CODE SPECIFICATIONS


MPU-Based Auto-Tuning PID Digital Controller
SERIES SR83-
DIN H96 × W96 mm
1 Thermocouple User-selectable inputs and ranges
2 R.T.D. User-selectable ranges
DC Voltage User-selectable 0~10, 10~50,
3 -10~10, 0~20, 0~50,
0~100mV DC linear inputs
INPUT
DC Current User-selectable 4~20, Programmable
4
0~20mA DC linear inputs Range
DC Voltage User-selectable 0~1,
6 1~5, -1~1, 0~2, 0~5,
0~10V DC linear inputs
Contact PB Cycle: 1~120 seconds, Contact Capacity:
Y- 240V AC 2.5A / resistive load,
1A / inductive load
Current 4~20mA DC
I-
CONTROL OUTPUT 1 Load resistance: 600 Ω Max.
SSR Voltage PB Cycle 1~120 seconds, Output rating:
P-
12V ±1.5V DC 30mA Max.
Voltage 0~10V DC
V-
Maximum load current: 2mA Max.
N- None
Contact PB Cycle: 1~120 seconds, Contact Capacity:
Y- 240V AC 2.5A / resistive load,
1A / inductive load
CONTROL OUTPUT 2 Current 4~20mA DC
I-
[OPTION] Load resistance: 600 Ω Max.
SSR Voltage PB Cycle: 1~120 seconds, Output rating:
P-
12V ±1.5V DC 30mA Max.
Voltage 0~10V DC
V-
Maximum load current: 2mA Max.
90- 100~240V AC ±10% 50/60Hz
POWER SUPPLY 10- 24V AC ±10% 50/60Hz
02- 24V DC ±10%
0 None
1 Contact output, Contact capacity: 240V AC 1A / resistive load
EVENT OUTPUT (3 points)
Contact output + Heater break alarm Selectable
(2 points when 2 output option is 2
(with 30A CT) only for
added) [OPTION]
Contact output + Heater break alarm Y or P
3
(with 50A CT) Control output
00 None
Current 4~20mA DC
14
REMOTE INPUT Receiving resistance: 250 Ω
(Not selectable together with Heater Voltage 1~5V DC Non-Isolated
15
break alarm function) [OPTION] Input resistance: 500k Ω Min. input
Voltage 0~10V DC
16
Input resistance: 500k Ω Min.
0 None
ANALOG OUTPUT
3 Voltage 0~10mV DC, Output resistance: 10 Ω
(Not selectable together with CC-Link
4 Current 4~20mA DC, Load resistance: 300 Ω Max.
function) [OPTION]
6 Voltage 0~10V DC, Load current: 2mA Max.
0 None
INTERFACE FUNCTION
5 RS-485
(When CC-Link function is selected, simultaneous
7 RS-232C
selection of Analog output is not possible)
CC-Link (Conforming with Mitsubishi Electric Company's CC-
[OPTION] 8
Link) (Not selectable together with Analog output function)
0 None
EXTERNAL INPUT CONTROL SIGNAL /
Control input 2 points, Non-voltage contact, Open collector
SET VALUE BIAS [OPTION] 1
input (about 5V / 2mA impress)
0 Without
REMARKS
9 With (Please consult before ordering.)
Note: Selection together with ANALOG OUTPUT and INTERFACE FUNCTION (RS485 or RS232C) is possible.
TERMINAL ARRANGEMENT Series SR80

• SR83

Analog Output/Interface
A-output RS-232C RS-485 CC-Link
Power Supply

21 SG 23 SG 23 DA 21 L
11 11 24V DC
100-240V AC
22 SD 24 24 DB 22 N 50/60Hz 12VA or
12 12 24V AC
50/60Hz 9VA
RD 25 25 DG 23
13 13
GND GND
DI SLD 24

FG 25
2 DI 1

3 DI 2 Control Output/One Output Control Output/Two Output


4 COM I, V Output I, V Output
Contact Output SSR Drive Contact Output SSR Drive
Output Output
1 1 21 21 31 31 11 11

14
2 2 22 22 32 32 12 12
14 14 14
REM CT
15 OUT 1
3 3 23 23 33 33 13 13
15 15 15
5 5
4 4 24 24 34 34 14 14 16

6 6
5 5 25 25 35 35 15 15

16 16
6 6 26 26 36 36 16 16
OUT 2
17 17
Input 7 7 27 27 37 37 17 17

I•V TC RTD
8 8 28 28 38 38 18 18

A
7 7 7 9 9 29 29 39 39 19 19
Event Output/One Output Event Output/Two Output
B
8 10 10 30 30 40 40 20 20
COM 17
B COM 18
9 9 9 EV 1 18
EV 1 19
EV 2 19
EV 2 20
EV 3 20

EXTERNAL DIMENSIONS & PANEL CUTOUT

111
96 11 100

130min
PV

SV ˚C
130min
96

SV2 RUN
OUT1 OUT2 EV1 EV2 EV3 AT MAN SB REM STBY COM
92+0.8

DISP
0

AT ENT MADE IN JAPAN

SR83 SHIMADEN

92+0.8
0

(Unit : mm)
ORDERING INFORMATION Series SR80

ITEMS CODE SPECIFICATIONS


MPU-Based Auto-Tuning PID Digital Controller
SERIES SR84-
DIN H96 × W48 mm
1 Thermocouple User-selectable inputs and ranges
2 R.T.D. User-selectable ranges
DC Voltage User-selectable 0~10, 10~50,
3 -10~10, 0~20, 0~50,
0~100mV DC linear inputs
INPUT
DC Current User-selectable 4~20, Programmable
4
0~20mA DC linear inputs Range
DC Voltage User-selectable 0~1,
6 1~5, -1~1, 0~2, 0~5,
0~10V DC linear inputs
Contact PB Cycle: 1~120 seconds, Contact Capacity:
Y- 240V AC 2.5A / resistive load,
1A / inductive load
Current 4~20mA DC
I-
CONTROL OUTPUT 1 Load resistance: 600 Ω Max.
SSR Voltage PB Cycle: 1~120 seconds, Output rating:
P-
12V ±1.5V DC 30mA Max.
Voltage 0~10V DC
V-
Maximum load current: 2mA Max.
N- None
Contact PB Cycle: 1~120 seconds, Contact Capacity:
Y- 240V AC 2.5A / resistive load,
1A / inductive load
CONTROL OUTPUT 2 Current 4~20mA DC
I-
[OPTION] Load resistance: 600 Ω Max.
SSR Voltage PB Cycle 1~120 seconds, Output rating:
P-
12V ±1.5V DC 30mA Max.
Voltage 0~10V DC
V-
Maximum load current: 2mA Max.
90- 100~240V AC ±10% 50/60Hz
POWER SUPPLY 10- 24V AC ±10% 50/60Hz
02- 24V DC ±10%
0 None
1 Contact output, Contact capacity: 240V AC 1A / resistive load
EVENT OUTPUT (3 points)
Contact output + Heater break alarm Selectable
(2 points when 2 output option is 2
(with 30A CT) only for
added) [OPTION]
Contact output + Heater break alarm Y or P
3
(with 50A CT) Control output
00 None
Current 4~20mA DC
14
REMOTE INPUT Receiving resistance: 250 Ω
(Not selectable together with Heater Voltage 1~5V DC Non-Isolated
15
break alarm function) [OPTION] Input resistance: 500k Ω Min. input
Voltage 0~10V DC
16
Input resistance: 500k Ω Min.
0 None
ANALOG OUTPUT
3 Voltage 0~10mV DC, Output resistance: 10 Ω
(Not selectable together with Interface
4 Current 4~20mA DC, Load resistance: 300 Ω Max.
function) [OPTION]
6 Voltage 0~10V DC, Load current: 2mA Max.
INTERFACE FUNCTION 0 None
(Not selectable together with Analog output 5 RS-485
function) [OPTION] 7 RS-232C
0 None
EXTERNAL INPUT CONTROL SIGNAL /
Control input 2 points, Non-voltage contact, Open collector
SET VALUE BIAS [OPTION] 1
input (about 5V / 2mA impress)
0 Without
REMARKS
9 With (Please consult before ordering.)
TERMINAL ARRANGEMENT Series SR80

• SR84

Analog Output/Interface
A-output RS-232C RS-485
Power Supply

21 SG 1 SG 1 L
11 11 24V DC
100-240V AC
22 SD 21 21 N 50/60Hz 12VA or
12 12 24V AC
50/60Hz 9VA
RD 22 22
13 13
GND GND
DI

2 DI 1

3 DI 2 Control Output/One Output Control Output/Two Output


4 COM I, V Output I, V Output
Contact Output SSR Drive Contact Output SSR Drive
Output Output

14
14 14 14
REM CT 1 1 11 11
15 OUT 1
15 15 15
5 5 2 2 12 12
16

6 6 3 3 13 13

4 4 14 14 16 16
OUT 2
5 5 15 15 17 17
Input
I•V TC RTD 6 6 16 16

7 7
A
7
7 7 17 17

Event Output/One Output Event Output/Two Output


B 8
8 8 18 18
COM 17
B COM 18
9 9 9 9 9 19 19 EV 1 18
EV 1 19
EV 2 19
10 10 21 22 20 20 EV 2 20
EV 3 20
21 22

EXTERNAL DIMENSIONS & PANEL CUTOUT

111
48 11 100 45+0.6
0

PV
92+0.8
0

SV
130min.
96

OUT1 OUT2 EV1 EV2 EV3 AT

SV2
MAN SB REM STBY COM

DISP

AT ENT 48 x N-3 +10

SR84
92 +0.8
0

(Unit : mm)
MEASURING RANGE CODES Series SR80

Input type Code Measuring range Code Measuring range Note: The following codes represent the respective factory-set
*1 B 01 0 1800 °C 15 0 3300 °F measuring ranges.
R 02 0 1700 °C 16 0 3100 °F
S 03 0 1700 °C 17 0 3100 °F Input Standard/rating Code Measuring range
K1 04 -100.0 400.0 °C 18 -150 750 °F Thermocouple JIS K 05 0.0 800.0°C
K2 05 0.0 800.0 °C 19 0 1500 °F R.T.D. JIS Pt100 07 0.0 200.0°C
K3 06 -200 1200 °C 20 -300 2200 °F Voltage (mV) 0 10mV DC 02 0.0 100.0
E 07 0 700 °C 21 0 1300 °F Voltage (V) 1 5V DC 05 0.0 100.0
Thermocouple

J 08 0 600 °C 22 0 1100 °F Current (mA) 4 20mA DC 02 0.0 100.0


T 09 -199.9 200.0 °C 23 -300 400 °F
Note: If you change a measuring range code, all measuring
N 10 0 1300 °C 24 0 2300 °F
ranges related to data such as SV value, event set values,
PLII 11 0 1300 °C 25 0 2300 °F
PID are initialized.
WRe5-26 12 0 2300 °C 26 0 4200 °F
Note: When a type code of event, remote input or analog output
U 13 -199.9 200.0 °C 27 -300 400 °F is changed, all data related to it are initialized.
L 14 0 600 °C 28 0 1100 °F
K 29 10.0 350.0 K
AuFe-Cr 30 0.0 350.0 K
K 31 10 350 K
ACCESSORY REQUIRED FOR HEATER BREAK ALARM FUNCTION
AuFe-Cr 32 0 350 K
• CT wiring
01 -200 600 °C 17 -300 1100 °F To CT terminal
02 -100.0 100.0 °C 18 -150.0 200.0°F (Without polarity)
03 -100.0 300.0 °C 19 -150 600 °F
Pt100
04 -50.0 50.0 °C 20 -50.0 120.0°F
(New)
05 0.0 50.0 °C 21 0.0 120.0°F
JIS/IEC
06 0.0 100.0 °C 22 0.0 200.0°F Heater power supply cable
07 0.0 200.0 °C 23 0.0 400.0°F
R.T.D.

08 0.0 500.0 °C 24 0 1000 °F


09 -200 500 °C 25 -300 1000 °F
10 -100.0 100.0 °C 26 -150.0 200.0 °F
11 -100.0 300.0 °C 27 -150 600 °F • 30A (CTL-6-S) 21
JPt100
12 -50.0 50.0 °C 28 -50.0 120.0 °F 15 2.8

7.5
(Old)
13 0.00 50.00 °C 29 0.0 120.0 °F ø5.8
JIS
14 0.0 100.0 °C 30 0.0 200.0 °F

25
200.0 °C 31 400.0 °F
10.5

15 0.0 0.0
3
16 0.0 500.0 °C 32 0 1000 °F
40
mV -10 10 01 30
0 10 02 The scaling function allows you to select
10

0 20 03 any value within the following ranges:


5

2-ø3.5
0 50 04
10 50 05 Scaling range: -1999~9999 count
Span: 10~5000 count • 50A (CTL-12-S36-8) 30 2.36
0 100 06
but lower limit side < higher limit side
9

V -1 1 01 ø12

0 1 02 *1 Thermocouple B: 400 ˚C and 750 ˚F


ø12
40

0 2 03 or below is not covered by accuracy


0 5 04 guarantee.
1 5 05 40
2-M3
0 10 06 5 30 5

mA 0 20 01
15

4 20 02 (Unit : mm)
7.5

Warning
• The SR80 series is designed for the control of temperature, humidity and other physical values of general industrial
equipment. (It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety.)
Caution
• If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists, proper
safety measures must be made before the instrument is put into use so as to prevent the occurrence of trouble.

ISO 9001
(The contents of this brochure are subject to change without notice.)