YKW U1000
YKW U1000
Technical Manual
Type: CIMR-U
Rated Output Current: 200 V Class: 22 to 248 A
400 V Class: 9.6 to 414 A
To properly use the product, read this manual thoroughly and retain for
easy reference, inspection, and maintenance. Ensure the end user receives
this manual.
Receiving 1
Mechanical Installation 2
Electrical Installation 3
Start-Up Programming &
Operation 4
Parameter Details 5
Troubleshooting 6
Periodic Inspection &
Maintenance 7
Peripheral Devices &
Options 8
Specifications A
Parameter List B
MEMOBUS/Modbus
Communications
C
Standards Compliance D
MANUAL NO. SIEP C710636 03A
Quick Reference Sheet E
Copyright © 2014 YASKAWA ELECTRIC CORPORATION.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior
written permission of Yaskawa. No patent liability is assumed with respect to the use of the information
contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the
information contained in this manual is subject to change without notice. Every precaution has been taken in
the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
Preset parameter defaults are available for setting up applications. Refer to Application Selection on page 110.
U1000 can operate synchronous PM motors. Refer to Subchart A-3: Operation with Permanent Magnet Motors on page 108.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 116.
Standards Compliance
YEG
Refer to European Standards on page 518.
Refer to UL Standards on page 521.
1. RECEIVING .............................................................................................................. 27
1.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.2 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
U1000 Model Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Control Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.3 Model Number and Nameplate Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.4 Drive Models and Enclosure Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.5 Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
IP00 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
IP20/NEMA Type 1 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Front Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2. MECHANICAL INSTALLATION............................................................................... 39
2.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2.2 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Installation Orientation and Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Instructions on Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Digital Operator Remote Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Exterior and Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
i.1 PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
i.2 GENERAL SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
i.1 Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection
and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa
accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances
should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without
exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All
systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with
appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa
must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in
conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR
IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims
arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of U1000 Series Drives. Read this manual before
attempting to install, operate, maintain, or inspect a drive and keep it in a safe, convenient location for future reference.
Be sure you understand all precautions and safety information before attempting application.
Applicable Documentation
The following manuals are available for U1000 series drives:
Symbols
Note: Indicates a supplement or precaution that does not cause drive damage.
Trademarks
• CANopen is a trademark of CAN in Automation (CiA).
• CC-Link is a trademark of CC-Link Partner Association (CLPA).
• DeviceNet is a trademark of Open DeviceNet Vendor Association, Inc. (ODVA).
• PROFIBUS-DP is a trademark of PROFIBUS International (PI).
• MECHATROLINK-II and MECHATROLINK-III are a trademark of MECHATROLINK Members Association
(MMA).
• LONWORKS is a trademark of ECHELON USA.
• Modbus TCP/IP is a trademark of Modbus-IDA.
• EtherNet/IP is a trademark of the ODVA.
• Other companies and product names mentioned in this manual are trademarks of those companies.
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Restore covers or
shields before operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to
all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be
changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest
Yaskawa sales office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest
Yaskawa sales office.
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed
according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could
result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings
in this manual.
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Before servicing, disconnect all power to the equipment. The capacitor for the control power supply remains charged
even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on
the drive before touching any components.
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft
keys and machine loads before applying power to the drive.
When using DriveWorksEZ to create custom programming, the drive I/O terminal functions change from
factory settings and the drive will not perform as outlined in this manual.
Unpredictable equipment operation may result in death or serious injury.
Take special note of custom I/O programming in the drive before attempting to operate equipment.
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
When an EMC filter is installed or with models CIMR-U40414 and larger, the leakage current exceeds 3.5 mA.
Therefore according to IEC/EN 61800-5-1 automatic power supply interruption in case of discontinuity of the
protective earthing conductor must be provided or a protective earthing conductor with a cross section of at least 10
mm2 (Cu) or 16 mm2 (Al) must be used.
Use appropriate equipment for residual current monitoring/detection (RCM/RCD).
This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual
current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use
an RCM or RCD of type B according to IEC/EN 60755.
WARNING
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Crush Hazard
Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental
dropping of the load.
The drive does not possess built-in load drop protection for lifting applications.
Failure to comply could result in death or serious injury from falling loads.
Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry.
If using a crane or a lifter to transport the drive, make sure that only qualified personnel are allowed operating.
Incorrect operation may cause the drive to suddenly drop, resulting in serious injury.
Only allow qualified personnel to operate a crane or hoist to transport the drive.
Failure to comply could result in death or serious injury from falling equipment.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the
wiring and the selection of the peripheral devices.
Contact your supplier if the cause cannot be identified after checking the above.
Do not restart the drive or immediately operate the peripheral devices if a fuse is blown or equipment for
residual current monitoring/detection (RCM/RCD) is tripped.
Check the wiring and the selection of peripheral devices to identify the cause.
Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class), 480 Vac maximum (400 V Class: CIMR-U4E, CIMR-U4W), and 500 Vac
maximum (400 V Class: CIMR-U4A, CIMR-U4P).
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Application Notes
Selection
Drive Rated Output Current
Make sure that the motor rated current is less than the rated output current for the drive.
When running more than one motor in parallel from a single drive, the capacity of the drive should be larger than [motor
rated current 1.1]. Run only one motor from each drive when using vector control. It is not possible to run more than
one motor from one drive with vector control.
When 2 Seconds is Required for Momentary Power Loss Ride-Thru Time
Use the units listed below when continuing drive operation after the power is restored even after a momentary loss of
power of 2 seconds occurs:
• 200 V class Momentary Power Loss Ride-Thru unit: Model No. P0010
• 400 V class Momentary Power Loss Ride-Thru unit: Model No. P0020
Drive Start-Up Time
The drive requires 1.5 seconds to prepare for operation after the power is turned on. Be mindful of this delay when using
an external reference input.
Note: 1.5 seconds is the required time when no optional devices are used with the drive. When using an optional communication
device, the time required for the drive to be ready for operation will vary in accordance with the start up time of the
communication card.
Repetitive Starting/Stopping
Cranes (hoists), elevators, punching presses, and other such applications with frequent starts and stops often exceed
150% of their rated output current values. Heat stress generated from repetitive high current can shorten the life span of
the IGBTs. The expected lifetime of the IGBTs is about 8 million start and stop cycles with a 4 kHz carrier frequency and
a 150% peak current.
For crane-type applications using an inching function in which the motor is quickly started and stopped, Yaskawa
recommends selecting a large enough drive so that peak current levels remain below 150% of the drive rated current.
Run only one motor from each drive when using vector control. It is not possible to run more than one motor from one
drive with vector control.
Carrier Frequency Derating
When the carrier frequency of the drive is increased above the factory default setting, the rated output current of the drive
should be reduced. Refer to Carrier Frequency Derating on page 398 for details.
Installation
Enclosure Panels
Keep the drive in a clean environment by either selecting an area free of airborne dust, lint, and oil mist, or install the
drive in an enclosure panel. Be sure to leave the required space between drives to provide for cooling, and that proper
measures are taken so that the ambient temperature remains within allowable limits. Keep flammable materials away
from the drive. If the drive must be used in an area where it is subjected to oil mist and excessive vibration, protective
designs are available. Contact Yaskawa or your Yaskawa agent for details.
Installation Direction
The drive should be installed upright as specified in the manual. For more information on installation, refer to
Mechanical Installation on page 42.
Settings
Upper Limits
The drive is capable of running the motor up to 400 Hz. Due to the danger of accidentally of operating at high speed, be
sure to set the upper limit for the frequency. The default setting for the maximum output frequency is 50 Hz.
DC Injection Braking
Motor overheat can result if there is too much current used during DC Injection Braking, or if the time for DC Injection
Braking is too long.
Acceleration/Deceleration Times
Acceleration and deceleration times are affected by how much torque the motor generates, the load torque, and the
moment of inertia. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened
for as long as the Stall Prevention function is operating. For faster acceleration and deceleration, use a larger drive and
motor.
General Handling
Wiring Check
Be sure to perform a final check of all sequence wiring and other connections before turning the power on. Make sure
there are no short circuits on the control terminals (+V, AC, etc.), as this could damage the drive.
Selecting a Circuit Breaker or Leakage Circuit Breaker
Yaskawa recommends installing equipment for residual current monitoring/detection (RCM/RCD) to the power supply
side. The RCM/RCD should be designed for use with an AC drive (e.g. Type B according to IEC/EN 60755).
Select a MCCB (Molded Case Circuit Breaker) or RCM/RCD with a rated current that is 1.5 to 2 times higher than the
rated current of the drive in order to avoid nuisance trips caused by harmonics in the drive input current. Also refer to
Installing a Molded Case Circuit Breaker (MCCB) and Equipment for Residual Current Monitoring/Detection
(RCM/RCD) on page 388.
Single-Phase Motor
Variable speed drives are not designed for operation with single phase motors. Using capacitors to start the motor causes
excessive current to flow and can damage drive components. A split-phase start or a repulsion start can end up burning
out the starter coils because the internal centrifugal switch is not activated. The U1000 is for use with three-phase motors
only.
Motor with Brake
Caution should be taken when using a drive to operate a motor with a built-in holding brake. If the brake is connected to
the output side of the drive, it may not release at start due to low voltage levels. A separate power supply should be
installed for the motor brake. Motors with a built-in brake tend to generate a fair amount of noise when running at low
speeds.
Notes on Power Transmission Parts (belts, chains, gear boxes, ...)
Installing a drive in a machine that was directly connected to the power supply allows to adjust the machine speed.
Continuous operation above or below the rated speed can wear out lubrication material in gear boxes and other power
transmission parts. In order to avoid machine damage make sure lubrication is sufficient within the whole speed range.
Note that operation above the rated speed can increase the noise generated by the machine.
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor
discharge after disconnecting
power supply.
To conform to rrequirements,
make sure to ground the supply
neutral for 400V class.
After disconnecting from power
supply,please wait 5 minutes
before inspecting, performing
maintenance or wiring the
converter.
Hot Surfaces
Wait 5 minutes or longer
until the unit has cooled.
Figure i.1 Warning Information
Figure i.2
Warning Label
Warranty Information
Restrictions
U1000 was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives
or health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health
care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa
representatives or the nearest Yaskawa sales office.
This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in
any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a
facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the
likelihood of any accident.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor connected to a U1000 may operate at a higher temperature than a utility-fed motor and the operating
speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the
additional heating with the intended operating conditions.
Note: Current derating is required when setting the carrier frequency higher. Refer to Carrier Frequency Derating on page 398 for
details.
Receiving
1
<1> Use a larger drive or increase the drive capacity to achieve this value.
<2> Available when High Frequency Injection is enabled (n8-57 = 1).
Nameplate
Figure 1.1
YEG
FILE NO : E131457
PASS
YASKAWA ELECTRIC CORPORATION MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan <1>
<1> The address of the head office of Yaskawa Electric Corporation (responsible for
product liability) is shown on the nameplate.
Figure 1.1 Nameplate Information
Receiving
1
Model Number
CIMR - U C 2 A 0028 A A A
U1000 Series Customized Enclosure Design
No. No. Type
Specifications Revision
A Standard model A IP00 Order
No. Region
Code EMC Noise Filter NEMA
E Built-in F Type 1
C Europe
24 V Power
P Supply Unit
Built-in Environmental
No.
EMC Noise Filter Specification <1>
and 24 V Power A Standard
W Supply Unit
Built-in K Gas-resistant
M Humidity- and
dust-resistant
No. Voltage Class N Oil-resistant
S Vibration-resistant
YEC_common 2
4
3-phase, 200-240 Vac
3-phase, 380-480 Vac
Refer to Table 1.3 and Table 1.4.
<1> Drives with these specifications do not guarantee complete protection for the
environmental conditions indicated.
Three-Phase 200 V
Table 1.3 Model Number and Specifications (200 V)
Rated Output Current (A)
No. Heavy Duty (HD) Normal Duty (ND)
[C6-01 = 0] [C6-01 = 1]
0028 22 28
0042 28 42
0054 42 54
0068 54 68
0081 68 81
0104 81 104
0130 104 130
0154 130 154
0192 154 192
0248 192 248
Three-Phase 400 V
Table 1.4 Model Number and Specifications (400 V)
Rated Output Current (A)
No. Heavy Duty (HD) Normal Duty (ND)
[C6-01 = 0] [C6-01 = 1]
0011 9.6 11
0014 11 14
0021 14 21
0027 21 27
0034 27 34
0040 34 40
0052 40 52
0065 52 65
0077 65 77
0096 77 98
0124 96 124
0156 124 156
0180 156 180
0216 180 216
0240 216 240
0302 240 302
0361 302 361
0414 361 414
Note: 1. Use parameter C6-01 to select between Normal duty and Heavy duty (default).
2. Refer to Drive Models and Enclosure Types on page 33 for differences regarding enclosure protection types and component
descriptions.
Receiving
40180A 40180F <1>
40216A 40216F <1>
40240A 40240F <1>
40302A 40302F <1>
40361A 40361F <1>
1
40414A 40414F <1>
<1> Remove the top protective cover when installing an IP20/NEMA Type 1 enclosure drive in a cabinet. Removing the top protective cover
from a IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while retaining IP20 conformity. Attaching a top protective
cover and bottom cover to an IP00 enclosure drive will convert the drive to an IP20/NEMA Type 1 enclosure drive.
IP00 Enclosure
Three-Phase AC200 V CIMR-U20028A to 20081A
Three-Phase AC400 V CIMR-U40011A to 40077A
Figure 1.2
F
A
E B
common_TMonly
F A
B
D
common_TMonly
G
A
B
F
E
D
common_TMonly
A – Cooling fan E – Front cover
B – Heatsink F – Drive cover
C – Terminal cover G – Hanging bracket
D – Digital operator
Figure 1.4 IP00 Enclosure Components
(CIMR-U20154A)
Receiving
H
A
common_TMonly
G B 1
E
D
H
A
G
F B
common_TMonly
H
A
G
E B
common_TMonly
I
A
H
F
E
common_TMonly
Receiving
J
A
I
common_TMonly
H 1
B
F
E
Front Views
Figure 1.10
common_
TMonly
C
C A
NOTICE
Equipment Hazard
Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during drive
installation and project construction.
Failure to comply could result in damage to the drive.
Place a temporary cover over the top during installation. Be sure to remove the temporary cover before start-up, as the
cover will reduce ventilation and cause the unit to overheat.
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and
may lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is
required continuously at low speed, consider using a special drive or vector-control motor. Select a motor that is
compatible with the required load torque and operating speed range.
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special
attention to the motor insulation voltage or use a drive-rated motor with reinforced insulation.
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously
operated at a constant speed.
Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the
machine.
The motor may require more acceleration torque with drive operation than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor.
The rated input current of submersible motors is higher than the rated input current of standard motors.
Mechanical
Select an appropriate drive according to its rated output current. When the distance between the motor and drive is
Installation
long, use a cable thick enough to connect the motor to the drive to prevent motor torque reduction.
The current rating differs for a motor with variable pole pitches differs from a standard motor.
Check the maximum current of the motor before selecting the drive capacity. Only switch motor poles when the motor 2
is stopped. Switching between motor during run will trigger overcurrent protection circuitry or result in overvoltage
from regeneration, and the motor will simply coast to stop.
When using an explosion-proof motor, it must be subject to an explosion-proof test in conjunction with the
drive.
This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is
not explosion-proof, always install it in a safe place.
Never lift the drive up while the cover is removed.
This can damage the terminal board and other components.
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in an environmental matching the
specifications in Table 2.1.
Table 2.1 Installation Environment
Environment Conditions
Installation Area Indoors
IP00 enclosure: -10°C to +50°C
IP20/NEMA Type 1 enclosure: -10°C to +40°C
Drive reliability improves in environments without wide temperature fluctuations.
Ambient Temperature
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure
does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
Surrounding Area • combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Altitude 1000 m, up to 3000 m with derating (for details, refer to Altitude Derating on page 399)
10 to 20 Hz at 9.8 m/s2
Vibration 20 to 55 Hz at 5.9 m/s2 (CIMR-U20028 to 20081, 40011 to 40077)
20 to 55 Hz at 2.0 m/s2 (CIMR-U20104 to 20248, 40096 to 40414)
Orientation Install the drive vertically to maintain maximum cooling effects.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the
temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
A
C
B B E
A D
Instructions on Installation
Eye bolts and hanging brackets are used to install the drive or to temporarily lift the drive when replacing it. Using the
eye bolts and hanging brackets, the drive can be installed in an enclosure panel or on a wall. Do not leave the drive
suspended by the wires in a horizontal or vertical position for long periods of time. Do not transport the drive over long
distances. Read the following precautions and instructions before installing the drive.
WARNING! Crush Hazard. Observe the following instructions and precautions. Failure to comply could result in serious injury or death
from falling equipment.
• Only use vertical suspension to temporarily lift the drive during installation to an enclosure panel. Do not
Mechanical
Installation
use vertical suspension to transport the drive.
• Confirm that the spring washer is completely closed prior to lifting to prevent damage to the drive.
• Use screws to securely affix the drive front cover, terminal blocks, and other drive components prior to
vertical suspension.
• Do not subject the drive to vibration or impact greater than 1.96 m/s2 (0.2 G) while it is suspended by the
wires. 2
• Do not leave the drive unattended while it is suspended by the wires.
Figure 2.3
• Do not attempt to flip the drive over while it is suspended by the wires.
D
B
C
A
A – No space between drive and washer C – Space between drive and washer
B – Spring washer fully closed D – Spring washer open
Figure 2.3 Spring Washer
Horizontal Suspension of the Drive Models 20154 to 20248 and 40156 to 40414
To make a wire hanger or frame for use when lifting the drive with a crane, lay the drive in a horizontal position and pass
a wire through the hanging brackets.
Note: Use the hanging brackets on the top and hanging holes of the bottom cover when lifting models 20154F, 20192F, 40156F,
40180F.
Figure 2.4
1. Pass wire through the holes of the two eye bolts or two hanging brackets.
Figure 2.5
Suspending angle:
50 degree or greater
Figure 2.5 Drive Suspension Using Wires and Eye Bolts (20028 to 20130, 40011 to 40124)
2. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
3. Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor then
begin lowering the drive again very slowly until the drive is placed correctly.
1. Remove the two hanging brackets from the drive lower side panels and bolt them on the top panel.
Note: 1. Tighten the hanging brackets with the specified tightening torque: M10: 18 to 23 Nm, M12: 32 to 40 Nm.
2. Four hanging brackets are attached to the top of NEMA Type 1 drives 20154F, 20192F, 40156F, and 40180F.
Figure 2.6
Suspending angle:
50° or greater
Mechanical
Installation
Figure 2.7 Drive Suspension Using Wires and Hanging Brackets (20154 to 20248, 40156 to 40414)
3. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight. 2
4. Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor,
then slowly begin lowering the drive again very slowly until the drive is placed correctly.
Drive Operator
Comm Port
S / N : J007XE273710001
common_
TMonly
Communication Cable Connector
S / N : J007XE273710001
90
78
15
7.9 44
60
minimum
50 Unit: mm
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during
installation. Remove the temporary cover before drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.11.
2. Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in
Figure 2.10.
Figure 2.9
Digital Operator M3 × 6
Phillips recessed
pan head machine screw × 2
Enclosure panel
common_TMonly
Unit: mm
Figure 2.10 External/Face-Mount Installation
Figure 2.10
Mechanical
Installation
22
common_TMonly
2
78
26
22
2
22
14
Unit: mm
Internal/Flush-Mount
An internal flush-mount requires an installation support set that must be purchased separately. Contact your Yaskawa
representative to order an installation support set and mounting hardware. Figure 2.12 illustrates how to attach the
Installation Support Set A.
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.13.
2. Mount the digital operator to the installation support.
3. Mount the installation support set and digital operator to the enclosure panel.
Figure 2.11
Enclosure panel
Digital Operator
M4 × 10 Installation Support Set A
Phillips truss head screw × 4 M3 × 6
(for panel widths between 1 and 1.6) Phillips recessed
pan head machine screw × 2
common_TMonly
Unit: mm
120
45 common_TMonly
59 +0.5
0
Unit: mm
Mechanical
Installation
2
H4
4-d
H1
H
t1
H2
W D1
D
common_TMonly Figure 1
W1
H4
4-d t2
H1
t1
D1
H2
W D
Figure 2
H4
W1 4-d t2
H1
H
t1
H2
Max 15 W Max 15 D1
D
Figure 3
W1 common_TMonly
H4
W2 W2 6-d
t2
H1
H
t1
H2
D1
Max 15 Max 15 D
Figure 4
Table 2.4 Dimensions for IP00 Enclosure: 200 V Class
Dimensions (mm) Weight (kg)
Model
Figure CIMR-U CIMR-U
CIMR-U W H D W1 W2 H1 H2 H4 D1 t1 t2 d 2A/2P 2E/2W
20028A 250 480 360 205 – 463 6.5 40 100 2.3 4 7 20 21
20042A
32 33
20054A 1
264 650 420 218 – 629 11.5 40 115.5 2.3 4 10
20068A
35 36
20081A
20104A
2 264 816 450 218 – 795 11.5 40 124.5 2.3 2.3 10 60 63
20130A
20154A
3 415 990 403 250 – 966 11 40 165 4.5 3.9 12 110 115
20192A
20248A 4 490 1132 450 360 180 1104 14.5 49 181 4.5 4.5 14 176 181
Mechanical
Installation
CIMR-U Figure CIMR-U CIMR-U
W H D W1 W2 H1 H2 H4 D1 t1 t2 d 4A/4P 4E/4W
40011A
40014A
40021A 250 480 360 205 – 463 6.5 40 100 2.3 4 7 20 21
40027A 2
40034A 1
40040A
32 33
40052A
264 650 420 218 – 629 11.5 40 115.5 2.3 4 10
40065A
35 36
40077A
40096A
2 264 816 450 218 – 795 11.5 40 124.5 2.3 2.3 10 60 63
40124A
40156A
3 415 990 403 250 – 966 11 40 165 4.5 3.9 12 110 115
40180A
40216A
490 1132 450 360 180 1104 14.5 49 181 4.5 4.5 14 176 181
40240A
40302A 4
40361A 695 1132 450 560 280 1102 14.5 65 178 4.5 4.5 14 259 267
40414A
H4
H1
H0
H
t1
H2
H3
D1
W D
Figure 1
W1 4-d common_TMonly t2
H4
H1
H0
H
t1
H3
H2
D1
W
D
Figure 2
common_TMonly
H4
W1 4-d t2
H1
H0
H
H3
H2
t1
D1
Max 15 W Max 15
D
Figure 3
W1 common_TMonly
H4
6-d
W2 W2 t2
H1
H0
H
H2
H3
t1
D1
Max 15 W Max 15 D
Figure 4
Mechanical
Installation
Dimensions (mm) Weight (kg)
Model
CIMR-U Figure CIMR-U CIMR-U
W H D W1 W2 H0 H1 H2 H3 H4 D1 t1 t2 d
4A/4P 4E/4W
40011F
40014F
2
40021F 250 524 360 205 – 480 463 6.5 42 40 100 2.3 4 7 21.5 22.5
40027F
40034F 1
40040F
34 35
40052F
264 705 420 218 – 650 629 11.5 54 40 115.5 2.3 4 10
40065F
37 38
40077F
40096F
2 264 885 450 218 – 816 795 11.5 68 40 124.5 2.3 2.3 10 62 65
40124F
40156F
3 415 1107 403 250 – 990 966 11 85 8 165 4.5 3.9 12 113 118
40180F
40216F
490 1320 450 360 180 1132 1104 14.5 169 29 181 4.5 4.5 14 180 185
40240F
40302F 4
40361F 695 1460 450 560 280 1132 1102 14.5 300 29 178 4.5 4.5 14 270 278
40414F
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning
work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the
power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive
before touching any components.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the drive to a combustible surface. Never place combustible materials on the drive.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive.
Carefully review instruction manual when connecting, wiring, or replacing the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
Electrical Installation
3
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the
motor insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.
NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in damage to the drive. Refer to
Control I/O Connections on page 80 for details.
N.O.
Slide Switch S6
DM+,DM-
N.C./N.O. Selection
N.C.
Electrical Installation
M6
<5> −V Power supply, -10.5 Vdc, max. 20 mA 30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Termination resistor
(120 Ω, 1/2 W) MP Multi-function pulse train output
(Output frequency)
AC 0 to 32 kHz (2.2 kΩ)
DIP
Switch S2
R+ 0V
R <8>
MEMOBUS/Modbus S+ FM
comm. RS-422/RS-485 + Multi-function analog output 1
(Output frequency)
max. 115.2 kbps S FM -10 to +10 Vdc (2mA) or 4 to 20 mA
Safety
Switch IG <9> <10>
AM
S2
<11>
Safe Disable inputs H1
AC
AM
+ Multi-function analog output 2
(Output current)
-10 to +10 Vdc (2mA) or 4 to 20 mA
3
S1 H2 0V
EMC filter <10>
Switch <14>
E (G)
ON
Open Wire OFF EDM (Safety Electronic Device Monitor)
jumper
Safety relay / DM+ shielded line
controller <12> <13>
HC twisted-pair shielded line
DM
24 V 24 control circuit terminal
24 V Power Supply
0V 0 Unit Terminals <15> main circuit terminal
FE
<1> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply.
<2> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install the wire link
between terminals SC-SP for Sink mode and SC-SN for Source mode. Leave it out for external power supply. Never short terminals SP and
SN as doing so will damage the drive.
<3> The maximum current supplied by this voltage source is 150 mA if no digital input option card DI-A3 is used.
<4> Wire the fault relay output separately from the main circuit power supply and other power lines.
<5> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and AC, as
this can cause erroneous operation or damage the drive.
<6> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<7> Set DIP switch S4 to select between analog or PTC input for terminal A3.
<8> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
<9> Use jumper S5 to selection between voltage or current output signals at terminal AM and FM. Set parameters H4-07 and H4-08 accordingly.
<10> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as
a feedback-type of signal.
<11> Use jumper S3 to select between Sink mode, Source mode or external power supply for the Safe Disable inputs.
<12> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
<13> Slide the switch S6 to select N.C. or N.O. as the state of the DM+ and DM- terminals for EDM output.
<14> Models CIMR-UE and W have EMC filter switch.
<15> Models CIMR-UP and W have terminals 24, 0, and FE.
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal
parameters are properly set. Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire
control, a momentary closure on terminal S1 may cause the drive to start.
WARNING! Sudden Movement Hazard. When using a 3-Wire sequence, set the drive to 3-Wire sequence prior to wiring the control
terminals and set parameter b1-17 to 0 so the drive will not accept a Run command at power up (default). If the drive is wired for a
3-Wire sequence but set up for a 2-Wire sequence (default), and parameter b1-17 is set to 1 so the drive accepts a Run command at
power up, the motor will rotate in reverse direction at drive power up and may cause injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before executing the application preset
function. Executing the application preset function or setting A1-06 0 will change the drive I/O terminal functions and may cause
unexpected equipment operation. Failure to comply may cause death or serious injury.
WARNING! When using the automatic fault restart function with wiring designed to shut off the power supply upon drive fault, make
sure the drive does not trigger a fault output during fault restart (L5-02 = 0, default). Failure to comply will prevent the automatic fault
restart function from working properly.
p1
Control common_
n1
board
TMonly
Control power supply
R/L1 U/T1
T/L3 W/T3
Electrical Installation
3
Figure 3.2
common_
TMonly
CHARGE
n1 p1 R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
CHARGE
common_
TMonly
Figure 3.3 Main Circuit Terminal Arrangements (20042 to 20081, 40040 to 40077)
Figure 3.4
n1 p1
common_
TMonly
Electrical Installation
R/L1 S/L2 T/L3 U/L1 V/L2 W/L3
Figure 3.4 Main Circuit Terminal Arrangements (20104, 20130, 40096, 40124)
Figure 3.5
SW 24 0 FE 3
n1 p1
common_
TMonly
Figure 3.5 Main Circuit Terminal Arrangements (20154, 20192, 40156, 40180)
SW
OFF
ON
▼
n1 p1
common_
TMonly
n1 p1
common_
TMonly
R/L1 S/L2 T/L3 U/L1 V/L2 W/L3
common_
TMonly
Figure 3.8 Removing the Terminal Cover
2. Push in on the hook located on the bottom of the terminal cover, and gently pull forward. This should remove the
terminal cover.
Figure 3.9
Electrical Installation
common_
TMonly
Figure 3.9 Removing the Terminal Cover
common_
<1> TMonly
Figure 3.10 Reattaching the Terminal Cover
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
common_
TMonly
Figure 3.11 Removing the Terminal Cover
2. Pull forward on the terminal cover to free it from the drive.
Figure 3.12
common_
TMonly
common_
<1> TMonly
common_
TMonly
Figure 3.14 Removing the Digital Operator
common_
Electrical Installation
TMonly
common_
TMonly
Figure 3.16 Remove the Front Cover (20028 to 20130, 40011 to 40124)
common_
TMonly
Hook Hook
Front cover
installation screw
Figure 3.17 Remove the Front Cover (20154 to 20248, 40156 to 40414)
4. Unhook the left side of the front cover then swing the left side towards you as shown in the figure below until the
cover comes off.
Figure 3.18
common_
TMonly
Figure 3.18 Remove the Front Cover (20154 to 20248, 40156 to 40414)
common_
TMonly
Figure 3.19 Reattach the Front Cover (20154 to 20248, 40156 to 40414)
2. Once the hooks have connected to the drive, press firmly on the cover to make sure it locks into place.
common_TMonly
Electrical Installation
Type 1 protection while maintaining IP20 conformity.
Figure 3.21
common_TMonly
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC
bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from
switching the drive on and off more than once every 30 minutes.
Figure 3.22 Main Circuit Protective Cover (20028 to 20081, 40011 to 40077)
Attach the protective covers after wiring the main circuit terminals, p1, and n1 terminals on models 20104 to 20248,
40096 to 40414.
Figure 3.23
Electrical Installation
Three-Phase 200 V Class
Table 3.4 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
For Asia <1> For U.S.A. <2> For Europe and China <3>
Model Screw Tightening
Terminal Recomm. Applicable Recomm. Applicable Recomm. Applicable Torque
CIMR-U Gauge Gauge Gauge Gauge Gauge Gauge Size Nm (lb.in.)
mm2 mm2 AWG, kcmil AWG, kcmil mm2 mm2
R/L1, S/L2, T/L3 5.5 3.5 to 8 8 10 to 8 4 2.5 to 10 M5 2.3 to 2.7
U/T1, V/T2, W/T3 5.5 3.5 to 8 8 10 to 8 4 2.5 to 10 M5 (20.4 to 23.9) 3
20028 3.9 to 4.9
5.5 5.5 to 14 8 10 to 6 6 6 to 16 M6
(34.7 to 43.4)
1 to 1.4
p1, n1 2 2 to 3.5 14 14 to 12 2.5 2.5 to 4 M4
(8.9 to 12.4)
R/L1, S/L2, T/L3 14 5.5 to 22 6 8 to 3 10 5.5 to 25 M6 4 to 6
U/T1, V/T2, W/T3 14 5.5 to 22 6 8 to 3 10 5.5 to 25 M6 (35.4 to 53.1)
For Asia <1> For U.S.A. <2> For Europe and China <3>
Tightening
Model Terminal Recomm. Applicable Recomm. Applicable Recomm. Applicable Screw Torque
CIMR-U Gauge Gauge Gauge Gauge Gauge Gauge Size Nm (lb.in.)
mm2 mm2 AWG, kcmil AWG, kcmil mm2 mm2
R/L1, S/L2, T/L3 30 22 6 2P 6 to 3 2P 25 16 to 25 M6 4 to 6
U/T1, V/T2, W/T3 30 22 6 2P 6 to 3 2P 25 16 to 25 M6 (35.4 to 53.1)
For Asia <1> For U.S.A. <2> For Europe and China <3>
Tightening
Model Recomm. Applicable Recomm. Applicable Recomm. Applicable Screw
CIMR-U Terminal Torque
Gauge Gauge Gauge Gauge Gauge Gauge Size Nm (lb.in.)
mm2 mm2 AWG, kcmil AWG, kcmil mm2 mm2
R/L1, S/L2, T/L3 5.5 3.5 to 8 8 10 to 8 4 2.5 to 10 M5 2.3 to 2.7
U/T1, V/T2, W/T3 5.5 3.5 to 8 8 10 to 8 4 2.5 to 10 M5 (20.4 to 23.9)
Electrical Installation
40096 8.8 to 10.8
22 22 to 38 4 4 to 1 25 10 to 35 M8
(78.1 to 95.5)
1.2 to 2.0
p1, n1 2 2 to 3.5 14 14 to 12 2.5 2.5 to 4 M4
(10.6 to 17.7)
R/L1, S/L2, T/L3 22 2P 14 to 60 2P 4 2P 6 to 1/0 2P 16 2P 10 to 50 2P M8 8 to 10
U/T1, V/T2, W/T3 22 2P 14 to 60 2P 4 2P 6 to 1/0 2P 16 2P 10 to 50 2P M8 (70.8 to 88.5)
For Asia <1> For U.S.A. <2> For Europe and China <3>
Tightening
Model Terminal Recomm. Applicable Recomm. Applicable Recomm. Applicable Screw Torque
CIMR-U Gauge Gauge Gauge Gauge Gauge Gauge Size Nm (lb.in.)
mm2 mm2 AWG, kcmil AWG, kcmil mm2 mm2
R/L1, S/L2, T/L3 50 2P 38 to 100 2P 1/0 2P 1/0 to 4/0 2P 50 2P 35 to 95 2P M10 15 to 20
U/T1, V/T2, W/T3 50 2P 38 to 100 2P 1/0 2P 1/0 to 4/0 2P 50 2P 35 to 95 2P M10 (133 to 177)
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in
damage to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
Note: 1. When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all connected
motors.
2. The maximum cable length is 100 m when using OLV/PM (A1-02 = 5) or AOLV/PM (A1-02 = 6).
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and
minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment
chassis, which could result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. Improper equipment grounding could result in death
or serious injury by contacting ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could
result in abnormal operation of drive or equipment.
Refer to Figure 3.24 when using multiple drives. Do not loop the ground wire.
Figure 3.24
Electrical Installation
Figure 3.25
common_
TMonly
A
CHARGE
n1 p1 R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
B
3
A – Protective Covert for Terminal p1 and n1 B – Main Circuit Protective Cover
Figure 3.25 Protecting Cover to Prevent Miswiring
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting
parameter A1-06 may change the I/O terminal function automatically from the factory setting. Refer to Application Selection on
page 110. Failure to comply may result in death or serious injury.
Input Terminals
Table 3.7 lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Table 3.7 Control Circuit Input Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
S1 Multi-function input 1 (Closed: Forward run, Open: Stop)
S2 Multi-function input 2 (Closed: Reverse run, Open: Stop)
S3 Multi-function input 3 (External fault, N.O.) Photocoupler
S4 Multi-function input 4 (Fault reset) 24 Vdc, 8 mA
Set the wire jumper between SC and SN or SC and SP for selection of sinking/
S5 Multi-function input 5 (Multi-step speed reference 1) sourcing mode and power supply. Refer to Sinking/Sourcing Mode for Digital Inputs 432
Multi-Function S6 Multi-function input 6 (Multi-step speed reference 2) on page 80.
Digital Inputs S7 Multi-function input 7 (Jog reference)
S8 Multi-function input 8 (Baseblock command (N.O.))
SC Multi-function input common Multi-function input common
SP Digital input power supply +24 Vdc 24 Vdc power supply for digital inputs, 150 mA max (only when not using digital
input option DI-A3) 80
SN Digital input power supply 0 V NOTICE: Do not jumper or short terminals SP and SN. Failure to comply will
damage the drive.
H1 Safe Disable input 1 24 Vdc, 8 mA
One or both open: Output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Safe Disable Off time of at least 1 ms
H2 Safe Disable input 2 Disconnect the wire jumpers shorting terminals H1, H2, and HC to use the Safe 529
Inputs
Disable inputs. Set the S3 jumper to select between sinking, sourcing mode, and the
power supply as explained in Sinking/Sourcing Mode Selection for Safe Disable
Inputs on page 81.
HC Safe Disable function common Safe disable function common
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70% 145
RP Multi-function pulse train input (Frequency reference)
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc 254
Input impedance: 3 k
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA) 144
-V Power supply for analog inputs -10.5 Vdc (max allowable current 20 mA) –
144
Analog Inputs / A1 Multi-function analog input 1 (Frequency reference bias) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
247
Pulse Train Input
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k) 144
A2 Multi-function analog input 2 (Frequency reference bias) 4 to 20 mA, 0 to 20 mA (input impedance: 250 ) 145
Voltage or current input must be selected by DIP switch S1 and H3-09 248
Multi-function analog input 3 (auxiliary frequency -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
A3 144
reference) / PTC Input Use DIP switch S4 on the terminal board to select between analog and PTC input.
AC Frequency reference common 0V 144
E (G) Ground for shielded lines and option cards – –
Output Terminals
Table 3.8 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Table 3.8 Control Circuit Output Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
MA N.O. output (Fault)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Fault Relay Output MB N.C. output (Fault) 237
Minimum load: 5 Vdc, 10 mA
MC Fault output common
M1
Multi-function digital output (During run)
M2
Multi-Function M3 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Multi-function digital output (Zero Speed) 237
Digital Output <1> M4 Minimum load: 5 Vdc, 10 mA
M5
Multi-function digital output (Speed Agree 1)
M6
MP Pulse train output (Output frequency) 32 kHz (max) 254
FM Analog monitor output 1 (Output frequency) -10 to +10 Vdc, 0 to +10 Vdc, or 4-20 mA
Use jumper S5 on the terminal board to select between voltage or current output
Monitor Output 252
AM Analog monitor output 2 (Output current) signals.
Resolution: 1/1000
AC Monitor common 0V –
DM+ Safety monitor output Outputs status of Safe Disable function. Closed when both Safe Disable
Safety Monitor channels are closed. Up to +48 Vdc 50 mA. Slide the switch S6 to select N.C. or
518
Output DM- Safety monitor output N.O. as the state of the DM+ and DM- terminals for EDM output as explained
on 81 page.
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
Electrical Installation
<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. For more
information on the termination resistor, see Control I/O Connections on page 80.
Terminal Configuration
The control circuit terminals should are arranged as shown in Figure 3.26.
Figure 3.26
3
YEG
V+ AC V- A1 A2 A3 FM AM AC MP RP AC M1 M2 M5
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC
Wire Size
Select appropriate wire type and gauges from Table 3.10. For simpler and more reliable wiring, use crimp ferrules on the
wire ends. Refer to Ferrule-Type Wire Terminals on page 78 for ferrule terminal types and sizes.
d1
YEG
8 mm
d2
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, p1, n1) and other
high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for output terminals MA, MB, MC, M1, and M2 to M6 from wiring to other control circuit lines. Improper wiring
practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in drive performance degradation due to improper power supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices
could result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive
or equipment malfunction or nuisance trips.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
Figure 3.28 and Figure 3.29 for details. Prepare the ends of the control circuit wiring as shown in Figure 3.30. Refer to
Wire Size on page 78.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
Control Wires
Terminal Board
YEG
45 °
Use a screwdriver with a blade
width of max 2.5 mm and a
thickness of max 0.4 mm
Control Wires
Terminal Board
YEG
Figure 3.29 Removing Wires from the Terminal Board
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires
(preparing wire ends as shown in Figure 3.30 and connect the shield to the ground terminal (E [G]) of the drive.
Figure 3.30
Electrical Installation
E B
A C
NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters
when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system
performance.
DIP Switch S1
Slide Switch S6 Terminal A2 Signal
Terminal DM+,DM-
N.C./N.O. Selection
Selection
V I
YEG
N.O.
N.C.
Jumper S5
Terminal AM/FM Signal
Jumper S3 Selection
Terminal H1/H2
Sink/Source Sel.
V
FM AM
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
M3 M6 M4
V+ AC V- A1 A2 A3 FM AM AC MP RP AC M1 M2 M5
DIP Switch S4
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC
Terminal A3 Analog/
DIP Switch S2 PTC Input Sel.
RS-422/485
Termination Resistor
Off On PTC
AI
S7 S7
S8 S8
SC SC
24 Vdc 24 Vdc
SP External SP
24 Vdc
Drive Internal Power Supply (Terminal SN and SP) External 24 Vdc Power Supply
S7 S7
S8 S8
SC SC
24 Vdc 24 Vdc
External
SP SP
24 Vdc
Jumper S3 Jumper S3
24 Vdc 24 Vdc
HC HC
External
24 Vdc
Sinking Mode
H1 H1
H2 H2
Jumper S3 Jumper S3
24 Vdc 24 Vdc
HC HC
Electrical Installation
External
24 Vdc
Sourcing Mode
H1 H1
H2 H2
3
Terminal DM+ and DM- Output Signal Selection
Slide the switch S6 to select N.C. or N.O. as the state of the DM+ and DM- terminals for EDM output. The switch is
initially set to N.C.
Table 3.14 EDM Switch Settings
S6 Position Description
N.O. Normal Open
N.C. Normal Close (default setting)
Note: Refer to Safe Disable Input Function on page 529 for details on EDM.
Load Impedance
MP
VMP RL
AC
common_
TMonly
Figure 3.32 Pulse Output Connection Using Internal Voltage Supply
Load Impedance
MP
Sink Current
AC
common_
TMonly
V V
Terminal AM I I
FM AM FM AM
V V
Terminal FM I I
FM AM FM AM
Electrical Installation
3
3.11 Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to the USB port of a PC using a USB 2.0, AB type cable (sold separately). DriveWizard Plus can
then be used to monitor drive performance and manage parameter settings. Contact Yaskawa for more information on
DriveWizard Plus.
Figure 3.34
USB Cable
(Type-AB)
(Type-B) (Type-A)
PC
common_TMonly
Electrical Installation
3
WARNING! Electrical Shock Hazard. Connect the ground cable correctly. Failure to comply may result in death or serious injury.
NOTICE: When disabling the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque.
Completely removing the screws or tightening the screws to an incorrect torque may cause drive failure.
Note: For floating, impedance grounded, or asymmetrically grounded networks, disconnect the internal EMC filter by moving the SW
screw to the OFF position.
Table 3.21 shows asymmetrical grounded networks. Asymmetrical networks require first moving the SW screw to
disconnect the internal ground connection. (Drives are shipped with SW screw installed at the OFF position.)
Table 3.21 Asymmetrical Grounded Network
L1
L3 L2
L1
L3 L2
L1
L1
L1
L2
Three-phase variable transformer without solidly grounded
neutral L2
L3
L3
If EMC is a concern and the network is grounded symmetrically, install the SW screw to the ON position. Installing the
SW screw enables the internal EMC filter (Drives are shipped with SW screw installed at the OFF position).
Figure 3.35
L1
L3 L2
A ON
B OFF
SW
A ON
B OFF
SW
Electrical Installation
Figure 3.37 EMC Filter Switch Location (2E0042, 2E0054, 2W0042, 2W0054, 4E0040 to 4E0077, 4W0040 to 4W0077)
Figure 3.38
A ON
B OFF
SW
B
A
A
B
B
A
Operation Ready
When the “Operation ready” signal has been set to one of the multi-function contact outputs, that output will close when
the drive is ready to accept a Run command or is already running. Under the following conditions the Operation ready
signal will switch off and remain off, even if a Run command is entered:
• when the power supply is shut off
• during a fault
• when there is problem with the control power supply
• when a parameter setting error renders the drive unable to run even when entering a Run command
• when a fault such as overvoltage or undervoltage is triggered as soon as the Run command is entered
• when the drive is in the Programming mode and will not accept a Run command even when entered
Interlock Circuit Example
Two drives running a single application might interlock with the controller using the Operation ready and Fault output
signals as shown below. The figure illustrates how the application would not be able to run if either drive experiences a
fault or is unable to supply an Operation ready signal.
Operation ready
Stop
Run common_
TMonly
Figure 3.42
Drive 1 Controller
Electrical Installation
MA
Relay 1 SA Relay 1
Max
Run Fault MB 250 Vac Fault 1
S1
Output
SC MC
Relay 2
Relay 2 SA Ready 1
M1
Operation Ready M2
3
common_
Drive 2 Controller TMonly
MA
Relay 1 SA Relay 1
Max
Run Fault MB 250 Vac Fault 2
S1
Output
SC MC
Relay 2
Relay 2 SA Ready 2
M1
Operation Ready
M2
9 Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3. 61
Properly wire the drive and motor together.
10 The motor lines and drive output terminals U/T1, V/T2, and W/T3 should match in order to produce the desired phase order. If the phase order 74
is incorrect, the drive will rotate in the opposite direction.
11 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. 71
Use the correct wire gauges for the main circuit. Refer to Main Circuit Wire Gauges and Tightening Torque on page 71. 71
• When using comparatively long motor cable, calculate the amount of voltage drop. 71
3 × wire resistance (Ω/km) × cable length (m) × motor rated current (A) × 10 -3
• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly. 74
13 Properly ground the drive. 75
Tightly fasten all terminal screws (control circuit terminals, grounding terminals).
14 71
Refer to Main Circuit Wire Gauges and Tightening Torque on page 71.
Set up overload protection circuits when running multiple motors from a single drive.
MC2 OL2
15 MC1 - MCn ... magnetic contactor –
M2 OL 1 - OL n ... thermal relay
MCn OLn
Mn
Note: Close MC1 through MCn before operating the drive (MC1 through MCn cannot be switched off during run).
16 Verify that ground wiring for models 2E/2W/4E/4W is correct before turning on the EMC filter switch. 86
17 Verify phase advancing capacitors, input noise filters, or ground fault circuit interrupters are NOT installed on the output side of the drive. –
Control circuit wiring
18 Use twisted-pair line for all drive control circuit wiring. 76
25 Ensure that no frayed wires on the terminal block are touching other terminals or connections. –
29 Verify the logic of Safety Monitor Output Signal (DM+, DM-). 529
Disconnect the internal EMC filter by moving the SW screw to the OFF position for floating, impedance grounded, or asymmetrically
30 86
grounded networks.
Electrical Installation
3
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may include drives without covers or safety shields to illustrate details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
A separate holding brake should be prepared by the user.
The holding brake should be wired so that it is activated by an external sequence when a fault occurs, the power
is shut off, or an emergency switch is triggered.
Failure to comply could result in death or serious injury.
Precautions should be taken on the machine side in crane and hoist applications to ensure that load does not fall
or slip.
Failure to take proper safety precautions can result in serious injury.
1
11
F1 F2
2 ESC
LO
RE
9
3 RESET ENTER
8
10 RUN STOP
4 5 6 7
Figure 4.1 Keys and Displays on the Digital Operator
F1
Function Key The functions assigned to F1 and F2 vary depending on the menu that is currently displayed. The name of each
1
(F1, F2) function appears in the lower half of the display window.
F2
5 Up Arrow Key Scrolls up to display the next item, selects parameter numbers and increments setting values.
Start-Up Programming
6 Down Arrow Key Scrolls down to display the previous item, selects parameter numbers and decrements setting values.
& Operation
7 STOP STOP Key <1> Stops drive operation.
10 RUN RUN Light Lit while the drive is operating the motor. Refer to page 97 for details.
11 LO LO/RE Light Lit while the operator is selected to run the drive (LOCAL mode). Refer to page 97 for details.
RE
12 ALM LED Light Refer to ALARM (ALM) LED Displays on page 97 for details.
<1> The STOP key has highest priority. Pressing the STOP key will always cause the drive to stop the motor, even if a Run command is active at
any external Run command source. To disable the STOP key priority, set parameter o2-06 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. To disable the LO/RE key to prohibit switching
between LOCAL and REMOTE, set parameter o2-01 to 0.
LCD Display
Figure 4.2
1 2 3 4
8 9 10
Figure 4.2 LCD Display
Table 4.1 Display and Contents
No. Name Display Content
MODE Displayed when in Mode Selection.
MONITR Displayed when in Monitor Mode.
VERIFY Indicates the Verify Menu.
1 Operation Mode Menus
PRMSET Displayed when in Parameter Setting Mode.
A.TUNE Displayed during Auto-Tuning.
SETUP Displayed when in Setup Mode.
DriveWorksEZ Function
2 DWEZ Displayed when DriveWorksEZ is being used.
Selection
DRV Displayed when in Drive Mode.
3 Mode Display Area
PRG Displayed when in Programming Mode.
4 Ready Rdy Indicates the drive is ready to run.
5 Data Display – Displays specific data and operation data.
OPR Displayed when the frequency reference is assigned to the LCD Operator.
AI Displayed when the frequency reference is assigned to the drives Analog Input.
Frequency Reference
6 COM Displayed when the frequency reference is assigned to the drives MEMOBUS/Modbus Communication Inputs.
Assignment <1>
OP Displayed when the frequency reference is assigned to a drive Option Unit.
RP Displayed when the frequency reference is assigned to the drives Pulse Train Input.
RSEQ Displayed when the reference is supplied from a remote source.
LSEQ Displayed when the reference is supplied from the operator keypad.
7 LO/RE Display <2>
RREF Displayed when the frequency reference is supplied from a remote source.
LREF Displayed when the frequency reference is supplied from the operator keypad.
Function Key 1
8 Pressing scrolls the cursor to the left.
(F1) F1
Examples
<1> Refer to Figure 4.3 for the difference between “flashing” and “flashing quickly”.
Start-Up Programming
Figure 4.3
1s
ON ON
& Operation
Flashing
common_TM
only
Flashing ON ON ON ON
quickly
4
Figure 4.3 RUN LED Status and Meaning
Figure 4.4
- MODE - PRG
Programming Mode <2>
Quick Setting
Initial Display <5>
U1000
HELP FWD DATA XX.XX/XX.XXA
U1000 <XXXXXXXXX>
YASKAWA
<6>
- MODE - PRG
Programming
AUTO
- MODE - PRG
Modified Consts
Verify Menu Modified Lists all parameters that have been edited or changed from default settings. Refer to Verifying Parameter
Start-Up Programming
X Parameters Changes: Verify Menu on page 102.
HELP FWD DATA
& Operation
- MODE - PRG
Quick Setting A select list of parameters necessary to get the drive operating quickly. Refer to Using the Setup Group on
Setup Group page 103.
Note: Parameters listed in the Setup Group differ depending the Application Preset in parameter A1-06. Refer to
- MODE - PRG
Programming
Parameter Setting
Mode Allows the user to access and edit all parameter settings. Refer to Parameter Table on page 404.
- MODE - PRG
Auto-Tuning
Auto-Tuning Mode Motor parameters are calculated and set automatically. Refer to Auto-Tuning on page 116.
AUTO
Frequency reference
display at power up
F1 F2
- MODE - DRV Rdy - MODE - DRV Rdy -MONITR- DRV Rdy
FREF (AI) FREF (OPR) FREF (d1-01) left right
U1-01= 0.00Hz U1-01= 0.00Hz
U1-01= 000.00Hz
U1-02= 0.00Hz RSEQ U1-02= 0.00Hz LSEQ 㧔0.00㨪50.00㧕
U1-03= 0.00A RREF U1-03= 0.00A LREF ̌0.00Hz̍
JOG FWD JOG FWD FWD/REV FWD Press until the frequency
Press to select reference changes to 006.00 Hz
LOCAL
-MONITR- DRV Rdy -MONITR- DRV Rdy - MODE - DRV Rdy YEG_TM
FREF (d1-01) FREF (d1-01) FREF (OPR)
U1-01= 006.00Hz U1-01= 006.00Hz ESC U1-01= 6.00Hz
U1-02= 0.00Hz LSEQ
only
㧔0.00㨪50.00㧕 Entry Accepted 㧔0.00㨪50.00㧕
̌0.00Hz̍ ̌0.00Hz̍ U1-03= 0.00A LREF
FWD FWD JOG FWD FWD/REV
Figure 4.6 Setting the Frequency Reference while in the Drive Mode
Note: The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is
entered. This feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency
reference as soon as changes are made without requiring the ENTER key, set o2-05 to 1.
100 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.3 The Drive and Programming Modes
Step Display/Result
- MODE - PRG
Programming
2.
Press the or key until the Parameter Setting Mode screen appears.
HELP FWD DATA
-PRMSET- PRG
Initialization
3. A1-00=0
Press the key to enter the parameter menu tree. Select Language
FWD
-PRMSET- PRG
Basic Setup
4. C1-01= 10.0 sec
Press or key to select the C parameter group. Accel Time 1
FWD
-PRMSET- PRG
Decel Time 1
6. C1-02= 10.0Sec
Press or key to select the parameter C1-02. (0.0~6000.0)
“10.0 sec”
FWD
-PRMSET- PRG
Decel Time 1
7. C1-02= 0010.0Sec
Press to view the current setting value (10.0 s). Left digit flashes. (0.0~6000.0)
“10.0 sec”
Start-Up Programming
FWD
-PRMSET- PRG
Decel Time 1
& Operation
8. C1-02=0010.0Sec
Press F1 , F2 or until the desired number is selected. “1” flashes. (0.0~6000.0)
“10.0 sec”
FWD
-PRMSET- PRG
Decel Time 1
C1-02=0020.0Sec
4
9. (0.0~6000.0)
Press the key and enter 0020.0.
“10.0 sec”
FWD
10.
Press and the drive will confirm the change. Entry Accepted
-PRMSET- PRG
Decel Time 1
C1-02= 20.0Sec
11. The display automatically returns to the screen shown in Step 4. (0.0~6000.0)
“10.0 sec”
FWD
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 101
4.3 The Drive and Programming Modes
The following example is a continuation of the steps above. Here, parameter C1-02 is accessed using the Verify Menu,
and is changed again from 10.0 s to 20.0 s.
To check the list of edited parameters:
Step Display/Result
- MODE - PRG
Modified Consts
2. Press or until the display shows the top of the Verify Menu. Modified
X Parameters
HELP FWD DATA
5.
Press and the drive will confirm the change. Entry Accepted
102 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.3 The Drive and Programming Modes
- SETUP - PRG
Control Method
A1-02= 2 ∗2∗
Open Loop Vector
Start-Up Programming
Home FWD DATA - SETUP - PRG
Ref Source 1
b1-01= 0 ∗1∗
Entry Accepted Operator
“1”
& Operation
FWD
- SETUP - PRG
Run Source 1 Operator
b1-02= 1 ∗1∗ <2>
Digital Inputs
4
- SETUP - PRG
StallP Decel Sel
L3-04= 1 ∗1∗
General Purpose
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 103
4.3 The Drive and Programming Modes
Note: Parameter availability depends on the control mode set in A1-02 that is used to run the drive and motor. Consequently, some of
the parameters listed above may not be accessible in certain control modes.
The operation can be switched between LOCAL and REMOTE either by using the LO/RE key on the digital operator or
a digital input.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Step Display/Result
- MODE - DRV Rdy
FREF (AI)
U1-01= 0.00Hz
1. Turn on the power to the drive. The initial display appears.
U1-02= 0.00Hz RSEQ
U1-03= 0.00A RREF
JOG FWD
Press . The LO/RE light will light up. The drive is now in LOCAL. F1 F2
2. ESC
LO
RE
RESET ENTER
To set the drive for REMOTE operation, press the key again.
RUN STOP
104 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.4 Start-Up Flowcharts
START
NO
Set the control mode in parameter A1-02. Refer to
Application
Selection section
Set the basic parameters
C6-01 for heavy/normal duty mode selection
b1-01/02 for frequency reference and run command source selection
H1-, H2-, H3-, H4-, H6- for I/O terminal setting
d1- for multi-speed references if used
C1- and C2- for accel./decel. and S-curve time settings
common_TMo
Control Mode
nly
A1-02 =
Start-Up Programming
0: V/f 2: OLV 5: OLV/PM
1: V/f w/PG 3: CLV 6: AOLV/PM
7: CLV/PM
& Operation
To To To
Flowchart A-1 Flowchart A-2 Flowchart A-3
4
From Flowchart A-1, A-2, or A-3
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 105
4.4 Start-Up Flowcharts
From
Flowchart
A
Is there a YES
PG encoder
on the motor?
NO
YES
Perform Rotational YES
Auto-Tuning for V/f Control Is the motor cable longer than
(T1-01 = 3) 50 meters?
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Return to
Flowchart
A
Figure 4.9 Simple Motor Setup with Energy Savings or Speed Search
106 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.4 Start-Up Flowcharts
From
Flowchart
A
NO
<2>
Motor test report/ YES Perform Stationary Perform Rotating
data sheet available? Auto-Tuning 2 (T1-01 = 4) Auto-Tuning (T1-01 = 0)
NO
NO
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Run the operation in test mode for Auto-Tuning 3.
common_TMo
nly
Connect the load to the motor.
Is there a PG NO
encoder on the
motor?
YES
Start-Up Programming
Should the YES
drive set ASR gain
automatically?
& Operation
NO
Return to
Flowchart
A
<1> The load must be decoupled from the motor to properly perform Rotational Auto-Tuning.
<2> Rotational Auto-Tuning can still be performed if the load is 30% or less, though Stationary Auto-Tuning will probably yield better control
performance.
<3> Run the operation in test mode for Auto-Tuning 3. The drive will automatically set motor parameters automatically. For details, refer to
Stationary Auto-Tuning 3 on page 120.
<4> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<5> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward function.
Figure 4.10 Flowchart A-2: High Performance Operation Using OLV or CLV
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 107
4.4 Start-Up Flowcharts
From
Flowchart
A
YES NO
Input the motor data. Input the motor data. Perform PM
(T2-01 = 0) <1> (T2-01 = 1) <1> Rotational Auto-Tuning.
(T2-01 = 14)
YES
Is the motor cable longer
than 50 meters?
PM Stationary Auto-Tuning for
NO Stator Resistance (T2-01 = 2)
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
NO Is there a
PG encoder on the
motor?
YES
NO Has PG been common_TMo
replaced after Auto-Tuning was
performed? nly
YES
Disconnect the motor from the load so that the motor shaft can rotate.
Is reverse NO
operation disabled?
(b1-04 = 1)
YES
Enable reverse operation.
(b1-04 = 0)
YES
Should the drive set ASR?
NO
Return to
Flowchart
A
<1> A motor code can be entered as the parameter setting for E5-01 when using a Yaskawa PM motor (SMRA Series, SSR1 Series, and SST4
Series). If using a motor from another manufacturer, enter FFFF.
<2> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<3> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward function.
Figure 4.11 Operation with Permanent Magnet Motors
108 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.5 Powering Up the Drive
Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
- MODE - DRV
Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 312
Fault EF3
Ext Fault S3 for more information and possible solution. ALM is displayed.
FWD RESET
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 109
4.6 Application Selection
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change
the I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
110 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.6 Application Selection
Start-Up Programming
Setting 4: HVAC Fan Application
Table 4.12 HVAC Fan: Parameter Settings
& Operation
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
b1-17 Run Command at Power Up 1: Run command issued, motor operation start
C6-01 Drive Duty Model Selection 1: Normal Duty (ND) 4
C6-02 Carrier Frequency Selection 1: 4.0 Hz <1>
H2-03 Terminal M5-M6 Function Selection (Relay) 39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior to control power supply shut
L2-01 Momentary Power Loss Operation Selection
down.
L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
L8-38 Carrier Frequency Reduction Selection 2: Enabled across entire frequency range.
<1> Max. setting value varies by the drive model selection (o2-04).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 111
4.6 Application Selection
112 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.6 Application Selection
Notes on Controlling the Brake when Using the Hoist Application Preset
Prevent accidental Brake Release during Baseblock
The hoist application selection uses the frequency detection function for controlling the brake.
Although the drive output will be shut off, the drive still maintains the frequency reference if the Run command remains
active when an External Baseblock command is given (H1- = 8 or 9). Disable the frequency detection during
baseblock by setting parameter L4-07 = 0 to prevent the brake remaining open while the drive is in baseblock.
Controlling the Brake in Closed Loop Vector Control
For hoist applications using Closed Loop Vector Control, Yaskawa recommends setting the “During frequency output”
signal to a digital output (H2-01 = 37 for terminal M1-M2) in order to control the brake. This way, the brake will always
close during baseblock, and the setting of parameter L4-07 as described above will not affect brake control.
Brake Control During Safe Disable Input
If the Safe Disable input is triggered, the drive output will shut off and the frequency reference will reset to 0. The brake
will also close, regardless if the Run command is active. The Run command must be cycled before the drive can restart.
Related Parameter Settings
Table 4.18 shows the parameter settings needed when using output terminals M1-M2 as brake control output.
Table 4.18 Parameter Settings for Brake Control Output (M1-M2)
Function Parameter Setting Comment
Frequency Detection 2 Digital Output
H2-01 5
Start-Up Programming
(for brake control)
Speed Agreement Detection Level
L4-01 1.0 to 3.0 Hz <1> Use this setup for V/f control modes or Open Loop Vector
(frequency for the brake to open)
control
Speed Agreement Width
& Operation
L4-02 0.0 to 0.5 Hz <2>
(bandwidth for the brake to close)
Frequency Detection during Baseblock L4-07 0
DC Injection Braking Start Frequency
b2-01 0.1 to 0.5 Hz Use this setup in Closed Loop Vector control for IM or PM
(frequency for the brake to close)
motors
During Frequency Output H2-01 37
4
<1> This is the setting recommended when using Open Loop Vector Control. If using V/f Control, set the level as the motor rated slip frequency
plus 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend to slip. Make sure this value is greater
than the minimum output frequency and greater than the value of L4-02, as shown in the diagram below. If set too high, however, there may be
a jolt at start.
<2> Hysteresis for Frequency detection 2 can be adjusted by the Frequency detection width (L4-02) between 0.0 and 0.5 Hz. If the load slips during
stop, make changes in steps of 0.1 Hz until the load no longer slips.
Figure 4.11
L4-01
L4-02
Output
YEG_TMonly
time
frequency
ON OFF
Frequency
Dectection 2
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 113
4.6 Application Selection
OFF ON
S1-SC UP
Input
S6-SC Fast/Slow OFF ON
b6-02
YEG_TMonly
d1-01
d1-03
Output frequency b6-01 b2-04
0
Speed Agreement Detection Level DC Injection braking Time
Output L4-01
Frequency Detection 2 b2-01 (DC injection braking start frequency)
(H2-01 = 05) ON OFF or E1-09 (Min. output frequency) <1>
M1-M2
Holding brake
Closed Open Closed
<1> The drive brakes at the frequency set to b2-01 or E1-09, whichever value is higher.
Figure 4.14 Holding Brake Time Chart (V/f, V/f w/PG, OLV)
Figure 4.14
OFF ON
S1-SC UP
Input
S6-SC Fast/slow OFF ON
d1-01
YEG_TMonly
d1-03
Output frequency b2-04
L4-01
0
Output Time
Zero speed control
b2-01 (DC injection braking start frequency)
During frequency output ON OFF or E1-09 (Min. output frequency) <1>
M1-M2 (H2-01 = 37)
Holding brake
Closed Open Closed
<1> The drive brakes at the frequency set to b2-01 or E1-09, whichever value is higher.
Figure 4.15 Holding Brake Time Chart (CLV, CLV/PM)
114 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.6 Application Selection
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 115
4.7 Auto-Tuning
4.7 Auto-Tuning
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of
Auto-Tuning used differs further based on the control mode and other operating conditions. Refer to the tables below to
select the type of Auto-Tuning that bests suits the application. Directions on how to execute Auto-Tuning are listed in
Start-Up Flowcharts on page 105.
Note: The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set to A1-02. If the control
mode is for an induction motor, the Auto-Tuning parameters for PM motors will not be available. If the control mode is for a PM
motor, the Auto-Tuning parameters for induction motors will not be available. Inertia Tuning and ASR Gain Tuning parameters
and setting options will be visible only when the drive is set for operation with Closed Loop Vector or CLV/PM.
Table 4.22 lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting
Auto-Tuning.
The information needed is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to Subchart A-1: Simple Motor Setup Using V/f Control on page 106 and Subchart A-2: High
Performance Operation Using OLV or CLV on page 107 for details on Auto-Tuning process and selections.
Table 4.22 Auto-Tuning Input Data
Tuning Type (T1-01)
Input 2 3
Input Value Unit 0 4 5
Parameter Line-to-Line Rotational for
Standard Stationary 2 Stationary 3
Resistance V/f Control
Control Mode A1-02 – 2, 3 0, 1, 2, 3 0, 1 2, 3 2, 3
Motor Rated Power T1-02 kW YES YES YES YES YES
Motor Rated Voltage T1-03 Vac YES N/A YES YES YES
Motor Rated Current T1-04 A YES YES YES YES YES
Motor Rated Frequency T1-05 Hz YES N/A YES YES YES
Number of Motor Poles T1-06 – YES N/A YES YES YES
Motor Rated Speed T1-07 min-1 YES N/A YES YES YES
PG Number of Pulses Per
T1-08 – YES <1> N/A N/A YES <1> YES <1>
Revolution
Motor No-load Current T1-09 A N/A N/A N/A YES YES
116 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
Table 4.24 lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting
Start-Up Programming
Auto-Tuning.
The information needed is usually listed on the motor nameplate or in the motor test report provided by the motor
& Operation
manufacturer. Also refer to Subchart A-3: Operation with Permanent Magnet Motors on page 108 for details on the
tuning mode selection and the tuning process.
Figure 4.15
common_ 4
556 TMonly
&4+8' 122
'0& '0&
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 117
4.7 Auto-Tuning
Note: Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between the machine and the motor shaft.
Table 4.26 explains that data that must be entered in order to perform the Inertia Tuning and ASR Gain Auto-Tuning.
Refer to Auto-Tuning for Permanent Magnet Motors on page 117 for details.
Table 4.26 Auto-Tuning Input Data
Tuning Type (T1-01 or T2-01)
Input Value Input Parameter Unit 8 9
Inertia Tuning ASR Gain Tuning
Control mode A1-02 – 3, 7 3, 7
Test signal frequency T3-01 Hz YES YES
Test signal amplitude T3-02 rad YES YES
Motor inertia T3-03 kgm2 YES YES
System response frequency T3-04 Hz N/A YES
118 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
Start-Up Programming
rotation.
• Ensure the motor-mounted brake is fully released if installed.
• Connected machinery should be allowed to rotate the motor.
& Operation
NOTICE: Make sure that the motor and the load are not connected when performing Auto-Tuning. Failure to comply may cause
damage to equipment or injury to personnel.
NOTICE: Electrical Shock Hazard. When executing Auto-Tuning, voltage is applied to the motor even before it rotates. Do not touch
the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock. If Rotational Auto-Tuning is 4
performed, the motor will remain stopped for approximately one minute with power applied and then the motor will rotate for one
minute.
WARNING! Sudden Movement Hazard. If installed, do not release the mechanical brake during stationary Auto-Tuning. Inadvertent
brake release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not
controlled by the drive multi-function digital outputs.
Stationary Auto-Tuning 2
• Perform these tuning methods when using a vector control mode but Rotational Auto-Tuning cannot be performed.
• Check the area around the motor to ensure that nothing will accidentally cause the motor to rotate during the
Auto-Tuning process.
• Perform Stationary Auto-Tuning 3 when the motor test report is not available. If the motor test report is available,
perform Stationary Auto-Tuning 2 instead.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 119
4.7 Auto-Tuning
Stationary Auto-Tuning 3
NOTICE: Electrical Shock Hazard. When executing Stationary Auto-Tuning 3, voltage is applied to the motor even before it rotates. Do
not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock.
NOTICE: When performing Stationary Auto-Tuning 3 for a motor while it is connected to the machine, such as a conveyor, do not
release the holding brake during Auto-Tuning.
Stationary Auto-Tuning 3 can be used in either Open Loop Vector control or Closed Loop Vector control. Set T1-01 to 5
and enter the input data from the motor nameplate. If the RUN key is pressed, the motor will remain stopped for
approximately one minute to automatically calculate the motor parameters that are needed. When the motor is used for
the first time in Drive Mode after Auto-Tuning has been performed, the motor parameters (E2-02 and E2-03) are set
automatically.
After Stationary Auto-Tuning 3 has been performed, make sure the following conditions are met and use the following
procedures to perform the operation in test mode.
1. Check the values of E2-02 and E2-03 in Verify Menu or Parameter Setting Mode.
2. Operate the motor once in Drive Mode with the following conditions.
• Do not disconnect the wiring between the motor and drive.
• Do not lock the motor shaft with a mechanical brake or other device.
• The maximum motor load should be 30% of the rated load.
• Maintain a constant speed of 30% of E1-06 (base frequency, default value = maximum frequency) or higher
for one second or longer.
3. After the motor is stopped, recheck the values of E2-02 and E2-03 in Verify Mode or Parameter Setting Mode.
4. Confirm that the input data is correct.
Note: 1. If the aforementioned conditions are not met when using the motor for the very first use, there will be large discrepancies between the
values set for the motor rated slip (E2-02) and the motor no-load current (E2-03), and the motor test report and the data given in
Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) on page 469. This could result in motor vibration, hunting,
insufficient torque, or overcurrent. For hoist applications, this could result in the cage falling or serious injury. Either perform
Stationary Auto-Tuning 3 again and then perform operation with the above procedure and conditions, or perform Stationary
Auto-Tuning 2, or rotational Auto-Tuning.
2. If midway initialization is performed, restart the entire procedure from the beginning.
3. Use the following guidelines for a general-purpose motor: Motor rated slip (E2-02): 0.5 Hz to 3 Hz, Motor no-load current (E2-03):
30% to 65% of the rated current. Generally speaking, for larger motor capacities the rated slip is smaller and the no-load current as a
percentage of the rated current is smaller. Refer to Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) on page 469 for
details.
Stationary Auto-Tuning for Line-to-Line Resistance and PM Motor Stator Resistance
• Perform when entering motor data manually while using motor cables longer than 50 m.
• If the motor cables have been replaced with line over 50 m long after Auto-Tuning as already been performed, then
execute Stationary Auto-Tuning for line-to-line resistance.
Notes on Inertia Tuning and ASR Gain Auto-Tuning
WARNING! Electrical Shock Hazard. When executing Inertia Tuning or ASR Gain Auto-Tuning, voltage is applied to the motor even
before it rotates. Do not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock.
• Both tuning methods must be performed with the machine connected to the motor but without load applied.
• The motor will rotate during the Auto-Tuning process. Make sure the areas around the motor and connected machinery
are clear.
• The drive will let the system rotate at a certain speed while superimposing a sine wave test signal. Make sure this
tuning process does not cause any problem or malfunction in the machine before using it.
• Ensure the motor-mounted brake is fully released if installed.
• Connected machinery should be allowed to rotate the motor.
120 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
common_
DIGITAL OPERATOR JVOP-180
ALM DIGITAL OPERATOR JVOP-180
ALM TMonly
- A.TUNE - DRV Rdy - MODE - DRV
REV DRV
DRV FOUT
Tune Proceeding
X.XX Hz/ X.XXA Er-03
STOP key
FWD FWD RESET
Step Display/Result
- MODE - DRV Rdy
FREF (AI)
U1-01= 0.00Hz
1. Turn on the power to the drive. The initial display appears.
U1-02= 0.00Hz RSEQ
U1-03= 0.00A RREF
JOG FWD
- MODE - PRG
Auto-Tuning
2.
Press the or key until the Auto-Tuning display appears. AUTO
- A.TUNE - PRG
Tuning Mode Sel
3. Press to begin setting parameters.
T1-01= 0 ∗0∗
Standard Tuning
- A.TUNE - PRG
Start-Up Programming
Tuning Mode Sel
4. T1-01= 0 ∗0∗
Press to select the value for T1-01. <1> Standard Tuning
“0”
FWD
& Operation
5.
Save the setting by pressing . Entry Accepted
- A.TUNE - PRG
4
Tuning Mode Sel
6. The display automatically returns to the display shown in Step 3. T1-01= 0 ∗0∗
Standard Tuning
<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1- = 16).
Step Display/Result
- A.TUNE - PRG
Mtr Rated Power
1. Press to access the motor output power parameter T1-02. T1-02= 0.75kW
The value set for E2-11 prior to turning on the power is displayed for T1-02. (0.00 ~ 650.00)
“0.75kW”
ESC FWD DATA
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 121
4.7 Auto-Tuning
Step Display/Result
- A.TUNE - PRG
Mtr Rated Power
2. The setting value of T1-02 flashes when is pressed. T1-02= 000.75kW
The setting can be changed. (0.00 ~ 650.00)
“0.75kW”
FWD
- A.TUNE - PRG
Mtr Rated Power
3. Press F1 , F2 , , and to enter the motor power nameplate data in kW.
T1-02= 000.40kW
(0.00 ~ 650.00)
“0.75kW”
FWD
4.
Press to save the setting. Entry Accepted
- A.TUNE - PRG
Mtr Rated Power
5. The display automatically returns to the display in Step 1. T1-02= 0.40kW
(0.00 ~ 650.00)
“0.75kW”
ESC FWD DATA
- A.TUNE - PRG
Rated Voltage
T1-03= 200.0VAC
Repeat Steps 1 through 5 to set the following parameters: (0.0 ~ 255.0)
• T1-03, Motor Rated Voltage “200.0VAC”
ESC FWD DATA
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
6.
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency
• T1-09, Motor No-Load Current (Stationary Auto-Tuning 2 only) - A.TUNE - PRG
Mtr Rated Slip
• T1-10, Motor Rated Slip (Stationary Auto-Tuning 2 only)
T1-10= X.XX Hz
(0.00 ~ 20.00)
“X.XX Hz”
ESC FWD DATA
Note: 1. For details on each setting, refer to Parameter Settings during Induction Motor Auto-Tuning: T1 on page 123.
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death
or serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in
improper operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Enter the required information from the motor nameplate. Press to proceed to the Auto-Tuning start display.
Note: These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
Step Display/Result
- MODE - DRV
FWD RESET
122 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E1- and E2- for motor 1.
Setting 2: Motor 2
Auto-Tuning automatically sets parameters E3- and E4- for motor 2. Make sure that motor 2 is connected to the
drive for Auto-Tuning.
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used. Refer to Auto-Tuning for Induction Motors on page 116 for details on the
different types of Auto-Tuning.
Start-Up Programming
Setting 9: ASR Gain Auto-Tuning
Note: Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between the machine and the motor shaft.
& Operation
T1-02: Motor Rated Power
Sets the motor rated power according to the motor nameplate value.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 123
4.7 Auto-Tuning
124 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
Start-Up Programming
If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code for the motor
in parameter T2-02. This will automatically set parameters T2-03 through T2-14. If using a specialized motor or one
& Operation
designed by a manufacturer other than Yaskawa, set T2-02 to FFFF. Data from the motor nameplate or the motor test
report will then need to be entered as prompted.
Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ by the
control mode that has been selected. Refer to E5: PM Motor Settings on page 216 for motor codes. 4
No. Name Setting Range Default
T2-02 PM Motor Code Selection 0000 to FFFF Depending on A1-02 and o2-04
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 125
4.7 Auto-Tuning
<1> The setting range and default value shown here is for a 200 V class drive. These values double when using a 400 V class unit.
126 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.7 Auto-Tuning
Setting 0: mV (min-1)
Setting 1: mV (rad/s)
Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2 (for PM Motors)), and will automatically
set E5-09 (Motor Induction Voltage Constant 1 (Ke) (for PM Motors)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09
and will automatically set E5-25 to 0.0.
Start-Up Programming
No. Name Setting Range Default
& Operation
T2-17 Encoder Z-Pulse Offset () -180.0 to 180.0 deg 0.0 deg
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 127
4.7 Auto-Tuning
128 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.8 No-Load Operation Test Run
Step Display/Result
F1 F2
2.
LO
ESC
RE
Press the key to select LOCAL. The LO/RE light will turn on. RESET ENTER
RUN STOP
Off On
Start-Up Programming
3. Set the frequency reference to 6 Hz. Refer to Figure 4.6 (page 100) for the setting procedure. – –
& Operation
- MODE - DRV Rdy
FREF (OPR)
U1-01= 6.00Hz
U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
F1 F2
LO
ESC
RE
4. Press to give the drive a Run command. RUN will light and the motor will rotate at 6 Hz. RESET ENTER
RUN STOP
4
RUN RUN
Off On
Motor
5. Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
Forward
If there is no error in step 4, increase the frequency reference. Refer to Figure 4.6 (page 100) for the procedure
to change the frequency reference. Increase the frequency in increments of 10 Hz, verifying smooth operation
6. – –
at all speeds. For each frequency, check the drive output current using monitor U1-03. The current should be
well below the motor rated current.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 129
4.8 No-Load Operation Test Run
Step Display/Result
F1 F2
LO
ESC
RE
7. The drive should operate normally. Press STOP to stop the motor. RUN flashes during deceleration to stop
RESET ENTER
RUN RUN
Off On
130 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.9 Test Run with Load Connected
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 131
4.10 Verifying Parameter Settings and Backing Up Changes
132 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.10 Verifying Parameter Settings and Backing Up Changes
Copy Function
Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive
supports the following copy options:
• LCD Operator (standard in all models)
The LCD operator used to operate the drive also supports copying, importing, and verifying parameter settings. Refer
to o3: Copy Function on page 294 for details.
• LED Operator
The optional LED operator also supports copying, importing, and verifying parameter settings. Refer to the manual
supplied with the LED operator for instructions.
• USB Copy Unit and CopyUnitManager
The copy unit is an external option connected to the drive to copy parameter settings from one drive and save those
settings to another drive. Refer to the manual supplied with the USB Copy Unit for instructions.
The CopyUnitManager is a PC software tool. It allows the user to load parameter settings from the Copy Unit onto a
PC, or from the PC onto a Copy Unit. This is useful when managing parameters for various drives or applications.
Refer to the manual supplied with the CopyUnitManager for instructions.
• DriveWizard Plus
DriveWizard is a PC software tool for parameter management, monitoring, and diagnosis. DriveWizard can load, store,
and copy drive parameter settings. For details, refer to Help in the DriveWizard software.
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 133
4.11 Test Run Checklist
Check the items that correspond to the control mode being used.
WARNING! Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to
comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on
terminal S1 may cause the drive to start.
6 Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. 186
Open Loop Vector Control (A1-02 = 2) or Closed Loop Vector Control (A1-02=3)
7 Decouple motor shafts and machines when performing Rotational Auto-Tuning. 116
11 Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if possible. 186
Open Loop Vector Control for PM (A1-02 = 5)
12 Perform Auto-Tuning as described. 125
Advanced Open Loop Vector Control for PM (A1-02 = 6)
13 Perform Auto-Tuning as described. 125
14 Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. 186
Closed Loop Vector Control for PM (A1-02 = 7)
15 Set PM motor data using E5- parameters. 125
16 Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if possible. 186
18 Set the offset between the rotor magnetic axis and the Z-pulse of the encoder connected to E5-11. 217
19 The should be displayed on the LCD operator after giving a Run command. –
20 To give a Run command and frequency reference from the digital operator, press to set to LOCAL. The LO/RE key will light. 95, 104
If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/T1, V/T2, W/T3) or change
21 344
parameter b1-14.
22 In accordance with load condition, set Heavy Duty or Normal Duty mode using C6-01. Heavy Duty is the default setting. 189
23 Set the correct values for the motor rated current (E2-01, E4-01, E5-03) and motor protection (L1-01) to ensure motor thermal protection. 210, 257
134 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
4.11 Test Run Checklist
If the Run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE and be sure the LO/RE
24 104
light is out.
If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0 to 10 V or -10 to +10 V)
25 144
or the correct current input signal level (4 to 20 mA or 0 to 20 mA).
26 Apply the proper signal level (-10 to +10 V or 0 to 10 V) to terminal A1, A2, or A3. 144
27 Apply the proper signal level (-10 to +10 V, 4 to 20 mA or 0 to 20 mA) to terminal A2. 144
Set the level for current signal to H3-09 (set to 2 for 4 to 20 mA, or 3 for 0 to 20 mA). Set terminal A2 function to H3-10 (set to 0 for
28 144
Frequency Bias).
Set DIP switch S1 on the drive to “I” when using terminal A2 as current input.
29 82
Set DIP switch S1 on the drive to “V” when using terminal A2 as voltage input.
If the frequency reference is supplied via one of the analog inputs, make sure the analog input produces the desired frequency reference. Make
the following adjustments if the drive does not operate as expected:
• Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1, H3-11 for input A2, H3-07
30 247, 249
for analog input A3) until the frequency reference value reaches the desired value.
• Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2, H3-08
for analog input A3) until the frequency reference value reaches the desired minimum value.
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 135
4.11 Test Run Checklist
136 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5
Parameter Details
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 137
5.1 A: Initialization
5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
A1: Initialization
A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 2 2
138 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.1 A: Initialization
Parameter Details
Setting 1110: User Initialize
Drive parameters are reset to values selected by the user as User Settings. User Settings are stored when parameter o2-03
is set to “1: Set defaults”.
Note: A “user-initialization” resets all parameters to a user-defined set of default values that were previously saved to the drive. To
clear the user-defined default values, set parameter o2-03 to 2.
Setting 2220: 2-Wire Initialization
5
Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as Forward run and
Reverse run, respectively. For more on digital input functions, refer to Setting 40, 41: Forward run, Reverse run
command for 2-wire sequence on page 234.
Setting 3330: 3-Wire Initialization
The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as Run, Stop,
and Forward/Reverse respectively. Also refer to digital input functions, Setting 0: 3-Wire Sequence on page 227.
Setting 5550: oPE04 Reset
If parameters on a certain drive have been edited and then a different terminal block is installed with different settings
saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the
terminal block memory, set A1-03 to 5550.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 139
5.1 A: Initialization
- MODE - PRG
Programming
2.
Press the key until the Parameter Setting Mode screen appears.
HELP FWD DATA
-PRMSET- PRG
Initialization
3. A1-00=0
Press the key to enter the parameter menu tree. Select Language
FWD
-PRMSET- PRG
Select Language
4. Select the flashing digits by pressing . A1-00=0 ∗0∗
English
FWD
-PRMSET- PRG
Enter Password
5. Select A1-04 by pressing .
A1- 04 = 0
(0~9999)
“0”
FWD
140 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.1 A: Initialization
Step Display/Result
-PRMSET- PRG
Select Password
Press the key while holding down at the same time. A1-05 will appear.
6. A1- 05 = 04
(0~9999)
Note: Because A1-05 is hidden, it will not be displayed by simply pressing the key. “0”
FWD
-PRMSET- PRG
Select Password
7. Press the key.
A1- 05 = 0000
(0~9999)
“0”
FWD
-PRMSET- PRG
Select Password
8. Use F1 , F2 , , and to enter the password. A1-05= 1234
(0~9999)
left right “0”
FWD
9.
Press to save what was entered. Entry Accepted
-PRMSET- PRG
Select Password
10. The display automatically returns to the display shown in step 5. A1- 05 = 1234
(0~9999)
“0”
FWD
Table 5.3 Check to see if A1-02 is locked (continuing from step 10 above)
Step Display/Result
-PRMSET- PRG
Control Method
1. A1-02= 2 ∗2∗
Press to display A1-02. Open Loop Vector
FWD
2. – –
Press to make sure that the setting values cannot be selected.
- MODE - PRG
Programming
3. Press to return to the first display.
HELP FWD DATA
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 3 above)
Step Display/Result
-PRMSET- PRG
Parameter Details
Initialization
1. A1-00=0
Press to enter the parameter setup display. Select Language
FWD
-PRMSET- PRG
Select Language
2. A1-00=0 ∗0∗
Press to select the flashing digits as shown. English
FWD
5
-PRMSET- PRG
Enter Password
3. A1- 04 = 0
Press to scroll to A1-04. (0~9999)
“0”
FWD
-PRMSET- PRG
Press the key. Enter Password
4. A1- 04 = 1234
Use F1 , F2 , , and to enter the password. (0~9999)
“0”
left right FWD
5.
Press to save the new password. Entry Accepted
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 141
5.1 A: Initialization
Step Display/Result
-PRMSET- PRG
Enter Password
6. Drive returns to the parameter display. A1- 04 = 0
(0~9999)
“0”
FWD
-PRMSET- PRG
Control Method
7. A1-02= 2 ∗2∗
Press and scroll to A1-02. Open Loop Vector
“2”
FWD
-PRMSET- PRG
Control Method
8. A1-02= 2 ∗2∗
Press to display the value set to A1-02. Open Loop Vector
FWD
-PRMSET- PRG
Control Method
9. A1-02= 0 ∗2∗
Use or to change the value if desired (though changing the control mode at this point is not typically done). V/F Control
“2”
FWD
10.
Press to save the setting, or press to return to the previous display without saving changes. Entry Accepted
-PRMSET- PRG
Control Method
11. The display automatically returns to the parameter display. A1-02= 0 ∗0∗
V/F Control
FWD
Note: Parameter settings can be edited after entering the correct password. Performing a 2-wire or 3-wire initialization resets the
password to “0000”. Reenter the password to parameter A1-05 after drive initialization.
142 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.1 A: Initialization
Parameter Details
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 143
5.2 b: Application
5.2 b: Application
b1: Operation Mode Selection
b1-01: Frequency Reference Selection 1
Use parameter b1-01 to select the frequency reference source 1 for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light. However, the RUN indicator LED will light in zero speed control when A1-02 is set to 3, 5, or
6.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Figure 5.1
Drive Drive
V 10.5 V, 20 mA power supply V 10.5 V, 20 mA power supply
0 to 10 V -10 to 10 V
2 kΩ A1 Analog Input 1 4 kΩ A1 Analog Input 1
144 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 5.6 to set terminal A2 for current input.
Table 5.6 Analog Input Settings for Frequency Reference Using a Current Signal
Parameter Settings
Terminal Signal Level Notes
Signal Level Selection Function Selection Gain Bias
4 to 20 mA H3-09 = 2 H3-10 = 0 Make sure to set DIP switch S1 on the
A2 H3-11 H3-12
0 to 20 mA H3-09 = 3 (Frequency Bias) terminal board to “I” for current input.
Figure 5.2
DIP switch S1
V I Drive
V 10.5 V, 20 mA power supply
A1 Analog Input 1
0 or 4 to 20 mA
A2 Analog Input 2
A3 Analog Input 3
Parameter Details
When b1-01 is set to 4, the frequency reference must be provided by a pulse train signal to terminal RP. Follow the
directions below to make sure the pulse train signal is working properly.
Verifying Pulse Train is Working Properly
• Make sure that b1-04 is set to 4 and H6-01 is set to 0.
• Set the pulse input scaling H6-02 to the pulse train frequency value that equals 100% of the frequency reference. 5
• Enter a pulse train signal to terminal RP and check if the correct frequency reference is displayed.
b1-02: Run Command Selection 1
Parameter b1-02 determines the Run command source 1 in the REMOTE mode.
Setting 0: Operator
This setting requires entering the Run command via the digital operator RUN key and also illuminates the LO/RE
indicator on the digital operator.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 145
5.2 b: Application
Output frequency
Deceleration in the time set
b2-04
Figure 5.3 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum output frequency), then DC Injection Braking will begin as
soon as the frequency falls to the value set to E1-09.
146 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Output frequency
Deceleration in the time set
Output frequency
Deceleration in the time set
b2-04
Figure 5.5 Zero Speed Control at Stop in CLV and CLV/PM
Note: If b2-01 is set to lower than the minimum output frequency (E1-09), then Zero Speed Control begins at the frequency set to
E1-09.
Setting 1: Coast to stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled
deceleration) to stop. The stopping time is determined by the inertia and the friction in the driven system.
Figure 5.6
Run
command ON OFF
Parameter Details
Output
frequency
Drive output is shut off
Motor speed
5
Figure 5.6 Coast to Stop
Note: After a stop is initiated, any subsequent Run command entered will be ignored until the momentary power loss minimum
baseblock time (L2-03) has expired. Do not enter Run command until it has come to a complete stop. To start the motor back up
before it has stopped completely, use DC Injection at start (refer to b2-03: DC Injection Braking Time at Start on page 154) or
Speed Search (refer to b3: Speed Search on page 155).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 147
5.2 b: Application
Run
command ON OFF
DC Injection Braking
Output with the current set in
frequency b2-02
Motor speed
Motor coasts
Momentary Power
Loss Minimum
Baseblock Time
(L2-03)
b2-0410
b2-04
148 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration
time.
Figure 5.10
S1 S1
S1
S2
t t
Set deceleration time Set deceleration time
Parameter Details
the deceleration time that was active only when the Run command was removed.
• The Dwell function must be deactivated (b6-03 and b6-04 = 0).
• Stall Prevention during stop must be deactivated (L3-04 = 0). For regenerative loads a braking option might be
necessary.
• High Slip Braking must be deactivated (H1- must be different from 68).
• The S-curves at deceleration start and deceleration end must be inactive (C2-03/C2-04 = 0).
5
b1-04: Reverse Operation Selection
For some applications, reverse motor rotation is not appropriate and may cause problems (e.g., air handling units, pumps,
etc.).
Note: Setting parameter b1-04 to 1 instructs the drive to ignore any Reverse run commands.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 149
5.2 b: Application
b1-05: Action Selection below Minimum Output Frequency (CLV and CLV/PM)
Parameter b1-05 sets the operation when the frequency reference is lower than the minimum output frequency set in
parameter E1-09.
Run OFF ON
Command common_TMonly
E1-09 Min.
Output Frequency
Frequency
reference Zero Speed Zero Speed
IM: Initial Excitation Control
PM: Zero Spd. Contr. b2-01 DC Control
Injection Braking E1-09
Start Frequency
Motor
Speed b2-03 b2-04
DC Injection Braking Time at Start DC Injection Braking Time at Stop
Figure 5.12 Run at the Frequency Reference
Setting 1: Coast to Stop
The motor is started first when the frequency reference exceeds the setting of parameter E1-09. Once the motor is
running and the frequency reference falls below E1-09 the drive output is shut off and the motor coasts. When the motor
speed falls below the zero speed level set in parameter b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 5.13
Run OFF ON
Command
E1-09 Min.
Output Frequency
Frequency
reference Motor common_TMonly
IM: Initial Excitation Coasts
PM: Zero Spd. Contr. b2-01 DC Zero Speed
Injection Braking Control
Start Frequency
Motor
Speed b2-03 b2-04
DC Injection Braking Time DC Injection Braking Time at Stop
at Start
Figure 5.13 Coast to Stop
Setting 2: Run at the minimum frequency
Whenever a Run command is active and the frequency reference is smaller than the value of parameter E1-09, the drive
runs the motor at the speed set in E1-09. When the Run command is removed, the drive decelerates the motor. As soon as
the motor speed reaches the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 5.14
Run OFF ON
Command
E1-09 Min.
Output Frequency
Frequency common_TMonly
reference Run at
Run at Zero Speed
IM: Initial Excitation E1-09 E1-09
b2-01 DC Control
PM: Zero Spd. Contr.
Injection Braking
Start Frequency
Motor
Speed b2-03 b2-04
DC Injection Braking Time at Start DC Injection Braking Time at Stop
150 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Run OFF ON
Command
E1-09 Min.
Output Frequency
Frequency
common_TMonly
reference Zero
Zero Speed
IM: Initial Excitation Speed
b2-01 DC Control
PM: Zero Spd. Contr. Control
Injection Braking E1-09
Motor Start Frequency
Speed b2-03 b2-04
DC Injection Braking Time at Start DC Injection Braking Time at Stop
Figure 5.15 Zero Speed Control
Parameter Details
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run
command may already be present at the location the source was switched to. Parameter b1-07 can be used to determine
how the Run command is treated in this case.
5
No. Parameter Name Setting Range Default
b1-07 LOCAL/REMOTE Run Selection 0 or 1 0
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 151
5.2 b: Application
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
152 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Setting 0: Run command is not accepted when b2-01 motor speed < E1-09.
Setting 1: Run command is accepted when b2-01 motor speed < E1-09.
b1-24: Commercial Power Switching Selection
When the output frequency matches the power supply frequency (50 Hz), the PWM switching operation stops and
switches to operation with a direct commercial power supply connection.
Note: 1. Commercial power switching can be enabled when an induction motor is being driven in V/f or OLV control modes (A1-02 = 0 or 2).
2. Input and output current value may change when a switch is made.
3. Verify that the induction motor can be driven with the commercial power supply (e.g., the rated voltage and rated speed) prior to
enabling the commercial power switching selection.
0: Disabled
A voltage will be output with PWM switching operation regardless of the output frequency.
1: Enabled
When the deviation between the output frequency and the power supply frequency is less than or equal to the commercial
power switching output frequency coincidence level (b1-26), the PWM switching operation stops and switches to
operation with a direct commercial power supply connection.
Operation with a direct commercial power supply continues until the deviation between the output frequency and the
power supply frequency is greater than or equal to the commercial power switching output frequency coincidence/
non-coincidence level (b1-25 + b1-26).
Parameter Details
b1-25/b1-26 Commercial Power Supply Cancellation Level/Switching Level
These parameters set the value in 0.1 Hz increments at which commercial power supply switching selection is enabled
and disabled.
When the deviation between the output frequency and the power supply frequency becomes equal to or less than the
setting values of b1-26, an output frequency coincidence condition exists. 5
The drive will operate in commercial power switching mode.
If the drive will not switch to commercial power supply switching mode, set b1-26.
When the deviation between the output frequency and the power supply frequency becomes equal to or greater than the
setting value of b1-25 + b1-26, the drive will operate in PWM switching mode.
If commercial power switching mode and PWM switching mode are repeated frequently, increase the setting value of
b1-25.
Note: The drive will not switch to commercial power switching mode when L3-06, Stall Prevention Level during Run, is exceeded and
L3-05, Stall Prevention Selection during Run, is enabled.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 153
5.2 b: Application
The function triggered by parameter b2-01 depends on the control mode that has been selected.
OLV/PM, AOLV/PM, V/f, V/f w/PG and OLV (A1-02 = 0, 1, 2, 5, 6)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at stop. Once the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
Figure 5.16
DC Injection
common_ E1-09 Min. Output Braking
Frequency
TMonly b2-01 DC Injection
Braking Start Frequency
Output Time
frequency
b2-04
Figure 5.16 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum output frequency), then DC Injection Braking will begin as
soon as the frequency falls to the value set to E1-09.
CLV and CLV/PM (A1-02 = 3, 7)
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop.
Once the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter
b2-04.
Figure 5.17
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should
only be increased to the level necessary to hold the motor shaft.
b2-03: DC Injection Braking Time at Start
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) at start. Used to stop a coasting
motor before restarting it or to apply braking torque at start. Disabled when set to 0.00 s.
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), DC Injection or Speed Search should
be used to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur.
154 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
When a Run command is issued, the DC current level injected into the motor changes linearly from the level set to b2-08
to E2-03 within the time set to b2-03.
Note that the level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor
rated current, whichever value is smaller.
Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to b2-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.
Parameter Details
The operation timing of the Speed Search after a momentary power loss is shown in Figure 5.18. The operation timing
after restarting is shown in Figure 5.19.
After restoring power, the Speed Search operation remains in baseblock status for at least the time set in b3-05.
However, Speed Search will not start if the time set in L2-03, Minimum Baseblock Time, has not expired after the power
stops. 5
When induced voltage remains in the motor, the Speed Search operation starts after the time set in b3-05 without waiting
for the time set in L2-03.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 155
5.2 b: Application
Figure 5.18
Output frequency
Figure 5.18 Time Chart for Speed Search after Recovery from Momentary Power Loss
When performing a speed search operation at start, the speed search operation will start after waiting for the longer of the
times set in b3-05 and L2-03 after the Run command input is received.
When induced voltage remains in the motor, the Speed Search operation starts after the time set in b3-05 without waiting
for the time set in L2-03.
Figure 5.19
Run command
Output
frequency
Momentary Power
Loss
common_TMonly Minimum Baseblock
Time (L2-03)
b3-05
156 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
• Use Current Detection Speed Search 2 instead of Speed Estimation when operating motors smaller than 1.5 kW. Speed
Estimation can end up stopping smaller motors, as it might not be able to detect the speed or rotation direction of such
small motors.
Speed Search Activation
Speed Search can be activated as described below. Select the Speed Search type in parameter b3-24 independent of the
activation method.
1. Automatically activate Speed Search with every Run command. Set b3-01, Speed Search Selection at Start, to 1
(Enabled). External Speed Search commands are ignored.
2. Activate Speed Search using the digital input terminals.
The following input functions for H1- can be used.
Table 5.7 Speed Search Activation by Digital Inputs
Setting Description b3-24 = 1 b3-24 = 2
Closed: Activate Current Detection Speed Search from the
61 External Search Command 1
maximum output frequency (E1-04).
Activate Speed Estimation Speed Search
Closed: Activate Current Detection Speed Search from the
62 External Search Command 2
frequency reference.
To activate Speed Search by a digital input, the input must always be set together with the Run command, or the Run
command must be entered after the Speed Search command is given.
3. After automatic fault restart
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically
perform Speed Search as specified by b3-24 following a fault.
4. After momentary power loss
This mode requires that the Power Loss Ride-Thru function be enabled always or at least enabled during CPU
operation (L2-01 = 1 or 2). Refer to L2-01: Momentary Power Loss Operation Selection on page 262
5. After external baseblock is released
The drive will resume the operation starting with Speed Search if the Run command is present and the output
frequency is above the minimum frequency when the Baseblock command is released.
Rotation Direction Detection Conditions for Backspin
Backspin occurs when the motor rotates in the opposite direction from the rotation direction command.
Specify the speed search direction when power is recovered after a momentary power loss in applications in which
backspin can occur, such as for an oil pump when backspin may occur due to the weight of the oil after a momentary
power loss. The search starts from the rotation direction specified in the direction command when the momentary power
loss time is short.
The search starts from the opposite direction of the direction specified in the direction command when the momentary
Parameter Details
power loss time is long. The rotation for the Speed Search is determined as follows:
[t] is the time from the momentary power loss to recovery.
• 0 t < b3-50: The search is started in the direction specified by the frequency reference.
• b3-50 t < b3-51: The motor is not restarted and the baseblock continues.
The search starts from the opposite direction of the direction command when the momentary power loss time exceeds 5
the setting value of b3-51.
• b3-51 t: The search is started in the direction opposite to the frequency reference.
Refer to b3-50/b3-51 Backspin Search Direction Judgment Time 1/2 on page 161 for details on the backspin direction
judgment time.
Note: 1. Set b3-50 to a value higher than 0.0 s to enable rotation direction detection for backspin.
2. When setting b3-50, be sure to also set the following parameters to the values specified. Setting these parameters to any other values
will trigger an oPE08 fault.
b3-50 b3-51
b3-14 = 0
b3-24 = 2
3. Backspin detection is not necessary with a PM motor.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 157
5.2 b: Application
Setting 0: Disabled
When the Run command is entered, the drive starts operating at the minimum output frequency. If external Speed Search
1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
Speed Search is performed whenever the Run command is entered. The drive begins running the motor once Speed
Search is complete.
b3-03: Speed Search Deceleration Time
Parameter b3-03 sets the output frequency reduction ramp. The time entered into b3-03 will be the time to decelerate
from maximum frequency (E1-04) to minimum output frequency (E1-09).
In Current Detection Type 2 Speed Search, the time set in this parameter is used as the acceleration or deceleration time
for the output frequency while searching.
Note: If Speed Estimation is not working correctly even after adjusting b3-06, try using Current Detection Speed Search 2 instead.
b3-08: Current Control Gain during Speed Search (Speed Estimation Type)
There is normally no need to change this parameter from the default value.
Sets the proportional gain for the current controller during Speed Search.
158 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Setting 0: Disabled
The drive uses the frequency reference to determine the direction of motor rotation in order to restart the motor.
Setting 1: Enabled
The drive detects the motor rotation direction in order to restart the motor.
b3-17: Speed Search Restart Current Level (Speed Estimation Type)
A large current can flow into the drive if there is a fairly large difference between the estimated frequency and the actual
motor speed when performing Speed Estimation. This parameter sets the current level at which Speed Estimation is
restarted, thus avoiding overcurrent and overvoltage problems. Set as a percentage of the drive rated current.
Parameter Details
exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.
1: Speed Estimation
2: Current Detection 2
Note: 1. Enable or disable Speed Search at start with b3-01 and Speed Search after momentary power loss with L2-01.
2. Refer to Current Detection Speed Search 2 (b3-24 = 2) on page 156 and Speed Estimation Speed Search (b3-24 = 1) on page 156
for details on the Speed Search direction.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 159
5.2 b: Application
160 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Speed Search from the Direction Command (0.0 Momentary Power Loss Time t < b3-50)
When time t from the momentary power loss to recovery is shorter than the setting value of b3-50, Speed Search is
performed in the direction specified by the direction command. The deceleration time set in b3-52 is used for the search
frequency and the setting value of the maximum frequency is used as the starting search frequency.
Figure 5.20
Output frequency
Forward operation
b3-52
ed
r spe
Moto
Parameter Details
Search in progress
t
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 161
5.2 b: Application
Figure 5.21
Output frequency
Forward operation
M
ot
or
sp
ee
d
Output frequency
Forward operation
M
ot
or
sp
ee
d
b3-51
b3-53 common_TMonly
Search in progress
t
Figure 5.22 Speed Search in Direction Opposite to Direction Command (b3-50 t < )
162 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Parameter Details
Internal data of H2-01 ON ON On (Closed)
Off (Open)
Time period that the multi-function Time period that the multi-function
digital output is closed < 100 ms
common_
digital output is closed ≥ 100 ms
Time period that the multi-function
digital output is closed = 100 ms
Note: Even if the length of the off-delay time and on-delay time for multi-function digital outputs are each less than 100 ms, the
multi-function digital output closes for at least 100 ms.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 163
5.2 b: Application
PID input
Time
PID output
I control
common_TMonly
PID Output D control
P control
Time
Figure 5.24 PID Operation
164 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Note: A duplicate allocation of the PID setpoint input will result in an oPE alarm.
Note: A duplicate allocation of the PID feedback input will result in an oPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in Table 5.11. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.11 PID Differential Feedback Sources
PID Differential Feedback Source Settings
Analog Input A1 Set H3-02 = 16
Parameter Details
Analog Input A2 Set H3-10 = 16
Analog Input A3 Set H3-06 = 16
Note: A duplicate allocation of the PID differential feedback input will result in an oPE alarm.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 165
Figure 5.25
166
Frequency Reference
Upper Limit
Frequency Reference
PID disable when: Fmax x109%
Selection 1/2
b1-01/15 - b5-01=0
5.2 b: Application
2
Serial Comm Delay Time
3 0 50% 100% Always 1 b5-15
Option Card
Rev Run Fwd Run when PID Sleep Function Start Level
Pulse Input 4 1 PID off
Sleep Function
0
Disabled 1
PID Function Setting + Output
b5-01 = 1/2 b5-01 = 3/4 + Enabled 0 Frequency
d4-11 SFS
Bi-directional C1-
PID Target Output Sel.
Upper Limit
b5-18=1 PID Ouput
b5-19 not 1 Fmax x109%
(U5-03)
PID Setpoint 0
H3-02/10=C not C
Analog Input A1/A2/A3 PID SFS Cancel DI (U5-04) b5-11
H1-=34 Lower Limit 0 1
H6-01=2 not 2 On
Pulse Input
Enable / Disable Reverse
Off Upper Limit
Reg. 0Fh, bit 1 Operation when PID
MEMOBUS Reg. 0006h Fmax x109%
1 0 Output is Negative
Always 1 when
PID Input b5-01 = 3/4
PID Accel/Decel Time (U5-02) Lower Limit
b5-17 Fmax x109%
Feedback Z-1
(U5-05)
Parameter Details
b5-04: Integral Limit Setting
Sets the maximum output possible from the integral block. Set as a percentage of the maximum frequency (E1-04).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 167
5.2 b: Application
Note: Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant
frequency. Increasing this time constant may reduce the responsiveness of the drive.
168 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
PID
Feedback
Low Detection
Level
(b5-13) common_TMonly
time
no FbL
detection
FbL detection
Parameter Details
detection level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2- =
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to
b5-37. Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the
feedback value leaves the loss detection range, the output is reset.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, an “FbL - PID Feedback 5
Loss” alarm will be displayed and a digital output set for “PID feedback low” (H2- = 3E) will be triggered. If the
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, an “FBH - Feedback High” alarm
will be displayed and a digital output set for “PID feedback high” (H2- = 3F) will be triggered. Both events trigger
an alarm output (H2- = 10). The drive will continue operation. When the feedback value leaves the loss detection
range, the alarm and outputs are reset.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, an “FbL - PID Feedback
Loss” fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to
b5-37, an “FbH - Feedback High” fault will be displayed. Both events trigger a fault output (H2- = E) and cause the
drive to stop the motor.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 169
5.2 b: Application
PID Sleep
The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep
operation level for a certain time. The drive will resume operating once the PID output or frequency reference rises above
the PID Sleep operation level for the specified time. An example of PID Sleep operation appears in the figure below.
Figure 5.27
PID Output
PID Sleep Function
Start Level (b5-15)
b5-16 b5-16
common_TMonly
Internal Run PID Sleep Delay Time
command Run Stop
External Run Run command enabled
command Continues to output “During Run”
During Run
Figure 5.27 PID Sleep Operation
Notes on using the PID Sleep function
• The PID Sleep function is always active, even if PID control is disabled.
• The PID Sleep function stops the motor according to the stopping method in b1-03.
The parameters that control the PID Sleep function are explained below.
170 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint.
Parameter Details
Setting 1: Enabled
Parameter b5-19 is used as PID setpoint.
b5-19: PID Setpoint Value
Used as the PID setpoint if parameter b5-18 = 1.
5
No. Name Setting Range Default
b5-19 PID Setpoint Value 0.00 to 100.00% 0.00%
Setting 0: 0.01 Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 171
5.2 b: Application
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user defined display for the PID
setpoint value (b5-19) and PID feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
172 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Fine-Tuning PID
Once PID control parameters have been set, fine-tuning may be required. Follow the directions below.
Table 5.12 PID Fine Tuning
Goal Tuning Procedure Result
Time
After adjustment
Response
Quickly achieve stability, and some • Decrease the integral time (b5-03)
overshoot is permissible • Increase the derivative time (b5-05) Before adjustment
Time
Before adjustment
Response
Time
Before adjustment
Response
• If oscillation cycle time is close to the derivative
time, the derivative part is likely having too much
influence. Reduce the derivative time (b5-05). After adjustment
Suppress short cycle oscillations • If the derivative time is set to 0.00 s and
oscillations are still a problem, try reducing the
proportional gain (b5-02) or try increasing the
PID primary delay time (b5-08)
Time
Parameter Details
b6: Dwell Function
The Dwell function is used to temporarily hold the frequency reference at a predefined value for a set time, then continue
accelerating or decelerating.
If used with induction motors, the Dwell function can help prevent speed loss when starting and stopping a heavy load. If
running a PM motor in V/f control, the pause in acceleration allows the PM motor rotor to align with the stator field of 5
the motor, thus reducing the starting current.
Figure 5.28 shows how the Dwell function works.
Note: Using the Dwell function requires that the stopping method for the drive be set to “Ramp to stop” (b1-03 = 0).
Figure 5.28
OFF ON OFF
Run Command
common_TMonly
b6-01 b6-03
Output Frequency
b6-02 b6-04
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 173
5.2 b: Application
Motor A runs faster than B, pulling more load Motor B runs faster than A, pulling more load
common_TMonly
fref_B increase fref_B decrease
Droop Control increases the speed reference in Droop Control decreases the speed reference in
drive B accomplishing load balance drive B accomplishing load balance
Speed
Speed reference
Torque
0 100%
Figure 5.30 Droop Control Gain
174 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Setting 0: Disabled
Setting 1: Enabled
Setting 0: Disabled
Setting 1: Enabled
b8-02: Energy Saving Gain (OLV, CLV)
Sets the gain level for Energy Saving. A higher value results in lower magnetization of the motor and thereby less energy
consumption. However, if b8-02 is too high, the motor may stall.
Parameter Details
No. Name Setting Range Default
b8-02 Energy Saving Gain 0.0 to 10.0 Determined by A1-02
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 175
5.2 b: Application
Note: This default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically
when Auto-Tuning for Energy Saving is performed (Refer to Auto-Tuning on page 116).
176 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.2 b: Application
Parameter Details
No. Name Setting Range Default
b9-01 Zero Servo Gain 0 to 100 5
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 177
5.3 C: Tuning
5.3 C: Tuning
C parameters are used to set the acceleration and deceleration characteristics, as well as S-curves. Other parameters in
this group cover settings for slip compensation, torque compensation, and carrier frequency.
Figure 5.32 shows an operation example for changing accel/decel. times. The example below requires that the stopping
method be set for “Ramp to stop” (b1-03 = 0).
Figure 5.32
Time
ON OFF ON ON OFF ON
FWD (REV)
Run command
ON OFF ON
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1- = “7”)
ON
Accel/Decel Time Selection 2
(Terminals S1 to S8, H1- = “1A”)
178 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Output Frequency
C1-11
Accel/Decel Time
Switching Frequency
Parameter Details
and the Run command is cycled.
A digital output programmed for “During Fast Stop” (H2- = 4C) will be closed as long as Fast Stop is active.
A Fast Stop can be selected as the action the drive should take when certain faults occur, such as L8-03 (Overheat
Pre-Alarm Operation Selection).
5
No. Parameter Name Setting Range Default
C1-09 Fast Stop Time 0.0 to 6000.0 s <1> 10.0 s
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the
time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 179
5.3 C: Tuning
C1-10 cannot be set to 0 if any of the parameters C1-01 to C1-09 is set to 600.1 s or longer.
Setting 1: 0.1 s units
The accel/decel times are set in 0.1 s units. The setting range is 0.0 to 6000.0 s.
C1-11: Accel/Decel Time Switching Frequency
Sets the frequency at which the drive switches between accel/decel time settings. Refer to Switching Accel/Decel Times
by a Frequency Level on page 179.
FWD run
REV run
C2-02 C2-03
C2-04
common_TMonly
Output
frequency C2-01
C2-01 C2-04
C2-02 C2-03
180 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Note: Default setting is 0.0 in V/f Control (A1-02 = 0), and 1.0 in Open Loop Vector Control (A1-02 = 2). In Closed Loop Vector
Control, slip compensation is used to correct inaccuracies that can result from temperature fluctuation in the rotor.
Note: Default for V/f Control (A1-02 = 0) is 2000 ms. Default for Open Loop Vector Control (A1-02 = 2) is 200 ms.
The slip compensation limit is constant throughout the constant torque range (frequency reference E1-06). In the
constant power range (frequency reference E1-06), it is increased based on C3-03 and the output frequency as shown in
Figure 5.35.
Figure 5.35
E1-04
E1-06 × C3-03
C3-03
common_TMonly
Output Frequency
E1-06 E1-04
Base Maximum Output
Frequency Frequency
Parameter Details
Enables or disables slip compensation during regenerative operation.
Even if enabled, this function does not operate when the output frequency is too low.
Setting 0: Disabled
5
Slip compensation is not provided. Depending on the load and mode of operation, the actual motor speed will be lower or
higher than the frequency reference.
Setting 1: Enabled (6 Hz and above)
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)
Slip compensation is enabled during regenerative operation, and at frequencies as low as 2 Hz. The drive uses the motor
rated slip set in E2-02 to automatically calculate the frequency range where compensation will be disabled.
C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 181
5.3 C: Tuning
If the input power supply voltage is low or the motor has a high voltage rating, this function can help improve the speed
precision when moving heavy loads at high speeds. When this function is enabled, the reduction in flux causes a slightly
higher current at high speed. Keep this in mind when selecting the drive.
Setting 0: Disabled
Setting 1: Enabled
C3-21: Motor 2 Slip Compensation Gain
Used to improve speed accuracy for motor 2. Functions in the same way that C3-01 functions for motor 1.
Adjust this parameter only after the motor 2 rated current (E4-01), motor 2 rated slip (E4-02), and the motor 2 no-load
current (E4-03) have all been set.
Refer to C3-01: Slip Compensation Gain on page 180 for details on adjusting this parameter.
Note: Default setting is 0.0 in V/f Control (E3-01 = 0). Default setting is 1.0 in Open Loop Vector Control (E3-01 = 2) and Closed Loop
Vector Control (E3-01 = 3). In Closed Loop Vector Control, slip compensation gain acts as an adaptable gain.
Note: The default for V/f Control (E3-01 = 0) is 2000 ms. The default for Open Loop Vector Control (E3-01 = 2) is 200 ms.
The slip compensation limit is constant throughout the constant torque range (frequency reference E3-06). In the
constant power range (frequency reference E3-06), it is increased based on C3-23 and the output frequency as shown in
Figure 5.36.
Figure 5.36
E3-04
E3-06 × C3-23
common_TMonly
C3-23
Output Frequency
E3-06 E3-04
Base Maximum Output
Frequency Frequency
Figure 5.36 Slip Compensation Limit
182 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Setting 0: Disabled
Setting 1: Enabled (6 Hz and above)
Setting 2: Enabled (compensation provided wherever possible)
Parameter Details
No. Parameter Name Setting Range Default
C4-02 Torque Compensation Primary Delay Time 0 to 60000 ms Determined by A1-02
Adjustment
Although C4-02 rarely needs to be changed, adjustments may help in the following situations:
• If the motor vibrates, increase C4-02. 5
• If the motor responds too slowly to changes in the load, decrease C4-02.
C4-03: Torque Compensation at Forward Start (OLV)
Sets the amount of torque at start in the forward direction in order to improve motor performance during start with a
heavy load. Compensation is applied using the time constant set in parameter C4-05. Enable this function when the load
pulls the motor in reverse when starting with a Forward run command. Setting of 0.0% disables this feature.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 183
5.3 C: Tuning
function if the load pulls the motor in the forward direction when starting with a Reverse run command. Setting 0.0%
disables this feature.
+ Output frequency
Frequency
reference
+
ASR limit
+
common_TMonly
- +
Change
Detected speed
rate
P
limiter +
I
C5-01
C5-05
C5-03
C5-02, C5-04
Figure 5.37 Speed Control Block Diagram for V/f Control with PG
Figure 5.38
Torque limits
C5-01, C5-03
+ + Torque reference
Frequency Primary
P
reference
-
filter
common_TMonly
I +
I limit
C5-06
L7-01 to L7-04
Detected speed C5-02, C5-04 C5-08
<1>
<1> Advanced Open Loop Vector Control for PM motors estimates the speed using the motor model and does not require an encoder
feedback signal.
Figure 5.38 Speed Control Block Diagram for CLV, AOLV/PM and CLV/PM
184 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Parameter Details
Table 5.15 ASR Setup Problems and Corrective Actions
Problem Possible Solutions
Speed reference
Slow response to speed changes or speed • Increase the ASR proportional gain.
deviation lasts for too long Motor Speed
• Decrease the integral time.
5
Time
Motor Speed
Time
Speed reference
Time
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 185
5.3 C: Tuning
Speed reference
• Check the pulse number set to F1-01 and the gear ratio in F1-12 and F1-13.
The motor slip is not fully compensated when • Make sure the pulse signal from the encoder is set up properly.
running in V/f Control with PG Motor Speed • Check monitor U6-04 and check if the ASR is working at its output limit (setting of
C5-05). If so, increase C5-05.
Time
Integral operation is enabled in V/f Control with • Decrease the ASR proportional gain.
PG (C5-15 = 1) and over/undershoot occurs – • Increase the integral time.
when changing speed. • If the problem persists, reduce the ASR output limit set in C5-05.
• V/f control: Use C5-01/02 and C5-03/04 to set up different ASR settings at minimum
Oscillation at low speed and response is too and maximum speed.
–
slow at high speed (or vice versa) • CLV, AOLV/PM, CLV/PM: Use C5-01, C5-02 and C5-03, C5-04 to define optimal
ASR settings for high and low speed. Use C5-07 to define a switching frequency.
These parameter settings will function differently depending on the control mode.
V/f Control with PG
Parameters C5-01 and C5-02 determine the ASR characteristics at maximum speed, whereas C5-03 and C5-04 determine
the characteristics at minimum speed.
Figure 5.39
P = C5-01
P and I setting
I = C5-02
P = C5-03
I = C5-04
common_TMonly
Motor speed
0 E1-09 E1-04
Min. output frequency Max. output frequency
Figure 5.39 ASR Gain and Integral Time in V/fw/PG
CLV, AOLV/PM, and CLV/PM
In these control modes, parameters C5-03 and C5-04 define the ASR gain an integral time at zero speed. The settings in
C5-01 and C5-02 are used at speeds above the setting in C5-07. C5-07 is set to 0 as the default so that C5-01 and C5-02
are used over the entire speed range. Also refer to C5-07: ASR Gain Switching Frequency on page 187.
Figure 5.40
P = C5-01
P, I
I = C5-02
Ramp
P = C5-03 common_TMonly
I = C5-04 (Low speed)
186 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Figure 5.41
Proportional gain
Proportional gain (P) determined
by motor speed. common_TMonly
C5-03 gain setting
C5-02 C5-02
Figure 5.41 ASR Proportional Gain Switch
ASR Gain Tuning (C5-01, C5-03)
The higher this setting, the faster is the speed response. Too high of a setting can lead to oscillation. In general, this
setting should be increased with larger loads in order to minimize the speed deviation.
ASR Integral Time Tuning (C5-02, C5-04)
Determines how fast a continuous speed deviation problem is eliminated. Too long of an integral time makes the speed
control less responsive, while a too short of an integral time can cause oscillation.
C5-05: ASR Limit
Sets the ASR output limit as a percentage of the maximum output frequency (E1-04). If the motor rated slip is high, the
setting might need to be increased to provide proper motor speed control. Use the ASR output monitor U6-04 to
determine if ASR is working at the limit set in C5-05. If so, make sure the PG 1 pulses per revolution (F1-01), PG 1 gear
teeth 1 and 2 (F1-12, F1-13), and the PG signal are set correctly before making further changes to C5-05.
Parameter Details
No. Parameter Name Setting Range Default
C5-07 ASR Gain Switching Frequency 0.0 to 400.0 Hz <1> Determined by A1-02 <1>
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (0.0 to 100.0%) instead of in Hz.
Note: A multi-function input set for the ASR gain switch (H1- = 77) takes priority over the ASR gain switching frequency.
Switching the proportional gain and integral time in the low or high speed range can help stabilize operation and avoid 5
resonance problems. A good switching point is about 80% of the frequency where oscillation occurs, or at 80% of the
target speed. Refer to C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 186.
C5-08: ASR Integral Limit
Sets the upper limit for ASR as a percentage of the rated load.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 187
5.3 C: Tuning
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
C5-17, C5-18: Motor Inertia, Load Inertia Ratio
C5-17 and C5-18 determine the ratio of the machine inertia to the inertia of the motor being used.
Example: Setting C5-18 to 2.0 reflects a load inertia that is twice the motor inertia.
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed in CLV and CLV/PM control
modes. Refer to Auto-Tuning on page 116 for details on Auto-Tuning or enter the data manually.
C5-21, C5-23 / C5-22, C5-24: Motor 2 ASR Proportional Gain 1, 2 / Integral Time 1, 2
These parameters function for motor 2 in the same way that C5-01 through C5-04 function for motor 1. For more details,
see C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 186.
Note: A multi-function input set for the ASR gain switch (H1- = 77) takes priority over the ASR gain switching frequency.
188 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio
These parameters function for motor 2 in the same way that C5-17 and C5-18 function for motor 1.
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed for motor 2 in CLV and
CLV/PM control modes. Refer to Auto-Tuning on page 116 for details on Auto-Tuning or enter the data manually.
Parameter Details
Duty and Normal Duty Ratings on page 392 for details about the rated current.
Overload
150% Overload
120%
Rated Load
Rated Load 100%
100%
Performance
Use Heavy Duty Rating for applications requiring a high overload Use Normal Duty Rating for applications in which the torque requirements
Application tolerance with constant load torque. Such applications include extruders drop along with the speed. Examples include fans and pumps where a high
and conveyors. overload tolerance is not required.
Over load capability (oL2) 150% of drive rated Heavy Duty current for 60 s 120% of drive rated Normal Duty current for 60 s
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 189
5.3 C: Tuning
Note: By changing the Duty Mode selection, the maximum size motor the drive can run changes, and the E2- parameters are
automatically set to appropriate values (E4- for motor 2). Parameter settings determined by motor capacity are recalculated
automatically when the Duty Mode selection is changed. This includes b8-04, L2-03, n5-02, C5-17, and C5-37.
1: 4.0 kHz
2: 6.0 kHz
3: 8.0 kHz
4: 10.0 kHz
F: User defined (C6-03 to C6-05)
Guidelines for Carrier Frequency Parameter Setup
Symptom Remedy
Speed and torque are unstable at low speeds
Noise from the drive affects peripheral devices
Lower the carrier frequency.
Excessive leakage current from the drive
Wiring between the drive and motor is too long <1>
Audible motor noise is too loud Increase the carrier frequency or use Swing PWM.
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to Table 5.17.
Note: The maximum cable length is 100 m when using OLV/PM (A1-02 = 5) or AOLV/PM (A1-02 = 6).
C6-03, C6-04, C6-05: Carrier Frequency Upper Limit, Lower Limit, Proportional Gain
Use these parameters to set a user defined or a variable carrier frequency. To set the upper and lower limits and the carrier
frequency proportional gain, first set C6-02 to F.
190 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.3 C: Tuning
Parameter Details
C7-56 Power Factor Control Selection 0, 1 0
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 191
5.4 d: Reference Settings
b1-01
(Freq. Reference Selection 1)
LO/RE Key on Digital Operator or common_TMonly
=4 Digital Input H1- = 1
Pulse Train Input
=3
Option Card
=2
MEMOBUS comm.
Digital Input 0
=1 Remote
Terminal A1/A2/A3 H1- = 2 1
MS 1
=0
d1-01 Local
(Freq.Ref 1)
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is “Hz” (o1-03 = 0) in V/f, V/f w/PG, OLV, CLV, and OLV/PM control modes.
The default for AOLV/PM and CLV/PM control modes expresses the frequency reference as a percentage (o1-03 = 1).
192 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
• Multi-Step Speed 2
When setting terminal A3's analog input to Multi-Step Speed 2, set H3-06 (Terminal A3 Function Selection) to 2
(Auxiliary frequency reference 1). When setting d1-02 (Frequency Reference 2) to Multi-Step Speed 2, set H3-06 to F
(Through mode).
• Multi-Step Speed 3
When setting terminal A2's analog input to Multi-Step Speed 3, set H3-10 (Terminal A2 Function Selection) to 3
(Auxiliary frequency reference 2).
When inputting 0 to 10 V to terminal A2's analog input, set H3-09 to 0, and DIP switch S1 on the control circuit
terminal board to V (voltage).
The different speed references can be selected as shown in Table 5.18. Figure 5.43 illustrates the multi-step speed
selection.
Table 5.18 Multi-Step Speed Reference and Terminal Switch Combinations
Multi-Step Multi-Step Multi-Step Multi-Step Jog Reference
Reference Speed Reference 1 Speed Reference 2 Speed Reference 3 Speed Reference 4 Selection
H1- = 3 H1- = 4 H1- = 5 H1- = 32 H1- = 6
Frequency Reference 1 (set in b1-01) OFF OFF OFF OFF OFF
Frequency Reference 2 (d1-02 or input terminal A1, A2, A3) ON OFF OFF OFF OFF
Frequency Reference 3 (d1-03 or input terminal A1, A2, A3) OFF ON OFF OFF OFF
Frequency Reference 4 (d1-04) ON ON OFF OFF OFF
Frequency Reference 5 (d1-05) OFF OFF ON OFF OFF
Frequency Reference 6 (d1-06) ON OFF ON OFF OFF
Frequency Reference 7 (d1-07) OFF ON ON OFF OFF
Frequency Reference 8 (d1-08) ON ON ON OFF OFF
Frequency Reference 9 (d1-09) OFF OFF OFF ON OFF
Frequency Reference 10 (d1-10) ON OFF OFF ON OFF
Frequency Reference 11 (d1-11) OFF ON OFF ON OFF
Frequency Reference 12 (d1-12) ON ON OFF ON OFF
Frequency Reference 13 (d1-13) OFF OFF ON ON OFF
Frequency Reference 14 (d1-14) ON OFF ON ON OFF
Frequency Reference 15 (d1-15) OFF ON ON ON OFF
Frequency Reference 16 (d1-16) ON ON ON ON OFF
Jog Frequency Reference (d1-17) <1> ON
<1> The Jog frequency overrides whatever frequency reference is being used.
Figure 5.43
Frequency d1-16
reference d1-15
d1-14
d1-09
Parameter Details
d1-08
d1-07
d1-06
d1-05
d1-04
d1-03
(A3)
d1-02
(A2) 5
d1-01
(A1) d1-17
Time
FWD (REV) Run/Stop ON
ON ON ON ON ON ON
Multi-step Speed Ref. 1
ON ON ON
Multi-step Speed Ref. 2
ON ON
Multi-step Speed Ref. 3
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 193
5.4 d: Reference Settings
Internal frequency
reference common_TMonly
d2-01
Frequency Reference Upper Limit
Operating
range
194 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
Figure 5.45 shows the relationship between the Jump frequency and the output frequency.
Figure 5.45
Frequency
reference
Frequency
reference
decreases Frequency
reference
increases
Jump
Frequency
Width (d3-04)
common_TMonly
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Parameter Details
Stop command is entered or the power supply is shut down.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 195
5.4 d: Reference Settings
Setting 1: Enabled
• Acceleration hold
The last hold value will be saved when the Run command or the drive power is switched off. The drive will use the
value that was saved as the frequency reference when it restarts. The multi-function input terminal set for “Accel/decel
ramp hold” (H1- = A) must be enabled the entire time, or else the hold value will be cleared when the power is
switched on.
Figure 5.46
ON ON
Power supply
OFF
OFF ON OFF ON
Forward Run/Stop
OFF ON OFF ON
Hold Accel/Decel
Frequency reference
common_TMonly
d4-01 = 0
Hold Hold
Figure 5.46 Frequency Reference Hold with Accel/Decel Hold Function
• Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will
use the frequency reference that was saved when it restarts.
• Up/Down 2 with frequency reference from digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias
value is added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be
used to restart the drive after the power is cycled.
Figure 5.47
Frequency
reference
common_TMonly
Bias 5s
5s
Up 2 command
Figure 5.47 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
196 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
• Up/Down 2 with frequency reference from input sources other than the digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the bias value will be
saved in parameter d4-06. When restarting after the power is switched off, the drive will add the value saved in d4-06
as a bias to the frequency reference.
Figure 5.48
d4-06 value
common_TMonly
5s
Bias
5s
Up 2 command
Figure 5.48 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note: Make sure to set the limits for Up/Down 2 properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to
d4-08: Frequency Reference Bias Upper Limit (Up/Down 2) on page 199 and Refer to d4-09: Frequency Reference Bias
Lower Limit (Up/Down 2) on page 199 for details on the limit settings.
Clearing the Value that was Saved
Depending on which function is used, the frequency reference value that was saved can be cleared by:
• Releasing the input programmed for Acceleration hold.
• Setting an Up or Down command while no Run command is active.
• Parameter d4-06 is reset to zero. Refer to d4-06: Frequency Reference Bias (Up/Down 2) on page 198 for details.
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.
Parameter Details
Figure 5.49
Output
frequency
common_TMonly
Up 2 command
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 197
5.4 d: Reference Settings
Output
frequency
common_TMonly
Up 2 command
198 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
Parameter Details
Selects how the lower frequency limit is set when the Up/Down function is used. Refer to Setting 10, 11: Up, Down
command on page 230 for details on the Up/Down function in combination with frequency reference limits.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 199
5.4 d: Reference Settings
Setting 0: No Conversion
The frequency reference or PID output value is used as it is without being converted. The drive will operate in the
direction selected from 0 to 100% of the maximum output frequency.
Setting 1: Bi-Directional Output Conversion
When the frequency reference or PID output is below 50%, the drive reverses the selected direction. When it is above
50% the drive works in the selected direction.
d4-12: Stop Position Gain
Sets the gain for adjusting the stopping accuracy when simple positioning is selected as the stopping method (b1-03 = 9).
Increase the value if the motor stops before the desired stop position is reached. Decrease it if the motor stops too late.
Also refer to b1-03: Stopping Method Selection on page 146 for details on simple positioning.
Torque Compensation
d5-02
U1-09
External Torque Reference Torque Reference Delay
d5-08 L7-
C1- , C2-
+ Torque Internal Torque
Soft Limits Reference
External Speed Limit +
Starter 1 d5-03
2
Speed Limiter
Speed Limit set in d5-04
Compensated torque
reference
Speed Feedback
200 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
Setting the Torque Reference, Speed Limit, and Torque Compensation Values
Torque Control Reference Sources
Input values for Torque Control can be set like explained in Table 5.19.
Table 5.19 Torque Control Input Value Selection
Input Value Signal Source Settings Remarks
Make sure the signal level settings for the input terminal selected
Analog inputs A1/A2/A3 H3-02, H3-10, or H3-06 = 13 <1> match the signal used. Refer to H3: Multi-Function Analog Inputs
on page 247 for details on adjusting analog input signals.
The H3- settings become effective for the option board input
terminals. Make sure the signal level settings for the input terminal
• F2-01 = 0
Analog Option Card selected match the signal used. Refer to H3: Multi-Function
• H3-02, H3-10, or H3-06 = 13 <1>
Analog Inputs on page 247 for details on adjusting analog input
Torque Reference signals.
• b1-01 = 2
MEMOBUS Register 0004H • Set Register 000FH, Bit 2 = 1 to enable Torque –
reference from register 0004H
• b1-01 = 3
• F6-06 = 1
Communication Option Card –
Refer to the option card manual for details about
setting the torque reference.
d5-03 = 1
Signal selected as frequency The speed limit is taken from the input selected as The settings in C1- for accel/decel times and in C2- for
Speed Limit reference source frequency reference source in parameter b1-01 or S-curves are applied to the speed limit value.
b1-15. <1>
Parameter d5-04 d5-03 = 2 –
Make sure the signal level settings for the input terminal selected
Analog inputs A1/A2/A3 H3-02, H3-10, or H3-06 = 14 <1> match the signal used. Refer to H3: Multi-Function Analog Inputs
on page 247 for details on adjusting analog input signals.
The H3- settings become effective for the option card input
• F2-01 = 0
Analog Option Card terminals. Make sure the signal level settings for the input terminal
• H3-02, H3-10, or H3-06 = 14 <1>
selected match the signal used.
Torque Compensation
• b1-01 = 2
MEMOBUS Register 0005H • Set Register 000FH, bit 3 = 1 to enable the torque –
compensation setting by register 0005H
• b1-01 = 3
Communication Option Card • Refer to the option card manual for details about –
setting the torque compensation value.
<1> Sets analog input terminals A1, A2, and A3 to supply the speed limit, torque reference, or torque compensation. An oPE07 error
(Multi-Function Analog Input Selection Error) will occur if two analog inputs are set for the same function.
Parameter Details
in the reverse direction. However, if a Reverse Run command is input, the torque command will be for forward
rotation.
When analog inputs are used, negative input values can be generated by
• applying negative voltage input signals.
• using positive analog input signals but setting the analog input bias to negative values so that the input value can be 5
negative.
• applying positive voltage input signals and using a digital input that is programmed for H1- = 78.
When MEMOBUS/Modbus communication or a communication option card is used, only positive input values can be
set.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 201
5.4 d: Reference Settings
Winder Unwinder
Speed Torque Speed Torque Torque Speed Torque Speed
<1> The value of delta n in the drawings depends on the ASR setting in parameters C5-.
202 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
Figure 5.52
Operation Mode Speed Control Torque Control Speed Control Torque Control Speed Control
Frequency reference Speed Ref. Speed Limit Speed Ref. Speed Limit Speed Ref.
signal or d5-04
Setting 0: Disabled
Speed Control will be active. Also use this setting when H1- = 71 (Speed/Torque Control Switch).
Setting 1: Enabled
Torque Control is always enabled.
d5-02: Torque Reference Delay Time
A filter with the time constant set in parameter d5-02 can be applied to the torque reference signal in order to eliminate
oscillation that results from an unstable torque reference signal. A higher filter time will stabilize control, but also reduce
the responsiveness.
Parameter Details
No. Parameter Name Setting Range Default
d5-03 Speed Limit Selection 1 or 2 1
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 203
5.4 d: Reference Settings
Setting 0: Disabled
The speed limit bias is applied in both directions, the speed limit and the opposite direction.
Setting 1: Enabled
The speed limit bias is applied in the opposite direction of the speed limit only.
204 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.4 d: Reference Settings
Setting 0: Disabled
Setting 1: Enabled
d6-06: Field Forcing Limit
This parameter rarely requires adjustment. Sets the maximum level to what the Field Forcing function can boost the
excitation current reference. The value is set as a percentage of the motor no load current.
Frequency
Frequency SFS reference after
reference
soft starter
Multi-function
input (44) = on
Offset Frequency 1 [d7-01]
(Signed)
Multi-function
input (45) = on
Parameter Details
Offset Frequency 2 [d7-02]
(Signed)
Multi-function
input (46) = on
Offset Frequency 3 [d7-03]
(Signed)
common_TMonly
Figure 5.53 Offset Frequency Operation 5
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 205
5.5 E: Motor Parameters
206 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
30 30 30 30
18 18 18 18
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
100 100
70 70
18 18
16 16
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
48 48
38 38
26 30
22 22
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
Parameter Details
30 30 30 30
18 18 18 18
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Predefined V/f Patterns for Models CIMR-U20028 to 20192 and CIMR-U40021 to 40124
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
5
Table 5.26 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
Voltage (V)
Voltage (V)
14 14 14 14
7 7 7 7
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 207
5.5 E: Motor Parameters
Voltage (V)
Voltage (V)
Voltage (V)
50 50
14 35
7 7
7 6
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
23 23
18 18
11 13
9 9
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
14 14 14 14
7 7 7 7
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
12 12 12 12
6 6 6 6
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
50 50
35 35
6 6
5 5
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
208 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
20 20
15 15
9 11
7 7
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
12 12 12 12
6 6 6 6
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Parameter Details
E1-09 Minimum Output Frequency 0.0 to [E1-04] <1> <2> <3>
E1-10 Minimum Output Frequency Voltage 0.0 to 255.0 V <4> <2> <4>
E1-11 Middle Output Frequency 2 0.0 to [E1-04] 0.0 Hz <6>
E1-12 Middle Output Frequency Voltage 2 0.0 to 255.0 V <4> 0.0 V <4> <5> <6>
E1-13 Base Voltage 0.0 to 255.0 V <4> 0.0 V <4> <5> <7>
<1> Default setting is determined by E5-01 in OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01 = FFFFH.
<2> Default setting is determined by the control mode. 5
<3> When using PM motors, the default setting is determined by the motor code set to E5-01.
<4> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.
<5> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 2, 3).
<6> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<7> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
Figure 5.54
Frequency (Hz)
Figure 5.54 V/f Pattern
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 209
5.5 E: Motor Parameters
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 E1-07 E1-06 E1-11 E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the parameters are initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned
to their default values.
4. Parameters E1-11, E1-12, and E1-13 should only be used to fine-tune the V/f pattern in the constant output range. These parameters
rarely need to be changed.
If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate
and the formula below:
E2-02 = f (n p)/120
(f: rated frequency (Hz), n: rated motor speed (min-1), p: number of motor poles)
E2-03: Motor No-Load Current
Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 2 and 3). The motor
no-load current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
210 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
Parameter Details
E2-09: Motor Mechanical Loss
There is normally no need to change this parameter from the default value.
This parameter sets to the motor mechanical loss as a percentage of motor rated power (kW) capacity. Adjust this setting
in the following circumstances:
5
• When there is a large amount of torque loss due to motor bearing friction.
• When there is a large amount of torque loss in a fan or pump application.
The setting for the mechanical loss is added to the torque.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 211
5.5 E: Motor Parameters
212 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
Parameter Details
Figure 5.55
Output (V)
E3-05
E3-12
E3-13
E3-08 5
E3-10 common_TMonly
E3-09 E3-07 E3-06 E3-11 E3-04
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 213
5.5 E: Motor Parameters
214 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
Parameter Details
E4-10: Motor 2 Iron Loss
Sets the motor 2 iron loss in watts.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 215
5.5 E: Motor Parameters
Note: 1. E5- parameters are not reset when the drive is initialized using parameter A1-03.
2. When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03.
3. Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.
4. Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.
5. Default settings are:
• OLV/PM, AOLV/PM: Yaskawa SSR1 Series (1750 min-1)
• CLV/PM: Yaskawa SST4 Series (1750 min-1)
6. Selection may vary depending on the motor code entered to E5-01.
7. If an alarm or hunting occurs even though a motor code is used, enter the value indicated on the name plate. For details, refer to
Auto-Tuning for Permanent Magnet Motors on page 117.
216 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.5 E: Motor Parameters
Note: Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or
if neither parameter is set to 0. When E5-01 = FFFF, then E5-09 = 0.0.
Parameter Details
When E5-01 is set to FFFF, use either E5-09 or E5-24 for setting the voltage constant. This parameter is set during
Parameter Auto-Tuning for PM motors.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 217
5.6 F: Option Settings
F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An overspeed error (oS) is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set
in F1-09. The stopping method when an overspeed fault occurs can be selected in parameter F1-03.
Note: In AOLV/PM, the motor will coast to a stop (F1-03 = 1). The setting for F1-03 cannot be changed to 0,2, or 3.
218 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.6 F: Option Settings
F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-1. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
Example: To have a ratio of 1/32 between the PG card pulse input and output, set F1-06 = 032.
Parameter Details
F1-06 PG 1 Division Rate for PG Pulse Monitor CN5-C 001 to 032, 102 to 132 (1 to 1 ) 1
32
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 219
5.6 F: Option Settings
Note: A common cause for a dv3 fault is the incorrect setting of E5-11. Make sure the correct Z pulse offset has been entered to E5-11.
Note: 1. A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure the correct Z pulse offset is set to E5-11.
2. Set F1-19 to 0 for applications where the direction of the load is the opposite of the speed reference.
Setting 0: Disabled
Setting 1: Enabled
F1-21, F1-37: PG 1, PG 2 Signal Selection (V/f w/PG only)
Determines whether the signal to the PG option card is single track or two track.
Setting 0: CN5-C
Setting 1: CN5-B
220 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.6 F: Option Settings
Parameter Details
F2-01: Analog Input Option Card Operation Selection
Determines how the input terminals on the AI-A3 option card are to be used.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 221
5.6 F: Option Settings
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
222 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.6 F: Option Settings
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set
as a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is
limited to 10 V.
Parameter Details
2. Adjust F4-04 viewing the monitor connected to the terminal V2.
3. View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameter
being set in F4-03.
4. Adjust F4-06 viewing the output signal on the terminal V2.
F4-07, F4-08: Terminal V1, V2 Signal Level 5
Sets the output signal level for terminals V1 and V2.
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 223
5.6 F: Option Settings
Note: Refer to TOBP C730600 41 YASKAWA AC Drive-Option Card DO-A3 Installation Manual for more details on F5-09 settings.
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
Communication Protocol
Parameter
CC-Link MECHATROLINK-II MECHATROLINK-III PROFIBUS-DP CANopen DeviceNet LONWORKS Modbus TCP/IP EtherNet/IP
F6-01 to F6-03
F6-04 – – – – – – – –
F6-06 to F6-08
F6-10 to F6-14 – – – – – – – –
F6-20, F6-21 – – – – – – –
F6-22 – – – – – – – –
F6-23 to F6-26 – – – – – – –
F6-30 to F6-32 – – – – – – – –
F6-35 to F6-36 – – – – – – – –
F6-50 to F6-63 – – – – – – – –
F7-01 to F7-15 – – – – – – –
F7-16 – – – – – – – –
F7-17 to F7-42 – – – – – – – –
224 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.6 F: Option Settings
Setting 0: Disabled
Parameter Details
Setting 1: Enabled
F6-07: Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Selects how multi-step speed inputs are treated when the NetRef command is set.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 225
5.6 F: Option Settings
Setting 0: Do not reset parameters F6-/F7- when the drive is initialized with A1-03
Setting 1: Reset F6-/F7- when the drive is initialized with A1-03
Note: F6-08 is not reset when the drive is initialized.
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CC-Link Installation Manual
and Technical Manual.
MECHATROLINK-II Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK-II network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-II
Installation Manual and Technical Manual.
MECHATROLINK-III Parameters
Parameters F6-20, F6-21, F6-23 through F6-26 set up the drive to operate on a MECHATROLINK-III network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-III
Installation Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFIBUS-DP Installation
Manual and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CANopen Installation Manual
and Technical Manual.
DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option DeviceNet Installation Manual
and Technical Manual.
Modbus TCP/IP Parameters
Parameters F7-01 through F7-16, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate on a Modbus TCP/
IP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option Modbus TCP/IP Installation
Manual and Technical Manual.
EtherNet/IP Parameters
Parameters F7-01 through F7-15, F7-17 through F7-42, U6-80 through U6-93,U6-98, and U6-99 set up the drive to
operate on an EtherNet/IP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option EtherNet/IP Installation Manual
and Technical Manual.
226 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Setting
No. Parameter Name Default
Range
H1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to 9F 40 (F) <1>: Forward Run Command (2-wire sequence)
H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to 9F 41 (F) <1>: Reverse Run Command (2-wire sequence)
H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 9F 24: External Fault (N.O., always detected, coast to stop)
H1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to 9F 14: Fault Reset
H1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to 9F 3 (0) <1>: Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to 9F 4 (3) <1>: Multi-Step Speed Reference 2
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to 9F 6 (4) <1>: Jog Reference Selection
H1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to 9F 8: External Baseblock Command
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Parameter Details
230
11 Down command 67 Communications test mode 235
12 Forward jog 6A Drive enabled 235
231
13 Reverse jog 71 Speed/Torque Control switch 235
14 Fault reset 231 72 Zero Servo 235
15 Fast Stop (N.O.) 231 75 Up 2 command
235
16 Motor 2 selection 232 76 Down 2 command
17 Fast Stop (N.C.) 231 77 ASR gain switch 236
5
18 Timer function input 232 78 External torque reference polarity inversion 236
19 PID disable 232 7E Forward/reverse detection (V/f control with simple PG) 236
1A Accel/decel time selection 2 232 7F Bi-directional PID output enable 236
1B Program lockout 233 90 to 97 DriveWorksEZ Digital input 1 to 8 236
1E Reference sample hold 233 9F DriveWorksEZ disabled 236
20 to 2F External fault 233 – – –
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 227
5.7 H: Terminal Functions
Figure 5.56
Stop Switch
(N.C.)
Run Switch
(N.O.)
DRIVE
common_TMonly
S1
Run Command (Runs when Closed)
S2
Stop Command (Stops when Open)
S5
FWD/REV (Multi-Function Input)
(H1-05 = 0)
SC
Sequence Input Common
2 ms min.
Forward/reverse
command OFF (forward) ON (reverse)
Motor speed
common_
TMonly
Stop Forward Reverse Stop Forward
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING! The drive may start unexpectedly in reverse direction after power up if it is wired for 3-wire sequence but set up for 2-wire
sequence (default). Make sure b1-17 is set to “0” (drive does not accept a Run command active at power up). When initializing the
drive use 3-wire initialization. Failure to comply could result in death or serious injury from moving equipment.
Status Description
Closed LOCAL: Frequency reference and Run command are input from the digital operator.
REMOTE: Frequency reference and Run command are input from the external reference that has been selected in accordance with settings of b1-01 and b1-02 or
Open
b1-15 and b1-16.
Note: 1. If one of the multi-function input terminals is set to for LOCAL/REMOTE, then the LO/RE key on the operator will be disabled.
2. When the drive is set to LOCAL, the LO/RE LED will light.
3. The default setting of the drive is not to allow switching between LOCAL and REMOTE during run. To allow the drive to switch
between LOCAL and REMOTE during run, Refer to b1-07: LOCAL/REMOTE Run Selection on page 151.
Setting 2: External reference 1/2 selection
This function can be used to switch the Run command and frequency reference source between External reference 1 and
2 if the drive is in the REMOTE mode.
Status Description
Open External reference 1 is used (defined by parameters b1-01 and b1-02)
Closed External reference 2 is used (defined by parameters b1-15 and b1-16)
Note: With default settings the drive is not to allow switching between External reference 1 and 2 during run. Refer to b1-07: LOCAL/
REMOTE Run Selection on page 151 if this feature is required by the application.
Setting 3 to 5: Multi-Step Speed Reference 1 to 3
Used to switch multi-step speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1: Frequency
Reference on page 192 for details.
228 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Drive Operation
Digital Input Function
Input Open Input Closed
Setting 9 (N.C.) Baseblock (Interrupt output) Normal operation
Setting 8 (N.O.) Normal operation Baseblock (Interrupt output)
NOTICE: If using baseblock in hoist applications, make sure the brake closes when the drive output is cut off by a Baseblock
command triggered via one of the input terminals. Failure to do so will result in the motor suddenly coasting when the Baseblock
command is entered, causing the load to slip.
Figure 5.58
OFF ON
Run command
Baseblock
ON release
Baseblock input
Frequency
reference
Begin Speed Search from the
common_
previous frequency reference TMonly
Output frequency
Output off, motor coasts
Parameter Details
frequency. Acceleration or deceleration will resume once the input is opened again.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive will save the output frequency to memory
whenever the Ramp Hold input is closed. When the drive is restarted after stop or after power supply interruption, the
output frequency that was saved will become the frequency reference (provided that the Accel/decel ramp hold input is
still closed). Refer to d4-01: Frequency Reference Hold Function Selection on page 195 for details.
5
Setting B: Drive overheat alarm (oH2)
Triggers an oH2 alarm when the contact closes. Because this is an alarm, drive operation is not affected.
Setting C: Analog terminal input selection (terminal A1, A2, A3)
When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog
terminals.
Setting D: PG encoder disable
When closed the drive disregards PG feedback from the motor when using V/f Control with PG. When the terminal is
opened again, the drive resumes using PG feedback to control motor speed.
Setting E: ASR integral reset
Switches between PI control or simply P control by resetting the integral value. As long as the terminal is closed, integral
operation is disabled and the drive uses P control. When the terminal opens, PI control resumes.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 229
5.7 H: Terminal Functions
Note: 1. An oPE03 alarm will occur when only one of the functions Up/Down is programmed for a digital input.
2. An oPE03 alarm will occur if the Up/Down function is assigned to the terminals while another input is programmed for the Accel/
decel ramp hold function. For more information on alarms, Refer to oPE Codes, Causes, and Possible Solutions on page 331.
3. The Up/Down function can only be used for parameter b1-01. Consider this when using parameter b1-15 switching command
(H1- = 2).
230 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Figure 5.59
Output frequency
upper limit
Accelerates to
lower limit d4-01 = 1
Same
frequency
d4-01 = 0
Lower limit
FWD run/stop ON
ON
common_
Up command
ON Hold TMonly
Frequency
reset
Down command
ON ON
Power supply
d1-17
Output
Frequency
d1-17
ON
FJOG common_
RJOG
ON TMonly
Figure 5.60 FJOG/RJOG Operation
Setting 14: Fault reset
Whenever the drive detects a fault condition, the fault output contact will close and the drive’s output will shut off. The
motor then coasts to stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat).
Parameter Details
Once the Run command is removed, the fault can be cleared by either the RESET key on the digital operator or by
closing a digital input configured as a Fault Reset (H1- = 14).
Note: Fault Reset commands are ignored as long as the Run command is present. To reset a fault, first remove the Run command.
Setting 15, 17: Fast Stop (N.O., N.C.)
The Fast Stop function operates much like an emergency stop input to the drive. If a Fast Stop command is input while
the drive is running, the drive will decelerate to a stop by the deceleration time set to C1-09 (Refer to C1-09: Fast Stop
5
Time on page 179). The drive can only be restarted after is has come to a complete stop, the Fast Stop input is off, and
the Run command has been switched off.
• To trigger the Fast Stop function with a N.O. switch, set H1- = 15.
• To trigger the Fast Stop function with a N.C. switch, set H1- = 17.
Figure 5.61 shows an operation example of Fast Stop.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 231
5.7 H: Terminal Functions
Figure 5.61
Run/Stop
ON ON
Fast-Stop
H1- = 17 ON ON
Decelerates at C1-09
Output Frequency
common_
TIME TMonly
Figure 5.61 Fast Stop Sequence
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid
this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast Stop time to C1-09.
Drive M Motor 1
common_
M Motor 2
TMonly
Figure 5.62 Motor Selection
When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below,
Table 5.37 lists the parameters that correspond to each motor.
Table 5.37 Parameters for Switching Between Two Motors
No. Setting 16 Open (Motor 1) Setting 16 Closed (Motor 2)
C1-: Acceleration/Deceleration Time C1-01 to C1-04 C1-05 to C1-08
C3-: Slip Compensation C3-01 to C3-04 C3-21 to C3-24
C4-: Torque Compensation C4-01 C4-07
C5-: Speed Control (ASR) C5-01 to C5-08, C5-12, C5-17, C5-18 C5-21 to C5-28, C5-32, C5-37, C5-38
E1-, E3-: V/f Pattern
E1-, E2- E3- to E4-
E2-, E4-: Motor Parameters
F1- (PG Speed Control Card Settings) F1-01 to F1-21 F1-02 to F1-04, F1-08 to F1-11, F1-14, F1-31 to F1-37
Note: 1. When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
2. It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger the “rUn” alarm.
3. There is a 500 ms delay when switching between motors equipped with a PG encoder for feedback.
4. The motor 2 selection function cannot be used when PM motor is used.
If a digital output is programmed for “Motor 2 selection” (H2-01, H2-02, or H2-03 = 1C), the output is closed when
motor 2 is selected.
Setting 18: Timer function input
This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the
timer function output (H2- = 12). Refer to b4: Timer Function on page 163 for details.
Setting 19: PID disable
When the PID function has been enabled by parameter b5-01, it can be indefinitely disabled by closing a digital input.
When the input is released, the drive resumes PID operation. Also refer to PID Block Diagram on page 166.
Setting 1A: Accel/decel time selection 2
Used to select accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command. Refer to C1-01 to
C1-08: Accel, Decel Times 1 to 4 on page 178 for details.
232 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Frequency
reference
l
na
g sig
alo
An
Time
common_
Reference OFF ON TMonly
Sample Hold Input
100 ms 100 ms
Figure 5.63 Analog Frequency Reference Sample/Hold
An oPE03 error will occur when one of the following functions is used simultaneously with the Analog frequency
reference sample/hold command.
• Accel/decel ramp hold (setting: A)
• Up command, Down command (setting: 10, 11)
• Offset frequency (setting: 44 to 46)
• Up or Down 2 command (setting: 75, 76)
Setting 20 to 2F: External fault
By using the External fault command, the drive can be stopped when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to any value between 20 to 2F. The digital
operator will display EF where is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal S3, “EF3” will be displayed.
Select the value to be set in H1- from a combination of any of the following three conditions:
• Signal input level from peripheral devices (N.O., N.C.)
Parameter Details
• External fault detection method
• Operation after external fault detection
Table 5.38 shows the relationship between the conditions and the value set to H1-:
Table 5.38 Stopping Method for External Fault
Terminal Status <1> Detection Conditions <2> Stopping Method
5
Setting Detected during Ramp to Stop Coast to Stop Fast Stop Alarm Only
N.O. N.C. Always Detected Run only (fault) (fault) (fault) (continue running)
20 – – – – –
21 – – – – –
22 – – – – –
23 – – – – –
24 – – – – –
25 – – – – –
26 – – – – –
27 – – – – –
28 – – – – –
29 – – – – –
2A – – – – –
2B – – – – –
2C – – – – –
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 233
5.7 H: Terminal Functions
Drive
Forward Run
S1
Reverse Run
S2
234 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
OFF ON OFF
FWD Run command
DC Injection
DC Injection braking
braking DC Injection Braking
Start Frequency common_
Output frequency
(b2-01) TMonly
Figure 5.65 DC Injection Braking Input Timing Diagram
Setting 61, 62: External Speed Search command 1, 2
These input functions can be used to enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start). Refer
to Speed Search Activation on page 157 for details on how to use the input signals. Refer to b3: Speed Search on
page 155 for more about Speed Search.
Note: Operator error oPE03 will result if both Speed Search 1 and Speed Search 2 are set to the input terminals at the same time.
Setting 63: Field Weakening
Enabled in V/f Control. When closed, Field Weakening is performed. For details, Refer to d6: Field Weakening and
Field Forcing on page 204.
Setting 67: Communication test mode
The drive has a built-in function for self-diagnosing serial communications operation. The test involves wiring the send
and receive terminals of the RS-485/422 port together. The drive transmits data and then confirms that the
communications are received normally. Refer to Self-Diagnostics on page 514 for details on how to use this function.
Setting 6A: Drive enable
A digital input configured as a “Drive enable” (H1- = 6A) will prevent the drive from executing a Run command
until the input is closed. When the input is open, the digital operator will display “dnE” to indicate that the drive is
disabled.
If a Run command is enabled before the terminal set for “Drive enable” closes, then the drive will not run until the Run
Parameter Details
command is cycled (i.e., a new Run command is required). If the input is opened while the drive is running, the drive will
stop according to the stop method set to b1-03 (Refer to b1-03: Stopping Method Selection on page 146).
Setting 71: Speed/Torque Control switch
Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed,
and Speed Control is enabled when the terminal is open. Note that parameter d5-01 must be set to 0 when using this
function. Refer to d5: Torque Control on page 200 and Switching Between Torque and Speed Control on page 202.
5
Setting 72: Zero Servo
Used to activate the Zero Servo function that can be used to lock the rotor at a certain position. Refer to b9: Zero Servo
on page 177 for details.
Setting 75, 76: Up 2, Down 2 command
The Up 2 and Down 2 function can be used to add a bias to the frequency reference. The input programmed for 75 will
increase the bias and the input programmed for 76 will decrease it. Table 5.39 explains how the Up/Down 2 function
works depending on the frequency reference source and parameters d4-01, d4-03, and d4-05. Refer to d4: Frequency
Reference Hold and Up/Down 2 Function on page 195 for detailed explanations of these and other Up/Down 2 related
parameters.
Note: 1. The Up 2 and Down 2 functions must be set as a pair.
2. When using the Up 2 and Down 2, set appropriate bias limit values to parameters d4-08 and d4-09.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 235
5.7 H: Terminal Functions
Status Description
Open DriveWorksEZ enabled
Closed DriveWorksEZ disabled
236 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Parameter Details
1D During regeneration 243 – – –
Status
Open Drive is stopped.
Description
5
Closed A Run command is input or the drive is during deceleration or during DC injection.
Figure 5.66
Baseblock OFF ON
command
Output
frequency
common_
During Run OFF ON TMonly
Figure 5.66 During Run Time Chart
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 237
5.7 H: Terminal Functions
Status Description
Open Output frequency is more than or equal to the minimum output frequency set to E1-09 or b2-01
Closed Output frequency becomes less than the minimum output frequency set to E1-09 or b2-01
Note: When using CLV or CLV/PM control modes, the output terminal will close when the motor speed becomes less than or equal to
the zero speed level set for b2-01. In all other control modes, the output terminal will close when the output frequency becomes
less than or equal to the minimum output frequency set for E1-09.
Figure 5.67
Output frequency
or
E1-09 (Max. Output Frequency) or
motor speed
b2-01 (DC Injection Braking Start Frequency)
common_
OFF
Zero Speed
ON
TMonly
Figure 5.67 Zero-Speed Time Chart
Setting 2: Speed agree 1 (fref/fout Agree 1)
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02)
of the current frequency reference regardless of the direction.
Status Description
Open Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed Output frequency or motor speed is within the range of frequency reference ±L4-02.
Frequency common_TMonly
reference
L4-02
Speed agree 1 OFF ON
Status Description
Open Output frequency or motor speed and frequency reference are not both within the range of L4-01 ± L4-02.
Closed Output frequency or motor speed and the frequency reference are both within the range of L4-01 ± L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
238 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Figure 5.69
–L4-01
Frequency reference + L4-02
–L4-01 – L4-02
Frequency reference
Status Description
Open Output frequency or motor speed exceeded L4-01 + L4-02.
Closed Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.70
Output Frequency
or Motor Speed
L4-02
L4-01
L4-01
L4-02
Frequency
common_
detection 1 <1> ON OFF
TMonly
Parameter Details
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default setting for L4-07 is 0
(no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Figure 5.70 Frequency Detection 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 269 for more details.
Setting 5: Frequency Detection 2
Output closes whenever the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01. 5
The terminal remains closed until the output frequency or motor speed falls below L4-01 minus the setting of L4-02.
Status Description
Open Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 239
5.7 H: Terminal Functions
Figure 5.71
Output Frequency
or Motor Speed L4-02
L4-01
L4-01
L4-02
common_
Frequency
Detection 2
OFF ON TMonly
Figure 5.71 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 269 for more details.
Setting 6: Drive ready
Output closes whenever the drive is ready to operate the motor. The terminal will not close under the conditions listed
below, and any Run commands will be disregarded.
• When the power is shut off
• During a fault
• When the drive’s internal power supply has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: During Power Supply Voltage Fault
Output closes when the power supply voltage or the control circuit voltage falls below the drive operating voltage or
when the power supply frequency is incorrect.
Status Description
Open Normal
Closed One of the following faults will occur: Fdv (Power Supply Frequency Fault), AUv (Power Supply Undervoltage), or Uv (Undervoltage).
Status Description
Open Drive is not in a baseblock state.
Closed Baseblock is being executed.
Status Description
Open Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15)
Closed Frequency reference is being sourced from the digital operator.
Status Description
Open Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed Run command is being sourced from the digital operator.
Setting B, 17, 18, 19: Torque detection 1 (N.O., N.C.), Torque detection 2 (N.O., N.C.)
These digital output functions can be used to signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below. Refer to L6: Torque Detection on
page 271 for details.
240 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Status Description
Parameter Details
Open Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed Output frequency or motor speed is within the range of frequency reference ±L4-04.
Frequency
reference common_
Output Frequency L4-04 TMonly 5
or Motor Speed
L4-04
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 241
5.7 H: Terminal Functions
Status Description
Open Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04
Closed Output frequency or motor speed and the frequency reference are both with in the range of L4-03 ±L4-04
Figure 5.73
Frequency reference
L4-03 + L4-04
Frequency reference – L4-04
L4-03
common_
Output frequency
TMonly
Frequency reference
Figure 5.73 User Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 269 for more details.
Setting 15: Frequency detection 3
Output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level
set in L4-03. As the detection level L4-03 is a signed value, the detection works in the specified direction only.
Status Description
Open Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
Figure 5.74
Output Frequency
or Motor Speed L4-04 common_
L4-03 TMonly
Frequency
detection 3 <1> ON OFF
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default
setting for L4-07 is 0 (no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 269 for more details.
Setting 16: Frequency detection 4
Output closes whenever the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-03.
The terminal remains closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04. As
the detection level L4-03 is a signed value, frequency detection works in the specified direction only.
242 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Status Description
Open Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
Closed Output frequency or motor speed exceeded L4-03.
Figure 5.75
Output Frequency
or Motor Speed L4-04 common_
L4-03 TMonly
Frequency
OFF ON
Detection 4
Figure 5.75 Frequency Detection 4 Example with Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 269 for more details.
Setting 1A: During reverse
A digital output set for “During reverse” will close whenever the drive is running the motor in the reverse direction.
Status Description
Open Motor is being driven in the forward direction or stopped.
Closed Motor is being driven in reverse.
Figure 5.76
Output frequency
During Reverse
OFF ON common_
time TMonly
Figure 5.76 Reverse Direction Output Example Time Chart
Setting 1B: During baseblock (N.C.)
Parameter Details
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status Description
Open Baseblock is being executed.
Closed Drive is not in a baseblock state.
5
Setting 1C: Motor 2 selection
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1- = 16). Refer to Setting 16: Motor 2 selection on page 232 for details on switching motors.
Status Description
Open Motor 1 is selected.
Closed Motor 2 is selected.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 243
5.7 H: Terminal Functions
Status Description
Open The conditions described below are not present.
1. The frequency reference has reached the upper limit set in d2-01.
Closed 2. The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
3. Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency (E1-09).
Status Description
Open The drive is not outputting a frequency (one of the following functions is being performed: stop, baseblock, DC Injection Braking (during initial excitation)).
Closed Drive is outputting frequency.
244 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Figure 5.77
OFF ON
run command
baseblock OFF ON
command
output
frequency
OFF ON
during run
Status Description
Open REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference and Run command source
Closed LOCAL: The digital operator is used as frequency reference and Run command source
Parameter Details
Setting 3F: PID feedback high
Output terminal closes when an excessive PID feedback (FbH) is detected. The feedback is considered to be lost if it rises
beyond the level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 169
for details.
Setting 4C: During Fast Stop
5
Output terminal closes when a Fast Stop is being executed. Setting 15, 17: Fast Stop (N.O., N.C.) on page 231.
Setting 4D: oH pre-alarm time limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after ten frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm
Operation Selection on page 275 for a more detailed description.
Setting 60: Internal cooling fan alarm
Output closes when the drive’s internal cooling fan has failed.
Setting 61: Rotor position detection complete
After the Run command is given, the output terminal signals that the drive has detected the rotor position (PM motors).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 245
5.7 H: Terminal Functions
Setting 62: Memobus Regs1 (It selects it with H2-07 and H2-08.)
The contact output is closed if any of the bits that are specified by H2-08 for the MEMOBUS/Modbus register address
that is set in H2-07 turns on.
Setting 63: Memobus Regs2 (It selects it with H2-09 and H2-10.)
The contact output is closed if any of the bits that are specified by H2-10 for the MEMOBUS/Modbus register address
that is set in H2-09 turns on.
Setting 64: During commercial power operation
Output closes when operating on commercial power when commercial power switching is selected (b1-24 = 1).
Setting 90 to 92: DriveWorksEZ digital output 1 to 3
These settings are for output functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 100 to 192: Functions 0 to 92 with inverse output
These settings have the same function as settings 0 to 92 but with inverse output. Set as 1, where the “1” indicates
inverse output and the last two digits specify the setting number of the function.
Examples: For inverse output of “8: During baseblock”, set 108.
H2-06: Power Consumption Output Unit Selection
Sets the units for the output signal when one of the multi-function terminals is set to power consumption pulse output
(H2-01, H2-02, or H2-03 = 39).
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the
frequency that pulses are issued to keep track of the kWh for the drive.
Note: 1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
Figure 5.78
H2-06
(Watt Hour Output Unit Selection)
Integral Power
H2-01 to H2-03
㧔Multi-function Output) ON
OFF OFF
0.2 s common_TMonly
Figure 5.78 Watt Hour Output Example
The MEMOBUS/Modbus register addresses for sending data to multi-function digital outputs 62 and 63 are specified in
H2-07 and H2-09, and the bits for the MEMOBUS/Modbus registers are specified in H2-08 and H2-10.
246 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and
bias settings will be simply read as 0%.
Setting 1: -10 to 10 Vdc
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
H3-02: Terminal A1 Function Selection
Determines the function assigned to analog input terminal A1. Refer to Multi-Function Analog Input Terminal Settings
on page 250 for instructions on how to adjust the signal level.
Setting Examples
• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
Parameter Details
An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency
reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will
be equal to E1-04 above 5 Vdc.
Figure 5.79
H3-01 = 0 H3-01 = 1
common_
TMonly
Gain = 200 % Gain = 200 %
5
Frequency 100%
reference E1-04
-10 V -5 V
100 % 0V 5V 10 V
E1-04
-100%
E1-04
Figure 5.79 Frequency Reference Setting by Analog Input with Increased Gain
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 247
5.7 H: Terminal Functions
• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
Figure 5.80
H3-01 = 0 H3-01 = 1
common_
100 %
100% TMonly
Frequency H3-01 = 0
reference -10 V -6.0 V
2.0 V 10 V
-25% Analog Input
Voltage
0
2.0 V 10 V
Analog Input -100%
-25% Voltage E1-04
H3-01 = 1 -150%
Figure 5.80 Frequency Reference Setting by Analog Input with Negative Bias
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 0: 0 to 10 Vdc on page 247.
Setting 1: -10 V to 10 Vdc
The input level is -10 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 1: -10 to 10 Vdc on page 247.
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3. Refer to Multi-Function Analog Input Terminal Settings
on page 250 for a list of functions and descriptions.
When analog input A3 is used as PTC input set H3-06 = E and make sure switch S4 on the terminal board is set for PTC
input. Also refer to Terminal A3 Analog/PTC Input Selection on page 83.
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. Refer to Setting 0: 0 to 10 Vdc on page 247
248 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Parameter Details
When one of the multi-function digital input parameters is set for “Analog terminal input selection” (H1- = C), the
value set to H3-14 determines which of the analog input terminals will be enabled or disabled when the input is closed.
All analog input terminals will be enabled all of the time if H1- is not set to C. The terminals other than the one set as
the target are not influenced by input signals.
No.
H3-14
Name
Analog Input Terminal Enable Selection
Setting Range
1 to 7
Default
7
5
Setting 1: A1 only enabled
Setting 2: A2 only enabled
Setting 3: A1 and A2 only enabled
Setting 4: A3 only enabled
Setting 5: A1 and A3 only enabled
Setting 6: A2 and A3 only enabled
Setting 7: All analog input terminals enabled
H3-16 to H3-18 Terminal A1/A2/A3 Offset
Parameters H3-16 to H3-18 set the offset level of the selected input value to terminal A1, A2 or A3 that is equal to 0 Vdc
input. These parameters rarely need adjustment.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 249
5.7 H: Terminal Functions
250 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Figure 5.81
100%
Acceleration/deceleration gain from 1 to 10 V
(10 V)
= × 10 (%)
50% Input Voltage (V)
20%
10%
0 1V 2V 5V 10 V
common_TMonly
Figure 5.81 Accel/Decel Time Gain with Analog Input Terminal
Setting 6: DC Injection Braking current
The current level used for DC Injection Braking. Set as a percentage of the maximum output current using.
Figure 5.82
100%
Drive Rated
Current
common_TMonly
0 10 V
(4) (20 mA)
Figure 5.82 DC Injection Braking Current Using an Analog Input Terminal
Setting 7: Overtorque/Undertorque Detection level
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog
input. The analog input will replace the level set to L6-02. An analog input of 100% (10 V or 20 mA) will set a torque
detection level equal to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection
level settings are required. Refer to L6: Torque Detection on page 271 for details on torque detection.
Setting 8: Stall Prevention level
This setting allows an analog input signal to adjust the Stall Prevention level. Figure 5.83 shows the setting
characteristics. The drive will use either the Stall Prevention level set to L3-06 or the level coming from the analog input
terminal that has been selected, whichever value is lower.
Figure 5.83
30%
Parameter Details
Analog Input Level
0 30% 100%
Figure 5.83 Stall Prevention During Run Using an Analog Input Terminal
Setting 9: Output frequency lower limit level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID feedback 5
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input Methods on page 165.
Setting C: PID setpoint
An input set for this function supplies the PID setpoint value, and the frequency reference selected in parameter b1-01 is
no longer the PID setpoint. PID operation to be enabled in b5-01 to use this setting. Refer to PID Setpoint Input
Methods on page 165.
Setting D: Frequency bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used
with any frequency reference source.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 251
5.7 H: Terminal Functions
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as FM
and AM output levels can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).
H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias
H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias
Parameter H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at
100%. Parameter H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected
monitor is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or
4 mA. The output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc, -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08. Figure 5.84 illustrates how gain and bias settings work.
252 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
H4-07, 08 = 0 H4-07, 08 = 1
15V
Gain = 150%
Output Voltage
Bias = 0%
10V
Gain = 100%
10 V Bias = 0%
Gain 150% 5V
Bias 0% Gain = 50%
Output Voltage Bias = 0%
-100%
Gain 100%
5V Bias 0% 100%
Monitor Value
-5 V
Gain 50%
Bias 0%
0V -10 V common_
0% Monitor Value 100%
TMonly
-15 V
Figure 5.84 Analog Output Gain and Bias Setting Example 1 and 2
Example 3: To have an output signal of 3 V at terminal FM when the monitored value is at 0%, set H4-03 to 30%.
Figure 5.85
Gain = 100%
H4-07, 08 = 0 H4-07, 08 = 1
Bias = 30%
10V
Gain = 100%
10 V Output Voltage Bias = 0%
Bias 30% 3V
Output Voltage Gain 100% -100%
100%
Bias 0% Monitor Value
3V -4 V
Gain 100%
Parameter Details
0V -10 V
0% Monitor Value 100%
YEG_TMonly
Figure 5.85 Analog Output Gain and Bias Setting Example 3
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters 5
H4-07 and H4-08.
When changing the setting of these parameters make sure jumper S5 on the terminal board is set accordingly. Refer to
Terminal AM/FM Signal Selection on page 83 for details on setting S5.
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 253
5.7 H: Terminal Functions
254 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.7 H: Terminal Functions
Figure 5.86
Output Frequency
after Soft Starter
common_TMonly
Motor speed
Figure 5.86 Speed Control with ASR in V/f with Simple Speed Feedback
Enabling V/f Control with Simple Speed Feedback:
1. Set the drive to V/f Control (A1-02 = 0).
2. Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency
that is equal to the maximum speed to H6-02 (pulse train input scaling). Make sure the pulse input bias (H6-04)
is 0% and the gain (H6-03) is 100%.
3. Decide the signal used for detecting the direction. If a digital input is used, set H1- = 7E.
4. Use the ASR gain and integral time parameters described in C5: Automatic Speed Regulator (ASR) on
page 184 for adjusting the responsiveness.
Note: 1. C5 parameters will appear when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for simple PG feedback in
V/f Control (H6-01 = 3).
2. If running two motors from the same drive, note that the V/f Control with simple PG feedback can be used for motor 1 only.
Parameter Details
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 255
5.7 H: Terminal Functions
256 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Note: 1. When the motor protection function is enabled (L1-010), an oL1 alarm can be output through one of the multi-function outputs by
setting H2-01 to 1F. The output will close when the motor overload level reaches 90% of the oL1 detection level.
2. Select a method to protect the motor from overheat by setting L1-01 between 1 and 6 when running a single motor from the drive. An
external thermal relay is not needed.
Setting 0: Disabled (motor overload protection is not provided)
This setting should be used if no motor overheat protection is desired or if multiple motors are connected to a single
drive. In this case it is recommended that you install a thermal relay for each motor as shown in Figure 5.87.
Figure 5.87
Drive
Power M1
supply MC1 L10
M2
MC2 L20
NOTICE: Thermal protection cannot be provided when running multi-motors simultaneously with the same drive, or when using
motors with a current rating that is relatively high when compared with other standard motors (such as a submersible motor). Failure to
comply could result in motor damage. Disable the electronic overload protection of the drive (L1-01 = “0: Disabled”) and protect each
motor with individual motor thermal overloads.
NOTICE: Close MC1 and MC2 before operating the drive. (MC1 and MC2 cannot be switched off during run.)
Parameter Details
Setting 1: General-purpose motor (standard self-cooled)
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from
overheat throughout the entire speed range.
5
Overload Tolerance Cooling Ability Overload Characteristics
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 257
5.8 L: Protection Functions
Setting 2: Drive dedicated motor (speed range for constant torque: 1:10)
Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will
allow the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger
an overload fault.
150
Rated Speed=100% Speed
60 s
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
Torque (%)
Motor is designed to effectively cool itself even at Continuous operation with 100% load from 5 Hz to
low speeds. 50 Hz.
55
50
Continuous A
B
C
150
Rated Speed=100% Speed
60 s A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
100 C: Max. speed for 132MJ and below
Torque (%)
90
Motor is designed to effectively cool itself at Continuous operation with 100% load from 0.5 Hz to
ultra-low speeds. 50 Hz.
50 Continuous
A
B
C
0 1 100120 167 200
Speed (%)
150
120 60 s
Torque (%)
0.0 10 33 100
Motor Speed (%)
258 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
125
Torque (%)
115
Continuous
100
83
77 Motor is designed to effectively cool itself at Continuous operation with 100% load from 0.2% to
67
ultra-low speeds (about 0.2% of base speed). 100% of base speed.
100
90 Motor designed to operate from line power. Continuous operation at less than line power
Motor cooling is most effective when running at frequency with 100% load can trigger motor
rated base frequency (check the motor nameplate or overload (oL1). A fault is output and the motor will
specifications). coast to stop.
50 Continuous
A
B
C
05 33 100 120 167 200
Speed (%)
Parameter Details
continuous operation at 100% is clear, set that time as the value.
Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start; after continuous 5
operation at 100%.
• Figure 5.88 shows an example of the electrothermal protection operation time using a general-purpose motor
operating at 50 Hz with L1-02 set to one minute.
Motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Characteristics of motor protection operation time in response to an overload situation that was suddenly
reached when starting a stationary motor.
• Hot start: Characteristics of motor protection operation time in response to an overload situation that occurred while
the motor was operating continuously at or below its rated current.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 259
5.8 L: Protection Functions
Figure 5.88
10
7
3
Cold start (Characteristics when an overload occurs
at a complete stop)
1
0.4
Hot start (Characteristics when an overload occurs
during continuous operation at 100%)
0.1
Motor current (%)
0 100 150 200 E2-01 = 100% motor current
Figure 5.88 Protection Operation Time for General Purpose Motors at the Rated Output Frequency
DIP Switch S4
MC
YEG PTC
M1
M2
AI
M3 Multi-function
M4 digital outputs
A3 (0-10 V)
M5
PTC
M6
thermistor
AC
260 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Figure 5.90
common_TMonly
Tr’
Parameter Details
Setting 0: Ramp to stop
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
5
The drive stops the motor using the Fast Stop time set in parameter C1-09.
L1-05: Motor Temperature Input Filter Time (PTC input)
Used to set a filter on the PTC input signal in order to prevent a motor overheat fault from being mistakenly detected.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 261
5.8 L: Protection Functions
Setting 0: Disabled
Setting 1: Enabled
262 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Parameter Details
Sets the gain used to detect a power supply frequency fault (Fdv).
If an Fdv fault occurs with no momentary power loss, reduce the setting value in 0.1 increments.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 263
5.8 L: Protection Functions
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to
speed fast enough, thus tripping an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration. Operation varies, depending on the control mode.
• V/f Control, V/f Control with PG, and Open Loop Vector Control:
If the output current rises above the Stall Prevention level set in L3-02, then the drive stops accelerating. Acceleration
will not resume until the output current falls 15% below the setting in L3-02.
The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention
Limit during Acceleration/Deceleration on page 265.
Figure 5.91
Output current
common_TMonly
Stall Prevention Level
During Acceleration
L3-02
L3-02
-15%
Time
Output frequency
264 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
common_TMonly
Output current
L3-02 15 % of L3-02
Time
Output frequency
L3-27
L3-27
Time
Deceleration
using L3-22
Figure 5.92 Stall Prevention During Acceleration for Permanent Magnet Motors
Setting 3: Enabled (Current Limit)
The acceleration rate is automatically adjusted while limiting the output current at the setting value of the stall prevention
level during acceleration (L3-02).
The acceleration rate is automatically adjusted during acceleration of the load (the output current) increases and the
current limit is exceeded.
Figure 5.93
L3-02
Output current
Frequency reference
common_TMonly
Output frequency
Parameter Details
L3-02/L3-14: Stall Prevention Level during Acceleration/Deceleration
There is normally no need to change these parameters from their default values.
Set the output voltage level at which to enable stall prevention during acceleration as a percentage of drive rated current.
These parameters are valid when stall prevention during deceleration is selected (L3-04 = 1). Decrease the setting values
if stalling occurs when parameters are set to default. 5
<1> The upper limit and the default setting depend on C6-01, Drive Duty Selection, and L8-38, Carrier Frequency Reduction Selection.
• Stalling may occur when the motor is rated at a smaller current than the drive rated output current and the stall
prevention default settings are used. Set L3-02/L3-14 appropriately if stalling occurs.
• Also set parameter L3-03 when operating the motor in the constant power range.
L3-03: Stall Prevention Limit during Acceleration/Deceleration
The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets
the lower limit for this reduction as a percentage of the drive rated current.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 265
5.8 L: Protection Functions
L3-02
L3-14
L3-03
Output frequency
E1-06
Base frequency
common_TMonly
Figure 5.94 Stall Prevention Level and Limit During Acceleration
Setting 0: Disabled
The drive decelerates according to the set deceleration time.
High inertia loads or rapid deceleration may trigger an overcurrent (oC) fault. Switch to another L3-04 selection if an oC
fault occurs.
Setting 1: General-purpose Stall Prevention
With this setting the drive tries to decelerate within the set deceleration time. When the output current exceeds the Stall
Prevention level, the drive pauses deceleration. Deceleration continues as soon as the output current drops below that
level. Stall Prevention may be triggered repeatedly to avoid an overcurrent (oC) fault.
Figure 5.95 illustrates the function of Stall Prevention during deceleration.
Figure 5.95
Output Frequency
common_TMonly
Deceleration characteristics
when Stall Prevention was
triggered during deceleration
Time
266 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Figure 5.96
L3-14
15% of rated current
Frequency reference
common_
TMonly
Parameter Details
The Stall Prevention level can be adjusted using an analog input. Refer to Multi-Function Analog Input Terminal
Settings on page 250 for details.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 267
5.8 L: Protection Functions
Setting 0: Disabled
The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled
The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.
L3-27: Stall Prevention Detection Time
Sets a delay time from when the Stall Prevention level is reached and the actual Stall Prevention function is activated.
0: Disabled
1: Enabled
268 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 237, Settings 2, 3, 4, and
5.
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)
Parameter L4-03 sets the detection level for the digital output functions “Speed agree 2,” “User-set speed agree 2,”
“Frequency detection 3,” and “Frequency detection 4.”
Parameter L4-04 sets the hysteresis level for these functions.
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (-100.0 to 100.0%) instead of in Hz.
Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 237, Settings 13, 14, 15,
and 16.
L4-05: Frequency Reference Loss Detection Selection
The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is
detected when the frequency reference drops below 10% of the reference before or below 5% of the maximum output
frequency within 400 ms.
Parameter Details
Figure 5.97
Analog 100%
frequency
reference 10%
400 ms
Loss of
Reference
output
OFF ON
time
common_TMonly 5
Figure 5.97 Loss of Reference Function
To have a digital output trigger when frequency reference loss occurs, set H2-01, H2-02, or H2-03 to C. Refer to Setting
C: Frequency reference loss on page 241 for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
Setting 0: Stop
Drive follows the frequency reference (which is no longer present) and simply stops the motor.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 269
5.8 L: Protection Functions
The drive can attempt to restart itself following the faults listed below.
<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
270 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Parameter Details
H2-01, H2-02, H2-03
Description
Setting
B Torque detection 1, N.O. (output closes when overload or underload is detected)
17 Torque detection 1, N.C. (output opens when overload or underload is detected
18 Torque detection 2, N.O. (output close when overload or underload is detected)
19 Torque detection 2, N.C. (output opens when overload or underload is detected)
Figure 5.98 and Figure 5.99 show the function of overtorque and undertorque detection. 5
Figure 5.98
L6-02/05
L6-03/06 L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO) ON ON
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 271
5.8 L: Protection Functions
Figure 5.99
L6-02/05
L6-03/06 L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO) ON ON
Setting 0: Disabled
Setting 1: oL3, oL4 at speed agree (Alarm)
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detection and an oL3/oL4 alarm is triggered.
Setting 2: oL3, oL4 at run (Alarm)
Overtorque detection works as long as the Run command is active. The operation continues after detection and an oL3 or
oL4 alarm is triggered.
Setting 3: oL3, oL4 at speed agree (Fault)
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation is stopped and an oL3 or oL4 fault is triggered.
Setting 4: oL3, oL4 at run (Fault)
Overtorque detection works as long as a Run command is active. Operation stops and an oL3 or oL4 fault is triggered.
Setting 5: UL3, UL4 at speed agree (Alarm)
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detection and a UL3 or UL4 alarm is triggered.
Setting 6: UL3, UL4 at Run (Alarm)
Undertorque detection works as long as the Run command is active. The operation continues after detection and a UL3 or
UL4 alarm is triggered.
Setting 7: UL3, UL4 at Speed Agree (Fault)
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation is stopped and a UL3 or UL4 fault is triggered.
Setting 8: UL3, UL4 at run (Fault)
Undertorque detection works as long as a Run command is active. Operation stops and a UL3 or UL4 fault is triggered.
L6-02, L6-05: Torque Detection Level 1, 2
These parameters set the detection levels for the torque detection functions 1 and 2. In V/f and OLV/PM control modes
these levels are set as a percentage of the drive rated output current, while in vector control modes these levels are set as
a percentage of the motor rated torque. When Mechanical Weakening detection is enabled (L6-08 0), the level for
L6-02 is set as a percentage of the drive’ rated output current in all control modes.
272 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Note: The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3- = 7. Here, the analog value
has priority and the setting in L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input.
Setting 0: Disabled
Setting 1: Continue running if the speed is greater than L6-09 (signed) (Alarm)
Detection when the speed is above L6-09 (signed). Upon detection operation continues, but an oL5 alarm is output.
Setting 2: Continue running if the speed is greater than L6-09 (Alarm)
Detection when the speed is above L6-09 (unsigned). Upon detection operation continues, but an oL5 alarm is output.
Setting 3: Stop when motor speed is greater than L6-09 (signed) (Fault)
Detection when the speed is above L6-09 (signed). Upon detection operation is stopped and an oL5 fault is output.
Parameter Details
Setting 4: Stop when Motor Speed is Greater than L6-09 (Fault)
Detection when the speed is above L6-09 (unsigned). Upon detection operation is stopped and an oL5 fault is output.
Setting 5: Continue running if the speed is less than L6-09 (signed) (Alarm)
Detection when the speed is below L6-09 (signed). Upon detection operation continues, but a UL5 alarm is output. 5
Setting 6: Continue running if the speed is less than L6-09 (Alarm)
Detection when the speed is below L6-09 (unsigned). Upon detection operation continues, but a UL5 alarm is output.
Setting 7: Stop when Motor Speed is less than L6-09 (signed) (Fault)
Detection when the speed is below L6-09 (signed). Upon detection operation is stopped and a UL5 fault is output.
Setting 8: Stop when motor speed is less than L6-09 (Fault)
Detection when the speed is below L6-09 (unsigned). Upon detection the operation is stopped and a UL5 fault is output.
L6-09: Mechanical Weakening Detection Speed Level
Sets the speed level for Mechanical Weakening Detection.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 273
5.8 L: Protection Functions
The value is set as a percentage of the maximum frequency. If L6-08 is set for unsigned speed detection (L6-08 = 2, 4, 6,
8) then the absolute value of L6-09 is used (negative settings are treated as positive values).
L6-10: Mechanical Weakening Detection Time
Sets the time permitted for the situation selected in parameter L6-08 to arise before mechanical weakening is detected.
Example: If parameter L7-01 = 130%, L7-02 to L7-04 = 200%, and a general torque limit of 150% is set by an analog
input (H3-02, H3-06, H3-10 = 15), then the torque limit in quadrant 1 will be 130%, but 150% in all other quadrants.
Figure 5.100
274 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Note: If the multi-function analog input is programmed for “10: Forward torque limit”, “11: Reverse torque limit”, “12: Regenerative
torque limit”, or “15: General torque limit”, the drive uses the lower value in L7-01 through L7-04, or analog input torque limit.
Setting 0: Disabled
Toque limit is created at start without a delay time. Disable L7-16 to maximize response time when the application
requires sudden acceleration or deceleration at start.
Parameter Details
Setting 1: Enabled
A time filter is added to allow the torque limit to build at start.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 275
5.8 L: Protection Functions
fref
oH
Alarm
fref × (L8-19) Reset oH
Alarm Reset oH
oH Alarm
Alarm
fref × (L8-19)2
oH etc. oH
Alarm Alarm
fref × (L8-19)3
fref × (L8-19)4
time
oH alarm number
276 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Setting 0: Disabled
Setting 1: Fault when one phase is lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to
stop.
Setting 2: Fault when two phases are lost
An output phase loss fault (LF) is triggered when two and more output phases are lost. The output shuts off and the motor
coasts to stop.
L8-09: Output Ground Fault Detection Selection
Enables or disables the output ground fault detection.
Setting 0: Disabled
Ground faults are not detected.
Setting 1: Enabled
A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
L8-10: Heatsink Cooling Fan Operation Selection
Selects the heatsink cooling fan operation.
Parameter Details
No. Name Setting Range Default
L8-11 Heatsink Cooling Fan Off-Delay Time 0 to 300 s 60 s
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 277
5.8 L: Protection Functions
Setting 0: Disabled
Motor protection with LF2 is disabled.
278 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.8 L: Protection Functions
Setting 2: Enabled
An LF2 fault is triggered when an output current imbalance is detected. Drive output shuts off and the motor coasts to
stop.
L8-32 Cooling Fan Failure Selection
Determines drive operation when a FAn fault occurs.
Parameter Details
Lets the drive reduce the carrier frequency when the output current exceeds a certain level. This temporarily increases the
overload capability (oL2 detection), allowing the drive to run through transient load peaks without tripping.
L8-38 selects the operation of the carrier frequency reduction function.
Note: This function cannot be used in Advanced Open Loop Vector for PM motors.
Setting 0: Disabled
No carrier frequency reduction at high current.
Setting 1: Enabled for output frequencies below 6 Hz
The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The
drive returns to its normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for entire frequency range
The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 279
5.8 L: Protection Functions
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back
to the set value.
L8-40: Carrier Frequency Reduction Off-Delay Time
The following settings are used when the carrier frequency is to be reduced at start:
• Time taken for the reduced carrier frequency to return to the carrier frequency set at C6-02.
• Time taken to return to the set carrier frequency after reducing it by setting L8-38 to 1 or 2.
The carrier frequency reduction function at start is disabled if this value is 0.00 s.
Setting 0: Disabled
No alarm is detected.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an minor
fault (H2- = 10) will close.
L8-93: LSo Detection Time at Low Speed
Sets the amount of time until baseblock is executed once LSo has been detected at low speed. A setting of 0.0 s
essentially disables this parameters.
Setting 0: Rated Current Reduces the carrier frequency based on the drive rated current.
Setting 1: Derated Current Reduces the carrier frequency based on the drive current after derating due to
temperature or carrier frequency setting (C6-02).
280 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.9 n: Special Adjustments
Setting 0: Disabled
Setting 1: Enabled
n1-02: Hunting Prevention Gain Setting
Sets the gain for the Hunting Prevention Function.
Normally, n1-02 does not need to be changed, but adjustment may help under the following conditions:
• If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
• If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.
n1-03: Hunting Prevention Time Constant
Determines how responsive the Hunting Prevention function is (affects the primary delay time for Hunting Prevention).
Normally, n1-03 does not need to be changed, but adjustment may help under the following conditions:
Parameter Details
• Increase this value for applications with a large load inertia. A higher setting leads to slower response, though, which
can result in oscillation at lower frequencies.
• Lower this setting if oscillation occurs at low speed.
n1-05: Hunting Prevention Gain while in Reverse
5
This parameter is the same as n1-02, except that it is used when rotating in reverse. Refer to n1-02: Hunting Prevention
Gain Setting on page 281.
Note: When set to 0 ms, n1-02 is enabled even when the drive is operating in reverse.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 281
5.9 n: Special Adjustments
Normally there is no need to adjust n2-01 from the default setting. Make adjustments in the following cases:
• If hunting occurs, increase the setting value in steps of 0.05 while checking the response.
• If response is low, decrease the setting value in steps of 0.05 while checking the response.
n2-02: Speed Feedback Detection Control (AFR) Time Constant 1
Parameter n2-02 sets the time constant normally used by AFR.
These parameters rarely need to be changed. Adjust settings only under the following conditions:
• If hunting occurs, increase n2-02. If response is low, decrease it.
• If setting n2-02 to a higher value, also increase C4-02 (Torque Compensation Primary Delay Time) proportionally.
The optimum setting for n3-13 depends on the motor flux saturation characteristics.
• Increase the gain gradually by 1.25 to 1.90 to improve the braking power of Overexcitation Deceleration.
• If flux saturation characteristics cause overcurrent, try lowering n3-13. A high setting sometimes causes overcurrent
(oC), motor overload (oL1), or overload (oL2).
282 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.9 n: Special Adjustments
750 750
0 0
0 0.5 1 0 0.5 1
Time (s) Time (s)
common_TMonly
Conventional Speed Control Feed Forward Control
Figure 5.102 Overshoot Suppression by Feed Forward Control
Figure 5.103
Parameter Details
Enables or disables the Feed Forward function.
Setting 0: Disabled 5
Setting 1: Enabled
n5-02: Motor Acceleration Time
Sets the time required to accelerate the motor from a full stop up to the rated speed at the rated torque.
This value can be set automatically by Inertia Tuning. If Inertia Tuning cannot be performed, use one of the methods
below to determine the setting value for this parameter.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 283
5.9 n: Special Adjustments
Calculation
The motor acceleration time can be calculated by,
Where:
2π JMotor nrated • JMotor is the motor inertia in kgm/s2.
n5-02 =
60 Trated • nrated is the rated speed of the motor in min-1
• Trated is the rated torque of the motor in Nm.
or
Where:
4 π JMotor frated • JMotor is the motor inertia in kgm2.
n5-02 = • frated is the rated frequency of the motor in Hz.
p Trated
• p is the number of motor poles (not pole pairs!).
• Trated is the rated torque of the motor in Nm.
This value can be set automatically by Inertia Tuning. If Inertia Tuning cannot be performed, determine the value for
parameter n5-03 using the following steps.
1. Select the control mode; CLV (A1-02 = 3), AOLV/PM (A1-02 = 6), or CLV/PM (A1-02 = 7).
2. Setup parameter n5-02 correctly.
3. Couple motor and load.
4. Set the acceleration time C1-01 to 0.
5. Set the torque limits in the L7- parameters to a value that will easily be reached during the test (TLim_Test).
6. Set the frequency reference equal to a value in the upper speed range of the machine (fref_Test).
7. While monitoring the motor speed in U1-05, start the motor in the forward direction and measure the time it takes
to reach the reference speed (taccel).
8. Reverse the parameter settings above and calculate the set value for parameter n5-03 using the formula below.
Where:
• taccel is the measured acceleration time in s.
taccel TLim_Test frated
n5-03 = -1 • frated is the rated frequency of the motor in Hz.
n5-02 fref_Test 100 • TLim_Test is torque limit setting during the test (%).
• fref_Test is the frequency reference during the test in Hz.
284 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.9 n: Special Adjustments
Setting 0: Disabled
Setting 1: Line-to-line resistance tuning
This setting enables line-to-line resistance online tuning. This procedure is effective for speed values up to 6 Hz and
improves the overload capacity in the low speed range by adjusting the value set for the motor resistance.
Setting 2: Voltage correction
The drive adjusts the output voltage during run to improve overload tolerance and minimize the effects of high
temperatures on speed accuracy.
Note: This setting can only be selected if the Energy Saving function is disabled (b8-01 = 0).
Parameter Details
Note: This parameter is available in AOLV/PM or CLV/PM.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 285
5.9 n: Special Adjustments
Setting 0: Pull in
Starts the rotor using pull-in current.
Setting 1: High Frequency Injection
High frequency is injected in order to detect the rotor position. Some noise may be generated from the motor at start.
Setting 2: Pulse injection
A pulse signal is injected into the motor in order to detect the rotor position.
n8-36: High Frequency Injection Level
There is normally no need to change this parameter from the default value.
Sets the frequency level used for High Frequency Injection. Enabled when n8-57 = 1.
n8-39: Low Pass Filter Cutoff Frequency for High Frequency Injection
There is normally no need to change this parameter from the default value.
Sets a cutoff frequency of a low pass filter for high frequency injection. Enabled when n8-57 = 1.
286 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.9 n: Special Adjustments
Parameter Details
Although this setting seldom needs to be changed, please note the following:
• If motor operation is unstable when driving heavy loads, try lowering this setting.
• If motor parameters (E5-) have been changed, this value will be reset to 0 and will need to be readjusted.
Note: This parameter is available in OLV/PM.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 287
5.9 n: Special Adjustments
Setting 0: Disabled
Disable n8-57 with SPM motors. The speed control range will be limited to approximately 1:20.
Setting 1: Enabled
Enabling n8-57 with IPM motors allows precise speed detection in a speed control range of approximately 1:100.
Note: 1. Be aware that using this function will generate some audible noise in the motor up to a certain speed.
2. Set E1-09 to 0.0 when using zero speed control.
288 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.9 n: Special Adjustments
Parameter Details
If operating in Advanced OLV/PM (A1-02 = 6) or CLV/PM (A1-02 = 7), the drive determines motor polarity by
performing initial polarity estimation when it starts the motor (this is done only the first time the motor is started when
using CLV/PM). The drive may begin operating in the wrong direction if it determines motor polarity incorrectly as the
opposite direction of the Run command.
Monitor U6-57 displays the deviation from the integrated current, making it possible to see if initial polarity estimation 5
has successfully determined the motor polarity.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 289
5.10 o: Operator Related Settings
290 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.10 o: Operator Related Settings
Setting 0: Hertz
Setting 1: min-1
Note: For motor 2, o1-04 can only be set to 0 for Hertz.
Parameter Details
o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between
LOCAL and REMOTE. 5
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 5.42 lists the setting combinations for o2-01 and b1-07.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 291
5.10 o: Operator Related Settings
Setting 0: Disabled
Setting 1: Enabled
The STOP key can be used to terminate drive operation, even if the Run command source is not assigned to the digital
operator. If the drive is stopped by pressing the STOP key, the Run command must be cycled to restart the drive.
o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as user-set default values using parameter
o2-03. Once this has been done, the “Initialize Parameters” parameter (A1-03) will offer the choice of “1110: User
Initialize”. Choosing A1-03 = “1110: User Initialize” will reset all parameters to the values saved as user-set defaults.
Refer to A1-03: Initialize Parameters on page 139 for details on drive initialization.
292 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.10 o: Operator Related Settings
Setting 0: Forward
Parameter Details
Setting 1: Reverse
o2-19: Selection of Parameter Write During UV
Determines whether parameter settings can be changed during a DC bus undervoltage condition. To be used with 24V
POWER SUPPLY (PS-A10L, PS-A10H).
Note: When this parameter is set to 1, it is possible for a CPF06 Fault to occur. This function should only be used with 24V POWER 5
SUPPLY (PS-A10L, PS-A10H) REVISION B or later. Parameter changes might not occur correctly when using an older
revision.
Setting 0: Disabled
Setting 1: Enabled
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 293
5.10 o: Operator Related Settings
Setting 0: Disabled
Setting 1: Enabled
294 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.10 o: Operator Related Settings
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2- and U3- monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data
Parameter Details
and returns the display to 0.
o4-12: kWh Monitor Initialization
Resets the electric power (U9-01 to U9-03) and regenerative power (U9-04 to U9-06). Resets electric power rate (U9-07
to U9-10) and regenerative power rate (U9-11 to U9-14).
5
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0 or 1 0
Setting 0: No Action
Setting 1: Reset kWh Data
Once o4-12 is set to 1 and the ENTER key is pressed, kWh data is erased and the display returns to 0.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 295
5.10 o: Operator Related Settings
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.
o4-19: Power Unit Price
Sets the energy price per 1 kWh. This parameter is used to calculate the power rate displayed for total consumed power
(U9-07 to U9-10) and total regenerated power (U9-11 to U9-14).
q: DriveWorksEZ Parameters
q1-01 to q6-07 are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to Auto-Tuning on page 116 for details on Auto-Tuning parameters.
296 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
5.11 U: Monitor Parameters
Parameter Details
• kWh data
• Highest peak current that has occurred and output frequency at the time the peak current occurred
• Motor overload status information
• Detailed information about the present Run command and frequency reference source selection
Refer to U4: Maintenance Monitors on page 460 for a complete list of U4- monitors and descriptions. 5
U5: PID Monitors
These monitors display various aspects of PID control. Refer to PID Block Diagram on page 166 for details on how
these monitors display PID data.
U5: PID Monitors on page 461 has a complete list of U5- monitors and descriptions.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 297
5.11 U: Monitor Parameters
298 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6
Troubleshooting
This chapter provides descriptions of the drive faults, alarms, errors, related displays, and
guidance for troubleshooting. This chapter can also serve as a reference guide for tuning the
drive during a trial run.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 299
6.1 Section Safety
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may illustrate drives without covers or safety shields to display details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not touch terminals before the drive has fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The capacitor for the control power supply remains
charged even after the drive input power is turned off. After shutting off the power, wait for at least the amount of time
specified on the drive before touching any components.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry, or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning
work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
300 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of drives.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user.
Check all the wiring after installing the drive and connecting other devices to ensure that all connections are
correct.
Failure to comply could result in damage to the drive.
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 301
6.2 Motor Performance Fine-Tuning
302 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.2 Motor Performance Fine-Tuning
Suggested
Problem Parameter No. Corrective Action Default Setting
• If there is too much motor noise, the carrier frequency is too low.
• Motor noise • If motor hunting and oscillation occur at low speeds, reduce the carrier
Carrier Frequency Selection
• Motor hunting and oscillation occur frequency. 1 (4 kHz) 1 to max. setting
(C6-02)
at speeds below 10 Hz Note: The default setting for the carrier frequency depends on the Drive
Model Selection (o2-04) and Drive Duty Mode Selection (C6-01).
• If motor torque and speed response are too slow, increase the setting.
Middle Output Frequency E1-08: 11.0 V
• Poor motor torque at low speeds • If the motor exhibits excessive instability at start-up, reduce the setting.
Voltage (E1-08) <2> Default setting
• Poor speed response Note: The default value is for 200 V class units. Double this value when
Minimum Output Frequency E1-10: 2.0 V ±2 V
• Motor instability at start using a 400 V class drive. When working with a relatively light load,
Voltage (E1-10) <2>
increasing this value too much can result in overtorque.
<1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03.
When using OLV, leave the torque compensation gain (C4-01) at its default setting of 1.00.
Troubleshooting
is required, and vice versa.
• Perform Auto-Tuning.
Close to the actual
Load Inertia (n8-55) Adjust parameter n8-55 to meet the load inertia ratio of the machine. 0
load inertia ratio
Speed Feedback Detection
Decrease in
Control Gain (for PM Motors) Decrease the speed feedback detection control gain (n8-45). 0.8
Poor motor torque and speed response decrements of 0.05
(n8-45)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 303
6.2 Motor Performance Fine-Tuning
304 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.2 Motor Performance Fine-Tuning
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 305
6.3 Drive Alarms, Faults, and Errors
306 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.3 Drive Alarms, Faults, and Errors
Aov Power Supply Overvoltage 312 EF0 Option Card External Fault 315
CoF Current Offset Fault 313 FbH Excessive PID Feedback 315
doH Damping Resistor Overheat 313 to Option Card Error Occurred at Option Port
oFA02 to oFA06 318
CN5-A
dv1 Z Pulse Fault 313
dv2 Z Pulse Noise Fault Detection 314 , Option Card Error Occurred at Option Port
oFA10, oFA11 318
CN5-A
dv3 Inversion Detection 314
Troubleshooting
oFA12 to oFA17 Option Card Connection Error (CN5-A) 318
dv7 Polarity Judge Timeout 314
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 307
6.3 Drive Alarms, Faults, and Errors
oFb01 Option Card Fault at Option Port CN5-B 318 oL5 Mechanical Weakening Detection 1 320
oFb02 Option Card Fault at Option Port CN5-B 318 oPr External Digital Operator Connection Fault 321
oFC01 Option Card Fault at Option Port CN5-C 318 SCF Safety Circuit Fault 321
oFC02 Option Card Fault at Option Port CN5-C 319 SEr Too Many Speed Search Restarts 321
oH3 Motor Overheat Alarm (PTC Input) 319 UL4 Undertorque Detection 2 322
oH4 Motor Overheat Fault (PTC Input) 319 UL5 Mechanical Weakening Detection 2 322
oL2 Drive Overload 320 <3> Uv2 Control Power Supply Voltage Fault 323
<1> Displayed as CPF00 or CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display
will show CPF01 or CPF21.
<2> This function prevents continuous operation in reverse when using high frequency injection (n8-57 = 1) in the Advanced Open Loop Vector
Control mode for PM motors (A1-02 = 6) with a motor for which no motor code has been entered (it does not simply prevent reverse
operation). To quickly detect undesirable reverse operation, set L8-93, L8-94, and L8-95 to low values within range of erroneous detection.
<3> Fault trace (i.e., the fault history) is not kept when CPF00, CPF01, CPF06, CPF24, Fdv, oFA00, oFb00, oFC00, Uv1, Uv2, and Uv3 occur.
308 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.3 Drive Alarms, Faults, and Errors
AEr Station Address Setting Error (CC-Link, CANopen, MECHATROLINK) YES 324
Speed Deviation (when using a PG option card and PM Open Loop Vector Control
dEv YES 325
Mode without PG)
to
EF1 to EF8 External Fault (input terminal S1 to S8) YES 326
Troubleshooting
Fdv Power Supply Frequency Fault YES 327
LT-3 Soft Charge Bypass Relay Maintenance Time No output <1> 328
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 309
6.3 Drive Alarms, Faults, and Errors
Operation Errors
Table 6.12 Operation Error Displays
Digital Operator Display Digital Operator Display
Name Page Name Page
LED Operator LCD Operator LED Operator LCD Operator
oPE01 Unit Capacity Setting Fault 331 oPE10 V/f Data Setting Error 332
oPE02 Parameter Range Setting Error 331 oPE11 Carrier Frequency Setting Error 332
oPE03 Multi-Function Input Setting Error 331 oPE13 Pulse Monitor Selection Error 332
oPE04 Terminal Board Mismatch Error 332 oPE15 Torque Control Setting Error 333
oPE06 Control Method Selection Error 332 oPE18 Online Tuning Parameter Setting Error 333
oPE08 Parameter Selection Error 332 oPE30 Incorrect Input Voltage Adjustment 333
310 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.3 Drive Alarms, Faults, and Errors
Auto-Tuning Errors
Table 6.13 Auto-Tuning Error Displays
Digital Operator Display Digital Operator Display
Name Page Name Page
LED Operator LCD Operator LED Operator LCD Operator
End1 Excessive V/f Setting 334 Er-10 Motor Direction Error 335
End2 Motor Iron-Core Saturation Coefficient 334 Er-11 Motor Speed Error 335
End3 Rated Current Setting Alarm 334 Er-12 Current Detection Error 336
End4 Adjusted Slip Calculation Error 334 Er-13 Leakage Inductance Error 336
End5 Resistance Tuning Error 334 Er-14 Motor Speed Error 2 336
End6 Leakage Inductance Alarm 334 Er-15 Torque Saturation Error 336
Er-01 Motor Data Error 334 Er-17 Reverse Prohibited Error 336
Er-04 Line-to-Line Resistance Error 335 Er-20 Stator Resistance Error 336
Er-05 No-Load Current Error 335 Er-21 Z Pulse Correction Error 336
Troubleshooting
rdEr Error Reading Data 339
vFyE Parameter settings in the drive and those saved to the copy function are not the same 339
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 311
6.4 Fault Detection
312 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
to ,
CPF00 to CPF03, CPF07,
, ,
CPF08, CPF11 to CPF14,
to , CPF16 to CPF24,
Control Circuit Error
CPF26 to CPF35,
to ,
CPF40 to CPF45
to , <1>
to <1>
Cause Possible Solution
• Cycle power to the drive.
Hardware is damaged. • If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Connector on the operator is damaged. Replace the operator.
Digital Operator Display Fault Name
Control Circuit Error
CPF06
There is an error in the data saved to EEPROM.
Cause Possible Solution
The power supply was switched off when parameters
Reinitialize the drive (A1-03 = 2220, 3330).
were being saved to the drive.
• Turn the power off and check the connection between the control board and the drive.
Hardware is damaged. • If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
Troubleshooting
Motor brake engaged. Ensure the motor brake releases properly.
Increase the setting values of L7-01 to L7-04, the value of the torque limit from the analog input, or the value of the torque limit
The torque limit is small for the load.
set from the communication option.
Digital Operator Display Fault Name
Damping Resistor Overheat
doH
The temperature of the built-in damping resistor exceeded the set value.
Cause Possible Solution
6
• The capacity of the power supply is too small. • Increase the capacity of the power supply.
• The distortion in the power supply is too large. • Lower the impedance of the input power supply wiring.
A phase loss occurred in the input power supply. Check the input power supply for phase loss or an imbalance in the interphase voltages.
Digital Operator Display Fault Name
Z Pulse Fault
dv1 The motor turned one full rotation without the Z pulse being detected.
Note: Available in CLV/PM control mode only.
Cause Possible Solution
PG encoder is not connected, not wired properly, or is • Make sure the PG encoder is properly connected and all shielded lines are properly grounded.
damaged. • If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 313
6.4 Fault Detection
dWAL
DriveWorksEZ Fault
dWFL
314 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
Noise has corrupted data while writing to the EEPROM. • Correct the parameter setting.
• Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 340.
• Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
Hardware problem.
nearest sales representative.
Digital Operator Display Fault Name
Fan Fault
FAn
Fan failed.
Cause Possible Solution
Cycle power to the drive.
Check if the fan is operating or not.
Troubleshooting
Cooling fan has malfunctioned. Verify the cumulative operation time of the fan using monitor U4-03, and the fan maintenance timer in U4-04.
If the cooling fan has passed its expected performance life or is damaged in some way, follow the instructions in this manual to
replace it.
Fault detected in the internal cooling fan to the power Cycle power to the drive.
supply (models 20154 to 20248, 40156 to If the fault still occurs, either replace the control circuit board or the entire unit.
40414). For instructions on replacing the power board, contact the Yaskawa sales office directly or your nearest Yaskawa representative.
Digital Operator Display Fault Name
FbH
Excessive PID Feedback 6
PID feedback input is greater than the level set b5-36 for longer than the time set to b5-37. To enable fault detection, set b5-12 =
2 or 5.
Cause Possible Solution
Parameters are not set appropriately. Check the settings of parameters b5-36 and b5-37.
Wiring for PID feedback is incorrect. Correct the wiring.
• Check the sensor on the control side.
There is a problem with the feedback sensor.
• Replace the sensor if damaged.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 315
6.4 Fault Detection
316 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
Troubleshooting
Overexcitation gain is set too high.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).
• Enable Speed Search at start (b3-01 = 1).
Run command applied while motor was coasting.
• Program the Speed Search command input through one of the multi-function contact input terminals (H1- = 61 or 62).
The wrong motor code has been entered for PM Open • Enter the correct motor code to E5-01.
Loop Vector (Yaskawa motors only) or the motor data • If a non-Yaskawa PM motor is used, enter “FFFF” to E5-01. Set the correct motor data to the E5- parameters or perform
are wrong. Auto-Tuning.
The overcurrent level has exceeded the value set to L8-
27. (PM control modes)
Correct the value set to overcurrent detection gain (L8-27).
6
• Check which motor control method the drive is set to (A1-02).
The motor control method and motor do not match. • For IM motors, set A1-02 = “0”, “1”, “2”, or “3”.
• For PM motors, set A1-02 = “5”, “6” or “7”.
The drives rated output current is too small. Use a larger drive.
Digital Operator Display Fault Name
Option Card Connection Error at Option Port CN5-A
oFA00
Option compatibility error
Cause Possible Solution
The option card installed into port CN5-A is
Check if the drive supports the option card that you are attempting to install. Contact Yaskawa for assistance.
incompatible with the drive.
A PG option card is connected to option port CN5-A PG option boards are supported by option ports CN5-B and CN5-C only. Place the PG option card into the correct option port.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 317
6.4 Fault Detection
to oFA02 to oFA06
Option Card Error Occurred at Option Port CN5-A
, oFA10, oFA11
to oFb03 to oFb11
Option Card Error Occurred at Option Port CN5-B
to oFb12 to oFb17
Cause Possible Solution
• Cycle power to the drive.
Option card or hardware is damaged. • If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
Option Card Connection Error at Option Port CN5-C
oFC00
Option compatibility error
Cause Possible Solution
The option card installed into port CN5-C is
Check if the drive supports the option card that you are attempting to instal. Contact Yaskawa for assistance.
incompatible with the drive.
A communication option card has been installed in
Communication option cards are supported by option port CN5-A only. More than one comm. option cannot be installed.
option port CN5-C.
Digital Operator Display Fault Name
Option Card Fault at Option Port CN5-C
oFC01
Option not properly connected
Cause Possible Solution
• Turn the power off and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
The option board connection to port CN5-C is faulty.
• Try to use the card in another option port (in case of a PG option use port CN5-B). If it works there, replace the drive. If the
error persists (oFA01 or oFb01 occur), replace the option board.
318 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
to oFC03 to oFC11
Option Card Error Occurred at Option Port CN5-C
to oFC12 to oFC17
Cause Possible Solution
• Cycle power to the drive.
Option card or hardware is damaged. • If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
Troubleshooting
Cause Possible Solution
• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10.
Motor has overheated • Be careful not to lower E1-08 and E1-10 too much, as this reduces load tolerance at low speeds.
• Check the motor rated current.
•
•
Enter the motor rated current as indicated on the motor nameplate (E2-01).
Ensure the motor cooling system is operating normally.
6
• Repair or replace the motor cooling system.
Digital Operator Display Fault Name
Motor Overheat Fault (PTC Input)
oH4 • The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the fault detection level.
• Detection requires that multi-function analog input H3-02, H3-10, or H3-06 = “E”.
Cause Possible Solution
• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Be careful not to lower
Motor has overheated. E1-08 and E1-10 too much because this reduces load tolerance at low speeds.
• Check the motor rated current.
• Enter the motor rated current as indicated on the motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 319
6.4 Fault Detection
320 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
Troubleshooting
Cause Possible Solution
PG cable is disconnected. Reconnect the cable. Check the setting of F1-20.
Digital Operator Display Fault Name
Safety Circuit Fault
SCF
Safety Circuit Fault is detected.
Cause Possible Solution
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 321
6.4 Fault Detection
322 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.4 Fault Detection
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 323
6.5 Alarm Detection
324 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.5 Alarm Detection
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
A fault reset command was entered while the Run • Ensure that a Run command cannot be entered from the external terminals or option card during fault reset.
YES
command was still present. • Turn off the Run command.
Digital Operator Display Minor Fault Name
MECHATROLINK Comm. Cycle Setting Error
CyC
Comm. Cycle Setting Error was detected.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
The controller is using a comm. cycle beyond the
allowable setting range for the MECHATROLINK Set the comm. cycle for the upper controller within the allowable setting range for the MECHATROLINK option. YES
option.
Digital Operator Display Minor Fault Name
Speed Deviation (for Control Mode with PG)
dEv The deviation between the speed detection value for the pulse input and the speed reference after speed agreement was reached
exceeded the setting value of F1-10 for the time set in F1-11 or longer when the Operation Selection at Deviation was set to continue
operation (F1-04 = 3).
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
Load is too heavy Reduce the load.
Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08).
The load is locked up. Check the machine.
Parameter settings are inappropriate. Check the settings of parameters F1-10 and F1-11.
• Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed. YES
Incorrect speed feedback scaling if terminal RP is
• Adjust the speed feedback signal using parameters H6-03 through H6-05.
used as speed feedback input in V/f Control.
• Make sure the speed feedback signal frequency does not exceed he maximum input frequency of terminal RP.
The motor brake engaged. Ensure the brake releases properly.
Increase the setting values of L7-01 to L7-04, the value of the torque limit from the analog input, or the value of the
The torque limit is small for the load.
torque limit set from the communication option.
Troubleshooting
Digital Operator Display Minor Fault Name
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
“Drive Enable” is set to a multi-function contact
input (H1- = 6A) and that signal was switched Check the operation sequence. YES
off. 6
Digital Operator Display Minor Fault Name
Damping Resistor Overheat
doH
The temperature of the built-in damping resistor exceeded the set value.
Minor Fault
Cause Possible Solutions
(H2- = 10)
The capacity of the power supply is too small. Increase the capacity of the power supply.
The distortion in the power supply is too large. Lower the impedance of the input power supply wiring. YES
A phase loss occurred in the input power supply. Check the input power supply for phase loss or an imbalance in the interphase voltages.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 325
6.5 Alarm Detection
326 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.5 Alarm Detection
Troubleshooting
Cooling Fan Maintenance Time
LT-1 The cooling fan has reached its expected maintenance period and may need to be replaced.
Note: An alarm output (H2- = 10) will only be triggered if both (H2- = 2F and H2- = 10) are set.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
The cooling fan has reached 90% of its expected
Replace the cooling fan and reset the Maintenance Monitor by setting o4-03 to 0. YES
performance life.
Digital Operator Display Minor Fault Name 6
Capacitor Maintenance Time
LT-2 The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
The main circuit and control circuit capacitors have Replace either the control board or the entire drive. For instructions on replacing the control board, contact
YES
reached 90% of their expected performance life. Yaskawa or your nearest sales representative.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 327
6.5 Alarm Detection
328 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.5 Alarm Detection
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
MEMOBUS/Modbus test has finished normally. This verifies that the test was successful. No output
Digital Operator Display Minor Fault Name
PG Disconnect (for Control Mode with PG)
PGo
Detected when no PG pulses are received for a time longer than setting in F1-14.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
PG cable is disconnected. Reconnect the cable.
PG cable wiring is wrong. Correct the wiring.
YES
PG encoder does not have enough power. Make sure the correct power supply is properly connected to the PG encoder.
Brake is holding the PG. Ensure the brake releases properly
Digital Operator Display Minor Fault Name
PG Hardware Fault (detected when using a PG-X3 option card)
PGoH
PG cable has become disconnected.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
PG cable is disconnected. Reconnect the cable. Check the setting of F1-20. YES
Troubleshooting
Digital Operator Display Minor Fault Name
Motor Switch during Run
rUn
A command to switch motors was entered during run.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
A motor switch command was entered during run. Change the operation pattern so that the motor switch command is entered while the drive is stopped. YES
Digital Operator Display
MEMOBUS/Modbus Communication Test Mode Error
Minor Fault Name
6
SE
Note: This alarm will not trigger a multi-function output terminal that is set for alarm output (H2- = 10).
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
A digital input set to 67H (MEMOBUS/Modbus
Stop the drive and run the test again. YES
test) was closed while the drive was running.
Digital Operator Display Minor Fault Name
Phase Order Detection Fault
SrC
The phase rotation direction for the input power supply changed.
Minor Fault
Cause Possible Solutions
(H2-01 = 10)
An input power supply wiring terminal is loose.
Investigate and correct the cause and then reset the fault.
The fluctuation in the voltage of the input power YES
Refer to Diagnosing and Resetting Faults on page 340.
supply is too large.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 329
6.5 Alarm Detection
330 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.6 Operator Programming Errors
Troubleshooting
• Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)
One of the following settings was entered while H1- = 2 (External Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train input selection is not set for the frequency
reference (H6-01 > 0)
• b1-15 or b1-16 set to 3 but no option card is connected
• Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias) Correct the settings for the multi-function input terminal parameters.
H2- = 38 (Drive Enabled) but H1- is not set to 6A (Drive Enable).
H1- = 7E (Direction Detection) although H6-01 is not set to 3 (for V/f Control with PG 6
using terminal RP as speed feedback input).
H1- = 16 is selected when using PG-RT3. Correct the setting. PG-RT3 is not available for the application with Motor 2 Selection.
Digital Operator Display Error Name
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 331
6.6 Operator Programming Errors
332 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.6 Operator Programming Errors
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 333
6.7 Auto-Tuning Fault Detection
334 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.7 Auto-Tuning Fault Detection
Motor rated power and motor-rated current settings • Check the drive and motor capacities.
(T1-02 and T1-04) do not match. • Correct the settings of parameters T1-02 and T1-04.
Motor rated current and detected no-load current are • Check the motor rated current and no-load current.
not consistent with another. • Correct the settings of parameters T1-04 and E2-03.
Base frequency and motor rated speed (T1-05 and • Set T1-05 and T1-07 to the correct value.
T1-07) do not match. • Check if the correct pole number was entered to T1-06.
Digital Operator Display Error Name
Er-02 Minor Fault
Cause Possible Solutions
An alarm was triggered during Auto-Tuning. Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.
Digital Operator Display Error Name
Er-03 STOP Button Input
Cause Possible Solutions
Auto-Tuning canceled by pressing STOP button. Auto-Tuning did not complete properly and will have to be performed again.
Digital Operator Display Error Name
Er-04 Line-to-Line Resistance Error
Cause Possible Solutions
Motor data entered during Auto-Tuning was • Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
incorrect. • Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the parameter
setting range or the tuning process took too long. Check and correct faulty motor wiring.
Motor cable or cable connection faulty.
Digital Operator Display Error Name
Er-05 No-Load Current Error
Cause Possible Solutions
Motor data entered during Auto-Tuning was • Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
incorrect. • Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the parameter • Check and correct faulty motor wiring.
setting range or the tuning process took too long. • Perform Rotational Auto-Tuning.
• Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make sure the load is lower
The load during Rotational Auto-tuning was too
than 30%.
high.
• If a mechanical brake is installed, make sure it is fully lifted during tuning.
Digital Operator Display Error Name
Troubleshooting
Torque limit when motoring is too low (L7-01 and • Check the settings of parameters L7-01 and L7-02.
L7-02). • Increase the setting.
• Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make sure the load is lower
The load during Rotational Auto-Tuning was too
than 30%.
high.
• If a mechanical brake is installed, make sure it is fully lifted during tuning.
Digital Operator Display Error Name
Er-10 Motor Direction Error
Cause Possible Solutions
6
The encoder signal lines are not properly connected
Check and correct wiring to the PG encoder.
to the drive.
Check the motor speed monitor U1-05 while turning the motor manually in forward direction. If the sign displayed is negative,
Motor and PG direction are opposite.
change the setting of parameter F1-05.
The load pulled the motor in the opposite direction
of the speed reference and the torque exceeded Uncouple the motor from the load and repeat Auto-Tuning.
100%.
Digital Operator Display Error Name
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 335
6.7 Auto-Tuning Fault Detection
336 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.7 Auto-Tuning Fault Detection
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 337
6.8 Copy Function Related Displays
338 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.8 Copy Function Related Displays
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 339
6.9 Diagnosing and Resetting Faults
340 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.9 Diagnosing and Resetting Faults
- MODE - DRV
oC
Overcurrent
Fix the cause of the fault, restart the drive, and Press on the digital operator when error code is FWD RESET
displayed. ESC
LO
RE
RESET ENTER
RUN STOP
U1000
Close then open the fault signal digital input via terminal S4. Fault Reset Switch
Resetting via Fault Reset Digital Input S4 S4 Fault Reset Digital Input
S4 is set for “Fault Reset” as default (H1-04 = 14).
SC Digital Input Common
ON
If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after the digital
operator display is out.
OFF
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. The Run command must first be removed
before a fault situation can be cleared.
Troubleshooting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 341
6.10 Troubleshooting without Fault Display
Common Problems
Common Problems Page
Cannot Change Parameter Settings 342
Motor Does Not Rotate 343
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering
Motor Rotates in the Opposite Direction from the Run Command 344
External Run Command
Motor Rotates in One Direction Only 344
Motor is Too Hot 344
Drive Does Not Allow Selection of Rotational Auto-Tuning 344
oPE02 Error Occurs When Lowering the Motor Rated Current Setting 344
Motor Stalls During Acceleration or With Large Loads 345
Drive Frequency Reference Differs from the Controller Frequency Reference Command 345
Excessive Motor Oscillation and Erratic Rotation 345
Load Falls When Brake is Applied (Hoist-Type Applications) 345
Noise From Drive or Motor Cables When the Drive is Powered On 346
Equipment for Residual Current Monitoring/Detection (RCM/RCD) Trips During Run. 346
Unexpected Noise from Connected Machinery 346
Connected Machinery Vibrates When Motor Rotates
Oscillation or Hunting 346
PID Output Fault 346
Insufficient Starting Torque 346
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking) 347
Output Frequency is not as High as Frequency Reference 347
Buzzing Sound from Motor at 2 kHz 347
Unstable Motor Speed when Using PM or IPM 347
Motor Does Not Restart after Power Loss 347
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals DM+ and DM-) 347
• Scroll to A1-04. Press the STOP button and press at the same time. Parameter A1-05 will appear.
• Set a new password to parameter A1-05.
• Check the drive input power voltage by looking at the control circuit voltage (U1-07).
Undervoltage was detected.
• Check all main circuit wiring.
342 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.10 Troubleshooting without Fault Display
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering
External Run Command
Motor Does Not Rotate
• When the STOP button is pressed, the drive will decelerate to stop.
The STOP button was pressed when
• Switch off the Run command and then re-enter a new Run command.
the drive was started from a REMOTE
source. • The STOP button can be disabled when o2-02 is set to 0.
Motor starting torque is too low. Refer to Motor Performance Fine-Tuning on page 302
Troubleshooting
Frequency reference value is too low or the
Enter a value that is above the minimum output frequency determined by E1-09.
drive does not accept the value entered.
• If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not set to 0.
The sequence Start/Stop sequence is set up
• If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must be set to 0. Terminal S1
incorrectly.
will become the Start, terminal S2 will become the Stop input.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 343
6.10 Troubleshooting without Fault Display
2
1. Forward Rotating Motor (looking down the motor shaft)
2. Motor Shaft
The motor is running at almost 0 Hz and the Speed Search estimated
Disable bi-directional search (b3-14 = "0") so that Speed Search is performed only in the specified direction.
the speed to be in the opposite direction.
Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the
manufacturer of the motor.
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Cause Possible Solutions
• The user is trying to set the motor rated current in E2-01 to a value lower than the no-load current set in E2-03.
Motor rated current and the motor no-load current setting in the • Make sure that value set in E2-01 is higher than E2-03.
drive are incorrect. • If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change the setting in E2-01
as needed.
344 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.10 Troubleshooting without Fault Display
Torque limit has been reached or current suppression keeps the drive Take the following steps to resolve the problem:
from accelerating. • Reduce the load.
• Increase motor capacity.
Note: Although the drive has a Stall Prevention function and a Torque Compensation Limit function, accelerating too
Load is too heavy. quickly or trying to drive an excessively large load can exceed the capabilities of the motor.
Torque limit is not set properly. Check the torque limit setting.
• Check the maximum output frequency (E1-04).
• Increase E1-04 if it is set too low.
Frequency reference is too low. Check U1-01 for proper frequency reference.
Check if a frequency reference signal switch has been set to one of the multi-function input terminals.
Check for low gain level set to terminals A1, A2, or A3 (H3-03, H3-11, H3-07).
• Reduce the load so that the output current remains within the motor rated current.
• In extruder and mixer applications, the load will sometimes increase as the temperature drops.
Load is too heavy.
• Increase the acceleration time.
• Check if the mechanical brake is fully releasing as it should.
Acceleration time has been set too long. Check if the acceleration time parameters have been set too long (C1-01, C1-03, C1-05, C1-07).
• Set the correct V/f pattern so that it matches the characteristics of the motor being used.
Motor characteristics and drive parameter settings are incompatible
• Check the V/f pattern set to E1-03.
with one another.
• Execute Rotational Auto-Tuning.
• Perform Auto-Tuning.
Although the drive is operating in Open Loop Vector motor control
• Calculate motor data and reset motor parameters.
method, Auto-Tuning has not been performed.
• Switch to V/f Control (A1-02 = 0).
• Check the multi-function analog input settings. Multi-function analog input terminal A1, A2, or A3 is set for
frequency gain (H3-02, H3-10, or H3-06 is set to “1”), but there is no voltage or current input provided.
Incorrect frequency reference setting.
• Make sure H3-02, H3-10, and H3-06 are set to the proper values.
• See if the analog input value is set to the right value (U1-13 to U1-15).
• Check the Stall Prevention level during acceleration (L3-02).
The Stall Prevention level during acceleration and deceleration set
• If L3-02 is set too low, acceleration may be taking too long.
too low.
• Increase L3-02.
• Check the Stall Prevention level during run (L3-06).
The Stall Prevention level during run has been set too low. • If L3-06 is set too low, speed will drop as the drive outputs torque.
• Increase the setting value.
• The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance.
Drive reached the limitations of the V/f motor control method. • Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds.
• Consider switching to Open Loop Vector Control.
Troubleshooting
PID control is enabled, and the drive is consequently adjusting the
output frequency to match the PID setpoint. The drive will only
If PID control is not necessary for the application, disable it by setting b5-01 to “0”.
accelerate to the maximum output frequency set in E1-04 while
PID control is active.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 345
6.10 Troubleshooting without Fault Display
Note: To inspect for a motor error, set C6-02 to a value between 1 and 4 and check the motor.
Oscillation or Hunting
346 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
6.10 Troubleshooting without Fault Display
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)
Cause Possible Solutions
• Adjust the DC Injection braking settings.
DC Injection Braking is set too low and the drive cannot decelerate
• Increase the current level for DC Injection Braking Current (b2-02).
properly.
• Increase the DC Injection Braking time at stop (b2-04).
The stopping method is set so that the drive coasts to stop. Set b1-03 (Stopping Method Selection) to 0 or 2.
Troubleshooting
Cause Possible Solutions
• Check the sequence and wiring that has been set up to enter the Run command.
The Run command was not issued again when power was restored.
• A relay should be set up to make sure the Run command remains enabled throughout any power loss.
The relay that is supposed to maintain the Run command has been
Check wiring and circuitry for the relay intended to keep the Run command enabled.
switched off.
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals 6
(Terminals DM+ and DM-)
Cause Possible Solutions
• Check the wiring for the Safe Disable monitor output terminal.
There is faulty wiring in the Safe Disable monitor output terminals.
• Correct wiring mistakes.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 347
6.10 Troubleshooting without Fault Display
348 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7
Periodic Inspection & Maintenance
This chapter describes the periodic inspection and maintenance of the drive to ensure that it
receives the proper care to maintain overall performance.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 349
7.1 Section Safety
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning
work on the drive.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent
electric shock, wait for at least the time specified on the warning label; after all indicators are OFF, measure the DC bus
voltage level to confirm it has reached a safe level.
350 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.1 Section Safety
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Follow cooling fan replacement instructions. The cooling fan cannot operate properly when it is installed
incorrectly and could seriously damage the drive.
Follow the instructions in this manual to replace the cooling fan, making sure that the label is on top before inserting
the cooling fan into the drive. To ensure maximum useful product life, replace both cooling fans when performing
maintenance.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Periodic Inspection &
Failure to comply could result in damage to the drive.
Comply with proper wiring practices.
Maintenance
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 351
7.2 Inspection
7.2 Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of
use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and
periodic inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and
relays. The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note: The drive will require more frequent inspection if it is placed in harsh environments, such as:
High ambient temperatures
Frequent starting and stopping
Fluctuations in the AC supply or load
Excessive vibrations or shock loading
Dust, metal dust, salt, sulfuric acid, chlorine atmospheres
Poor storage conditions.
Perform the first equipment inspection one to two years after installation.
352 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.2 Inspection
Circulation Fan, Refer to Cooling Fan and Circulation Fan on page 356 for
• Check for damaged or missing fan blades.
Control Board Cooling Fan information on cleaning or replacing the fan.
Remove foreign particles and dust by sucking them out with a
Heatsink Inspect for dust or other foreign material collected on the surface.
vacuum cleaner to avoid touching parts.
Inspect air intake and exhaust openings. They must be free from • Visually inspect the area.
Air Duct
obstruction and properly installed. • Clear obstructions and clean air duct as required.
Display Periodic Inspection 7
• Make sure data appears on the operator properly. • Contact your Yaskawa representative if there is any trouble
Digital Operator • Inspect for dust or other foreign material that may have collected with the display or keypad.
on surrounding components. • Clean the digital operator.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 353
7.3 Periodic Maintenance
Replacement Parts
Table 7.3 contains the estimated performance life of components that require replacement during the life of the drive.
Only use Yaskawa replacement parts for the appropriate drive model and revision.
Table 7.3 Estimated Performance Life
Component Estimated Performance Life
Cooling Fan, Circulation Fan 10 years
Capacitors for the control power supply 10 years <1>
<1> Capacitors for the control power supply cannot be replaced on some models. Complete drive replacement may be required for these models.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage
conditions for estimated performance life:
• Ambient temperature: Yearly average of 40°C (IP00 enclosure)
• Load factor: 80% maximum
• Operation time: 24 hours a day
354 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.3 Periodic Maintenance
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2- = 2F). The alarm
will also trigger a digital output that is programmed for alarm indication (H2- = 10).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 355
7.4 Cooling Fan and Circulation Fan
Contact a Yaskawa representative or the nearest Yaskawa sales office to order replacement cooling fans as required.
For drives with multiple cooling fans, replace all the fans when performing maintenance to ensure maximum product
performance life.
Number of Fan
Three-Phase 200 V Class Three-Phase 400 V Class
Model Model
CIMR-U Cooling Fan Circulation Fan Page CIMR-U Cooling Fan Circulation Fan Page
20028 2 – 40011 2 –
20042 2 – 40014 2 –
20054 2 – 40021 2 –
20068 2 – 358 40027 2 –
20081 2 – 40034 2 –
20104 2 – 40040 2 – 358
20130 2 – 40052 2 –
20154 3 – 40065 2 –
360
20192 3 – 40077 2 –
20248 1 2 364 40096 2 –
– – – – 40124 2 –
– – – – 40156 3 –
360
– – – – 40180 3 –
– – – – 40216 1 2
– – – – 40240 1 2
– – – – 40302 2 2 364
– – – – 40361 2 2
– – – – 40414 2 2
356 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the
power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled
down.
NOTICE: Prevent Equipment Damage. Follow cooling fan and circulation fan replacement instructions. Fans cannot operate properly
when they are installed incorrectly and can damage the drive. Follow the instructions below to replace the fans, making sure that the
label is on top before inserting the fan into the drive. To ensure maximum useful product life, replace all fans when performing
maintenance.
Note: Procedures shown in this section use a representative drive model. Figures in these procedures may differ slightly from the actual
model used by the customer.
Figure 7.1
A A
B B
Maintenance
7
common_
TMonly
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 357
7.4 Cooling Fan and Circulation Fan
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the
power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled
down.
NOTICE: Prevent Equipment Damage. Follow cooling fan and circulation fan replacement instructions. Improper fan replacement
could cause damage to equipment. Make sure the fan is facing upwards when installing the replacement fan into the drive. Replace all
fans when performing maintenance to help ensure maximum useful product life.
common_TM
only
common_TM
only
Figure 7.3 Remove the Cooling Fan
3. Disconnect the pluggable connector and remove the fan.
Figure 7.4
common_TM
only
Figure 7.4 Disconnect the Cooling Fan
358 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
common_TMonly
B B
common_TMonly
common_TMonly
into place.
Note: The fan guard has a cutout on the front side for proper alignment.
Figure 7.8
common_TMonly
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 359
7.4 Cooling Fan and Circulation Fan
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the
power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled
down.
NOTICE: Prevent Equipment Damage. Follow cooling fan and circulation fan replacement instructions. Improper fan replacement
could cause damage to equipment. Make sure the fan is facing upwards when installing the replacement fan into the drive. Replace all
fans when performing maintenance to help ensure maximum useful product life.
A common_TMonly
A – Screw locations
Figure 7.9 Loosen the Screws
2. Slide the fan guard toward the front of the drive to remove it from the drive.
Figure 7.10
common_TMonly
A
common_TMonly
A – Hook locations
Figure 7.11 Release the Cables
360 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
A common_TMonly
A – Screw locations
Figure 7.12 Remove the Cooling Fan Unit
5. Disconnect the three pluggable connectors and remove the fan unit from the drive.
Figure 7.13
common_TMonly
common_TMonly
7
Figure 7.14 Plug in the Relay Connector
Figure 7.15
common_TMonly
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 361
7.4 Cooling Fan and Circulation Fan
2. Guide the fan cables through the provided hooks to hold the cables in place.
Figure 7.16
common_TMonly
A
common_TMonly
D
common_TMonly
B
A C
362 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
5. Thread the four fan unit screws into the proper holes approximately 2/3 of the way. Leave enough space to
reinsert the fan guard.
Figure 7.19
common_TMonly
A
A – Screw locations
A common_TMonly
A – Screw locations
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 363
7.4 Cooling Fan and Circulation Fan
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the
power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled
down.
NOTICE: Prevent Equipment Damage. Follow cooling fan and circulation fan replacement instructions. Improper fan replacement
could result in damage to equipment. Follow the instructions and replace the whole unit when replacing the cooling fan.
common_TMonly
A – Screw locations
Figure 7.21 Loosen the Screws
2. Slide the fan guard toward the right to remove it from the drive.
Figure 7.22
common_
TMonly
common_TMonly
A – Hook locations
Figure 7.23 Free the Cable
364 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
common_TMonly
common_TMonly
A – Opening
Figure 7.26 Attach the Relay Connector
Figure 7.27
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 365
7.4 Cooling Fan and Circulation Fan
2. Install the cooling fan unit and place the cable back into position.
Note: 1. Replace the whole unit when performing maintenance on the cooling fans.
2. Install the cooling fan unit while pulling the cable upward so that the cable does not get pinched between parts.
Figure 7.28
common_TMonly
A
common_TMonly
A – Screw locations
Figure 7.29 Attach the Cooling Fan Unit
4. Reattach the fan cover and then tighten the screws firmly so that the screws do not come loose.
Figure 7.30
common_TMonly
366 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.4 Cooling Fan and Circulation Fan
common_TMonly
A – Screw locations
Figure 7.31 Remove the Drive Cover
2. Unlock the two cable hooks.
Note: The circulation fan unit on models 40302 to 40414 is located on the right side of the drive.
Figure 7.32
common_TMonly
common_TMonly
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 367
7.4 Cooling Fan and Circulation Fan
4. Loosen the three screws, then slide the cooling fan unit up and carefully pull it out.
Figure 7.34
A
common_TMonly
A – Screw locations
Figure 7.34 Removing the Circulation Fan Unit
1. Reverse the procedure described above to install the replacement cooling fan unit.
Note: 1. Replace the whole unit when performing maintenance on the cooling fans.
2. Place the cables back into the hooks to secure.
3. Do not pinch the fan cable between parts when reassembling the fan unit.
4. Tighten the screws firmly so they do not come loose.
Figure 7.35
common_TMonly
368 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.5 Drive Replacement
Terminal Board
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains
on-board memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the
replacement drive. To transfer the terminal board, disconnect the terminal board from the damaged drive and reconnect it
to the replacement drive. There is no need to manually reprogram the replacement drive after transferring the terminal
board.
Note: If the damaged drive and the new replacement drive are have different capacities, the data stored in the terminal board cannot be
transferred to the new drive and an oPE01 error will appear on the display. The terminal board can still be used, but parameter
setting from the old drive cannot be transferred. The replacement drive must be initialized and manually programmed.
Figure 7.36
common_TMonly
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 369
7.5 Drive Replacement
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in
serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit
boards. Failure to comply may result in ESD damage to the drive circuitry.
The following procedure explains how to replace a drive. This section provides instructions for drive replacement only.
To install option boards or other types of options, then refer to the specific manuals for those options.
NOTICE: When transferring an option from a damaged drive to a new replacement drive, make sure it is working properly before
reconnecting it to the new drive. Replace broken options to prevent immediate breakdown of the replacement drive.
YEG_
TMon
ly
Figure 7.37 Remove the Terminal Cover
2. Loosen the screws holding the terminal board in place. Remove the screw securing the bottom cover and
remove the bottom cover from the drive.
Figure 7.38
YEG_
TMon
ly
Figure 7.38 Unscrew the Terminal Board
370 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
7.5 Drive Replacement
3. Slide the terminal board as illustrated by the arrows in Figure 7.39 to remove it from the drive along with the
bottom cover.
Figure 7.39
YEG_
TMon
ly
YEG_
TMon
ly
YEG_
TMon
ly
Periodic Inspection &
Maintenance
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 371
7.5 Drive Replacement
372 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8
Peripheral Devices & Options
This chapter explains the installation of peripheral devices and options available for the drive.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 373
8.1 Section Safety
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning
work on the drive.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
374 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the
wiring and the selection of the peripheral devices.
Contact your supplier if the cause cannot be identified after checking the above.
Do not restart the drive or immediately operate the peripheral devices if a fuse is blown or equipment for
residual current monitoring/detection (RCM/RCD) is tripped.
Check the wiring and the selection of peripheral devices to identify the cause.
Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 375
8.2 Drive Options and Peripheral Devices
376 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.3 Connecting Peripheral Devices
YASKAWA
USB Copy Unit
ERR
Supply
COM
JVOP-181
LOCK
py rify ad
Co Ve Re
Momentary
Power Loss
Recovery Unit
Zero-phase
Reactor
Ground
Motor
YEG_
Magnetic
Contactor TMonly
(switches to
line power) Ground
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 377
8.4 Option Card Installation
Figure 8.2 shows an exploded view of the drive with the option and related components for reference.
Figure 8.2
A
B D
C
K E
J
I
H
F
G
common_
TMonly
378 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.4 Option Card Installation
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in
death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar
with installation, adjustment and maintenance of AC drives and Option Cards.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option card, drive, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
NOTICE: Damage to Equipment. Tighten all terminal screws to the specified tightening torque. Failure to comply may cause the
application to operate incorrectly or damage the drive.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the digital
operator (E) and front covers (D, F). Refer to Digital Operator and Front Cover on page 67.
Figure 8.3
common_
TMonly
2. Insert the option card (B) into the CN5-A (I), CN5-B (J), or CN5-C (K) connectors located on the drive and fasten
it into place using one of the included screws (C).
Use both CN5-B and CN5-C when connecting two options.
Figure 8.4
B
C
Peripheral Devices &
K
J
Options
8
common_
TMonly
Figure 8.4 Insert the Option Card
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 379
8.4 Option Card Installation
3. Connect one end of the ground wire (G) to the ground terminal (H) using one of the remaining screws (C).
Connect the other end of the ground wire (G) to the remaining ground terminal and installation hole on the option
(B) using the last remaining provided screw (C).
Figure 8.5
G
common_
TMonly
Figure 8.5 Connect the Ground Wire
Note: 1. The option package includes two ground wires. Use the longer wire when plugging the option into connector CN5-C on the drive
side. Use the shorter wire when plugging the option into connector
CN5-B. Refer to the option card instruction manual for more information.
2. There are two screw holes on the drive for use as ground terminals (H). When connecting three options, two ground wires will need
to share the same drive ground terminal.
4. Prepare and connect the wire ends as shown in Figure 8.6 and Figure 8.7. Refer to Wire Gauges and
Tightening Torques on page 382 to confirm that the proper tightening torque is applied to each terminal. Take
particular precaution to ensure that each wire is properly connected and wire insulation is not accidentally
pinched into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections could
result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified tightening
torque may result in erroneous operation, damage to the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not contact other wiring. Insufficient
insulation may cause a short circuit and damage the option or drive.
Figure 8.6
Shield Insulation
PG at motor
PG option terminal
B3
Ground Terminal
FE/SD Shield sheath
(Insulate with electrical tape
common_
or shrink tubing) TMonly
Figure 8.6 Preparing Ends of Shielded Cable
Figure 8.7
380 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.4 Option Card Installation
5. For the PG-B3 and PG-X3 Option, wire the motor PG encoder to the terminal block. Refer to Figure 8.8 and
Figure 8.12 for wiring instructions.
Refer to Terminal Functions on page 382 for a detailed description of the option terminal functions.
R/L1 U/T1
S/L2 V/T2 M
T/L3 W/T3
YASKAWA TB1
Drive PGB3 3
A+
Option 4
A
5
B+
6 PG
B
Z+
Z
SD
NC
FE E
<1>
TB2
1
IP
IG 2
CN5 AO
IG A pulse monitor signal
Peripheral Devices &
BO
B pulse monitor signal
IG
ZO Z pulse monitor signal
FE IG
Options
Ground wire
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 381
8.4 Option Card Installation
Take the following steps to prevent erroneous operation caused by noise interference:
• Use shielded wire for the PG encoder signal lines.
• Limit the length of all motor output power cables to less than 100 m. Limit the length of open-collector output lines to
less than 50 m.
• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and
motor output power cables.
Interface Circuit
• Complementary Output
Figure 8.8
AO,BO,ZO
IG
Monitor Signals common_
TMonly
Figure 8.9 Complementary Outputs for the Interface Circuit
• Open-Collector Outputs
Figure 8.9
PGB3 IP Vcc
12 V PG Encoder
330 Ω A+,B+,Z+
470 Ω A,B,Z
A,B,Z
330 Ω
IG 0V
AO,BO,ZO
IG
Monitor Signals common_
TMonly
Figure 8.10 Open-Collector Outputs for the Interface Circuit
Terminal Functions
Table 8.3 Option Terminal Functions
Terminal Block Terminal Function Description
TB1
A+ A+ pulse signal input
A– A– pulse signal input • Pulse signal inputs from the PG.
B+ B+ pulse signal input • Signal inputs from complementary and open-collector outputs
A+ A- B+ B- Z+ Z-
• Signal level
B– B– pulse signal input
IP IG
TB1 H level: 8 to 12 V
Z+ Z+ pulse signal input L level: 2.0 V or less
Z– Z– pulse signal input
SD NC pin (open) For use when cables shields should not be grounded
AO IG BO IG ZO IG
<1> A separate UL Listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.
Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in Table 8.4. For simpler and more reliable wiring, use crimp ferrules on
the wire ends. Refer to the option manuals for the wire size and torque specifications of other options.
382 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.4 Option Card Installation
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications
listed in Table 8.5 for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 8.5 Crimp Terminal Sizes
Wire Size L d1 d2
mm2 Phoenix Contact Model mm (in) mm (in) mm (in)
0.25 (24 AWG) AI 0.25 - 6YE 10.5 (13/32) 0.8 (1/32) 2 (5/64)
0.34 (22 AWG) AI 0.34 - 6TQ 10.5 (13/32) 0.8 (1/32) 2 (5/64)
d1 6 mm d2
L 0.5 (20 AWG) AI 0.5 - 6WH 14 (9/16) 1.1 (3/64) 2.5 (3/32)
TB1 TB2
A+ A- B+ B- Z+ Z- SD FE IP IG AO IG BO IG ZO IG
3 4 5 6 E 1 2
TA1 A G
B H F
PG encoder side
C E
D
common_
Pin)
TMonly
Figure 8.11 Wiring PG Encoder Cable
Table 8.6 Connecting the PG Encoder Cable Specification
PG Encoder Cable
Option Terminal
Wire Color Pin
Peripheral Devices &
IP 1 Blue C
IG 2 White H
A+ 3 Yellow B
A– 4 White G
Options
B+ 5 Green A
B– 6 White F
FE E N/A (shield) D
8
Table 8.7 PG Encoder Cable Types
Length Type Length Type
10 m (32 ft.) W5010 50 m (164 ft.) W5050
30 m (98 ft.) W5030 100 m (328 ft.) W5100
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 383
8.4 Option Card Installation
R/L1 U/T1
S/L2 V/T2 M
T/L3 W/T3
TB1
YASKAWA
Drive PGX3 A+
Option A
B+
PG
B
Z+
Z
SD
NC
FE
<1>
CN3
IP12 TB2
IP5 IP
IG IG
SG
CN5-B a+
A pulse monitor signal
or a
CN5-C b+
B pulse monitor signal
b
z+
Z pulse monitor signal
FE z
Ground wire
twisted-pair shielded line
common_
main circuit terminal control circuit terminal TMonly
<1> Ground the shield on the PG side and the drive side. If noise problems arise in the PG signal, remove the shield ground from one end of the
signal line or remove the shield ground connection on both ends.
Figure 8.12 PG-X3 Option and PG Encoder Connection Diagram
Note: The PG-X3 Option reads a maximum input frequency from the PG of 300 kHz. Be sure to select a PG with an output pulse
frequency of maximum 300 kHz when operating at maximum speed.
384 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.4 Option Card Installation
Take the following steps to prevent erroneous operation caused by noise interference:
• Use shielded wire for the PG encoder signal lines.
• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and
motor output power cables.
Interface Circuit
Figure 8.11
PGX3 PG Encoder
A+,B+,Z+ A,B,Z
600 Ω
A,B,Z
26LS32 level A,B,Z 26LS31 level
a+,b+,z+
a,b,z
Monitor Signals
26LS31 level SG common_
TMonly
Figure 8.13 Interface Circuit (PG-X3)
Terminal Functions
Table 8.8 Option Terminal Functions
Terminal Block Terminal Function Description
A+ A+ pulse signal input
A– A– pulse signal input
TB1TB1
B+ B+ pulse signal input • Inputs for the A channel, B channel, and Z pulses from the PG encoder
B– B– pulse signal input • Signal level matches RS-422
A+ A− B+ B− Z+ Z−
A+ A− B+ B− Z+ Z−
Table 8.9 Setting the PG Encoder Power Supply Voltage (IP) with Jumper CN3
Voltage Level 5.5 V ± 5% (default) 12.0 V ± 5%
5.5 V 12 V 5.5 V 12 V
Peripheral Devices &
CN3 CN3
Jumper CN3
Options
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 385
8.4 Option Card Installation
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications
listed in Table 8.11 for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 8.11 Crimp Terminal Sizes
Wire Gauge L d1 d2
mm2 Phoenix Contact Model mm (in) mm (in) mm (in)
0.25 (24 AWG) AI 0.25 - 6YE 10.5 (13/32) 0.8 (1/32) 2 (5/64)
0.34 (22 AWG) AI 0.34 - 6TQ 10.5 (13/32) 0.8 (1/32) 2 (5/64)
d1 6 mm d2
L 0.5 (20 AWG) AI 0.5 - 6WH 14 (9/16) 1.1 (3/64) 2.5 (3/32)
common_
TMonly
Figure 8.14 Wire Routing Examples
386 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.4 Option Card Installation
7. Replace and secure the front covers of the drive (D, F) and replace the digital operator (E).
Figure 8.13
common_
TMonly
Figure 8.15 Replace the Front Covers and Digital Operator
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure cables are
not pinched between the front covers and the drive when replacing the covers.
8. For the PG-B3 and PG-X3 Option, set drive parameters for proper motor rotation.
With a two-pulse or three-pulse PG encoder, the leading pulse determines the motor rotation direction. A PG
encoder signal with leading A pulse followed by a B pulse displaced at 90 degrees is considered to be rotating
forward (counterclockwise when viewing rotation from motor load side).
Figure 8.14
A pulse
B pulse common_
Time TMonly
Figure 8.16 Displacement of A and B Pulses
After connecting the PG encoder outputs to the option, apply power to the drive and manually rotate the motor
and check the rotation direction by viewing monitor U1-05 on the digital operator.
Reverse motor rotation is indicated by a negative value for U1-05; forward motor rotation is indicated by a
positive value.
If monitor U1-05 indicates that the forward direction is opposite of what is intended, set F1-05 or F1-32 to 1, or
reverse the two A pulse wires with the two B pulse wires on option terminal TB1 as shown in Figure 8.17.
Figure 8.15
B3
A+ A- B+ B- Z+ Z- A+ A- B+ B- Z+ Z-
Peripheral Devices &
3 4 5 6 5 6 3 4 common_
TMonly
Options
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 387
8.5 Installing Peripheral Devices
Installing a Molded Case Circuit Breaker (MCCB) and Equipment for Residual
Current Monitoring/Detection (RCM/RCD)
Install an MCCB or an RCM/RCD for line protection between the power supply and the main circuit power supply input
terminals R/L1, S/L2, and T/L3. This protects the main circuit and devices wired to the main circuit while also providing
overload protection.
Consider the following when selecting and installing a MCCB or an RCM/RCD:
• The capacity of the MCCB or RCM/RCD should be 1.5 to 2 times the rated output current of the drive. Use an MCCB
or an RCM/RCD with operation characteristics so that the MCCB or RCM/RCD does not trip faster than the drive
overload protection (shuts off the drive after 1 min. operation at 150% of the drive rated current).
• If several drives are connected to one MCCB or RCM/RCD, use a sequence that shuts the power OFF when an error
occurs in one drive by using a magnetic contactor (MC) as shown in the following figure.
Figure 8.16
A MCCB or RCM/RCD MC
R/L1
S/L2
T/L3 YEG_TMo
MC
MB nly
C MC
MC
WARNING! Electrical Shock Hazard. Switch off and lock the MCCB (or RCM/RCD) and MC before wiring terminals. Failure to comply
may result in serious injury or death.
388 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
8.5 Installing Peripheral Devices
NOTICE: Install a MC on the input side of the drive when the drive should not automatically restart after power loss. To get the full
performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply off and on more than
once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
NOTICE: Use a magnetic contactor (MC) to ensure that power to the drive can be completely shut off when necessary. The MC should
be wired so that it opens when a fault output terminal is triggered.
Note: 1. To keep the drive from restarting automatically when power is restored after momentary power loss, install a magnetic contactor to
the drive input.
2. To have the drive continue operating through momentary power loss, set up a delay for the magnetic contactor so that it does not open
prematurely.
Reducing Noise
Preventing Induced Noise
Use shielded cables and internal EMC-filter models or zero phase reactors to prevent induced noise. Lay the cables at
least 30 cm away from the signal line to prevent induced noise.
Figure 8.17
B
C
A MCCB D
R/L1 U/T1
S/L2 V/T2 M
T/L3 W/T3
G
common_
F TMonly
Peripheral Devices &
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 389
8.5 Installing Peripheral Devices
390 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Appendix: A
Specifications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 391
A.1 Heavy Duty and Normal Duty Ratings
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, and
current limit. The default setting is HD (C6-01 = 0).
392 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
A.2 Three-Phase 200 V Class Drives
Specifications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 393
A.3 Three-Phase 400 V Class Drives
Item Specification
CIMR-U4 0180 0216 0240 0302 0361 0414
HD Rating 142 164 197 218 275 329
Input Current (A) <1>
ND Rating 164 197 218 275 329 377
HD Rating 130 150 180 200 251 300
Rated Input Capacity (kVA) <2>
ND Rating 150 180 200 251 300 344
Rated Output Current HD Rating 156 180 216 240 302 361
Input/
(A) <3> <4> ND Rating 180 216 240 302 361 414
Output
Rating HD Rating: 150% of rated output current for 60 s
Overload Tolerance ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency 4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Maximum Output Voltage (V) Proportional to input voltage <5>
Maximum Output Frequency (Hz) 400 Hz <6>
Three-phase (CIMR-U4A/4P) 380 to 500 Vac 50/60 Hz
Rated Voltage Rated Frequency
Three-phase (CIMR-U4E/4W) 380 to 480 Vac 50/60 Hz
Power Allowable Voltage Fluctuation -15 to 10%
Supply Allowable Frequency Fluctuation 3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage
2% or less
Unbalance
Harmonic Current Harmonic Distortion <5> 5% or less (IEEE519 compliant)
Input Power Factor <5> 0.98% or more (During rated operation)
<1> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<2> Rated input capacity is calculated with a power line voltage of 480 V 1.1.
<3> The rated output current of the drive output amps should be equal to or greater than the motor rated current.
<4> Carrier frequency is set to 4 kHz. Current derating is required in order to raise the carrier frequency.
<5> If one of the following specifications are needed, the maximum output voltage will be the equivalent to the input voltage 0.87.
Harmonic current distortion of 5% or less
Harmonic suppression guidelines compliance
Input power factor of 0.98 or more
<6> User-adjustable
394 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
A.4 Drive Specifications
Item Specification
The following control methods can be set using drive parameters:
• V/f Control (V/f)
• V/f Control with PG (V/f w/PG)
• Open Loop Vector Control (OLV)
Control Method
• Closed Loop Vector Control (CLV)
• Open Loop Vector Control for PM (OLV/PM)
• Advanced Open Loop Vector Control for PM (AOLV/PM)
• Closed Loop Vector Control for PM (CLV/PM)
Frequency Control Range 0.01 to 400 Hz
Frequency Accuracy Digital input: within ±0.01% of the max output frequency (-10°C to +40°C)
(Temperature Fluctuation) Analog input: within ±0.1% of the max output frequency (25°C ±10°C)
Digital inputs: 0.01 Hz
Frequency Setting Resolution
Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Output Frequency Resolution 0.001 Hz
Main speed frequency reference: DC -10 to +10 V (20 k), DC 0 to +10 V (20 k), 4 to 20 mA (250 ), 0 to 20 mA (250 ),
Frequency Setting Signal
Main speed reference: Pulse train input (max. 32 kHz)
V/f, V/f w/PG: 150% at 3 Hz
OLV: 200% at 0.3 Hz <1>
Starting Torque
CLV, AOLV/PM, CLV/PM: 200% at 0.0 min-1 <1>
Control OLV/PM: 100% at 3 Hz
Characteristics V/f, V/f w/PG: 1:40
OLV: 1:200
Speed Control Range CLV, CLV/PM: 1:1500
OLV/PM: 1:20
AOLV/PM: 1:100
Speed Control Accuracy OLV: 0.2% (25°C ±10°C), CLV: 0.02% (25°C ±10°C) <2>
OLV: 10 Hz (25°C ±10°C)
Speed Response
CLV: 250 Hz (25°C ±10°C)
Torque Limit Parameters setting allow separate limits in four quadrants (available in OLV, CLV, AOLV/PM, CLV/PM)
Accel/Decel Time 0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Braking Torque Same value as overload tolerance
V/f Characteristics User-selected programs and V/f preset patterns possible
Torque Control, Droop Control, Speed/torque Control Switching, Feed Forward Control, Zero Servo Function, Momentary
Power Loss Ride-Thru, Speed Search, Synchronous Transfer with Commercial Power Supply, Overtorque/Undertorque
Detection, Torque Limit, 17 Step Speed (max), Accel/decel Switch, S-curve Accel/decel, 3-wire Sequence, Auto-tuning
(rotational, stationary tuning), Dwell, Cooling Fan on/off Switch, Slip Compensation, Torque Compensation, Frequency Jump,
Main Control Functions
Upper/lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, PID Control (with sleep function), Energy
Saving Control, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Fault Restart, Application Presets,
DriveWorksEZ (customized function), Removable Terminal Block with Parameter Backup Function, Online Tuning,
Overexcitation Deceleration, Inertia (ASR) Tuning, High Frequency Injection, etc.
Power Supply Regeneration Available
Motor Protection Electronic thermal overload relay
Momentary Overcurrent Protection Drive stops when output current reaches about 200% of the rated current
Overload Protection Drive stops after 60 s at 150% of rated Heavy Duty output current <3>
200 V class: Stops when input voltage exceeds approx. 315 V
Overvoltage Protection
400 V class: Stops when input voltage exceeds approx. 630 V
Protection 200 V class: Stops when input voltage falls below approx. 150 V
Functions Undervoltage Protection
400 V class: Stops when input voltage falls below approx. 300 V
Momentary Power Loss Ride-Thru Immediately stop after 2 ms or longer power loss. <4> Continuous operation during power loss than 2 s (standard) <5>
Heatsink Overheat Protection Thermistor
Stall Prevention Stall Prevention is available during acceleration, deceleration, and during run.
Ground Protection Electronic circuit protection <6>
Charge LED of Capacitor for Control
Remains lit until control power supply voltage falls below 50 V
Power Supply
Area of Use Indoors
Ambient Temperature IP20/NEMA Type 1 enclosure: -10C to +40C, IP00 enclosure: -10C to +50C
Specifications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 395
A.4 Drive Specifications
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> May be shorter due to load conditions and motor speed.
<5> A separate Momentary Power Loss Ride-Thru Unit is required for the drives if the application needs to continue running during a momentary
power loss up to 2 s.
<6> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<7> Up to 3000 m with output current and voltage derating. Refer to Altitude Derating on page 399 for details.
<8> Reattaching the top protective cover and bottom cover on an IP00 enclosure drive may convert this drive to a NEMA Type 1 conformity.
396 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
A.5 Drive Watt Loss Data
Specifications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 397
A.6 Drive Derating Data
100%
90%
80%
70%
common_
TMonly
0 4 kHz 6 kHz 8 kHz 10 kHz
398 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
A.6 Drive Derating Data
Temperature Derating
To ensure the maximum performance life, the drives output current must be derated like shown in Figure A.2 when the
drive is installed in areas with high ambient temperature. In order to ensure reliable drive overload protection, the
parameters L8-12 and L8-35 must also be set according to the installation conditions.
Parameter Settings
0: IP00 Enclosure
Drive operation between -10C and 50C allows 100% continuous current without derating.
2: NEMA Type 1 Enclosure
Drive operation between -10C and 40C allows 100% continuous current without derating. Operation between 40C
and 50C requires output current derating.
3: External Heatsink Installation, Finless Drive
Drive operation between -10C and 40C allows 100% continuous current without derating. Operation between 40C
and 50C requires output current derating.
Figure A.2
85
70
55
common_
L8-12
TMonly
0
-10 30 40 50 (Ambient temp: °C)
Altitude Derating
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m both the drive
rated voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m. Specifications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 399
A.6 Drive Derating Data
400 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Appendix: B
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 401
B.1 Understanding the Parameter Table
V/f Parameter is available when operating the drive with V/f Control.
V/f w/PG Parameter is available when operating the drive with V/f with PG Control.
OLV Parameter is available when operating the drive with Open Loop Vector.
CLV Parameter is available when operating the drive with Closed Loop Vector.
OLV/PM Parameter is available when operating the drive with Open Loop Vector for PM motors.
AOLV/PM Parameter is available when operating the drive with Advanced Open Loop Vector for PM motors.
CLV/PM Parameter is available when operating the drive with Closed Loop Vector for PM motors.
Motor 2 Refers to a second motor when the drive is operating two motors. Switch between these motors using the multi-function input terminals.
Note: If a parameter is not available in a certain control mode, the symbol for that control mode is grayed out.
402 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.2 Parameter Groups
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 403
B.3 Parameter Table
A1-00 0: English
(100H) 1: Japanese
Default: 0
2: German
Language Selection Min: 0 138
3: French
Max: 7
4: Italian
<3>
5: Spanish
6: Portuguese
7: Chinese
A1-01 common_
(101H) All Modes TMonly Default: 2
Access Level Selection 0: View and set A1-01 and A1-04. U- parameters can also be viewed. Min: 0 138
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32) Max: 2
<2> 2: Advanced Access (access to view and set all parameters)
common_
All Modes TMonly
0: V/f Control
A1-02 1: V/f Control with PG Default: 0
(102H) Control Method Selection 2: Open Loop Vector Control Min: 0 138
<3> 3: Closed Loop Vector Control Max: 7
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
common_
All Modes TMonly
0: No initialization Default: 0
A1-03
Initialize Parameters 1110: User Initialize (parameter values must be stored using parameter o2-03) Min: 0 139
(103H)
2220: 2-wire initialization Max: 5550
3330: 3-wire initialization
5550: oPE04 error reset
A1-04
Password common_
Default: 0000
(104H) All Modes TMonly
Min: 0000 140
A1-05 When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
Password Setting Max: 9999
(105H) through A1-03, A1-06, A1-07, and A2-01 through A2-32 cannot be changed.
common_
All Modes TMonly
0: General-purpose
1: Water supply pump
Default: 0
A1-06 2: Conveyor
Application Preset Min: 0 142
(127H) 3: Exhaust fan
Max: 7
4: HVAC fan
5: Air compressor
6: Hoist
7: Crane (Traveling)
common_
All Modes TMonly Default: 0
A1-07
DriveWorksEZ Function Selection 0: DWEZ disabled Min: 0 142
(128H)
1: DWEZ enabled Max: 2
2: Digital input (enabled when H1- = 9F)
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<3> The parameter setting is not reset to the default value when A1-03 is used to initialize the drive.
404 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
Enabled when an input terminal set for “External reference” (H1- = 2) closes.
Default: 0
b1-15 0: Digital operator
Frequency Reference Selection 2 Min: 0 152
(1C4H) 1: Terminals (analog input terminals)
Max: 4
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
common_
All Modes TMonly
Enabled when a terminal set for “External reference” (H1- = 2) closes. Default: 0
Parameter List
b1-16
Run Command Selection 2 0: Digital operator Min: 0 152
(1C5H)
1: Digital input terminals Max: 3
2: MEMOBUS/Modbus communications
3: Option card
common_
All Modes Default: 0
TMonly
b1-17
Run Command at Power Up Min: 0 152
(1C6H) 0: Disregarded. A new Run command needs to be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command is already enabled.
Max: 1
B
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 405
B.3 Parameter Table
406 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 407
B.3 Parameter Table
b4-06 Sets the length of the delay time for contact outputs to open or close for the related functions set Min: 0 ms 163
H2-02 OFF Delay Time in H2-. Max: 65000 ms
(B33H)
b4-07
H2-03 ON Delay Time
(B34H)
b4-08
H2-03 OFF Delay Time
(B35H)
0: Disabled
1: Enabled (PID output becomes output frequency reference, deviation D controlled)
2: Enabled (PID output becomes output frequency reference, feedback D controlled)
3: Enabled (PID output added to frequency reference, deviation D controlled) Default: 0
b5-01
PID Function Setting 4: Enabled (PID output added to frequency reference, feedback D controlled) Min: 0 167
(1A5H)
5: Mode that is compatible with setting 1 of similar product from a past line Max: 8 <6>
6: Mode that is compatible with setting 2 of similar product from a past line
7: Mode that is compatible with setting 3 of similar product from a past line
8: Mode that is compatible with setting 4 of similar product from a past line
Note: If the used drive is replaced with Varispeed F7 inverter or a similar product from a past
line, use settings 5 to 8 instead of settings 1 to 4.
b5-02
common_ Default: 1.00
(1A6H) All Modes TMonly
Proportional Gain Setting (P) Min: 0.00 167
Sets the proportional gain of the PID controller. Max: 25.00
b5-03
common_ Default: 1.0 s
(1A7H) All Modes TMonly
Integral Time Setting (I) Min: 0.0 s 167
Sets the integral time for the PID controller. Max: 360.0 s
b5-04 common_
All Modes Default: 100.0%
(1A8H) TMonly
Integral Limit Setting Min: 0.0% 167
Sets the maximum output possible from the integrator as a percentage of the maximum output
Max: 100.0%
frequency.
b5-05
common_ Default: 0.00 s
(1A9H) All Modes TMonly
Derivative Time (D) Min: 0.00 s 167
Sets D control derivative time. Max: 10.00 s
b5-06 common_
All Modes TMonly Default: 100.0%
(1AAH)
PID Output Limit Min: 0.0% 168
Sets the maximum output possible from the entire PID controller as a percentage of the
Max: 100.0%
maximum output frequency.
b5-07 common_
All Modes Default: 0.0%
(1ABH) TMonly
PID Offset Adjustment Min: -100.0% 168
Applies an offset to the PID controller output. Set as a percentage of the maximum output
Max: 100.0%
frequency.
b5-08
common_ Default: 0.00 s
(1ACH) All Modes TMonly
PID Primary Delay Time Constant Min: 0.00 s 168
Sets a low pass filter time constant on the output of the PID controller. Max: 10.00 s
408 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
common_
All Modes TMonly Default: 0
b5-11
PID Output Reverse Selection 0: Negative PID output triggers zero limit. Min: 0 168
(1AFH)
1: Rotation direction reverses with negative PID output. Max: 1
When using setting 1, make sure reverse operation is permitted by parameter b1-04.
common_
All Modes TMonly
common_
All Modes TMonly
Default: <5>
b5-39 0: No decimal places
PID Setpoint Display Digits Min: 0 172
(1FFH) 1: One decimal places
Max: 3
2: Two decimal places
3: Three decimal places
common_
All Modes Default: 0
B
b5-40 Frequency Reference Monitor TMonly
Min: 0 172
(17FH) Content during PID 0: Display the frequency reference (U1-01) after PID compensation has been added.
Max: 1
1: Display the frequency reference (U1-01) before PID compensation has been added.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 409
B.3 Parameter Table
410 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 411
B.3 Parameter Table
C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip compensation, torque
compensation, and carrier frequency selections.
C1: Acceleration and Deceleration Times
C1-02
common_
(201H) All Modes TMonly
Deceleration Time 1 178
Sets the time to decelerate from maximum frequency to 0.
C1-03
common_
(202H) All Modes TMonly
Acceleration Time 2 178
Sets the time to accelerate from 0 to maximum frequency.
C1-04
common_
(203H) All Modes TMonly
Deceleration Time 2 178
Sets the time to decelerate from maximum frequency to 0.
C1-05
common_ Default: 10.0 s
(204H) Acceleration Time 3 (Motor 2 All Modes TMonly Min: 0.0 s 178
Accel Time 1)
Sets the time to accelerate from 0 to maximum frequency. Max: 6000.0 s <12>
C1-06
common_
(205H) Deceleration Time 3 (Motor 2 All Modes TMonly 178
Decel Time 1)
Sets the time to decelerate from maximum frequency to 0.
C1-07
common_
(206H) Acceleration Time 4 (Motor 2 All Modes TMonly 178
Accel Time 2)
Sets the time to accelerate from 0 to maximum frequency.
C1-08
common_
(207H) Deceleration Time 4 (Motor 2 All Modes TMonly 178
Decel Time 2)
Sets the time to decelerate from maximum frequency to 0.
C1-09 common_
(208H) All Modes TMonly
Fast Stop Time 179
Sets the time for the Fast Stop function.
common_
All Modes TMonly Default: 1
C1-10
Accel/Decel Time Setting Units Min: 0 179
(209H) 0: 0.01 s (0.00 to 600.00 s)
Max: 1
1: 0.1 s (0.0 to 6000.0 s)
common_ Default: <10>
C1-11 Accel/Decel Time Switching All Modes TMonly
Min: 0.0 Hz 180
(20AH) Frequency
Sets the frequency to switch between accel/decel time settings Max: 400.0 Hz
<10> Default setting is determined by the control mode (A1-02).
<12> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting
range becomes 0.00 to 600.00 seconds.
412 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Max: 200.0%
Sets torque compensation at forward start as a percentage of motor torque.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 413
B.3 Parameter Table
414 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Inertia Auto-Tuning.
1: 4.0 kHz
Default: <4>
C6-02 2: 6.0 kHz
Carrier Frequency Selection Min: 1 190
(224H) 3: 8.0 kHz
Max: F
4: 10.0 kHz
F: User defined (determined by C6-03 through C6-05)
Note: Setting F is not available in AOLV/PM control mode (A1-02 = 6).
common_
All Modes TMonly Default: <13>
C6-03
Carrier Frequency Upper Limit C6-04 and C6-05 are available only in V/f and V/f w/PG control modes. Min: 4.0 kHz 190
(225H)
Determines the upper and lower limits for the carrier frequency. Max: 10.0 kHz
In OLV, C6-03 determines the upper limit of the carrier frequency.
Carrier Frequency
Default: <13>
C6-04
Carrier Frequency Lower Limit Min: 4.0 kHz 190
Parameter List
(226H) C6-03
Max: 10.0 kHz
C6-04 Output Frequency
× (C6-05)
Output Default: <13>
C6-05 Carrier Frequency Proportional
E1-04 Frequency Min: 0 190
(227H) Gain
Max Output Max: 99
Frequency
B
V/f V/f w/PG OLV CLV common_
TMonly Default: 0
C6-09 Carrier Frequency during OLV/PM AOLV/PM CLV/PM Min: 0 191
(22BH) Rotational Auto-Tuning
0: Carrier Frequency = 4 kHz <74> Max: 1
1: Setting value for C6-03 <75>
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 415
B.3 Parameter Table
<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<13> Default setting value is dependent on the carrier frequency selection (C6-02).
<74> In PM control mode, this value is 4 kHz.
<75> In PM control mode, this value is the carrier frequency that is set in C6-02.
416 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
d: Reference Settings
Reference parameters are used to set the various frequency reference values during operation.
d1: Frequency Reference
d1-02
(281H)
Frequency Reference 2 192
d1-03
(282H)
Frequency Reference 3 192
d1-04
(283H)
Frequency Reference 4 192
d1-05
(284H)
Frequency Reference 5 192
d1-06
(285H)
Frequency Reference 6 192
d1-07
(286H)
Frequency Reference 7 192
d1-08
(287H)
Frequency Reference 8 common_ 192
All Modes TMonly Default: 0.00 Hz
Min: 0.00 Hz
Sets the frequency reference for the drive. Setting units are determined by parameter o1-03.
d1-09 Max: 400.00 Hz
Note: The value set to o1-03 is changed to 1 and the unit is changed to percentage automatically
(288H) <20> <63>
Frequency Reference 9 when A1-02 is set to 6 or 7 192
d1-10
(28BH)
Frequency Reference 10 192
d1-11
(28CH)
Frequency Reference 11 192
d1-12
(28DH)
Frequency Reference 12 192
d1-13
(28EH)
Frequency Reference 13 192
d1-14
(28FH)
Frequency Reference 14 192
d1-15
(290H)
Frequency Reference 15 192
d1-16
(291H)
Parameter List
<20> Range upper limit is determined by the maximum output frequency (E1-04) and the upper limit of the frequency reference (d2-01). B
<63> The value of o1-03 is changed to 1 and the unit is also changed to a percentage (%) when the control mode is set to CLV/PM or AOLV/PM.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 417
B.3 Parameter Table
418 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Enables or disables the conversion of frequency reference or PID output value into
Default: 0
d4-11 bi-directional internal frequency reference.
Bi-Directional Output Selection Min: 0 200
(2B7H) 0: Disabled - Operation in the selected direction between 0 to 100% frequency reference or PID
Max: 1
output
1: Enabled - Operation in reverse direction when frequency reference or PID output < 50%, else
operation in the selected direction.
common_ Default: 1.00
d4-12 All Modes TMonly
Stop Position Gain Min: 0.50 200
(2B8H)
Sets the gain used by the simple positioning stop function in order to fine adjust the position. Max: 2.55
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 419
B.3 Parameter Table
E: Motor Parameters
E1: V/f Pattern for Motor 1
420 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
<14> Default setting value is dependent on the motor code set to E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<21> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<27> When E1-13 (Base Voltage) is set to 0.0, output voltage is controlled with E1-05 (Maximum Voltage) = E1-13. When Auto-Tuning is
performed, E1-05 and E1-13 are automatically set to the same value.
<29> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
<30> The setting value is F in OLV.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 421
B.3 Parameter Table
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<50> When E3-13 (Motor 2 Base Voltage) is set to 0.0, output voltage is controlled with E3-05 (Motor 2 Max. Voltage) = E3-13. When
Auto-Tuning is performed, E3-05 and E3-13 are automatically set to the same value.
422 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
common_
Motor d-Axis Inductance (Ld) TMonly
(32EH) OLV/PM AOLV/PM CLV/PM Min: 0.00 mH 217
(for PM Motors)
<3> Max: 300.00 mH
Sets the d-axis inductance for the PM motor.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 423
B.3 Parameter Table
F: Option Settings
F parameters are used to program the drive for PG feedback from the motor and to function with option cards.
F1: PG Speed Control Card Settings (PG-B3/PG-F3/PG-RT3/PG-X3)
Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 are used to set up a PG option card plugged into
option connector CN5-C of the drive. They include “PG 1” in the parameter name.
Parameters F1-31 through F1-37 are used to set up a PG option card plugged into option connector CN5-B of the drive.
They include “PG 2” in the parameter name.
Other parameters in the F1 group are used to set operation for PG options plugged into connector CN5-C and CN5-B.
424 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
F1-31
V/f V/f w/PG OLV CLV common_ Default: 1024 ppr B
PG 2 Pulses Per Revolution TMonly Min: 1 ppr 218
(3B0H) OLV/PM AOLV/PM CLV/PM
Max: 60000 ppr
Sets the number of pulses for a PG option card connected to port CN5-B.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 425
B.3 Parameter Table
F2-03
common_ Default: 0.0%
(369H) All Modes TMonly
Analog Input Option Card Bias Min: -999.9% 222
Sets the bias for the input signal to the analog card. Max: 999.9%
426 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
Default: 0
F3-01 Digital Input Option Card Input 5: BCD, 0.01 Hz units
Min: 0 222
(390H) Selection 6: BCD customized setting (5 digit), 0.02 Hz units
Max: 7
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
common_
All Modes TMonly Default: 2
F3-03 Digital Input Option DI-A3 Data
0: 8 bit Min: 0 222
(3B9H) Length Selection
1: 12 bit Max: 2
2: 16 bit
common_
All Modes TMonly Default: 103
F4-03
Terminal V2 Monitor Selection Min: 000 223
(393H) Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
Max: 999
the desired U- monitor. Some U parameters are available only in certain control modes.
F4-04
common_ Default: 50.0%
(394H) All Modes TMonly
Terminal V2 Monitor Gain Min: -999.9% 223
Sets the gain for voltage output via terminal V2. Max: 999.9%
F4-05
common_ Default: 0.0%
(395H) All Modes TMonly
Terminal V1 Monitor Bias Min: -999.9% 223
Sets the amount of bias added to the voltage output via terminal V1. Max: 999.9%
F4-06
common_ Default: 0.0%
(396H) All Modes TMonly
Terminal V2 Monitor Bias Min: -999.9% 223
Sets the amount of bias added to the voltage output via terminal V2. Max: 999.9%
Default: 0
F4-07
Terminal V1 Signal Level common_ Min: 0 223
(397H) All Modes TMonly Max: 1
0: 0 to 10 V Default: 0
F4-08 1: -10 to 10 V
Terminal V2 Signal Level Min: 0 223
(398H)
Max: 1
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 427
B.3 Parameter Table
428 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
MECHATROLINK-II
Default: 0
F6-21 0: 32 byte
MECHATROLINK Frame Size Min: 0 –
(36CH) 1: 17 byte
Max: 1
MECHATROLINK-III
0: 64 byte
1: 32 byte
MECHATROLINK-II
Default: 21
Min: 20
common_
F6-20 MECHATROLINK Station All Modes TMonly Max: 3FH
–
(36BH) Address MECHATROLINK-III
Sets the station address when the MECHATROLINK option has been installed.
Default: 21
Min: 03
Max: EFH
common_
All Modes TMonly Default: 0
F6-22
MECHATROLINK Link Speed Min: 0 –
(36DH) 0: 10 Mbps
Max: 1
1: 4 Mbps
common_ Default: 0
F6-23 MECHATROLINK Monitor All Modes TMonly Min: 0 –
(36EH) Selection (E)
Sets the MECHATROLINK monitor (E). Max: FFFFH
common_ Default: 0
F6-24 MECHATROLINK Monitor All Modes TMonly Min: 0 –
(36FH) Selection (F)
Sets the MECHATROLINK monitor (F). Max: FFFFH
common_
All Modes TMonly
Operation Selection at Default: 1
F6-25 0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
MECHATROLINK Watchdog Min: 0 –
(3C9H) 1: Coast to stop.
Timer Error (E5) Max: 3
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
common_ Default: 2
F6-26 MECHATROLINK bUS Errors All Modes TMonly Min: 2 –
(3CAH) Detected
Sets the number of option communication errors (bUS). Max: 10
common_ Default: 0
F6-30 All Modes TMonly
PROFIBUS-DP Node Address Min: 0 –
(3CBH)
Sets the node address. Max: 125
common_
All Modes TMonly Default: 0
F6-31 PROFIBUS-DP Clear Mode
Min: 0 –
(3CCH) Selection 0: Resets drive operation with a Clear mode command.
Max: 1
1: Maintains the previous operation state when Clear mode command is given.
common_
All Modes TMonly Default: 0
F6-32 PROFIBUS-DP Data Format
Min: 0 –
(3CDH) Selection 0: PPO Type
Max: 1
1: Conventional
common_ Default: 0
F6-35 All Modes TMonly
CANopen Node ID Selection Min: 0 –
(3D0H)
Sets the node address. Max: 126
common_
All Modes TMonly
0: Auto-detection
1: 10 kbps
2: 20 kbps Default: 6
F6-36
CANopen Communication Speed 3: 50 kbps Min: 0 –
(3D1H)
4: 125 kbps Max: 8
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
common_ Default: 0
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 429
B.3 Parameter Table
430 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 431
B.3 Parameter Table
H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
H1: Multi-Function Digital Inputs
common_
All Modes TMonly
0 3-wire Sequence 227
Closed: Reverse rotation (only if the drive is set up for 3-wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop command.
common_
All Modes TMonly
1 LOCAL/REMOTE Selection Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2 (b1-01, b1-02 or 228
b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from the digital operator.
common_
All Modes TMonly
2 External Reference 1/2 Selection 228
Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)
3 Multi-Step Speed Reference 1 common_ 228
All Modes TMonly
4 Multi-Step Speed Reference 2 228
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
5 Multi-Step Speed Reference 3 terminals will create a multi-step speed sequence using the frequency references set in d1-01 through d1-08. 228
common_
All Modes TMonly
6 Jog Reference Selection 229
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference sources.
common_
All Modes TMonly
7 Accel/Decel Time Selection 1 229
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set in C1-03, C1-04).
common_
All Modes TMonly
8 Baseblock Command (N.O.) 229
Closed: No drive output
common_
All Modes TMonly
9 Baseblock Command (N.C.) 229
Open: No drive output
common_
All Modes TMonly
A Accel/Decel Ramp Hold 229
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the output frequency.
common_
All Modes TMonly
B Drive Overheat Alarm (oH2) 229
Closed: Closes when an oH2 alarm occurs
common_
All Modes TMonly
C Analog Terminal Input Selection 229
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
432 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
The drive accelerates when the Up command terminal closes, and decelerates when the Down command closes.
When both terminals are closed or both are open, the drive holds the frequency reference. The Up and Down
11 Down Command commands must always be used in conjunction with one another. 230
common_
All Modes TMonly
12 Forward Jog 231
Closed: Runs forward at the Jog frequency d1-17.
common_
All Modes TMonly
13 Reverse Jog 231
Closed: Runs reverse at the Jog frequency d1-17.
common_
All Modes TMonly
14 Fault Reset 231
Closed: Resets faults if the cause is cleared and the Run command is removed.
common_
All Modes TMonly
15 Fast Stop (N.O.) 231
Closed: Decelerates at the Fast Stop time set to C1-09.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 433
B.3 Parameter Table
434 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Sets the units for the output signal when one of the multi-function terminals is set to power
consumption pulse output (H2-01, H2-02, or H2-03 = 39). Outputs a 200 ms pulse signal when Default: 1
H2-06 Power Consumption Output Unit
the watt-hour counter increases by the units selected. Min: 1 246
(437H) Selection
1: 1 kWh units Max: 4
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
common_
All Modes Default: 1
TMonly
H2-07
Memobus Regs1 Address Select Min: 1 246
(B3AH) Sets the addresses of the MEMOBUS/Modbus registers from which data will be sent to contact
Max: 1FFFH
outputs 62 and 162.
common_
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 435
B.3 Parameter Table
common_
All Modes TMonly
0 During Run 237
Closed: A Run command is active or voltage is output.
common_
All Modes TMonly
Open: Output speed is greater than or equal to the value of E1-09 (Minimum Output Frequency) or b2-01 (DC Injection
1 Zero Speed 238
Braking Start Frequency).
Closed: Output frequency is less than the value of E1-09 (Minimum Output Frequency) or b2-01 (DC Injection Braking
Start Frequency).
common_
All Modes TMonly
2 Speed Agree 1 238
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
common_
All Modes TMonly
3 User-set Speed Agree 1 238
Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
common_
All Modes TMonly
4 Frequency Detection 1 239
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
common_
All Modes TMonly
5 Frequency Detection 2 239
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
common_
All Modes TMonly
6 Drive Ready 240
Closed: Power up is complete and the drive is ready to accept a Run command.
common_
All Modes TMonly
7 During Power Supply Voltage Fault 240
Closed: The main circuit DC voltage dropped to the control circuit undervoltage (Uv1) detection level.
common_
All Modes TMonly
8 During Baseblock (N.O.) 240
Closed: Drive has entered the baseblock state (no output voltage).
common_
All Modes TMonly
9 Frequency Reference Source 240
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
common_
All Modes TMonly
A Run Command Source 240
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
common_
B Torque Detection 1 (N.O.) All Modes TMonly 240
Closed: An overtorque or undertorque situation has been detected.
common_
All Modes TMonly
C Frequency Reference Loss 241
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below 10% of the reference within 400 ms.
common_
All Modes TMonly
E Fault 241
Closed: Fault occurred (this excludes faults CPF00 and CPF01).
common_
All Modes TMonly
F Through Mode 241
Select this setting when the terminal is not used or when using the terminal in the pass-through mode.
common_
All Modes TMonly
10 Minor Fault 241
Closed: An alarm has been triggered.
common_
All Modes TMonly
11 Fault Reset Command Active 241
Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the
digital operator’s RESET key has been pressed.
common_
All Modes TMonly
12 Timer Output 241
Closed: Timer output.
common_
All Modes TMonly
13 Speed Agree 2 241
Closed: When drive output frequency equals the frequency reference ±L4-04.
common_
All Modes TMonly
14 User-set Speed Agree 2 242
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
common_
All Modes TMonly
15 Frequency Detection 3 242
Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04.
common_
All Modes TMonly
16 Frequency Detection 4 242
Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04.
common_
All Modes TMonly
17 Torque Detection 1 (N.C.) 240
Open: Overtorque or undertorque has been detected.
436 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
37 During Frequency Output Open: No frequency output from drive if stopped, with baseblock, or with DC injection braking during initial 244
excitation.
Closed: Drive is outputting a frequency.
common_
All Modes TMonly
38 Drive Enabled 245
Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A)
common_
All Modes TMonly
39 Power Consumption Pulse Output 245
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
common_
All Modes TMonly
3A Regenerated Power Pulse Output 245
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 437
B.3 Parameter Table
H3-04
common_ Default: 0.0%
(412H) All Modes TMonly
Terminal A1 Bias Setting Min: -999.9% 247
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1. Max: 999.9%
common_
All Modes TMonly Default: 0
H3-05 Terminal A3 Signal Level
Min: 0 248
(413H) Selection 0: 0 to 10 V
Max: 1
1: -10 to 10 V
common_ Default: 2
H3-06 All Modes TMonly
Terminal A3 Function Selection Min: 0 248
(414H)
Sets the function of terminal A3. Max: 32
H3-07
common_ Default: 100.0%
(415H) All Modes TMonly
Terminal A3 Gain Setting Min: -999.9% 248
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3. Max: 999.9%
H3-08
common_ Default: 0.0%
(416H) All Modes TMonly
Terminal A3 Bias Setting Min: -999.9% 248
Sets the level of the input value selected in H3-06 when 0 V is input at terminal A3. Max: 999.9%
common_
All Modes TMonly
0: 0 to 10 V Default: 2
H3-09 Terminal A2 Signal Level
1: -10 to 10 V Min: 0 248
(417H) Selection
2: 4 to 20 mA Max: 3
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
438 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
H3-12
common_ Default: 0.0%
(41AH) All Modes TMonly
Terminal A2 Bias Setting Min: -999.9% 249
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2. Max: 999.9%
Determines which of the analog input terminals will be enabled or disabled when a digital input
programmed for “Analog input enable” (H1- = C) is activated. The terminals other than the
one set as the target are not influenced by input signals.
Default: 7
H3-14 Analog Input Terminal Enable 1: Terminal A1 only
Min: 1 249
(41CH) Selection 2: Terminal A2 only
Max: 7
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
common_ Default: 0
H3-16 All Modes TMonly
Terminal A1 Offset Min: -500 249
(2F0H)
Adds an offset when the analog signal to terminal A1 is at 0 V. Max: 500
common_ Default: 0
H3-17 All Modes TMonly
Terminal A2 Offset Min: -500 249
(2F1H)
Adds an offset when the analog signal to terminal A2 is at 0 V. Max: 500
common_ Default: 0
H3-18 All Modes TMonly
Terminal A3 Offset Min: -500 249
(2F2H)
Adds an offset when the analog signal to terminal A3 is at 0 V. Max: 500
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 439
B.3 Parameter Table
H4-03
common_ Default: 0.0%
(41FH) Multi-Function Analog Output All Modes TMonly Min: -999.9% 252
Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the selected monitor value. Max: 999.9%
common_
All Modes TMonly
Default: 103
H4-04 Multi-Function Analog Output
Selects the data to be output through multi-function analog output terminal AM. Min: 000 252
(420H) Terminal AM Monitor Selection
Set the desired monitor parameter to the digits available in U-. For example, enter “103” Max: 999
for U1-03.
H4-05
common_ Default: 50.0%
(421H) Multi-Function Analog Output All Modes TMonly Min: -999.9% 252
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value. Max: 999.9%
H4-06
common_ Default: 0.0%
(422H) Multi-Function Analog Output All Modes TMonly Min: -999.9% 252
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the selected monitor value. Max: 999.9%
common_
All Modes TMonly
Multi-Function Analog Output Default: 0
H4-07
Terminal FM Signal Level 0: 0 to 10 V Min: 0 253
(423H)
Selection 1: -10 to 10 V Max: 2
2: 4 to 20 mA
440 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
0: 1200 bps
1: 2400 bps
2: 4800 bps
Default: 3
H5-02 3: 9600 bps
Communication Speed Selection Min: 0 492
(426H) 4: 19200 bps
Max: 8
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
common_
All Modes TMonly
Default: 0
H5-03 0: No parity
Communication Parity Selection Min: 0 492
(427H) 1: Even parity
Max: 2
2: Odd parity
Cycle power for the setting to take effect.
common_
All Modes TMonly
Default: 3
H5-04 Stopping Method After 0: Ramp to stop
Min: 0 492
(428H) Communication Error (CE) 1: Coast to stop
Max: 3
2: Fast Stop
3: Alarm only
common_
All Modes TMonly Default: 1
H5-05 Communication Fault Detection
Min: 0 493
(429H) Selection 0: Disabled
Max: 1
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
common_ Default: 5 ms
H5-06 All Modes TMonly
Drive Transmit Wait Time Min: 5 ms 493
(42AH)
Set the wait time between receiving and sending data. Max: 65 ms
common_
All Modes TMonly Default: 1
H5-07
RTS Control Selection Min: 0 493
(42BH) 0: Disabled. RTS is always on.
Max: 1
1: Enabled. RTS turns on only when sending.
common_
All Modes TMonly Default: 2.0 s
H5-09 Communication Fault Detection
Min: 0.0 s 493
(435H) Time Sets the time required to detect a communications error. Adjustment may be needed when
Max: 10.0 s
networking several drives.
common_
All Modes TMonly Default: 0
H5-10 Unit Selection for MEMOBUS/
Min: 0 494
(436H) Modbus Register 0025H 0: 0.1 V units
Max: 1
1: 1 V units
common_
All Modes TMonly Default: 0
H5-11 Communications ENTER Function
Min: 0 494
(43CH) Selection 0: Drive requires an Enter command before accepting any changes to parameter settings.
Max: 1
1: Parameter changes are activated immediately without the Enter command.
common_
All Modes TMonly Default: 0
H5-12
Run Command Method Selection Min: 0 494
(43DH) 0: FWD/Stop, REV/Stop
Max: 1
1: Run/Stop, FWD/REV
common_
All Modes TMonly
There is normally no need to change this parameter from the default value. Default: 0
H5-17 Operation Selection when Unable
Selects operation when an attempt is made to write data into EEPROM by MEMOBUS/Modbus Min: 0 494
(11A1H) to Write into EEPROM
communications, when writing into EEPROM is not possible. Max: 1
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 441
B.3 Parameter Table
H6-03 common_
All Modes Default: 100.0%
(42EH) TMonly
Pulse Train Input Gain Min: 0.0% 255
Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is
Max: 1000.0%
input.
H6-04
common_ Default: 0.0%
(42FH) All Modes TMonly
Pulse Train Input Bias Min: -100.0% 255
Sets the level of the value selected in H6-01 when 0 Hz is input. Max: 100.0%
H6-05
common_ Default: 0.10 s
(430H) All Modes TMonly
Pulse Train Input Filter Time Min: 0.00 s 255
Sets the pulse train input filter time constant. Max: 2.00 s
H6-06 common_
All Modes Default: 102
(431H) TMonly
Pulse Train Monitor Selection Min: 000 256
Select the pulse train monitor output function (value of the - part of U-).
Max: 809
Example: To select U5-01, set “501”.
H6-07 common_
All Modes Default: 1440 Hz
(432H) TMonly
Pulse Train Monitor Scaling Min: 0 Hz 256
Sets the terminal MP output signal frequency when the monitor value is 100%. As an example,
Max: 32000 Hz
have the pulse train monitor output equal the output frequency, set H6-06 to 102 and H6-07 to 0.
common_
All Modes TMonly Default: 0.5 Hz
H6-08 Pulse Train Input Minimum
Min: 0.1 Hz 256
(43FH) Frequency Sets the minimum frequency for the pulse train input to be detected. Enabled when H6-01 = 0,
Max: 1000.0 Hz
1, or 2.
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, torque limits, and other types of hardware protection.
L1: Motor Protection
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10 Default: <10>
L1-01 Motor Overload Protection
3: Vector motor with a speed range of 1:100 Min: 0 257
(480H) Selection
4: PM motor with variable torque Max: 6
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when multiple motors are used, even if
overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
common_ Default: 1.0 min
L1-02 All Modes TMonly
Motor Overload Protection Time Min: 0.1 min 259
(481H)
Sets the motor thermal overload protection (oL1) time. Max: 5.0 min
common_
All Modes TMonly
Sets operation when the motor temperature analog input (H3-02, H3-06, or H3-10 = E) exceeds
Default: 3
L1-03 Motor Overheat Alarm Operation the oH3 alarm level.
Min: 0 261
(482H) Selection (PTC input) 0: Ramp to stop
Max: 3
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (“oH3” will flash)
common_
All Modes TMonly
Sets stopping method when the motor temperature analog input (H3-02, H3-06, or H3-10 = E) Default: 1
L1-04 Motor Overheat Fault Operation
exceeds the oH4 fault level. Min: 0 261
(483H) Selection (PTC input)
0: Ramp to stop Max: 2
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
common_ Default: 0.20 s
L1-05 Motor Temperature Input Filter All Modes TMonly Min: 0.00 s 261
(484H) Time (PTC input)
Adjusts the filter for the motor temperature analog input (H3-02, H3-06, or H3-10 = E). Max: 10.00 s
442 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
0: Disabled
1: Enabled
General purpose. Acceleration is paused when the current is above the L3-02 setting. Default: 1
L3-01 Stall Prevention Selection during
2: Enabled Min: 0 264
(48FH) Acceleration
Intelligent Stall Prevention. Accelerate in the shortest possible time without exceeding the Max: 2
L3-02 level.
3: Enabled (Current Limit)
The acceleration rate is automatically adjusted while limiting the output current at the setting
value of the stall prevention level (L3-02). B
Note: Setting 2 is not available in OLV/PM.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 443
B.3 Parameter Table
0: Disabled
Deceleration at the active deceleration rate. An ov fault may occur.
1: General-purpose Stall Prevention Default: 1
L3-04 Stall Prevention Selection during
Deceleration is paused when the output current exceeds the Stall Prevention level. Min: 0 266
(492H) Deceleration
4: Overexcitation Deceleration Max: 6 <34>
Decelerates while increasing the motor flux.
6: Enable (Current Limit)
The deceleration rate is automatically adjusted while limiting the regeneration current at the
setting value of the stall prevention level (L3-14).
444 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
<35> The upper limit of the setting range and default setting is determined by the values set to the duty selection (C6-01) and the carrier frequency
reduction selection (L8-38).
Default: 0.0 Hz
L4-03 Speed Agreement Detection Level
Min: -400.0 Hz 269
(49BH) (+/-) common_
All Modes TMonly
Max: 400.0 Hz
L4-03 sets the frequency detection level for digital output functions H2- = 13, 14, 15, 16.
Default: <10>
L4-04 Speed Agreement Detection Width L4-04 sets the hysteresis or allowable margin for speed detection.
Min: 0.0 Hz 269
(49CH) (+/-)
Max: 20.0 Hz
common_
All Modes TMonly Default: 0
L4-05 Frequency Reference Loss
Min: 0 269
(49DH) Detection Selection 0: Stop. Drive stops when the frequency reference is lost.
Max: 1
1: Run. Drive runs at a reduced speed when the frequency reference is lost.
common_
All Modes TMonly Default: 80.0%
L4-06 Frequency Reference at Reference
Min: 0.0% 270
(4C2H) Loss Sets the percentage of the frequency reference that the drive should run with when the
Max: 100.0%
frequency reference is lost.
common_
All Modes TMonly Default: 0
L4-07
Speed Agree Detection Selection Min: 0 270
(470H) 0: No detection during baseblock.
Max: 1
1: Detection always enabled.
<10> Default setting is determined by the control mode (A1-02).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 445
B.3 Parameter Table
0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection Default: 0
L6-04
Torque Detection Selection 2 3: oL4 detection only active during speed agree, output shuts down on an oL4 fault Min: 0 272
(4A4H)
4: oL4 detection always active during run, output shuts down on an oL4 fault Max: 8
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
common_ Default: 150%
L6-05 All Modes TMonly
Torque Detection Level 2 Min: 0% 272
(4A5H) Sets the overtorque and undertorque detection level. Max: 300%
common_ Default: 0.1 s
L6-06 All Modes TMonly
Torque Detection Time 2 Min: 0.0 s 273
(4A6H)
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 2. Max: 10.0 s
common_
All Modes TMonly
This function can detect an overtorque or undertorque in a certain speed range as a result of
machine fatigue. It is triggered by a specified operation time and uses the oL1 detection settings
(L6-01 and L6-03)
0: Mechanical Weakening Detection disabled.
Default: 0
L6-08 Mechanical Weakening Detection 1: Continue running (alarm only). Detected when the speed (signed) is greater than L6-09.
Min: 0 273
(468H) Operation 2: Continue running (alarm only). Detected when the speed (not signed) is greater than L6-09.
Max: 8
3: Interrupt drive output (fault). Detected when the speed (signed) is greater than L6-09.
4: Interrupt drive output (fault). Detected when the speed (not signed) is greater than L6-09.
5: Continue running (alarm only). Detected when the speed (signed) is less than L6-09.
6: Continue running (alarm only). Detected when the speed (not signed) is less than L6-09.
7: Interrupt drive output (fault). Detected when the speed (signed) is less than L6-09.
8: Interrupt drive output (fault). Detected when the speed (not signed) is less than L6-09.
common_
All Modes TMonly Default: 110.0%
L6-09 Mechanical Weakening Detection
Min: -110.0% 273
(469H) Speed Level Sets the speed that triggers Mechanical Weakening Detection. When L6-08 is set for an
Max: 110.0%
unsigned value, the absolute value is used if the setting is negative.
common_ Default: 0.1 s
L6-10 Mechanical Weakening Detection All Modes TMonly Min: 0.0 s 274
(46AH) Time
Sets the time mechanical weakening has to be detected before an alarm or fault is triggered. Max: 10.0 s
common_ Default: 0 h
L6-11 Mechanical Weakening Detection All Modes TMonly Min: 0 h 274
(46BH) Start Time
Sets the operation time (U1-04) required before Mechanical Weakening Detection is active. Max: 65535 h
446 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
0: Disabled Default: 0
L8-07 Output Phase Loss Protection
1: Enabled (triggered by a single phase loss) Min: 0 276
(4B3H) Selection
2: Enabled (triggered when two phases are lost) Max: 2
Note: Low motor rated current in comparison to the drive rated output current may erroneously
trigger output phase loss detection. Disable this parameter in such cases.
common_
All Modes TMonly Default: <6>
L8-09 Output Ground Fault Detection
Min: 0 277
(4B5H) Selection 0: Disabled
Max: 1
1: Enabled
common_
All Modes TMonly
Default: 0
L8-10 Heatsink Cooling Fan Operation 0: Run with timer (Fan operates only during run and for L8-11 seconds after stop.)
Min: 0 277
(4B6H) Selection 1: Run always (Cooling fan operates whenever the drive is powered up.)
Max: 1
Note: The cooling fan will turn on when a Damping Resistor Overheat (doH) fault is detected
regardless of the setting value.
Default: 60 s
common_
L8-11 Heatsink Cooling Fan Off Delay All Modes TMonly
Min: 0 s 277
(4B7H) Time
Sets a delay time to shut off the cooling fan after the Run command is removed when L8-10 = 0. Max: 300 s
common_ Default: 40C
L8-12 All Modes TMonly
Ambient Temperature Setting Min: -10C 277
(4B8H)
Enter the ambient temperature. This value adjusts the oL2 detection level. Max: 50C
common_
All Modes TMonly Default: 1
L8-15 oL2 Characteristics Selection at
Min: 0 277
(4BBH) Low Speeds 0: No oL2 level reduction below 6 Hz.
Max: 1
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 447
B.3 Parameter Table
n: Special Adjustments
The n parameters are used to adjust more advanced performance characteristics such as Hunting Prevention, speed
feedback detection, and Online Tuning for motor line-to-line resistance.
n1: Hunting Prevention
448 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
common_
TMonly Default: <17>
n8-11 Induction Voltage Estimation Gain OLV/PM AOLV/PM CLV/PM Min: 0.0 285
(54AH) 2
There is normally no need to change this parameter from the default value. Max: 1000.0
Sets the gain for estimating the speed.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 449
B.3 Parameter Table
450 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Sets the units the drive should use to display the frequency reference and motor speed monitors. Default: <10>
o1-03
Digital Operator Display Selection 0: 0.01 Hz Min: 0 290
(502H)
1: 0.01% (100% = E1-04) Max: 3
2: min-1 (calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 451
B.3 Parameter Table
0: Copy select
Default: 0
o3-01 1: INV OP READ (Read parameters from the drive, saving them onto the digital operator.)
Copy Function Selection Min: 0 294
(515H) 2: OP INV WRITE (Copy parameters from the digital operator, writing them to the drive.)
Max: 3
3: OP INV VERIFY (Verify parameter settings on the drive to check if they match the data
saved on the operator.)
To read the drive’ parameter settings into the digital operator, set o3-02 to 1 (to allow reading).
common_
All Modes TMonly Default: 0
o3-02
Copy Allowed Selection Selects whether the read operation (o3-01 = 1) is enabled or disabled. Min: 0 294
(516H)
0: Read operation prohibited Max: 1
1: Read operation allowed
452 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
common_
All Modes TMonly Default: 0
o4-11
U2, U3 Initialization 0: U2- and U3- monitor data is not reset when the drive is initialized (A1-03). Min: 0 295
(510H)
1: U2- and U3- monitor data is reset when the drive is initialized (A1-03). (The value Max: 1
of o4-11 is automatically returned to 0.)
common_
All Modes TMonly Default: 0
o4-12
kWh Monitor Initialization Min: 0 295
(512H) 0: No action
Max: 1
1: Reset kWh data (The value of o4-12 is automatically returned to 0.)
common_
All Modes TMonly Default: 0
o4-13 Number of Run Commands
0: U4-02 monitor data is not reset when the drive is initialized (A1-03). Min: 0 296
(528H) Counter Initialization
1: U4-02 monitor data is reset when the drive is initialized (A1-03). (The value of o4-13 is Max: 1
automatically returned to 0.)
q: DriveWorksEZ Parameters
No. (Addr.) Name Description Setting Page
q1-01 to
common_
q6-07 All Modes TMonly Refer to Help in the
DriveWorksEZ Parameters 296
(1600H to DWEZ software.
Reserved for DriveWorksEZ
1746H)
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
T1: Induction Motor Auto-Tuning
TMonly
OLV/PM AOLV/PM CLV/PM
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line Resistance
T1-01 3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation Default: 0
(701H) Auto-Tuning Mode Selection Speed Search) Min: 0 123
<37> 4: Stationary Auto-Tuning 2 Max: 4, 5, 8, 9 <10>
5: Stationary Auto-Tuning 3
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning) B
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-Tuning)
Note: Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between
the machine and the motor shaft.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 453
B.3 Parameter Table
454 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 455
B.3 Parameter Table
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<37> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<39> Default setting is determined by the drive capacity and the motor code selected in T2-02.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
<40> Displayed only when performing Inertia Tuning or ASR Gain Auto-Tuning (T1-01 = 9 or T2-01 = 9).
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
U1: Operation Status Monitors
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
U1-01 All Modes TMonly 10 V: Max frequency
Frequency Reference 0.01 Hz –
(40H) (-10 to +10 V)
Monitors the frequency reference. Display units are determined by o1-03.
common_
U1-02 All Modes TMonly 10 V: Max frequency
Output Frequency 0.01 Hz –
(41H) Displays the output frequency. Display units are determined by o1-03. (-10 to +10 V)
common_
U1-03 All Modes TMonly 10 V: Drive rated
Output Current <19> <23> –
(42H) current
Displays the output current.
common_
All Modes TMonly
0: V/f Control
1: V/f Control with PG
U1-04 No signal output
Control Method 2: Open Loop Vector Control – –
(43H) available
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
456 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
All Modes TMonly
Displays the input terminal status.
U1 - 10= 0 0 0 0 0 0 0 0
1 Digital input 1
(terminal S1 enabled)
1 Digital input 2
(terminal S2 enabled)
1 Digital input 3
U1-10 (terminal S3 enabled) No signal output
Input Terminal Status – –
(49H) available
1 Digital input 4
(terminal S4 enabled)
1 Digital input 5
(terminal S5 enabled)
1 Digital input 6
(terminal S6 enabled)
1 Digital input 7
(terminal S7 enabled)
1 Digital input 8
(terminal S8 enabled)
common_
All Modes TMonly
Displays the output terminal status.
U1 - 11= 0 0 0 0 0 0 0 0
1 Multi-Function
Digital Output
(terminal M1-M2)
U1-11 No signal output
(4AH)
Output Terminal Status 1 Multi-Function
Digital Output available
– –
YEG_ (terminal M3-M4)
TMonly 1Multi-Function
Digital Output
(terminal M5-M6)
Not Used
1Fault Relay Output
(terminal MA-MC closed
MA/MB-MC open)
common_
All Modes TMonly
Displays the drive operation status.
U1 - 12= 0 0 0 0 0 0 0 0
1 During run
1 During zero-speed
U1-12
Drive Status
1 During REV No signal output
– –
(4BH) available
1 During fault reset
signal input
1 During speed agree
1 Drive ready
1 During alarm
detection
1 During fault detection
common_
U1-13 All Modes TMonly 10 V: 100%
Terminal A1 Input Level 0.1% –
(4EH) (-10 to +10 V)
Displays the signal level to analog input terminal A1.
common_
U1-14 All Modes TMonly 10 V: 100%
Terminal A2 Input Level 0.1% –
(4FH) (-10 to +10 V)
Displays the signal level to analog input terminal A2.
common_
U1-15 All Modes TMonly 10 V: 100%
Terminal A3 Input Level 0.1% –
(50H) (-10 to +10 V)
Displays the signal level to analog input terminal A3.
common_
U1-16 Output Frequency after Soft All Modes 10 V: Max frequency
Parameter List
TMonly 0.01 Hz –
(53H) Starter (-10 to +10 V)
Displays output frequency with ramp time and S-curves. Units determined by o1-03.
common_
All Modes TMonly
U1-17 No signal output
DI-A3 Input Status Displays the reference value input from the DI-A3 option card. – –
(58H) available
Display will appear in hexadecimal as determined by the digital card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
U1-18
oPE Fault Parameter
All Modes
common_
TMonly No signal output
– –
B
(61H) available
Displays the parameter number that caused the oPE02 or oPE08 (Operation error).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 457
B.3 Parameter Table
U1 - 19= 0 0 0 0 0 0 0 0
1 CRC Error
U1-19 MEMOBUS/Modbus Error 1 Data Length Error No signal output
– –
(66H) Code 0 Not Used available
1 Parity Error
1 Overrun Error
1 Framing Error
1 Timed Out
0 Not Used
common_
U1-21 AI-A3 Terminal V1 Input All Modes TMonly 10 V: 100%
0.1% –
(77H) Voltage Monitor (-10 to +10 V)
Displays the input voltage to terminal V1 on analog input card AI-A3.
common_
U1-22 AI-A3 Terminal V2 Input All Modes TMonly 10 V: 100%
0.1% –
(72AH) Voltage Monitor (-10 to +10 V)
Displays the input voltage to terminal V2 on analog input card AI-A3.
common_
U1-23 AI-A3 Terminal V3 Input All Modes TMonly 10 V: 100%
0.1% –
(72BH) Voltage Monitor (-10 to +10 V)
Displays the input voltage to terminal V3 on analog input card AI-A3.
common_
U1-24 All Modes TMonly
Input Pulse Monitor Determined by H6-02 1 Hz –
(7DH)
Displays the frequency to pulse train input terminal RP.
common_
U1-25 All Modes TMonly No signal output
Software Number (Flash) – –
(4DH) available
FLASH ID
common_
U1-26 All Modes TMonly No signal output
Software No. (ROM) – –
(5BH) available
ROM ID
200 V class
U1-54 Drive Input Power Voltage All Modes common_TMonly 10 V: 400 V
1V –
(1083H) Effective Value 400 V class
Displays the effective value of the drive input power voltage.
10 V: 800 V
U1 - 72= 0 0 0 0 0 0 0 0
Bit 0: AUv reset. (0: Not completed, 1: Reset)
Bit 1: PF reset (0: Not completed, 1: Reset)
U1-72 Input Power Supply Bit 2: Rated frequency detection No signal output
(0: Not completed, 1: Completed) – –
(1095H) Information available
Bit 3: Phase order detection
(0: Not completed, 1: Completed)
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Fdv detection (0: Not detected, 1: Detected)
Bit 6: PF detection (0: Not detected, 1: Detected)
Bit 7: Reserved.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<19> Display is in the following units.
CIMR-U20028, 20042, and 40011 to 40027: 0.01 A units
CIMR-U20054 to 20248, and 40034 to 40414: 0.1 A units
<22> Display is in the following units.
CIMR-U20028, 20042, and 40011 to 40027: 0.01 kW units
CIMR-U20054 to 20248, and 40034 to 40414: 0.1 kW units
<23> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are
checked using MEMOBUS/Modbus communications, the monitor value in MEMOBUS/Modbus communications is: displayed numeric value
/ 8192 drive’ rated current (A), from the condition “8192 (maximum value) = drive’ rated current (A)”
<60> In V/f and V/f w/PG control mode, 10 V = drive rated current (A) voltage class (V). In OLV, CLV, OLV/PM, AOLV/PM, or CLV/PM
control mode, 10 V = motor rated power (E2-11) (kW).
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
U2-01 All Modes TMonly No signal output
Current Fault – –
(80H) available
Displays the current fault.
458 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
U2-02 All Modes TMonly No signal output
Previous Fault – –
(81H) available
Displays the previous fault.
common_
U2-03 Frequency Reference at All Modes TMonly No signal output
0.01 Hz –
(82H) Previous Fault available
Displays the frequency reference at the previous fault.
common_
U2-04 Output Frequency at Previous All Modes TMonly No signal output
0.01 Hz –
(83H) Fault available
Displays the output frequency at the previous fault.
common_
U2-05 Output Current at Previous All Modes TMonly No signal output
<19> <23> –
(84H) Fault available
Displays the output current at the previous fault.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 459
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Unit Page
Level
U3-01 to
U3-04 common_
All Modes TMonly No signal output
(90H to 93H First to 4th Most Recent Fault – –
available
(800H to Displays the first to the fourth most recent faults.
803H))
common_
All Modes TMonly
U3-05 to
U3-10 Displays the fifth to the tenth most recent faults. No signal output
5th to 10th Most Recent Fault – –
(804H to After ten faults have occurred in the drive, data for the oldest fault is deleted. The most recent available
809H) fault appears in U3-01, with the next most recent fault appearing in U3-02. The data is moved to
the next monitor parameter every time a fault occurs.
U3-11 to
U3-14 common_
Cumulative Operation Time at All Modes TMonly No signal output
(94H to 97H 1h –
1st to 4th Most Recent Fault available
(80AH to Displays the cumulative operation time when the first to the fourth most recent faults occurred.
80DH))
U3-15 to
common_
U3-20 Cumulative Operation Time at All Modes TMonly No signal output
1h –
(80EH to 5th to 10th Most Recent Fault available
Displays the cumulative operation time when the fifth to the tenth most recent faults occurred.
813H)
Analog Output
No. (Addr.) Name Description Unit Page
Level
common_
All Modes TMonly
U4-01
Displays the cumulative operation time of the drive. The value for the cumulative operation No signal output
(4CH) Cumulative Operation Time 1h –
time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation available
<26>
time should start as soon as the power is switched on or only while the Run command is present.
The maximum number displayed is 99999, after which the value is reset to 0.
common_
All Modes TMonly
U4-02 No signal output
Number of Run Commands 1 Time –
(75H) Displays the number of times the Run command is entered. Reset the number of Run commands available
using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535.
common_
All Modes TMonly
U4-03
No signal output
(67H) Cooling Fan Operation Time Displays the cumulative operation time of the cooling fan. The default value for the fan 1h –
operation time is reset in parameter o4-03. This value will reset to 0 and start counting again available
<58>
after reaching 99999.
common_
All Modes TMonly
U4-04 No signal output
Cooling Fan Maintenance Displays main cooling fan usage time in as a percentage of its expected performance life. 1% –
(7EH) available
Parameter o4-03 can be used to reset this monitor. The fan should be replaced when this
monitor reaches 90%.
common_
All Modes TMonly
U4-05 No signal output
Capacitor Maintenance Displays main circuit capacitor usage time in as a percentage of their expected performance life. 1% –
(7CH) available
Parameter o4-05 can be used to reset this monitor. The capacitor should be replaced when this
monitor reaches 90%.
common_
All Modes TMonly
U4-06 Soft Charge Bypass Relay No signal output
Displays the soft charge bypass relay maintenance time as a percentage of its estimated 1% –
(7D6H) Maintenance available
performance life. Parameter o4-07 can be used to reset this monitor. The soft charge bypass
relay should be replaced when this monitor reaches 90%.
common_
U4-08 All Modes TMonly
Heatsink Temperature 10 V: 100C 1C –
(68H)
Displays the heatsink temperature.
common_
U4-09 All Modes TMonly No signal output
LED Check – –
(5EH) available
Lights all segments of the LED to verify that the display is working properly.
common_
U4-13 All Modes TMonly No signal output 0.01 A
Peak Hold Current –
(7CFH) available <19> <23>
Displays the highest current value that occurred during run.
common_
U4-14 All Modes TMonly No signal output
Peak Hold Output Frequency 0.01 Hz –
(7D0H) available
Displays the output frequency when the current value shown in U4-13 occurred.
common_
All Modes TMonly
U4-16 Motor Overload Estimate
10 V: 100% 0.1% –
(7D8H) (oL1) Shows the value of the motor overload detection accumulator. 100% is equal to the oL1
detection level.
460 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
All Modes TMonly
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
U4-18 Frequency Reference Source 1-00 = Analog No signal output
– –
(7DAH) Selection 1-01 = Analog (terminal A1) available
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
7-01 = DWEZ
9-01 = Up/Down Command
common_
U4-19 Frequency Reference from All Modes TMonly No signal output
0.01% –
(7DBH) MEMOBUS/Modbus Comm. available
Displays the frequency reference provided by MEMOBUS/Modbus (decimal).
common_
U4-20 All Modes TMonly No signal output
Option Frequency Reference – –
(7DCH) available
Displays the frequency reference input by an option card (decimal).
common_
All Modes TMonly
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
U4-21 Run Command Source No signal output
7 = DWEZ – –
(7DDH) Selection available
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1 flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
common_
All Modes TMonly
U4-22 MEMOBUS/Modbus No signal output
– –
(7DEH) Communications Reference Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H available
as a four-digit hexadecimal number.
common_
U4-23 Communication Option Card All Modes TMonly No signal output
– –
(7DFH) Reference available
Displays drive control data set by an option card as a four-digit hexadecimal number.
<19> Display is in the following units.
CIMR-U20028, 20042, and 40011 to 40027: 0.01 A units
CIMR-U20054 to 20248, and 40034 to 40414: 0.1 A units
<23> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are
checked using MEMOBUS/Modbus communications, the monitor value in MEMOBUS/Modbus communications is: displayed numeric value
/ 8192 drive’ rated current (A), from the condition “8192 (maximum value) = drive’ rated current (A)”
<26> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<58> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
U5-01 All Modes TMonly 10 V: 100%
PID Feedback 0.01% –
(57H) (-10 to +10 V)
Displays the PID feedback value.
Parameter List
common_
U5-02 All Modes TMonly 10 V: 100%
PID Input 0.01% –
(63H) (-10 to +10 V)
Displays the amount of PID input (deviation between PID setpoint and feedback).
common_
U5-03 All Modes TMonly 10 V: 100%
PID Output 0.01% –
(64H) (-10 to +10 V)
Displays PID control output.
common_
U5-04 All Modes 10 V: 100%
(65H)
PID Setpoint
Displays the PID setpoint.
TMonly
(-10 to +10 V)
0.01% –
B
common_
U5-05 All Modes TMonly 10 V: 100%
PID Differential Feedback 0.01% –
(7D2H) (-10 to +10 V)
Displays the 2nd PID feedback value if differential feedback is used (H3- = 16).
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 461
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Unit Page
Level
10 V: Motor
common_
U6-01 All Modes TMonlysecondary rated
Motor Secondary Current (Iq) 0.1% –
(51H) current
Displays the value of the motor secondary current (Iq). Motor rated secondary current is 100%.
(-10 to +10 V)
462 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Level Unit Page
common_
All Modes TMonly
U6-21
Offset Frequency 10 V: Max frequency 0.1% –
(7D5H) The total value of the offset frequencies d7-01, d7-02 and d7-03 selected with digital inputs 44
to 46 is displayed.
Analog Output
No. (Addr.) Name Description Level Unit Page
U8-01 to
common_
U8-10 DriveWorksEZ Custom All Modes TMonly 10 V: 100% 0.01% –
(1950H to Monitor 1 to 10
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 463
B.3 Parameter Table
Analog Output
No. (Addr.) Name Description Unit Page
Level
U9-01 Shows the total amount of electric power consumed. No signal output
Electric Power (GWh) 1 GWh –
(820H) available
U9-02 000 000 000 kW No signal output
Electric Power (MWh) 1 MWh –
(821H) U9-03 available
These parameters show the electric power rate in Power Unit Price (o4-19) that is calculated
from the total electrical power consumption in U9-01 to U9-03.
U9-10: Digit 1 to digit 3
U9-09: Digit 4 to digit 6
U9-08: Digit 7 to digit 9
U9-07: Digit 10 to digit 12
U9-07 to
U9-10 000 000 000 000 No signal output
Electric Power Rates 1 to 4 – –
(826H to U9-10 available
829H)
U9-09
U9-08
U9-07
The values shown in U9-07 to U9-10 are calculated by multiplying U9-01 to U9-03 by the value
set in o4-19.
These parameters show the regenerative power rate in Power Unit Price (o4-19) that is
calculated from the total electrical power consumption in U9-04 to U9-06.
U9-14: Digit 1 to digit 3
U9-13: Digit 4 to digit 6
U9-12: Digit 7 to digit 9
U9-11: Digit 10 to digit 12
U9-11 to
U9-14 Regenerative Power Rates 000 000 000 000 No signal output
– –
(82AH to 1 to 4 U9-14 available
82DH)
U9-13
U9-12
U9-11
The values shown in U9-11 to U9-14 are calculated by multiplying U9-04 to U9-06 by the value
set in o4-19.
464 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.4 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 465
B.4 Control Mode Dependent Parameter Default Values
466 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.4 Control Mode Dependent Parameter Default Values
<41> This default value is a calculated as a percentage of the maximum output frequency.
<55> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (0.0 to 100.0%) instead of in Hz.
<56> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (0.0 to 40.0%) instead of in Hz.
<57> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (-100.0 to 100.0%) instead of in Hz.
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 467
B.5 V/f Pattern Default Values
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0
E1-05
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
<18>
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 –
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 –
E1-08
V 15.0 15.0 15.0 15.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 15.0 15.0 15.0 15.0 14.4 –
<18>
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.3 0.5 –
E1-10
V 9.0 9.0 9.0 9.0 8.0 9.0 8.0 9.0 11.0 13.0 11.0 15.0 9.0 9.0 9.0 9.0 3.0 –
<18>
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
468 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
E5-01 Motor Code Selection (for PM Motors) Hex. 120F 120F 1210 1210 1212 1212 1213 1213
L2-02 Momentary Power Loss Ride-Thru Time s 1 1 1 1.1 1.1 1.1 1.1 1.2
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.6 0.6 0.6 0.6 0.6 0.6 0.6 1
L2-04 Momentary Power Loss Voltage Recovery Time V 150 150 150 150 150 150 150 150
L8-02 Overheat Alarm Level C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 2 2 2 2 2 2 2 2 B
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.317 0.355 0.355 0.323 0.323 0.32 0.32 0.387
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 469
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
Table B.9 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No. Name Unit Default Settings
Model CIMR-U – 40011 40014 40021 40027
HD ND HD ND HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 95 97 99 9A
E2-11 (E4-11) Motor rated Output kW 2.2 3.7 3.7 5.5 5.5 7.5 7.5 11
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Current Control Gain during Speed Search
b3-08 – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
(Speed Estimation Type)
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 313.6 245.8 245.8 189.5 189.5 145.38 145.38 140.88
C5-17 (C5-37) Motor Inertia kgm2 0.0088 0.0158 0.0158 0.0255 0.026 0.037 0.037 0.053
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 4.2 7 7 9.8 9.8 13.3 13.3 19.9
E2-02 (E4-02) Motor Rated Slip Hz 3 2.7 2.7 1.5 1.5 1.3 1.3 1.7
E2-03 (E4-03) Motor No-Load Current A 1.5 2.3 2.3 2.6 2.6 4 4 5.6
E2-05 (E4-05) Motor Line to Line Resistance 6.495 3.333 3.333 1.595 1.595 1.152 1.152 0.922
E2-06 (E4-06) Motor Leakage Inductance % 18.7 19.3 19.3 18.2 18.2 15.5 15.5 19.6
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 77 130 130 193 193 263 263 385
E5-01 Motor Code Selection (for PM Motors) Hex. 1236 1236 1238 1238 123A 123A 123B 123B
L2-02 Momentary Power Loss Ride-Thru Time s 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.9
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-04 Momentary Power Loss Voltage Recovery Time V 300 300 300 300 300 300 300 300
L8-02 Overheat Alarm Level C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 2 2 2 2 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.145 0.154 0.154 0.168 0.168 0.175 0.175 0.265
470 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 471
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
472 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
The following tables show parameters and default settings that change with the motor code selection E5-01 when Open
Loop Vector for PM motors is used.
Table B.11 200 V, 3600 min-1 Type YASKAWA SMRA Series SPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 0103 0105 0106 0108
Voltage Class V 200 200 200 200
E5-01
Rated Power kW 0.75 1.5 2.2 3.7
Rated Speed min-1 3600 3600 3600 3600
E5-02 Motor Rated Power (for PM Motors) kW 0.75 1.5 2.2 3.7
E5-03 Motor Rated Current (for PM Motors) A 4.1 8.0 10.5 16.5
E5-04 Number of Motor Poles (for PM Motors) – 8 8 8 8
E5-05 Motor Stator Resistance (r1) (for PM Motors) 0.538 0.20 0.15 0.097
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 3.2 1.3 1.1 1.1
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 3.2 1.3 1.1 1.1
Motors)
Motor Induction Voltage Constant 1 (Ke) (for
E5-09 mVs/rad 0 0 0 0
PM Motors)
Motor Induction Voltage Constant 2 (Ke) (for
E5-24 mV/(min-1) 32.4 32.7 36.7 39.7
PM Motors)
E1-04 Maximum Output Frequency Hz 240 240 240 240
E1-05 Maximum Voltage V 200.0 200.0 200.0 200.0
E1-06 Base Frequency Hz 240 240 240 240
E1-09 Minimum Output Frequency Hz 12 12 12 12
C5-17 Motor Inertia kgm2 0.0007 0.0014 0.0021 0.0032
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 473
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
474 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.13 400 V, 1750 min-1 Type YASKAWA SSR1 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 1232 1233 1235 1236 1238 123A 123B 123D 123E 123F
Voltage Class V 400 400 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18
Rated Speed min-1 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.50
E5-03 Motor Rated Current (for PM Motors) A 0.89 1.56 2.81 4.27 7.08 10.31 13.65 20.7 27.5 33.4
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 25.370 9.136 6.010 3.297 1.798 0.982 0.786 0.349 0.272 0.207
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 169.00 92.08 67.71 34.40 32.93 22.7 16.49 13.17 10.30 8.72
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 197.50 119.56 81.71 54.00 37.70 26.80 23.46 15.60 12.77 11.22
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 392.6 440.6 478.3 466.3 478.8 478.1 520.0 481.5 498.8 509.5
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
C5-17 Motor Inertia kgm2 0.0011 0.0017 0.0023 0.0043 0.0083 0.014 0.017 0.027 0.046 0.055
n5-02 Motor Acceleration Time s 0.092 0.076 0.052 0.066 0.075 0.083 0.077 0.084 0.102 0.101
d-Axis Current for High Efficiency
n8-49 % -8.6 -11.5 -10.3 -19.8 -8.5 -11.0 -18.6 -12.5 -15.5 -17.9
Control (for PM Motors) (OLV/PM)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 475
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.14 200 V, 1450 min-1 Type YASKAWA SSR1 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 1302 1303 1305 1306 1308 130A 130B 130D
Voltage Class V 200 200 200 200 200 200 200 200
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Speed min-1 1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0
E5-03 Motor Rated Current (for PM Motors) A 1.88 3.13 5.63 8.33 14.17 20.63 27.71 39.6
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 3.190 1.940 1.206 0.665 0.341 0.252 0.184 0.099
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 32.15 26.12 14.72 12.27 8.27 6.49 6.91 4.07
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 41.74 34.30 20.15 14.77 9.81 7.74 7.66 4.65
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 264.3 269.6 284.3 287.1 284.5 298.0 335.0 303.9
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm2 0.0017 0.0023 0.0043 0.0083 0.0136 0.017 0.027 0.046
n5-02 Motor Acceleration Time s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096
d-Axis Current for High Efficiency
n8-49 % -6.6 -10.9 -13.5 -9.0 -9.5 -10.1 -6.0 -9.3
Control (for PM Motors) (OLV/PM)
476 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.15 400 V, 1450 min-1 Type YASKAWA SSR1 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 1332 1333 1335 1336 1338 133A 133B 133D 133E 133F
Voltage Class V 400 400 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18
Rated Speed min-1 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.50
E5-03 Motor Rated Current (for PM Motors) A 0.94 1.56 2.81 4.27 6.98 10.21 13.85 19.5 27.4 32.9
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 12.760 7.421 4.825 2.656 1.353 0.999 0.713 0.393 0.295 0.223
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 128.60 85.11 58.87 46.42 31.73 26.20 27.06 15.51 12.65 9.87
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 166.96 113.19 80.59 60.32 40.45 30.94 33.45 19.63 15.87 12.40
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 528.6 544.2 568.5 572.8 562.9 587.6 670.1 612.7 624.6 610.4
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm2 0.0017 0.0023 0.0043 0.0083 0.0136 0.017 0.027 0.046 0.055 0.064
n5-02 Motor Acceleration Time s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096 0.085 0.080
d-Axis Current for High Efficiency
n8-49 % -6.6 -9.2 -13.5 -12.1 -13.7 -10.1 -12.2 -15.5 -15.1 -16.0
Control (for PM Motors) (OLV/PM)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 477
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.16 200 V, 1150 min-1 Type YASKAWA SSR1 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 1402 1403 1405 1406 1408 140A 140B
Voltage Class V 200 200 200 200 200 200 200
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Rated Speed min-1 1150 1150 1150 1150 1150 1150 1150
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5
E5-03 Motor Rated Current (for PM Motors) A 1.88 3.02 6.00 8.85 14.27 20.21 26.67
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 4.832 2.704 1.114 0.511 0.412 0.303 0.165
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 48.68 32.31 19.22 12.15 7.94 11.13 6.59
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 63.21 40.24 24.38 15.35 11.86 14.06 8.55
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 320.4 327.1 364.4 344.4 357.5 430.8 391.5
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm2 0.0017 0.0023 0.0083 0.0136 0.0171 0.027 0.046
n5-02 Motor Acceleration Time s 0.062 0.044 0.080 0.090 0.067 0.072 0.088
d-Axis Current for High Efficiency
n8-49 % -8.8 -9.9 -9.3 -10.0 -17.7 -12.3 -15.3
Control (for PM Motors) (OLV/PM)
478 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.17 400 V, 1150 min-1 Type YASKAWA SSR1 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 1432 1433 1435 1436 1438 143A 143B 143D 143E
Voltage Class V 400 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated Speed min-1 1150 1150 1150 1150 1150 1150 1150 1150 1150
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15
E5-03 Motor Rated Current (for PM Motors) A 0.94 1.51 3.00 4.43 7.08 10.10 13.33 19.9 27.8
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 19.320 10.800 4.456 2.044 1.483 1.215 0.660 0.443 0.331
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 194.70 129.20 76.88 48.60 37.58 44.54 26.36 19.10 15.09
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 252.84 160.90 97.52 61.40 47.65 56.26 34.20 24.67 18.56
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 640.9 654.1 728.8 688.9 702.0 861.5 783.0 762.2 749.6
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm2 0.0017 0.0023 0.0083 0.0136 0.0171 0.027 0.046 0.055 0.064
n5-02 Motor Acceleration Time s 0.062 0.044 0.080 0.090 0.067 0.072 0.088 0.073 0.062
d-Axis Current for High Efficiency
n8-49 % -8.8 -9.9 -9.3 -10.0 -12.8 -12.3 -15.3 -16.7 -14.9
Control (for PM Motors) (OLV/PM)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 479
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
480 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.19 400 V, 1750 min-1 Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 2232 2233 2235 2236 2238 223A 223B 223D
Voltage Class V 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Speed min-1 1750 1750 1750 1750 1750 1750 1750 1750
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0
E5-03 Motor Rated Current (for PM Motors) A 0.92 1.77 3.33 4.48 7.50 10.42 14.27 20.5
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 8.935 4.570 3.096 1.906 0.972 1.103 0.630 0.429
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 80.14 48.04 35.60 30.31 20.03 23.41 14.86 14.34
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 110.76 64.88 47.84 38.36 24.97 28.70 17.25 17.25
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 416.5 399.4 438.5 475.5 463.7 485.8 470.4 513.4
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
C5-17 Motor Inertia kgm2 0.0016 0.0022 0.0042 0.0081 0.0133 0.013 0.017 0.027
n5-02 Motor Acceleration Time s 0.134 0.099 0.094 0.124 0.121 0.081 0.075 0.082
d-Axis Current for High Efficiency
n8-49 % -7.5 -8.5 -9.8 -8.2 -9.1 -13.1 -9.2 -12.4
Control (for PM Motors) (OLV/PM)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 481
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.20 200 V, 1450 min-1 Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 2302 2303 2305 2306 2308 230A 230B 230D
Voltage Class V 200 200 200 200 200 200 200 200
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Speed min-1 1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0
E5-03 Motor Rated Current (for PM Motors) A 1.77 3.33 5.94 9.48 14.17 20.42 27.92 39.6
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 3.154 1.835 0.681 0.308 0.405 0.278 0.180 0.098
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 28.46 19.46 10.00 6.88 8.15 5.77 6.32 3.34
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 39.29 25.89 15.20 9.25 10.76 8.60 8.80 4.61
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 268.8 256.9 271.9 260.2 286.8 314.9 300.8 292.3
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm2 0.0016 0.0022 0.0081 0.0133 0.0133 0.017 0.027 0.044
n5-02 Motor Acceleration Time s 0.092 0.068 0.125 0.139 0.083 0.070 0.082 0.092
d-Axis Current for High Efficiency
n8-49 % -7.5 -9.4 -13.9 -10.0 -15.0 -17.9 -22.7 -20.5
Control (for PM Motors) (OLV/PM)
482 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.21 400 V, 1450 min-1 Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 2332 2333 2335 2336 2338 233A 233B 233D 233E 233F 2340
Voltage Class V 400 400 400 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18 22
Rated Speed min-1 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.50 22.00
E5-03 Motor Rated Current (for PM Motors) A 0.91 1.67 3.02 4.74 7.08 10.21 13.96 20.5 27.1 34.2 37.6
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 12.616 7.340 2.724 1.232 1.509 1.112 0.720 0.393 0.291 0.220 0.192
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 113.84 77.84 40.00 27.52 31.73 23.09 25.28 13.36 11.77 8.94 8.32
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 157.16 103.56 60.80 37.00 40.88 34.39 35.20 18.44 14.60 11.40 10.64
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 490.8 513.8 543.7 520.3 580.8 602.7 601.5 584.6 610.3 595.2 711.6
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm2 0.0016 0.0022 0.0081 0.0133 0.0133 0.017 0.027 0.044 0.054 0.063 0.113
n5-02 Motor Acceleration Time s 0.092 0.068 0.125 0.139 0.083 0.070 0.082 0.092 0.083 0.079 0.118
d-Axis Current for High Efficiency
n8-49 % -9.5 -9.4 -13.7 -10.0 -12.9 -19.9 -22.8 -19.8 -14.5 -16.1 -11.8
Control (for PM Motors) (OLV/PM)
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 483
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.22 200 V, 1150 min-1 Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 2402 2403 2405 2406 2408 240A 240B 240D
Voltage Class V 200 200 200 200 200 200 200 200
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Speed min-1 1150 1150 1150 1150 1150 1150 1150 1150
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0
E5-03 Motor Rated Current (for PM Motors) A 1.77 3.44 5.94 9.17 14.79 20.21 27.40 39.0
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 2.680 1.520 1.071 0.542 0.362 0.295 0.162 0.115
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 30.55 15.29 17.48 11.98 8.60 9.54 5.31 4.44
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 42.71 24.28 22.51 15.51 10.69 13.84 8.26 5.68
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 313.1 313.1 345.3 342.9 363.8 384.3 379.9 370.2
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm2 0.0022 0.0042 0.0081 0.0133 0.0168 0.027 0.044 0.054
n5-02 Motor Acceleration Time s 0.080 0.081 0.078 0.088 0.066 0.070 0.085 0.071
d-Axis Current for High Efficiency
n8-49 % -8.4 -11.0 -10.7 -10.7 -9.4 -22.5 -22.2 -16.7
Control (for PM Motors) (OLV/PM)
484 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
Table B.23 400 V, 1150 min-1 Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
Motor Code Selection (for PM Motors) 2432 2433 2435 2436 2438 243A 243B 243D 243E 243F 2440
Voltage Class V 400 400 400 400 400 400 400 400 400 400 400
E5-01
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18 22
Rated Speed min-1 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.50 22.00
E5-03 Motor Rated Current (for PM Motors) A 0.89 1.72 3.02 4.58 7.40 10.21 13.75 19.5 27.7 32.7 39.2
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6 6 6 6
Motor Stator Resistance (r1) (for PM
E5-05 10.720 6.080 4.336 2.143 1.428 1.199 0.648 0.460 0.325 0.260 0.209
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06 mH 122.20 61.16 70.24 46.20 33.87 41.67 21.24 17.76 12.83 11.68 10.09
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07 mH 170.80 97.12 90.04 60.28 42.98 69.15 33.04 22.72 17.19 15.16 16.25
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09 mVs/rad 626.1 626.1 703.1 727.6 699.0 861.5 759.7 740.4 716.6 809.1 786.2
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24 mV/(min-1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
(for PM Motors)
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm2 0.0022 0.0042 0.0081 0.0133 0.0168 0.027 0.044 0.054 0.063 0.113 0.137
n5-02 Motor Acceleration Time s 0.080 0.081 0.078 0.088 0.066 0.070 0.085 0.071 0.061 0.089 0.090
d-Axis Current for High Efficiency
n8-49 % -8.4 -11.0 -9.9 -9.0 -11.4 -23.2 -22.1 -16.7 -20.2 -15.2 -27.7
Control (for PM Motors) (OLV/PM)
Parameter List
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 485
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
486 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Appendix: C
MEMOBUS/Modbus Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 487
C.1 MEMOBUS/Modbus Configuration
Slave (U1000)
common_
TMonly
Figure C.1 Connecting Multiple Drives to a PLC
488 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.2 Communication Specifications
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 489
C.3 Connecting to a Network
IG R+ R- S+ S- (TB4)
YEG_TMonly
S- Send (-)
S+ Send (+)
R- Receive (-)
R+ Receive (+)
IG Shield Ground
R– S–
U1000
R+ S+
PLC
S– R– S2
S+ R+
IG IG OFF
S–
U1000
S+
R– S2
R+
IG OFF
S–
U1000
common_
S+
R– S2
TMonly
R+ ON
IG
490 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.3 Connecting to a Network
RS-422 Interface
Figure C.4
R– S–
U1000
R+ S+
PLC
S– R– S2
S+ R+
IG IG OFF
S–
U1000
S+
R– S2
R+
IG OFF
common_
S–
S+
U1000
TMonly
R– S2
R+ ON
IG
Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination
resistor that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the
termination resistor by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not
located at the network line end.
Refer to MEMOBUS/Modbus Termination on page 85 for details on setting S2.
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 491
C.4 MEMOBUS/Modbus Setup Parameters
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01
to any value besides 0 assigns the drive its address in the network. Slave address don’t need to be assigned in sequential
order, but each address needs to be unique so that no two drives have the same address.
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note: After changing this parameter, the power must be cycled to enable the new setting.
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
H5-04: Stopping Method after Communication Error
Selects the stopping method after a MEMOBUS/Modbus communications error (CE) has occurred.
492 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.4 MEMOBUS/Modbus Setup Parameters
Setting 0: Disabled
No communication error detection. The drive continues operation.
Setting 1: Enabled
If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered
and the drive will operate as determined by parameter H5-04.
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
common_
TMonly
24 bit length H5-06 setting
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 493
C.4 MEMOBUS/Modbus Setup Parameters
494 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.5 Drive Operations by MEMOBUS/Modbus
Refer to b1-01: Frequency Reference Selection 1 on page 144 and b1-02: Run Command Selection 1 on page 145 for
details on external reference parameter selections. Refer to Setting 2: External reference 1/2 selection on page 228 for
instructions on how to select external reference 1 and 2.
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 495
C.6 Communications Timing
common_
24 bit length Master Send
Wait Time
TMonly
Figure C.6 Minimum Wait Time for Sending Messages
A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no
response is received within a certain amount of time, the master should try resending the message.
common_
24 bit length H5-06 TMonly
setting
496 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.7 Message Format
ERROR CHECK
Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a
message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves
do not provide a response to a broadcast type message.
Function Code
The three types of function codes are shown in the table below.
Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test)
and the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers
must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 497
C.7 Message Format
Error Check
The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure
described below when calculating the CRC-16 checksum for command data or when verifying response data.
Command Data
When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value
received within the message. Both must match before a command is processed.
An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations in the MEMOBUS/Modbus
protocol.
Calculate the CRC-16 checksum using the following steps:
1. The starting value is FFFFH.
2. Perform an XOR operation of this value and the slave address.
3. Right shift the result.
4. When the overflow bit of the shift operation becomes 1, perform an XOR operation of the result from step 3
above and the fix value A001H.
5. Repeat steps 3 and 4 until eight shift operations have been performed.
6. After eight shift operations, perform an XOR operation with the result and the next data in the message (function
code, register address, data). Continue with steps 3 to 5 until the last data has been processed.
7. The result of the last shift or XOR operation is the checksum.
The example in Table C.4 shows the CRC-16 calculation of the slave address 02H and the function code 03H, yielding
the result D140H.
Note: This example does not show the calculation for a complete MEMOBUS/Modbus command. Normally data would follow in the
calculation.
Table C.4 CRC-16 Checksum Calculation Example
Description Calculation Overflow Description Calculation Overflow
Initial Value (FFFFH) 1111 1111 1111 1111 Function Code 03H 0000 0000 0000 0011
Address 02H 0000 0000 0000 0010 XOR w result 1000 0001 0011 1101
XOR w initial value 1111 1111 1111 1101 Shift 1 0100 0000 1001 1110 1
Shift 1 0111 1111 1111 1110 1 XOR w A001H 1010 0000 0000 0001
XOR w A001H 1010 0000 0000 0001 XOR result 1110 0000 1001 1111
XOR result 1101 1111 1111 1111 Shift 2 0111 0000 0100 1111 1
Shift 2 0110 1111 1111 1111 1 XOR w A001H 1010 0000 0000 0001
XOR w A001H 1010 0000 0000 0001 XOR result 1101 0000 0100 1110
XOR result 1100 1111 1111 1110 Shift 3 0110 1000 0010 0111 0
Shift 3 0110 0111 1111 1111 0 Shift 4 0011 0100 0001 0011 1
Shift 4 0011 0011 1111 1111 1 XOR w A001H 1010 0000 0000 0001
XOR w A001H 1010 0000 0000 0001 XOR result 1001 0100 0001 0010
XOR result 1001 0011 1111 1110 Shift 5 0100 1010 0000 1001 0
Shift 5 0100 1001 1111 1111 0 Shift 6 0010 0101 0000 0100 1
Shift 6 0010 0100 1111 1111 1 XOR w A001H 1010 0000 0000 0001
XOR w A001H 1010 0000 0000 0001 XOR result 1000 0101 0000 0101
XOR result 1000 0100 1111 1110 Shift 7 0100 0010 1000 0010 1
Shift 7 0100 0010 0111 1111 0 XOR w A001H 1010 0000 0000 0001
Shift 8 0010 0001 0011 1111 1 XOR result 1110 0010 1000 0011
XOR w A001H 1010 0000 0000 0001 Shift 8 0111 0001 0100 0001 1
XOR result 1000 0001 0011 1110 XOR w A001H 1010 0000 0000 0001
XOR result 1101 0001 0100 0000
1101 0001 0100 0000
Perform operations with next data (function code) CRC-16 D 1 4 0
Lower Upper
Continue from here with next data.
Response Data
To be sure that the data is valid, perform a CRC-16 calculation on the response message data as described above.
Compare the result to the CRC-16 checksum that was received within the response message. Both should match.
498 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.8 Message Examples
Loopback Test
Function code 08H performs a loopback test. This test returns a response message with exactly the same content as the
command message and can be used to check communications between the master and slave. User-defined test code and
data values can be set.
The following table shows a message example when performing a loopback test with the slave 1 drive.
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 499
C.8 Message Examples
Note: For the number of bytes in the command message, take double the number of the data quantity.
500 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 501
C.9 MEMOBUS/Modbus Data Table
Monitor Data
Monitor data can be read only.
502 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
0038H PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
Communications
0039H PID Input, 0.1% units, signed, 100% / max. output frequency
003AH PID Output, 0.1% units, signed, 100% / max. output frequency
003BH, 003CH Reserved
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 503
C.9 MEMOBUS/Modbus Data Table
504 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 505
C.9 MEMOBUS/Modbus Data Table
506 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 507
C.9 MEMOBUS/Modbus Data Table
508 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
bit 6 to B Reserved
bit C Multi-Function Digital Input S5
bit D Multi-Function Digital Input S6
bit E Multi-Function Digital Input S7
bit F Multi-Function Digital Input S8
0002H Frequency Reference 30000/100%
C
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 509
C.9 MEMOBUS/Modbus Data Table
510 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.9 MEMOBUS/Modbus Data Table
001BH Motor Switch command input during run (rUn) 0043H Soft Charge Bypass Relay Maintenance Time (LT-3)
Communications
001DH Serial Communication Transmission Error (CALL) 0049H DriveWorksEZ Fault (dWAL)
001EH Undertorque Detection 1 (UL3) 0050H Power Supply Undervoltage (AUv)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 511
C.10 Enter Command
Note: Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The Enter
command registers are write-only. Consequently, if these registers are read, then the register address will be invalid (Error code:
02H). An Enter command is not required if reference or broadcast data are sent to the drive.
512 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
C.11 Communication Errors
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 513
C.12 Self-Diagnostics
C.12 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the
self-diagnosis function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait
at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
YEG_TM
only
514 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Appendix: D
Standards Compliance
This appendix explains the guidelines and criteria for maintaining CE and UL standards.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 515
D.1 Section Safety
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The capacitor for the control power supply remains
charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time
specified on the drive before touching any components.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning
work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
516 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded wire for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting other
devices.
Failure to comply could result in damage to the drive.
If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the
wiring and the selection of the peripheral devices.
Contact your supplier if the cause cannot be identified after checking the above.
Do not restart the drive or immediately operate the peripheral devices if a fuse is blown or equipment for
residual current monitoring/detection (RCM/RCD) is tripped.
Check the wiring and the selection of peripheral devices to identify the cause.
Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified.
Compliance
Standards
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 517
D.2 European Standards
YEC_common
The user(s) is solely responsible for ensuring that the end products used with this drive comply with all applicable
European directives and with other national regulations (if required).
518 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.2 European Standards
A D C
U/T1 U
V/T2 V
M YEC_common
W/T3 W
E
A – Drive D – Metal conduit
B – 10 m max cable length between drive and motor E – Ground wire should be as short as possible.
C – Motor
Figure D.2 Installation Method
4. Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING! Electrical Shock Hazard.
Because the leakage current exceeds 3.5 mA in models CIMR-U40302 and larger, IEC/EN 61800-5-1 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing
conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious
injury.
Figure D.3
A
YEC_common
C B
A – Braided shield cable C – Cable clamp (conductive)
B – Metal panel
Figure D.3 Ground Area
Compliance
Standards
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 519
D.2 European Standards
D
B
C
U1000
E
D I D
F A
A
PE
G
L3
L2 YEC_common
L1
A – Ground the cable shield F – Motor cable (braided shield cable, max. 10 m)
B – Enclosure panel G – Motor
C – Metal plate H – Cable clamp
D – Grounding surface (remove any paint or sealant) I – Ground plate (scrape off any visible paint)
E – Drive
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V/400 V Class)
520 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.3 UL Standards
D.3 UL Standards
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
Figure D.5
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 521
D.3 UL Standards
Table D.2 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Model Terminal Recomm. Gauge Applicable Gauge Screw Tightening Torque
CIMR-U AWG, kcmil AWG, kcmil Size Nm (lb.in.)
R/L1, S/L2, T/L3 14 14 to 8 M5 2.3 to 2.7
U/T1, V/T2, W/T3 14 14 to 8 M5 (20.4 to 23.9)
522 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.3 UL Standards
524 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.3 UL Standards
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 525
D.3 UL Standards
526 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.3 UL Standards
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
Compliance
Standards
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 527
D.3 UL Standards
Enable the motor overload protection (L1-01 = 1 to 6) when connecting the drive to a single motor, unless another motor
overload preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts
off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually
calculated as long as the drive is powered up.
L1-02 Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is
running at 50 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the
set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Figure D.6
10
7
3
Cold start
1
0.4
Hot start
0.1
Motor current (%)
0 100 150 200 E2-01 = 100% motor current
Setting Description
0 Ramp to Stop
1 Coast to Stop
2 Fast-Stop
3 Alarm Only (default setting)
Setting Description
0 Ramp to Stop
1 Coast to Stop (default setting)
2 Fast-Stop
528 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.4 Safe Disable Input Function
Safety Standards
The TUV mark indicates compliance with safety standards.
Figure D.7
Specifications
The Safe Disable inputs provide a stop function in compliance with “Safe Torque Off” as defined in the IEC/EN
61800-5-2. Safe Disable inputs have been designed to meet the requirements of the ISO/EN 13849-1 and IEC/EN 61508.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Table D.7 Specifications for Safe Disable Function
• Input signal specifications
Signal ON level: 18 to 28 Vdc
Signal OFF level: -4 to 4 Vdc
Inputs / Outputs • Inputs: 2
Safe Disable inputs H1, H2
• Outputs: 1
Safe Disable Monitor output EDM (DM+, DM-)
Response Time from Input Open to Drive Output Stop less than 3 ms
Response Time from Input Open of H1 and H2 Terminals to
less than 4 ms
EDM
Demand Rate Low PFD = 8.14E-6
Failure Probability Demand Rate High or
PFH = 1.96E-9
Continuous
The Safe Disable inputs satisfy the following requirements (DC from EDM considered).
Performance Level
Performance Level (PL) e according to ISO/EN 13849-1
HFT (Hardware Fault Tolerance) N=1
Classification of Subsystem Type B
Precautions
DANGER! Sudden Movement Hazard. Improper use of the Safe Disable function will result in serious injury or death. Make sure the
entire system or machinery uses the Safe Disable function in compliance with safety requirements. When implementing the Safe
Disable function into the safety system of a machine, a thorough risk assessment and validation for the whole system must be carried
out to ensure it complies with relevant safety norms (e.g., ISO/EN 13849, IEC/EN 61508, IEC/EN 62061).
DANGER! Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a
break down of two output transistors can cause current to flow through the motor winding, resulting in a rotor movement for a
maximum angle of 180 degrees (electrically). Ensure this condition will not affect the safety of the application when using the Safe
Disable function. Failure to comply will result in death or serious injury.
DANGER! Electrical Shock Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply
Compliance
and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or
Standards
installations on the drive input side as well as the drive output side. Failure to comply will result in death or serious injury.
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 529
D.4 Safe Disable Input Function
WARNING! Sudden Movement Hazard. If the motor is subjected to an external force, use a mechanical brake that meets the safety
requirements of entire system or machinery to stop the machine connected to the load. The motor will move when an external
gravitational force in the vertical axis is applied even if the Safety Disable function is in operation. Failure to comply may result in
serious injury or death.
WARNING! Sudden Movement Hazard. Connect the Safe Disable inputs to the devices in compliance with safety requirements.
Failure to comply will result in death or serious injury.
WARNING! Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals
H1, H2, and HC that were installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can
cause injury or even death.
WARNING! All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating
normally, there is a risk of serious personal injury.
WARNING! Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should
be permitted to wire, inspect, and maintain the Safe Disable input. Failure to comply may result in serious injury or death.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the
Safe Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
NOTICE: When utilizing the Safe Disable function, use only the EMC filters recommended in EMC Filter Installation on page 519.
Main Power
24 Vdc Control
Safety Relay or PLC HC Circuit
with safety functionality
Safety Jumper S3
Outputs Setting:
Feedback
SOURCE
H1 Gate Block 1
H2 Gate Block 2
N.C.
U1000 Slide Switch S6
YEG
Motor
530 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
D.4 Safe Disable Input Function
Motor coasts
Output to stop
Frequency
D
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 531
D.4 Safe Disable Input Function
532 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Appendix: E
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 533
E.1 Drive and Motor Specifications
Items Value
Model CIMR-U
Serial Number
Options used
(Option cards, etc.)
Motor Specifications
Induction Motor
Manufacturer Resolution
Interface – –
534 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
E.2 Basic Parameter Settings
Basic Setup
Item Setting Value Memo Item Setting Value Memo
Control Mode A1-02 = Frequency Reference Source b1-01 =
Normal/Heavy Duty Selection C6-01 = Run Command Source b1-02 =
Motor Setup
Item Setting Value Memo Item Setting Value Memo
Motor Rated Current E2-01 = Number of Motor Poles E2-04 =
Induction
Motor Rated Slip E2-02 = Line-to-Line Resistance E2-05 =
Motor
Motor No-Load Current E2-03 = Motor Leakage Inductance E2-06 =
Motor Code Selection E5-01 = Motor d-Axis Inductance E5-06 =
Motor Rated Power E5-02 = Motor q-Axis Inductance E5-07 =
PM Motor Motor Rated Current E5-03 = Induction Volt. Const.1 E5-09 =
Number of Motor Poles E5-04 = Encoder Z-pulse Offset E5-11 =
Motor Stator Resistance E5-05 = Induction Volt. Const. 2 E5-24 =
S1 H1-01 = S5 H1-05 =
S2 H1-02 = S6 H1-06 =
S3 H1-03 = S7 H1-07 =
S4 H1-04 = S8 H1-08 =
Monitor Outputs
Terminal Output Used Setting Value and Function Name Memo
FM H4-01 =
Quick Reference
AM H4-04 =
MP H6-06 =
Sheet
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 535 E
E.3 User Setting Table
User User
No. Name Setting No. Name Setting
A1-00 Language Selection b3-53 Backspin Search Deceleration Time 2
A1-01 Access Level Selection b4-01 Timer Function On-Delay Time
A1-02 Control Method Selection b4-02 Timer Function Off-Delay Time
A1-03 Initialize Parameters b4-03 H2-01 ON Delay Time
A1-04 Password b4-04 H2-01 OFF Delay Time
A1-05 Password Setting b4-05 H2-02 ON Delay Time
A1-06 Application Preset b4-06 H2-02 OFF Delay Time
A1-07 DriveWorksEZ Function Selection b4-07 H2-03 ON Delay Time
A2-01 to b4-08 H2-03 OFF Delay Time
User Parameters 1 to 32
A2-32 b5-01 PID Function Setting
A2-33 User Parameter Automatic Selection b5-02 Proportional Gain Setting (P)
b1-01 Frequency Reference Selection 1 b5-03 Integral Time Setting (I)
b1-02 Run Command Selection 1 b5-04 Integral Limit Setting
b1-03 Stopping Method Selection b5-05 Derivative Time (D)
b1-04 Reverse Operation Selection b5-06 PID Output Limit
b1-05 Action Selection below Minimum Output Frequency b5-07 PID Offset Adjustment
b1-06 Digital Input Reading b5-08 PID Primary Delay Time Constant
b1-07 LOCAL/REMOTE Run Selection b5-09 PID Output Level Selection
b1-08 Run Command Selection while in Programming Mode b5-10 PID Output Gain Setting
b1-14 Phase Order Selection b5-11 PID Output Reverse Selection
b1-15 Frequency Reference Selection 2 b5-12 PID Feedback Loss Detection Selection
b1-16 Run Command Selection 2 b5-13 PID Feedback Loss Detection Level
b1-17 Run Command at Power Up b5-14 PID Feedback Loss Detection Time
b1-21 Start Condition Selection at Closed Loop Vector Control b5-15 PID Sleep Function Start Level
b1-24 Commercial Power Switching Selection b5-16 PID Sleep Delay Time
Commercial Power Switching Output Frequency b5-17 PID Accel/Decel Time
b1-25
Non-coincidence Level
b5-18 PID Setpoint Selection
Commercial Power Switching Output Frequency
b1-26 b5-19 PID Setpoint Value
Coincidence Level
b2-01 DC Injection Braking Start Frequency b5-20 PID Setpoint Scaling
b2-02 DC Injection Braking Current b5-34 PID Output Lower Limit
b2-03 DC Injection Braking Time at Start b5-35 PID Input Limit
b2-04 DC Injection Braking Time at Stop b5-36 PID Feedback High Detection Level
b2-08 Magnetic Flux Compensation Value b5-37 PID Feedback High Detection Time
b3-01 Speed Search Selection at Start b5-38 PID Setpoint User Display
b3-03 Speed Search Deceleration Time b5-39 PID Setpoint Display Digits
b3-05 Speed Search Delay Time b5-40 Frequency Reference Monitor Content during PID
b3-06 Output Current 1 during Speed Search b5-47 PID Output Reverse Selection 2
Current Control Gain during Speed Search (Speed b6-01 Dwell Reference at Start
b3-08
Estimation Type) b6-02 Dwell Time at Start
b3-10 Speed Search Detection Compensation Gain b6-03 Dwell Reference at Stop
b3-12 Minimum Current Detection Level during Speed Search b6-04 Dwell Time at Stop
b3-14 Bi-Directional Speed Search Selection b7-01 Droop Control Gain
b3-17 Speed Search Restart Current Level b7-02 Droop Control Delay Time
b3-18 Speed Search Restart Detection Time b7-03 Droop Control Limit Selection
b3-19 Number of Speed Search Restarts b8-01 Energy Saving Control Selection
b3-24 Speed Search Method Selection b8-02 Energy Saving Gain
b3-25 Speed Search Wait Time b8-03 Energy Saving Control Filter Time Constant
b3-27 Start Speed Search Select b8-04 Energy Saving Coefficient Value
b3-29 Speed Search Induced Voltage Level b8-05 Power Detection Filter Time
b3-31 Speed Search Operation Current Level 1 (Common) b8-06 Search Operation Voltage Limit
Speed Search Operation Current Level 2 (Current b8-16 Energy Saving Parameter (Ki) for PM Motors
b3-32
Detection 2)
b8-17 Energy Saving Parameter (Kt) for PM Motors
Speed Search Selection when Driving Instruction is Input
b3-33 b9-01 Zero Servo Gain
in Uv
b9-02 Zero Servo Completion Width
b3-50 Backspin Search Direction Judgment Time 1
C1-01 Acceleration Time 1
b3-51 Backspin Search Direction Judgment Time 2
C1-02 Deceleration Time 1
b3-52 Backspin Search Deceleration Time 1
536 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
E.3 User Setting Table
C4-02 Torque Compensation Primary Delay Time d4-06 Frequency Reference Bias (Up/Down 2)
C4-03 Torque Compensation at Forward Start Analog Frequency Reference Fluctuation Limit (Up/Down
d4-07
2)
C4-04 Torque Compensation at Reverse Start
d4-08 Frequency Reference Bias Upper Limit (Up/Down 2)
C4-05 Torque Compensation Time Constant
d4-09 Frequency Reference Bias Lower Limit (Up/Down 2)
C4-07 Motor 2 Torque Compensation Gain
d4-10 Up/Down Frequency Reference Limit Selection
C5-01 ASR Proportional Gain 1
d4-11 Bi-directional Output Selection
C5-02 ASR Integral Time 1
d4-12 Stop Position Gain
C5-03 ASR Proportional Gain 2
d5-01 Torque Control Selection
C5-04 ASR Integral Time 2
d5-02 Torque Reference Delay Time
C5-05 ASR Limit
d5-03 Speed Limit Selection
C5-06 ASR Primary Delay Time Constant
d5-04 Speed Limit
C5-07 ASR Gain Switching Frequency
d5-05 Speed Limit Bias
C5-08 ASR Integral Limit
d5-06 Speed/Torque Control Switchover Time
C5-12 Integral Operation during Accel/Decel
d5-08 Unidirectional Speed Limit Bias
C5-17 Motor Inertia
d6-01 Field Weakening Level
C5-18 Load Inertia Ratio
d6-02 Field Weakening Frequency Limit
C5-21 Motor 2 ASR Proportional Gain 1
d6-03 Field Forcing Selection
C5-22 Motor 2 ASR Integral Time 1
d6-06 Field Forcing Limit
C5-23 Motor 2 ASR Proportional Gain 2
d7-01 Offset Frequency 1
C5-24 Motor 2 ASR Integral Time 2
d7-02 Offset Frequency 2
C5-25 Motor 2 ASR Limit
d7-03 Offset Frequency 3
C5-26 Motor 2 ASR Primary Delay Time Constant
E1-03 V/f Pattern Selection
C5-27 Motor 2 ASR Gain Switching Frequency
E1-04 Maximum Output Frequency
C5-28 Motor 2 ASR Integral Limit
E1-05 Maximum Voltage
C5-32 Integral Operation during Accel/Decel for Motor 2
E1-06 Base Frequency
C5-37 Motor 2 Inertia
E1-07 Middle Output Frequency
C5-38 Motor 2 Load Inertia Ratio
E1-08 Middle Output Frequency Voltage
C6-01 Drive Duty Selection
E1-09 Minimum Output Frequency
C6-02 Carrier Frequency Selection
E1-10 Minimum Output Frequency Voltage
C6-03 Carrier Frequency Upper Limit
E1-11 Middle Output Frequency 2
C6-04 Carrier Frequency Lower Limit
E1-12 Middle Output Frequency Voltage 2
C6-05 Carrier Frequency Proportional Gain
E1-13 Base Voltage
C6-09 Carrier Frequency during Rotational Auto-Tuning
E2-01 Motor Rated Current
C7-43 Input Voltage Offset Adjustment
E2-02 Motor Rated Slip
C7-56 Power Factor Control Selection
E2-03 Motor No-Load Current
C7-60 Output Voltage Limit Mode Selection
E2-04 Number of Motor Poles
d1-01 Frequency Reference 1
E2-05 Motor Line-to-Line Resistance
d1-02 Frequency Reference 2
E2-06 Motor Leakage Inductance
d1-03 Frequency Reference 3
Quick Reference
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 537 E
E.3 User Setting Table
E5-04 Number of Motor Poles (for PM Motors) Multi-Step Speed Enable/Disable Selection when NetRef/
F6-07
ComRef is Selected
E5-05 Motor Stator Resistance (for PM Motors)
F6-08 Reset Communication Parameters
E5-06 Motor d-Axis Inductance (for PM Motors)
F6-10 CC-Link Node Address
E5-07 Motor q-Axis Inductance (for PM Motors)
F6-11 CC-Link Communications Speed
E5-09 Motor Induction Voltage Constant 1 (for PM Motors)
F6-14 CC-Link bUS Error Auto Reset
E5-11 Encoder Z-pulse Offset (for PM Motors)
F6-20 MECHATROLINK Station Address
E5-24 Motor Induction Voltage Constant 2 (for PM Motors)
F6-21 MECHATROLINK Frame Size
Polarity Switch for Initial Polarity Estimation (for PM
E5-25 F6-22 MECHATROLINK Link Speed
Motors)
F1-01 PG 1 Pulses Per Revolution F6-23 MECHATROLINK Monitor Selection (E)
F1-02 Operation Selection at PG Open Circuit (PGo) F6-24 MECHATROLINK Monitor Selection (F)
538 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
E.3 User Setting Table
L3-44
Deceleration
H4-03 Multi-Function Analog Output Terminal FM Bias
Current-limited Maximum S-curve Selection during
Multi-Function Analog Output Terminal AM Monitor L3-45
H4-04 Deceleration
Selection
L4-01 Speed Agreement Detection Level
Sheet
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 539 E
E.3 User Setting Table
L5-01 Number of Auto Restart Attempts n8-45 Speed Feedback Detection Control Gain (for PM Motors)
L5-02 Auto Restart Fault Output Operation Selection Pull-In Current Compensation Time Constant (for PM
n8-47
Motors)
L5-04 Fault Reset Interval Time
n8-48 Pull-In Current (for PM Motors)
L5-05 Fault Reset Operation Selection
d-Axis Current for High Efficiency Control (for PM
L6-01 Torque Detection Selection 1 n8-49
Motors)
L6-02 Torque Detection Level 1 n8-51 Acceleration/Deceleration Pull-In Current (for PM Motors)
L6-03 Torque Detection Time 1 n8-54 Voltage Error Compensation Time Constant
L6-04 Torque Detection Selection 2 n8-55 Load Inertia
L6-05 Torque Detection Level 2 n8-57 High Frequency Injection
L6-06 Torque Detection Time 2 n8-62 Output Voltage Limit (for PM Motors)
L6-08 Mechanical Weakening Detection Operation n8-69 Speed Calculation Gain
L6-09 Mechanical Weakening Detection Speed Level n8-72 Speed Estimation Method Selection
L6-10 Mechanical Weakening Detection Time n8-84 Polarity Judge Current
L6-11 Mechanical Weakening Detection Start Time o1-01 Drive Mode Unit Monitor Selection
L7-01 Forward Torque Limit o1-02 User Monitor Selection After Power Up
L7-02 Reverse Torque Limit o1-03 Digital Operator Display Selection
L7-03 Forward Regenerative Torque Limit o1-04 V/f Pattern Display Unit
L7-04 Reverse Regenerative Torque Limit o1-05 LCD Contrast Control
L7-06 Torque Limit Integral Time Constant o1-10 User-Set Display Units Maximum Value
Torque Limit Control Method Selection during Accel/ o1-11 User-Set Display Units Decimal Display
L7-07
Decel
o2-01 LO/RE (LOCAL/REMOTE) Key Function Selection
L7-16 Torque Limit Process at Start
o2-02 STOP Key Function Selection
L8-02 Overheat Alarm Level
o2-03 User Parameter Default Value
L8-07 Output Phase Loss Protection
o2-04 Drive Model Selection
L8-09 Output Ground Fault Detection Selection
o2-05 Frequency Reference Setting Method Selection
L8-10 Heatsink Cooling Fan Operation Selection
Operation Selection when Digital Operator is
L8-11 Heatsink Cooling Fan Off Delay Time o2-06
Disconnected
L8-12 Ambient Temperature Setting o2-07 Motor Direction at Power Up when Using Operator
L8-15 oL2 Characteristics Selection at Low Speeds o2-19 Selection of Parameter Write During UV
L8-18 Software Current Limit Selection o3-01 Copy Function Selection
L8-19 Frequency Reduction Rate during Overheat Pre-Alarm o3-02 Copy Allowed Selection
L8-27 Overcurrent Detection Gain o4-01 Cumulative Operation Time Setting
L8-29 Current Unbalance Detection (LF2) o4-02 Cumulative Operation Time Selection
L8-32 Cooling Fan Failure Selection o4-03 Cooling Fan Maintenance Operation Time Setting
L8-35 Installation Method Selection o4-05 Capacitor Maintenance Setting
L8-38 Carrier Frequency Reduction Selection o4-07 DC Bus Pre-charge Relay Maintenance Setting
L8-40 Carrier Frequency Reduction Off-Delay Time o4-11 U2, U3 Initialize Selection
L8-41 High Current Alarm Selection o4-12 kWh Monitor Initialization
L8-93 LSo Detection Time at Low Speed o4-13 Number of Run Commands Counter Initialization
L8-94 LSo Detection Level at Low Speed o4-19 Power Unit Price
L8-95 Average LSo Frequency at Low Speed q1-01 to
DriveWorksEZ Parameters
L9-03 Carrier Frequency Reduction Level Selection q6-07
n1-01 Hunting Prevention Selection r1-01 to DriveWorksEZ Connection Parameter 1 to 20 (upper/
r1-40 lower)
n1-02 Hunting Prevention Gain Setting
T1-00 Motor 1/Motor 2 Selection
n1-03 Hunting Prevention Time Constant
T1-01 Auto-Tuning Mode Selection
n1-05 Hunting Prevention Gain while in Reverse
T1-02 Motor Rated Power
n2-01 Speed Feedback Detection Control (AFR) Gain
T1-03 Motor Rated Voltage
n2-02 Speed Feedback Detection Control (AFR) Time Constant 1
T1-04 Motor Rated Current
n3-13 Overexcitation Deceleration Gain
T1-05 Motor Base Frequency
n5-01 Feed Forward Control Selection
T1-06 Number of Motor Poles
n5-02 Motor Acceleration Time
T1-07 Motor Base Speed
n5-03 Feed Forward Control Gain
T1-08 PG Number of Pulses Per Revolution
n6-01 Online Tuning Selection
T1-09 Motor No-Load Current (Stationary Auto-Tuning)
n6-05 Online Tuning Gain
T1-10 Motor Rated Slip (Stationary Auto-Tuning)
n8-01 Initial Rotor Position Estimation Current
T1-11 Motor Iron Loss
n8-02 Pole Attraction Current
T2-01 PM Motor Auto-Tuning Mode Selection
n8-11 Induction Voltage Estimation Gain 2
T2-02 PM Motor Code Selection
n8-14 Polarity Compensation Gain 3
T2-03 PM Motor Type
n8-15 Polarity Compensation Gain 4
T2-04 PM Motor Rated Power
540 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
E.3 User Setting Table
Quick Reference
Sheet
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 541 E
AO-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Aov. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 312
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
542 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Carrier Frequency Reduction . . . . . . . . . . . . . . . . . . . . . . . . . . 447 Copy Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Carrier Frequency Reduction Off-Delay Time. . . . . . . . . . . . . 280 Copy Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133, 294
Carrier Frequency Reduction Selection . . . . . . . . . . . . . . . . . . 279 Copy Function Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Carrier Frequency Selection . . . . . . . . . . . . . . . . . . . 190, 302, 303 Copy Function Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Carrier Frequency Setting Error . . . . . . . . . . . . . . . . . . . . 310, 332 Copy Unit Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Carrier Frequency Upper Limit . . . . . . . . . . . . . . . . . . . . . . . . 190 CopyUnitManager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
CC-Link Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226 CPEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 312, 325 CPF06. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
CE Detection Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493 CPF11 to CPF14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
CE Low Voltage Directive Compliance . . . . . . . . . . . . . . . . . . 518 CPF20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
CF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 312 CPF21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Changing Parameter Settings or Values . . . . . . . . . . . . . . . . . . 101 CPF22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Closed Loop Vector control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 CPF23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Closed Loop Vector Control for PM Motors . . . . . . . . . . . . . . . 30 CPF24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Coast to stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 CPF25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 313
Coast to Stop with Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 CPyE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Command Messages from Master to Drive . . . . . . . . . . . . . . . 496 CRC-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498
Communication Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 CRC-16 Checksum Calculation Example . . . . . . . . . . . . . . . . 498
Communication Fault Detection Selection. . . . . . . . . . . . . . . . 493 CrST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 325
Communication Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . 224 CSEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Communication Option Card Reference . . . . . . . . . . . . . . . . . 461 Cumulative Operation Time. . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Communication Parity Selection . . . . . . . . . . . . . . . . . . . . . . . 492 Cumulative Operation Time at 5th Most Recent Fault . . . . . . 460
Communication Speed of Serial Encoder Selection. . . . . . . . . 221 Cumulative Operation Time at Most Recent Fault . . . . . . . . . 460
Communication Speed Selection . . . . . . . . . . . . . . . . . . . . . . . 492 Cumulative Operation Time at Previous Fault. . . . . . . . . . . . . 459
Communications Enter Function Selection . . . . . . . . . . . . . . . 494 Cumulative Operation Time Selection . . . . . . . . . . . . . . . 294, 453
Communications Error Operation Selection . . . . . . . . . . . . . . 225 Cumulative Operation Time Setting. . . . . . . . . . . . . . . . . 294, 452
Communications Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496 Current Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 327
Comparing Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . 339 Current Detection Error . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 336
Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Current Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Compressor Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Current Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Connected Machinery Vibrates When Motor Rotates . . . . . . . 346 Current Unbalance Detection (LF2). . . . . . . . . . . . . . . . . 278, 447
Connecting a Noise Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 Current-limited Integral Time Constant during Acceleration . 268
Connecting a Surge Absorber. . . . . . . . . . . . . . . . . . . . . . . . . . 389 Current-limited Integral Time Constant during Deceleration . 268
Connecting Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . 377 Current-limited Maximum S-curve Selection during
Connecting to a PC (USB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Connection of a Motor PTC . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 Current-limited Maximum S-curve Selection during
Continuous Electrothermal Operation Selection . . . . . . . . . . . 262 Deceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Control Circuit Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 313 Cyclic Redundancy Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498
Control Circuit Input Terminals . . . . . . . . . . . . . . . . . . . . . . . . . 76 D
Control Circuit Output Terminals. . . . . . . . . . . . . . . . . . . . . . . . 77
D Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Control Circuit Overvoltage . . . . . . . . . . . . . . . . . . . 308, 310, 321
d References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Control Circuit Terminal Arrangement . . . . . . . . . . . . . . . . . . . 77
Daily Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
Control Circuit Terminal Block Functions . . . . . . . . . . . . . . . . . 76
Damping Resistor Overheat . . . . . . . . . . . . . . . . . . . 307, 309, 313
Control Circuit Undervoltage . . . . . . . . . . . . . . . . . . . . . . 310, 330
d-Axis ACR Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
Control Circuit Undervoltage Fault . . . . . . . . . . . . . . . . . 308, 323
d-Axis Current for High Efficiency Control
Control Circuit Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
(for PM Motors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Control Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
DC Bus Pre-Charge Relay Maintenance Setting . . . . . . . . . . . 295
Control Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 312
DC Bus Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Control I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
DC Bus Voltage at Previous Fault . . . . . . . . . . . . . . . . . . . . . . 459
Control Method Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
DC Injection Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
Control Method Selection Error . . . . . . . . . . . . . . . . . . . . . . . . 332
DC Injection Braking at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138, 456
DC Injection Braking Current . . . . . . . . . . . . . . . . . . . . . 154, 347
Control Mode Dependent Parameter Default Values . . . . . . . . 465
DC Injection Braking Input Timing Diagram . . . . . . . . . . . . . 235
Control Mode Mismatch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
DC Injection Braking Start Frequency. . . . . . . . . . . . . . . . . . . 154
Control Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
DC Injection Braking Time at Start . . . . . . . . . . . . . . . . . . . . . 154
Control Modes and their Features . . . . . . . . . . . . . . . . . . . . . . . 30
DC Injection Braking Time at Stop . . . . . . . . . . . . . . . . . . . . . 155
Control Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463, 464
DC Injection Braking to Stop. . . . . . . . . . . . . . . . . . . . . . . . . . 148
Control Power Supply Undervoltage . . . . . . . . . . . . . . . . . . . . 308
Deceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Control Power Supply Voltage Fault . . . . . . . . . . . . . . . . . . . . 323
Deceleration Time at Stall Prevention during
Conveyor Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267, 444
Cooling Fan Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Defaults by Drive Model Selection (o2-04) and
Cooling Fan Maintenance Setting (Operation Time) . . . . . . . . 453
ND/HD (C6-01) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469
Cooling Fan Maintenance Time . . . . . . . . . . . . . . . . . . . . . . . . 327
Delay Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Cooling Fan Operation Time . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Derivative Time (D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Cooling Fan Operation Time Setting . . . . . . . . . . . . . . . . . . . . 295
dEv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 313, 325
CoPy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
DeviceNet Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Copy Allowed Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 543
dFPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 Droop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
DI-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Droop Control Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
DI-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222 Droop Control Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
Diagnosing and Resetting Faults . . . . . . . . . . . . . . . . . . . . . . . 340 Droop Control Limit Selection . . . . . . . . . . . . . . . . . . . . . . . . .175
Digital Input Card Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 222 During commercial power operation . . . . . . . . . . . . . . . . . . . . .246
Digital Input Option Card Input Selection . . . . . . . . . . . . . . . . 222 During Frequency Output Time Chart . . . . . . . . . . . . . . . . . . . .245
Digital Input Option DI-A3 Data Length Selection . . . . . . . . . 222 During Run 2, Motor Switch Command Input . . . . . . . . . . . . .310
Digital Input Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151 During Run Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .237
Digital Input Sink / Source / External Power Supply dv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .313
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 dv2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 dv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
Digital Operator Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 dv3 Detection Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .220
Digital Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532 dv4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
Digital Operator Display Selection . . . . . . . . . . . . . . . . . 290, 451 dv4 Detection Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .220
Digital Operator Installation Methods and Required Tools . . . . 47 dv7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
Digital Operator Keypad Functions . . . . . . . . . . . . . . . . . . . . . 291 dWAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .309, 314
Digital Operator Menu and Screen Structure . . . . . . . . . . . . . . . 98 Dwell Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173, 305
Digital Operator Remote Installation . . . . . . . . . . . . . . . . . . . . . 46 Dwell Reference at Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
Digital Operator Remote Usage . . . . . . . . . . . . . . . . . . . . . . . . . 46 Dwell Reference at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
Digital Output Card Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 224 Dwell Time at Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
Digital Output Option Card Terminal Function Selection . . . . 224 Dwell Time at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
DIP Switch S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 DWEZ Connection Parameters . . . . . . . . . . . . . . . . . . . . . . . . .453
DIP Switch S1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 DWEZ Version Control Monitor 1 to 3 . . . . . . . . . . . . . . . . . . .463
DIP Switch S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 dWF1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
DIP Switch S4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 dWFL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
DIP Switch S4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 E
Disabling and Enabling the Drive Output . . . . . . . . . . . . . . . . 531
E (G). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
DM- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
E3-01 (Motor 2 Control Mode) Dependent Parameters. . . . . . .467
DM+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
EEPROM Write Error . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 315
dnE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 325
EF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .309, 326
DO-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
EF0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 315, 326
DO-A3 Output Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . 224
EF1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
DO-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
EF1 to EF7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 309
doH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 313
EF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Derating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
EF3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Disabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 325
EF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Does Not Allow Selection of Rotational
EF5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
EF6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Duty Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
EF7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99, 100
EF8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .315, 326
Drive Mode Unit Monitor Selection . . . . . . . . . . . . . . . . 290, 451
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Drive Model Mismatch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
EMC Filter and Drive Installation for CE Compliance . . . . . . .520
Drive Model Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
EMC Filter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .519
Drive Models and Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
EMC Guidelines Compliance . . . . . . . . . . . . . . . . . . . . . . . . . .519
Drive Motor Overload Protection . . . . . . . . . . . . . . . . . . . . . . 527
Enclosure Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Drive Operation Status at Previous Fault . . . . . . . . . . . . . . . . . 459
Encoder Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .221
Drive Overheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Encoder Z-Pulse Offset . . . . . . . . . . . . . . . . . . . . . . . . . . .127, 217
Drive Overload. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320
End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .338
Drive Ready . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
End1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311, 334
Drive Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
End2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311, 334
Drive Short-Circuit Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 527
End3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311, 334
Drive Slave Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 492
End4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
End5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
Drive Standard Connection Diagram . . . . . . . . . . . . . . . . . . . . . 59
End6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
Drive Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
End7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
Drive Transmit Wait Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Energy Saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Drive Unit Setting Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Energy Saving Coefficient Value . . . . . . . . . . . . . . . . . . . . . . . .176
Drive Watt Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397
Energy Saving Control Filter Time Constant. . . . . . . . . . . . . . .175
Drive/kVA Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
Energy Saving Control Selection . . . . . . . . . . . . . . . . . . . . . . . .175
DriveWizard Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133, 376
Energy Saving Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
DriveWorksEZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Enter Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .512
DriveWorksEZ Connection Parameters . . . . . . . . . . . . . . . . . . 296
Enter command necessary . . . . . . . . . . . . . . . . . . . . . . . . . . . . .494
DriveWorksEZ Custom Monitor 1 to 10 . . . . . . . . . . . . . . . . . 463
Enter command not necessary . . . . . . . . . . . . . . . . . . . . . . . . . .494
DriveWorksEZ Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Enter Command Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .512
DriveWorksEZ Function Selection . . . . . . . . . . . . . . . . . . . . . 142
Enter Data from the Motor Nameplate . . . . . . . . . . . . . . . . . . .121
DriveWorksEZ Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
Entering the "Safe Torque Off" State . . . . . . . . . . . . . . . . . . . . .531
DriveWorksEZ Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
544 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Er-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 334 Field Forcing Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Er-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Field Forcing Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Er-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Field Weakening. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Er-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Field Weakening Frequency Limit . . . . . . . . . . . . . . . . . . . . . . 204
Er-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Field Weakening Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Er-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Fine-Tuning Advanced Open Loop Vector Control for PM
Er-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Er-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 Fine-Tuning Closed Loop Vector Control . . . . . . . . . . . . . . . . 303
Er-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335 Fine-Tuning Closed Loop Vector Control for PM Motors. . . . 304
Er-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 336 Fine-Tuning Open Loop Vector Control . . . . . . . . . . . . . . . . . 302
Er-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Fine-Tuning Open Loop Vector Control for PM Motors . . . . . 303
Er-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Fine-Tuning V/f Control and V/f Control with PG . . . . . . . . . 302
Er-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 FJOG/RJOG Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Er-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Er-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Formula to calculate the amount of voltage drop. . . . . . . . . . . . 71
Er-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Forward Regenerative Torque Limit . . . . . . . . . . . . . . . . 275, 446
Er-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Forward Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . 274, 446
Er-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Forward/Reverse Run Command Input Error . . . . . . . . . . . . . 326
Er-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Frequency Accuracy (Temperature Fluctuation) . . . . . . . . . . . 395
Er-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337 Frequency Control Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Err . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 315 Frequency Detection 1 Time Chart . . . . . . . . . . . . . . . . . . . . . 239
Error Reading Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339 Frequency Detection 2 Time Chart . . . . . . . . . . . . . . . . . . . . . 240
Error Writing Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 Frequency Detection 3 Example with a Positive L3-04
Errors and Displays When Using the Copy Function . . . . . . . 311 Value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
European Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 518 Frequency Detection 4 Example with Positive L3-04
Excessive Motor Oscillation and Erratic Rotation . . . . . . . . . . 345 Value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Excessive PID Feedback . . . . . . . . . . . . . . . . . 307, 309, 315, 326 Frequency Reduction Rate during Overheat
Excessive Speed Deviation Detection Delay Time . . . . . . . . . 219 Pre-Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278, 447
Excessive Speed Deviation Detection Level . . . . . . . . . . . . . . 219 Frequency Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 456
Excessive V/f Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 334 Frequency Reference at Previous Fault . . . . . . . . . . . . . . . . . . 459
Exhaust Fan Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Frequency Reference at Reference Loss . . . . . . . . . . . . . 270, 445
Exterior and Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . 49 Frequency Reference Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
External 24 Vdc Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . 80 Frequency Reference Bias (Up/Down 2) . . . . . . . . . . . . . . . . . 462
External Digital Operator Connection Fault. . . . . . . . . . . . . . . 321 Frequency Reference Bias Accel/Decel. . . . . . . . . . . . . . . . . . 198
External Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315, 326 Frequency Reference Bias Lower Limit . . . . . . . . . . . . . . . . . 199
External Fault (input terminal S1 to S7). . . . . . . . . . . . . . 307, 309 Frequency Reference Bias Operation Mode Selection . . . . . . 198
External Fault from Comm. Option Detection Selection . . . . . 225 Frequency Reference Bias Step . . . . . . . . . . . . . . . . . . . . . . . . 197
External Fault from Comm. Option Operation Selection. . . . . 225 Frequency Reference Bias Upper Limit. . . . . . . . . . . . . . . . . . 199
External Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Frequency Reference from MEMOBUS/Modbus Comm.. . . . 461
F Frequency Reference Hold. . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Frequency Reference Hold Function Selection . . . . . . . . . . . . 195
Fast Stop Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Frequency Reference Loss Detection Selection. . . . . . . . 269, 445
Fast Stop Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Frequency Reference Lower Limit . . . . . . . . . . . . . . . . . . . . . 194
Fault Causes and Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Frequency Reference Monitor Content During PID . . . . . . . . 172
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Frequency Reference Selection . . . . . . . . . . . . . . . . . . . . . . . . 405
Fault Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 308, 312
Frequency Reference Selection 1. . . . . . . . . . . . . . . . . . . 144, 343
Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297, 340, 460
Frequency Reference Selection 2. . . . . . . . . . . . . . . . . . . . . . . 152
Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Frequency Reference Setting / Decimal Display . . . . . . . . . . . 452
Fault Reset Interval Time . . . . . . . . . . . . . . . . . . . . . . . . . 271, 445
Frequency Reference Setting and User-Set Display . . . . . . . . 452
Fault Reset Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Frequency Reference Setting Hierarchy . . . . . . . . . . . . . . . . . 192
Fault Reset Operation Selection . . . . . . . . . . . . . . . . . . . . 271, 445
Frequency Reference Setting Method Selection . . . . . . . 293, 452
Fault Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Frequency Reference Source Selection . . . . . . . . . . . . . . . . . . 461
Fault Trace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297, 340, 458
Frequency Reference Upper Limit. . . . . . . . . . . . . . . . . . . . . . 194
Fault Trace / History Register Contents . . . . . . . . . . . . . . . . . . 510
Frequency Setting Resolution . . . . . . . . . . . . . . . . . . . . . . . . . 395
Fault Trace Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Frequency Setting Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307
Function Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
FbH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 315, 326
Function Key (F1, F2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
FbL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 316, 326
Function Key 1 (F1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Fdv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 316, 327
Function Key 2 (F2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Feed Forward Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Functions for Terminals S1 to S8. . . . . . . . . . . . . . . . . . . . . . . 227
Feed Forward Control Diagram . . . . . . . . . . . . . . . . . . . . . . . . 283
Feed Forward Control Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 G
Feed Forward Control Selection. . . . . . . . . . . . . . . . . . . . . . . . 283 General Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ferrule Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 GF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 316
Ferrule Terminal Types and Sizes . . . . . . . . . . . . . . . . . . . . . . . 78 Ground Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 316
Ferrule-Type Wire Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Ground Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Field Forcing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 545
H Installation Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
H1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Installing a Leakage Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . .388
H1 Multi-Function Digital Input Selections. . . . . . . . . . . . . . . 432 Installing a Magnetic Contactor. . . . . . . . . . . . . . . . . . . . . . . . .389
H1/H2 Sink/Source Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Installing a Molded Case Circuit Breaker (MCCB). . . . . . . . . .388
H2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Installing a Motor Thermal Overload (oL) Relay on the
H3 Multi-Function Analog Input Settings . . . . . . . . . . . . . . . . 439 Drive Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .390
Hbb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 327 Installing Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . .388
HbbF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 327 Insulation Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Integral Limit Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
HCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 327 Integral Operation during Accel/Decel . . . . . . . . . . . . . . . . . . .187
HD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 Integral Operation during Accel/Decel for Motor 2 . . . . . . . . .189
Heatsink Cooling Fan Off-Delay Time . . . . . . . . . . . . . . . . . . 277 Integral Time Setting (I). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
Heatsink Cooling Fan Operation Delay Time . . . . . . . . . . . . . 447 Interlock Circuit Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Heatsink Cooling Fan Operation Selection . . . . . . . . . . . 277, 447 Internal Resistance Fault . . . . . . . . . . . . . . . . . . . . . . . . . .308, 322
Heatsink Overheat . . . . . . . . . . . . . . . . . . . . . . 308, 309, 319, 328 Inversion Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314
Heatsink Overheat Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 Inversion Prevention Detection . . . . . . . . . . . . . . . . . . . . . . . . .314
Heatsink Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460 IP00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Heavy Duty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189, 392 J
Heavy Duty Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392 Jog Frequency Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .192
High Current Alarm Selection . . . . . . . . . . . . . . . . . . . . . . . . . 280 Jump Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194, 305
High Frequency Injection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 Jump Frequency Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194
High Frequency Injection Amplitude. . . . . . . . . . . . . . . . . . . . 286 Jumper S3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
High Frequency Injection Level. . . . . . . . . . . . . . . . . . . . . . . . 286 Jumper S5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
High Performance Operation Using OLV or CLV . . . . . . . . . . 107 Jumper S5 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Hoist Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Horizontal Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 K
Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Keys and Displays on the Digital Operator . . . . . . . . . . . . . . . . .95
Hunting Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 kWh Monitor Initial Value Selection . . . . . . . . . . . . . . . . . . . . .453
Hunting Prevention Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 kWh Monitor Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . .295
Hunting Prevention Gain Setting . . . . . . . . . . . . . . . . . . . 281, 448 L
Hunting Prevention Gain while in Reverse . . . . . . . . . . . 281, 448 L Protection Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .442
Hunting Prevention Selection. . . . . . . . . . . . . . . . . . . . . . 281, 448 L2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .263
Hunting Prevention Time Constant . . . . . . . . . . . . . . . . . 281, 448 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
HVAC Fan Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
I LCD Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .376
I Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 Leakage Inductance Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
iFEr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 Leakage Inductance Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . .336
IG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 LED Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .460
Incorrect Input Voltage Adjustment . . . . . . . . . . . . . . . . . 310, 333 LF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 316
Induced Noise. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 LF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 316
Induced Voltage Constant Unit Selection. . . . . . . . . . . . . . . . . 127 Line-to-Line Motor Resistance Online Tuning . . . . . . . . . . . . .449
Induction Voltage Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 Line-to-Line Resistance Error . . . . . . . . . . . . . . . . . . . . . .311, 335
Inertia Detection Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 LO/RE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97, 104, 129
Inertia Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 LO/RE (LOCAL/REMOTE) Key Function Selection. . . . . . . .291
Inertia Tuning Frequency Reference . . . . . . . . . . . . . . . . . . . . 128 LO/RE LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
Inertia Tuning Reference Amplitude . . . . . . . . . . . . . . . . . . . . 128 LO/RE Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Load Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .450
Initial Rotor Position Detection Selection . . . . . . . . . . . . . . . . 286 Load Falls When Brake is Applied . . . . . . . . . . . . . . . . . . . . . .345
Initial Rotor Position Estimation Current. . . . . . . . . . . . . . . . . 285 Load Inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .288, 450
Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Load Inertia Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .188
Initialization required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 LOCAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
Initialize Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132, 139 LOCAL/REMOTE Key Function Selection . . . . . . . . . . . . . . .452
Input Power Frequency Fault Detection Gain . . . . . . . . . . . . . 263 LOCAL/REMOTE Run Selection . . . . . . . . . . . . . . . . . . . . . . .151
Input Pulse Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458 Locations of Jumpers and Switches on the Terminal Board . . . .80
Input Terminal Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457 Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .499
Input Terminal Status at Previous Fault . . . . . . . . . . . . . . . . . . 459 Loss of Reference Function . . . . . . . . . . . . . . . . . . . . . . . . . . . .269
Input Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Low Input Voltage Detection Level . . . . . . . . . . . . . . . . . . . . . .263
Input Voltage Offset Adjustment . . . . . . . . . . . . . . . . . . . . . . . 191 Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .527
Inrush Prevention Circuit Fault . . . . . . . . . . . . . . . . . . . . . . . . 323 Low Voltage Wiring for Control Circuit Terminals . . . . . . . . . .527
Inrush Prevention Relay Maintenance Setting . . . . . . . . . . . . . 453 LSo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 317
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352, 353 LT-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .327
install . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 LT-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .327
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 LT-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .328
Installation Method Selection. . . . . . . . . . . . . . . . . . . . . . . . . . 279 M
Installation Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 M1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Installation Orientation and Spacing . . . . . . . . . . . . . . . . . . . . . 42 M2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
546 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
M3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Momentary Power Loss Operation Selection. . . . . . . . . . 262, 443
M4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Momentary Power Loss Ride-Thru . . . . . . . . . . . . . . . . . 262, 395
M5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Momentary Power Loss Ride-Thru Time . . . . . . . . . . . . 263, 443
M6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Momentary Power Loss Voltage Recovery
MA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Acceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263, 443
Magnetic Flux Compensation Value . . . . . . . . . . . . . . . . . . . . 155 Momentary Power Loss Voltage Recovery Ramp
Main Circuit Connection Diagram . . . . . . . . . . . . . . . . . . . . 61, 75 Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263, 443
Main Circuit Protective Cover . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Monitor Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Main Circuit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Monitor Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297, 456
Main Circuit Terminal and Motor Wiring . . . . . . . . . . . . . . . . . 74 Most Recent Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Main Circuit Terminal Functions . . . . . . . . . . . . . . . . . . . . . . . . 70 Motor 1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Main Circuit Terminal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Motor 1/Motor 2 Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Motor 2 ASR Gain Switching Frequency . . . . . . . . . . . . . . . . 188
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354, 355 Motor 2 ASR Integral Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Maintenance Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 Motor 2 ASR Integral Time . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Maintenance Monitor Settings . . . . . . . . . . . . . . . . . . . . . . . . . 294 Motor 2 ASR Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Maintenance Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . 297, 460 Motor 2 ASR Primary Delay Time Constant . . . . . . . . . . . . . . 188
Master Speed Reference Lower Limit . . . . . . . . . . . . . . . . . . . 194 Motor 2 ASR Proportional Gain . . . . . . . . . . . . . . . . . . . . . . . 188
Maximum Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Motor 2 Base Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Maximum Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Motor 2 Base Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
MB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Motor 2 Control Mode Selection . . . . . . . . . . . . . . . . . . . . . . . 213
MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Motor 2 Inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Motor 2 Iron Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Mechanical Weakening Detection . . . . . . . . . . . . . . . . . . . . . . 273 Motor 2 Leakage Inductance . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Mechanical Weakening Detection 1 . . . . . . . . . 308, 310, 320, 328 Motor 2 Line-to-Line Resistance . . . . . . . . . . . . . . . . . . . . . . . 214
Mechanical Weakening Detection 2 . . . . . . . . . . . . . . . . . . . . . 322 Motor 2 Load Inertia Ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Mechanical Weakening Detection Operation . . . . . . . . . . 273, 446 Motor 2 Max Output Frequency. . . . . . . . . . . . . . . . . . . . . . . . 213
Mechanical Weakening Detection Speed Level . . . . . . . . 273, 446 Motor 2 Max Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Mechanical Weakening Detection Start Time . . . . . . . . . 274, 446 Motor 2 Mechanical Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Mechanical Weakening Detection Time. . . . . . . . . . . . . . 274, 446 Motor 2 Mid Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . 213
MECHATROLINK Parameters . . . . . . . . . . . . . . . . . . . . . . . . 226 Motor 2 Mid Output Frequency 2 . . . . . . . . . . . . . . . . . . . . . . 213
MEMOBUS/Modbus Comm. Test Mode Complete . . . . . . . . 329 Motor 2 Mid Output Frequency Voltage . . . . . . . . . . . . . . . . . 213
MEMOBUS/Modbus Communication. . . . . . . . . . . . . . . . . . . . 77 Motor 2 Mid Output Frequency Voltage 2 . . . . . . . . . . . . . . . . 213
MEMOBUS/Modbus Communication Motor 2 Minimum Output Frequency . . . . . . . . . . . . . . . . . . . 213
Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 309, 312, 325 Motor 2 Minimum Output Frequency Voltage. . . . . . . . . . . . . 213
MEMOBUS/Modbus Communication Test Mode Error . . . . . 329 Motor 2 Motor Iron-Core Saturation Coefficient 1 . . . . . . . . . 215
MEMOBUS/Modbus Communications . . . . . . . . . . . . . . . . . . 487 Motor 2 Motor Iron-Core Saturation Coefficient 2 . . . . . . . . . 215
MEMOBUS/Modbus Communications Reference . . . . . . . . . 461 Motor 2 Motor Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
MEMOBUS/Modbus Data Table . . . . . . . . . . . . . . . . . . . . . . . 501 Motor 2 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
MEMOBUS/Modbus Error Code. . . . . . . . . . . . . . . . . . . . . . . 458 Motor 2 Rated Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
MEMOBUS/Modbus Error Codes . . . . . . . . . . . . . . . . . . . . . . 513 Motor 2 Rated No-Load Current . . . . . . . . . . . . . . . . . . . . . . . 214
MEMOBUS/Modbus Setup Parameters. . . . . . . . . . . . . . . . . . 492 Motor 2 Rated Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
MEMOBUS/Modbus Specifications . . . . . . . . . . . . . . . . . . . . 489 Motor 2 Rated Slip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
MEMOBUS/Modbus Switch Settings . . . . . . . . . . . . . . . . . 81, 85 Motor 2 Slip Compensation Gain . . . . . . . . . . . . . . . . . . . . . . 182
MEMOBUS/Modbus Termination . . . . . . . . . . . . . . . . . . . . . . . 85 Motor 2 Slip Compensation Limit . . . . . . . . . . . . . . . . . . . . . . 182
MEMOBUS/Modbus Test Mode Complete . . . . . . . . . . . . . . . 310 Motor 2 Slip Compensation Primary Delay Time . . . . . . . . . . 182
Menu Structure for Digital Operator . . . . . . . . . . . . . . . . . . . . . 98 Motor 2 Slip Compensation Selection during
Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497 Regeneration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Mid Output Voltage A . . . . . . . . . . . . . . . . . . . . . . . . . . . 302, 303 Motor 2 Torque Compensation Gain . . . . . . . . . . . . . . . . . . . . 184
Middle Output Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Motor Acceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Middle Output Frequency 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Motor Base Frequency . . . . . . . . . . . . . . . . . . . . . . . 122, 124, 454
Middle Output Frequency Voltage . . . . . . . . . . . . . . . . . . . . . . 209 Motor Base Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124, 454
Middle Output Frequency Voltage 2 . . . . . . . . . . . . . . . . . . . . 209 Motor Code Selection (for PM Motors). . . . . . . . . . . . . . 216, 473
Minimum Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Motor Data Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 334
Minimum Output Frequency Voltage . . . . . . . . . . . . . . . . . . . . 209 Motor d-Axis Current at Previous Fault. . . . . . . . . . . . . . . . . . 459
Minimum Output Voltage. . . . . . . . . . . . . . . . . . . . . . . . . 302, 303 Motor d-Axis Inductance (for PM Motors) . . . . . . . . . . . . . . . 217
Minimum Wait Time for Sending Messages . . . . . . . . . . . . . . 496 Motor Direction at Power Up when Using Operator . . . . 293, 452
Minor Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309 Motor Direction Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Minor Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 Motor Does Not Rotate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
Minor Fault and Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . 309 Motor Excitation Current (ld) . . . . . . . . . . . . . . . . . . . . . . . . . 462
Minor Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309 Motor Feedback Resolver Interface . . . . . . . . . . . . . . . . . . . . . 376
Minor Faults and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 306, 309 Motor Hunting and Oscillation Control Parameters . . . . . . . . 305
Model Number and Nameplate Check . . . . . . . . . . . . . . . . . . . . 31 Motor Induction Voltage Constant 1 (for PM Motors) . . . . . . 217
Model, Voltage Class, Capacity Mismatch. . . . . . . . . . . . . . . . 338 Motor Induction Voltage Constant 2 (for PM Motors) . . . . . . 217
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Motor Inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128, 188
Momentary Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . 395 Motor Iron Core Saturation Coefficient Error . . . . . . . . . . . . . 311
Momentary Power Loss Minimum Baseblock Time . . . . 263, 443 Motor Iron Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125, 454
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 547
Motor Iron Loss for Torque Compensation . . . . . . . . . . . . . . . 211 Multi-Function Analog Output Terminal FM Signal
Motor Iron-Core Saturation Coefficient. . . . . . . . . . . . . . . . . . 334 Level Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .253
Motor Iron-Core Saturation Coefficient 1 . . . . . . . . . . . . . . . . 211 Multi-Function Analog Outputs. . . . . . . . . . . . . . . . . . . . . . . . .252
Motor Iron-Core Saturation Coefficient 2 . . . . . . . . . . . . . . . . 211 Multi-Function Digital Input Terminal Settings . . . . . . . . . . . .227
Motor is Too Hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344 Multi-Function Digital Inputs . . . . . . . . . . . . . . . . . . . . . . .76, 227
Motor Leakage Inductance. . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 Multi-Function Digital Output . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Motor Line-to-Line Resistance . . . . . . . . . . . . . . . . . . . . . . . . 211 Multi-Function Digital Output Terminal Settings . . . . . . . . . . .237
Motor Mechanical Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 Multi-Function Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . .237
Motor No-Load Current . . . . . . . . . . . . . . . . . . . . . . . . . . 124, 210 Multi-Function Input Selection Error . . . . . . . . . . . . . . . . . . . .331
Motor Overheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 328 Multi-Function Input Setting Error . . . . . . . . . . . . . . . . . . . . . .310
Motor Overheat 1 (PTC input) . . . . . . . . . . . . . . . . . . . . . . . . . 308 Multiple Drive Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Motor Overheat 2 (PTC input) . . . . . . . . . . . . . . . . . . . . . . . . . 308 Multi-Step Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . .192
Motor Overheat Alarm (PTC Input). . . . . . . . . . . . . . . . . . . . . 319 N
Motor Overheat Alarm Operation Selection . . . . . . . . . . 261, 442
n Advanced Performance Set Up . . . . . . . . . . . . . . . . . . . . . . . .448
Motor Overheat Fault (PTC Input). . . . . . . . . . . . . . . . . . . . . . 319
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Motor Overheat Fault Operation Selection . . . . . . . . . . . 261, 442
Navigating the Drive and Programming Modes . . . . . . . . . . . . .99
Motor Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320
ND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189
Motor Overload Estimate (oL1). . . . . . . . . . . . . . . . . . . . . . . . 460
ndAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .338
Motor Overload Protection Selection. . . . . . . . . . . . 257, 442, 527
NEMA Type1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Motor Overload Protection Time . . . . . . . . . . . . . . . 259, 442, 528
NetRef/ComRef Function Selection . . . . . . . . . . . . . . . . . . . . .225
Motor Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Network Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .491
Motor Performance Fine-Tuning . . . . . . . . . . . . . . . . . . . . . . . 302
Noise From the Drive or Output Lines When the Drive
Motor PG Feedback Line Driver Interface . . . . . . . . . . . . . . . 376
is Powered On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .346
Motor PG Feedback Open Collector Interface. . . . . . . . . . . . . 376
No-Load Current Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
Motor Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
No-Load Current Error. . . . . . . . . . . . . . . . . . . . . . . . . . . .311, 335
Motor Produces Insufficient Torque. . . . . . . . . . . . . . . . . . . . . 346
No-Load Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
No-Load Operation Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . .129
Motor Protection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Normal Duty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189, 392
Motor Protection Using a Positive Temperature
Normal Duty Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .392
Coefficient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Notes on Controlling the Brake when Using the Hoist
Motor PTC Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Application Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
Motor q-Axis Current at Previous Fault. . . . . . . . . . . . . . . . . . 459
Notes on Inertia Tuning and ASR Gain Auto-Tuning . . . . . . . .120
Motor q-Axis Inductance (for PM Motors) . . . . . . . . . . . . . . . 217
Notes on Motor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Motor Rated Current . . . . . . . . . . . . 122, 124, 210, 216, 454, 527
Notes on Rotational Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . .119
Motor Rated Power . . . . . . . . . . . . . . . . . . . . . 123, 212, 216, 454
Notes on Stationary Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . .119
Motor Rated Slip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124, 210
nSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307
Motor Rated Voltage . . . . . . . . . . . . . . . . . . . . . . . . 122, 123, 454
Number of Auto Restart Attempts . . . . . . . . . . . . . . . . . . .270, 445
Motor Rotates After the Drive Output is Shut Off. . . . . . . . . . 347
Number of Motor Poles . . . . . . . . . . . . . . . . . . .124, 210, 216, 454
Motor Rotates Faster Than the Frequency Reference . . . . . . . 345
Number of PM Motor Poles. . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Motor Rotates in One Direction Only . . . . . . . . . . . . . . . . . . . 344
Number of Run Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . .460
Motor Secondary Current (Iq) . . . . . . . . . . . . . . . . . . . . . . . . . 462
Number of Run Commands Counter Initialization . . . . . . . . . .296
Motor Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Number of Speed Search Restarts . . . . . . . . . . . . . . . . . . . . . . .159
Motor Selection 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Motor Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456 O
Motor Speed at Previous Fault . . . . . . . . . . . . . . . . . . . . . . . . . 459 oC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 317
Motor Speed Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311 oFA00. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 317
Motor Speed Error 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 oFA01. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 318
Motor Speed Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 oFA03 to oFA06. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Motor Stalls During Acceleration or With Large Loads . . . . . 345 oFA10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Motor Stator Resistance (for PM Motors) . . . . . . . . . . . . . . . . 216 oFA11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Motor Switch during Run. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329 oFA12 to oFA17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Motor Temperature Input Filter Time . . . . . . . . . . . . . . . 261, 442 oFA30 to oFA43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307, 318
Motor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 oFb00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
MP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 oFb01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Input Selection Error . . . . . . . . . 310, 332 oFb02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Input Terminal Settings . . . . . . . . . . . 250 oFb03 to oFb11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 247 oFb12 to oFb17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Output Terminal AM Bias . . . . . . . . . 253 oFC00. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Output Terminal AM Gain . . . . . . . . . 253 oFC01. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
Multi-Function Analog Output Terminal AM Monitor oFC02. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .319
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 oFC03 to oFC11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .319
Multi-Function Analog Output Terminal AM Signal oFC12 to oFC17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .319
Level Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253 Offset Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205, 463
Multi-Function Analog Output Terminal FM Bias . . . . . . . . . 253 oH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .308, 309, 319, 328
Multi-Function Analog Output Terminal FM Gain . . . . . . . . . 253 oH1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .308, 319
Multi-Function Analog Output Terminal FM Monitor oH2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .309, 328
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 oH3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .308, 309, 319, 328
548 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
oH4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 319 Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
oL1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320 Output Current 1 During Speed Search . . . . . . . . . . . . . . . . . . 158
oL2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320, 347 Output Current at Previous Fault . . . . . . . . . . . . . . . . . . . . . . . 459
oL2 Characteristics Selection at Low Speeds . . . . . . . . . 277, 447 Output Current Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oL3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 309, 320, 328 Output Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
oL4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 309, 320, 328 Output Frequency after Soft Start . . . . . . . . . . . . . . . . . . . . . . 457
oL5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 320, 328 Output Frequency at Previous Fault. . . . . . . . . . . . . . . . . . . . . 459
Online Tuning Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285 Output Frequency is not as High as Frequency Reference . . . 347
Online Tuning Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 Output Frequency Reduction During Overheat Alarm . . . . . . 276
oPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 Output Frequency Resolution . . . . . . . . . . . . . . . . . . . . . . . . . 395
oPE Fault Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331, 457 Output Ground Fault Detection Selection . . . . . . . . . . . . 277, 447
oPE01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 331 Output of speed control (ASR) (for Simple V/f PG) . . . . . . . . 462
oPE02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 331 Output Phase Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 316
oPE03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 331 Output Phase Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . 447
oPE04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 331 Output Phase Loss Protection Selection . . . . . . . . . . . . . . . . . 276
oPE05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
oPE06 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Power at Previous Fault . . . . . . . . . . . . . . . . . . . . . . . . 459
oPE07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Terminal Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
oPE08 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Terminal Status at Previous Fault. . . . . . . . . . . . . . . . . 459
oPE09 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Voltage at Previous Fault . . . . . . . . . . . . . . . . . . . . . . . 459
oPE10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Voltage Limit (for PM Motors) . . . . . . . . . . . . . . . . . . 289
oPE11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332 Output Voltage Limit Mode Selection . . . . . . . . . . . . . . . . . . . 191
oPE13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 Output Voltage Limit Operation Selection. . . . . . . . . . . . . . . . 181
oPE15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 Output Voltage Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
oPE18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 Output Voltage Reference (Vd) . . . . . . . . . . . . . . . . . . . . . . . . 462
oPE20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 Output Voltage Reference (Vq) . . . . . . . . . . . . . . . . . . . . . . . . 462
oPE30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 ov . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 321, 329
Open Loop Vector Control . . . . . . . . . . . . . 30, 303, 312, 345, 346 ov Suppression Function Selection . . . . . . . . . . . . . . . . . . . . . 444
Open Loop Vector Control for IPM Motors . . . . . . . . . . . . . . . . 30 Overcurrent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 317
Open Loop Vector Control for PM Motors . . . . . . . . . . . . . . . . 30 Overcurrent Detection Gain . . . . . . . . . . . . . . . . . . . . . . . 278, 447
Open Loop Vector Control Mode Tuning. . . . . . . . . . . . . . . . . 302 Overexcitation Deceleration. . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Open Loop Vector Control Mode Tuning Parameters . . . 303, 304 Overexcitation Deceleration Gain . . . . . . . . . . . . . . 282, 317, 449
Open Loop Vector Control Mode Tuning Overheat 1 (Heatsink Overheat). . . . . . . . . . . . . . . . . . . . . . . . 319
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302, 303, 304 Overheat Alarm Level . . . . . . . . . . . . . . . . . . . . . . . . . . . 275, 447
Operating with the Load Connected. . . . . . . . . . . . . . . . . . . . . 131 Overheat Pre-Alarm Operation Selection . . . . . . . . . . . . 275, 447
Operation Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 310 Overspeed (for Control Mode with PG). . . . . . . . . . . . . . 321, 329
Operation Selection at Deviation (dEv) . . . . . . . . . . . . . . . . . . 219 Overspeed (for Simple V/f with PG) . . . . . . . . . . . . . . . . . . . . 310
Operation Selection at Overspeed (oS) . . . . . . . . . . . . . . . . . . 218 Overspeed Detection Delay Time . . . . . . . . . . . . . . . . . . . . . . 218
Operation Selection at PG Open Circuit (PGo) . . . . . . . . . . . . 218 Overspeed Detection Level . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Operation Selection when Digital Operator is Overtorque 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 328
Disconnected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293, 452 Overtorque 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309, 328
Operation Status Monitors . . . . . . . . . . . . . . . . 297, 298, 456, 462 Overtorque Detection 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320
Operation with Permanent Magnet Motors . . . . . . . . . . . . . . . 108 Overtorque Detection 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 320
Operator Connection Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 Overtorque Detection Operation . . . . . . . . . . . . . . . . . . . . . . . 271
Operator Programming Errors . . . . . . . . . . . . . . . . . . . . . . . . . 331 Overvoltage Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Operator Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 451 P
Operator Related Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
P Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
oPr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 321
Parameter Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Option Card Communications Error . . . . . . . . . . . . . . . . . . . . 309
Parameter Range Setting Error. . . . . . . . . . . . . . . . . . . . . . . . . 331
Option Card Connection Error at Option Port CN5-A. . . . . . . 317
Parameter Selection Error . . . . . . . . . . . . . . . . . . . . . . . . 310, 332
Option Card Connection Error at Option Port CN5-C . . . . . . . 318
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Option card error occurred at option port CN5-A . . . . . . . . . . 318
Parameters that Change with the Motor Code Selection
Option card error occurred at option port CN5-B . . . . . . . . . . 318
(for PM Motors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
Option card error occurred at option port CN5-C . . . . . . . . . . 319
Parameters to Minimize Motor Hunting and Oscillation . . . . . 305
Option Card External Fault . . . . . . . . . . . . . . . . . . . 307, 315, 326
PASS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 329
Option Card Fault at Option Port CN5-A. . . . . . . . . . . . . . . . . 318
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132, 140
Option Card Fault at Option Port CN5-B. . . . . . . . . . . . . . . . . 318
Password Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Option Card Fault at Option Port CN5-C. . . . . . . . . . . . . 318, 319
Password Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Option Card Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
Peak Hold Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Option Communication Error. . . . . . . . . . . . . . . . . . 307, 312, 324
Peak Hold Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Option Frequency Reference . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Performance Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
Option Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Performance Life Monitors Maintenance Monitors. . . . . . . . . 354
Option Unit Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Periodic Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Periodic Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
oS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 321, 329
Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Oscillation or Hunting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 549
Permanent Magnet Motor Control . . . . . . . . . . . . . . . . . . . . . . 108 PID Setpoint Display Digits. . . . . . . . . . . . . . . . . . . . . . . . . . . .172
PG 1 Division Rate for PG Pulse Monitor . . . . . . . . . . . . . . . . 219 PID Setpoint Input Methods . . . . . . . . . . . . . . . . . . . . . . . . . . .165
PG 1 Gear Teeth 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PID Setpoint Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
PG 1 Gear Teeth 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PID Setpoint Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
PG 1 Pulses Per Revolution . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 PID Setpoint User Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . .172
PG 1 Rotation Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PID Setpoint Value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
PG 1 Signal Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 PID Sleep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170
PG 2 Division Rate for PG Pulse Monitor . . . . . . . . . . . . . . . . 219 PID Sleep Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
PG 2 Gear Teeth 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PID Sleep Function Start Level . . . . . . . . . . . . . . . . . . . . . . . . .171
PG 2 Gear Teeth 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PM Inductance Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .336
PG 2 Pulses Per Revolution . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 PM Motor Auto-Tuning Mode Selection. . . . . . . . . . . . . . . . . .125
PG 2 Rotation Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 PM Motor Base Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG 2 Signal Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 PM Motor Base Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Disconnect (for any control modes using a PG option PM Motor Code Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
card) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 PM Motor Control Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .285
PG Disconnect (for Control Mode with PG) . . . . . . . . . . . . . . 329 PM Motor d-Axis Inductance . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Disconnect (for Simple V/f with PG). . . . . . . . . . . . . 308, 310 PM Motor Induced Voltage Constant. . . . . . . . . . . . . . . . . . . . .127
PG Hardware Fault (detected when using a PG-X3 option PM Motor Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . .117
card) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321, 329 PM Motor q-Axis Inductance . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Number of Pulses Per Revolution . . . . . . . . . . . . . . . . . . . 124 PM Motor Rated Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Number of Pulses Per Revolution for PM Motor PM Motor Rated Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 PM Motor Rated Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Open-Circuit Detection Time. . . . . . . . . . . . . . . . . . . . . . . 218 PM Motor Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216
PG Option Card Disconnection Detection 1 . . . . . . . . . . . . . . 220 PM Motor Stator Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . .126
PG Option Card Disconnection Detection 2 . . . . . . . . . . . . . . 220 PM Motor Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
PG Option Card Port for Motor 2 Selection. . . . . . . . . . . . . . . 220 PM Stationary Auto-Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . .117
PG Speed Control Card Settings . . . . . . . . . . . . . . . . . . . . . . . 218 PM Stationary Auto-Tuning for Stator Resistance . . . . . . . . . .117
PG-B3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Pole Attraction Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .285
PG-B3 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 Power Detection Filter Time . . . . . . . . . . . . . . . . . . . . . . . . . . .176
PG-F3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Power Factor Control Selection . . . . . . . . . . . . . . . . . . . . . . . . .191
PG-F3 Setting Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 333 Power Ratings (Three-Phase 200 V Class) . . . . . . . . . . . . . . . .393
PGo. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 321, 329 Power Ratings (Three-Phase 400 V Class) . . . . . . . . . . . . . . . .394
PGoH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321, 329 Power Supply Frequency Fault . . . . . . . . . . . . .307, 309, 316, 327
PGoH Detection Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221 Power Supply Frequency Fault Detection Width. . . . . . . . . . . .263
PG-RT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Power Supply Overvoltage . . . . . . . . . . . . . . . . . . . . . . . .307, 312
PG-X3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Power Supply Undervoltage . . . . . . . . . . . . . . . . . . .307, 309, 312
PG-X3 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 Power Unit Price . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .296
Phase Order Detection Fault . . . . . . . . . . . . . . 308, 310, 322, 329 Powering Up the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Phase Order Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Predefined V/f Patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
PID Accel/Decel Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
PID Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166 Preparing the Ends of Shielded Cables . . . . . . . . . . . . . . . . . . . .79
PID Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 Preset Reference Timing Diagram . . . . . . . . . . . . . . . . . . . . . . .193
PID Control Selection Error. . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Previous Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .459
PID Control Selection Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 PROFIBUS-DP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . .226
PID Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461 Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99, 100
PID Feedback High Detection Level . . . . . . . . . . . . . . . . . . . . 170 Proportional Gain Setting (P). . . . . . . . . . . . . . . . . . . . . . . . . . .167
PID Feedback High Detection Time . . . . . . . . . . . . . . . . . . . . 170 Protecting cover to prevent miswiring . . . . . . . . . . . . . . . . . . . . .38
PID Feedback Input Methods. . . . . . . . . . . . . . . . . . . . . . . . . . 165 PTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .260
PID Feedback Loss. . . . . . . . . . . . . . . . . . . . . . 307, 309, 316, 326 Pull-In Current (for PM Motors) . . . . . . . . . . . . . . . . . . . .287, 450
PID Feedback Loss Detection Selection . . . . . . . . . . . . . . . . . 169 Pull-In Current Compensation Time Constant
PID Feedback Low Detection Level . . . . . . . . . . . . . . . . . . . . 170 (for PM Motors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .287, 450
PID Feedback Low Detection Time . . . . . . . . . . . . . . . . . . . . . 170 Pull-In Current during Accel/Decel for PM. . . . . . . . . . . . . . . .322
PID Fine Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Pull-In Current Level for PM Motor Tuning . . . . . . . . . . . . . . .127
PID Function Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Pull-Out Detection . . . . . . . . . . . . . . . . . . . . . . . . . . .280, 308, 322
PID Input (feedback) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461 Pull-Out Detection Level at Low Speed . . . . . . . . . . . . . . . . . .280
PID Input Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 Pull-Out Detection Time at Low Speed . . . . . . . . . . . . . . . . . . .280
PID Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297, 461 Pull-Out Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .280
PID Offset Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Pull-put. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .317
PID Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461 Pulse Monitor Selection Error . . . . . . . . . . . . . . . . . . . . . . . . . .333
PID Output Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346 Pulse Output Connection Using External Voltage Supply. . . . . .82
PID Output Gain Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Pulse Output Connection Using Internal Voltage Supply . . . . . .82
PID Output Level Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Pulse Train Input Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255
PID Output Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Pulse Train Input Filter Time . . . . . . . . . . . . . . . . . . . . . . . . . . .255
PID Output Lower Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 Pulse Train Input Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255
PID Output Reverse Selection . . . . . . . . . . . . . . . . . . . . . . . . . 168 Pulse Train Input Minimum Frequency . . . . . . . . . . . . . . . . . . .256
PID Primary Delay Time Constant . . . . . . . . . . . . . . . . . . . . . 168 Pulse Train Input Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255
PID Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461 Pulse Train Input Terminal RP Function Selection . . . . . . . . . .254
550 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Pulse Train Input/Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254 RUN Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Pulse Train Monitor Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . 256 Run Speed after Soft Starter at Previous Fault. . . . . . . . . . . . . 459
Pulse Train Monitor Selection . . . . . . . . . . . . . . . . . . . . . . . . . 256 S
Q S- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
q-axis ACR Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462 S+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
R S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
R- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
R+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
S4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Ramp to stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
S5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Rated Current Depending on Carrier Frequency . . . . . . . . . . . 398
S6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Rated Current Setting Alarm . . . . . . . . . . . . . . . . . . . . . . 311, 334
S7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Rated Slip Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311, 335
S8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
rdEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Safe Disable Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Safe Disable Function Wiring Example (Source Mode) . . . . . 530
rEAd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Safe Disable Input Function. . . . . . . . . . . . . . . . . . . . . . . . . . . 529
Reading Drive MEMOBUS/Modbus Register Contents . . . . . 499
Safe Disable Input Sink / Source / External Power Supply
Reading Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Reattaching the Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . 67
Safe Disable Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Reattaching the Front Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Safe Disable Monitor Output Function and Digital
Reattaching the Terminal Cover on an IP00 Enclosure
Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 531
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Safe Disable Signal Input. . . . . . . . . . . . . . . . . . . . . . . . . 309, 327
Reattaching the Terminal Cover on an IP20/NEMA Type 1
Safe Disable Status Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . 531
Enclosure Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Safe Torque Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 531
Reattaching the Top Protective Cover . . . . . . . . . . . . . . . . . . . . 69
Safety Circuit Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 321
REMOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Safety Hazard Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Removing the Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . 67
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Removing the Front Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Safety Input and EDM Terminal Status . . . . . . . . . . . . . . . . . . 531
Removing the Terminal Cover on an IP00 Enclosure
Safety Monitor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Save Disable Signal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Removing the Terminal Cover on an IP20/NEMA Type 1
SC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Enclosure Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SCF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 321
Removing the Top Protective Cover . . . . . . . . . . . . . . . . . . . . . 69
S-Curve Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 180, 305
Removing Wires from the Terminal Board . . . . . . . . . . . . . . . . 79
SE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 329
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
Search Operation Voltage Limit . . . . . . . . . . . . . . . . . . . . . . . . 176
Replacing the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Self-diagnosing function of the serial communication
Reset Communication Parameters . . . . . . . . . . . . . . . . . . . . . . 226
interface circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 514
Resistance Tuning Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
SEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 321
Response Messages from Drive to Master . . . . . . . . . . . . . . . . 496
Serial Communication Terminals. . . . . . . . . . . . . . . . . . . . . . . . 77
Returning to Normal Operation after Safe Disable . . . . . . . . . 531
Serial Communication Transmission Error . . . . . . . . . . . 309, 324
Reverse Direction Output Example Time Chart. . . . . . . . . . . . 243
Serial Communications Cable Connection Terminals
Reverse Operation Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 149
(TB5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
Reverse Prohibited Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Serviceable Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Reverse Regenerative Torque Limit . . . . . . . . . . . . . . . . . 275, 446
Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Reverse Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275, 446
Setup Group Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Rotational Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . 116, 119
Setup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Rotational Auto-Tuning for V/f Control . . . . . . . . . . . . . . . . . 116
Shielded Twisted-Pair Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . 79
RP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Simple Motor Setup Using V/f Control . . . . . . . . . . . . . . . . . . 106
RS-422 Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
Simple Positioning Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
RS-422/485 Termination Resistor . . . . . . . . . . . . . . . . . . . . . . . 80
Simplified Setup Using the Setup Group . . . . . . . . . . . . . . . . . 103
RS-485 Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
Sinking Mode (NPN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
RTS Control Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Sinking/Sourcing Mode Selection for Safe Disable Inputs . . . . 81
rUn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 329
Sinking/Sourcing Mode Switch for Digital Inputs. . . . . . . . . . . 80
Run Command at Power Up. . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Slave Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
Run Command Input Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Slip Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Run Command Method Selection . . . . . . . . . . . . . . . . . . . . . . 494
Slip Compensation Gain . . . . . . . . . . . . . . . . . . . . . . . . . 180, 302
Run Command Selection . . . . . . . . . . . . . . . . . . . . . . . . . 343, 405
Slip Compensation Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Run Command Selection 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Slip Compensation Primary Delay Time . . . . . . . . . . . . . 181, 302
Run Command Selection 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Slip Compensation Selection during Regeneration . . . . . . . . . 181
Run Command Selection Error . . . . . . . . . . . . . . . . . . . . . . . . 310
SN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Run command selection while in Programming Mode . . . . . . 152
Snubber Discharge Resistor Overheat . . . . . . . . . . . . . . . 308, 322
Run Command Source Selection . . . . . . . . . . . . . . . . . . . . . . . 461
Soft Charge Bypass Relay Maintenance . . . . . . . . . . . . . . . . . 460
Run Command/Frequency Reference Source Selection
Soft Charge Bypass Relay Maintenance Time. . . . . . . . . . . . . 328
Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Soft Charge Circuit Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
RUN LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Soft CLA Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
RUN LED and Drive Operation . . . . . . . . . . . . . . . . . . . . . . . . . 97
Software Current Limit Selection . . . . . . . . . . . . . . . . . . . . . . 278
RUN LED Status and Meaning . . . . . . . . . . . . . . . . . . . . . . . . . 97
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 551
Software No. (Flash) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458 Stator Resistance Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .336
Software No. (ROM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458 Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Software version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 STo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .308, 322
SoH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 322 STOP button Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311, 335
Sourcing Mode (PNP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 STOP Key Function Selection . . . . . . . . . . . . . . . . . . . . . .292, 452
SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Stop Position Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
Speed Agree 1 Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238 Stopping Method after Communication Error . . . . . . . . . . . . . .492
Speed Agree 2 Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Stopping Method Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . .146
Speed Agree Detection Selection. . . . . . . . . . . . . . . . . . . . . . . 270 Storage Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Speed Agreement Detection Level. . . . . . . . . . . . . . . . . . 269, 445 SvE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .322
Speed Agreement Detection Level (+/-) . . . . . . . . . . . . . 269, 445 Switches and Jumpers on the Terminal Board . . . . . . . . . . . . . . .80
Speed Agreement Detection Width . . . . . . . . . . . . . . . . . 269, 445 Switching Between LOCAL and REMOTE . . . . . . . . . . . . . . .104
Speed Agreement Detection Width (+/-) . . . . . . . . . . . . . 269, 445 Switching Between Torque and Speed Control . . . . . . . . . . . . .202
Speed Control Accuracy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395 T
Speed Control Integral Time 1 . . . . . . . . . . . . . . . . . . . . . . . . . 329
T Motor Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .453
Speed Control Loop Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . 118
Task Complete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .338
Speed Control Proportional Gain 1 . . . . . . . . . . . . . . . . . . . . . 329
Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .399
Speed Control Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Terminal A1 Bias Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .247
Speed Deviation (for Control Mode with PG) . . . . . . . . . . . . . 313
Terminal A1 Function Selection . . . . . . . . . . . . . . . . . . . . . . . .247
Speed Deviation (for Simple V/f with PG) . . . . . . . . . . . 307, 309
Terminal A1 Gain Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .247
Speed Deviation (when using a PG option card) . . . . . . . . . . . 325
Terminal A1 Signal Level Selection . . . . . . . . . . . . . . . . . . . . .247
Speed Feedback Detection Contol (AFR) Tuning . . . . . . . . . . 281
Terminal A2 Bias Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249
Speed Feedback Detection Control (AFR) Gain . . . . . . . 282, 448
Terminal A2 Function Selection . . . . . . . . . . . . . . . . . . . . . . . .249
Speed Feedback Detection Control (AFR) Time
Terminal A2 Gain Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249
Constant 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282, 449
Terminal A2 Input Signal Selection. . . . . . . . . . . . . . . . . . . . . . .82
Speed Feedback Detection Control Gain
Terminal A2 Signal Level Selection . . . . . . . . . . . . . . . . . . . . .248
(for PM Motors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287, 450
Terminal A3 Analog/PTC Input Selection. . . . . . . . . . . . . . . . . .83
Speed Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Terminal A3 Bias Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .248
Speed Limit Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 204
Terminal A3 Function Selection . . . . . . . . . . . . . . . . . . . . . . . .248
Speed Limit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Terminal A3 Gain Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .248
Speed Limitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Terminal A3 Signal Level Selection . . . . . . . . . . . . . . . . . . . . .248
Speed Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Terminal AM/FM Signal Selection . . . . . . . . . . . . . . . . . . . . . . .83
Speed Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155, 321
Terminal Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38, 369
Speed Search Deceleration Time . . . . . . . . . . . . . . . . . . . . . . . 158
Terminal Board not connected . . . . . . . . . . . . . . . . . . . . . . . . . .307
Speed Search Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Terminal Board Wiring Guide . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Speed Search Detection Compensation Gain. . . . . . . . . . . . . . 159
Terminal Connections for Communication
Speed Search Estimation Type . . . . . . . . . . . . . . . . . . . . . . . . . 320
Self-Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .514
Speed Search Method Selection. . . . . . . . . . . . . . . . . . . . . . . . 159
Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Speed Search Operation Current Level 1
Terminal M1-M2 Function Selection. . . . . . . . . . . . . . . . . . . . .237
(Current Detection Type 2). . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Terminal M1-M2 Output Selection . . . . . . . . . . . . . . . . . . . . . .224
Speed Search Operation Current Level 2
Terminal M3-M4 Function Selection. . . . . . . . . . . . . . . . . . . . .237
(Current Detection 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Terminal M3-M4 Output Selection . . . . . . . . . . . . . . . . . . . . . .224
Speed Search Restart Current Level. . . . . . . . . . . . . . . . . . . . . 159
Terminal M5-M6 Function Selection. . . . . . . . . . . . . . . . . . . . .237
Speed Search Restart Detection Time . . . . . . . . . . . . . . . . . . . 159
Terminal P1-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
Speed Search Selection at Start . . . . . . . . . . . . . . . . . . . . . . . . 158
Terminal P2-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
Speed Search Wait Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Terminal P3-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
Speed/Torque Control Switchover Time . . . . . . . . . . . . . . . . . 204
Terminal P4-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
SrC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 322, 329
Terminal P5-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
Srr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 322
Terminal P6-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . .224
Stall Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264, 305
Terminal V1 Monitor Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Detection Time . . . . . . . . . . . . . . . . . . . . . . . 268
Terminal V1 Monitor Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention during Deceleration . . . . . . . . . . . . . . . . . . . . 320
Terminal V1 Monitor Selection . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Level during Acceleration . . . . . . . . . . . . . . . 444
Terminal V1 Signal Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Level during Run . . . . . . . . . . . . . . . . . . 267, 444
Terminal V2 Monitor Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Limit during Acceleration . . . . . . . . . . . 265, 444
Terminal V2 Monitor Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Selection during Acceleration . . . . . . . . 264, 443
Terminal V2 Monitor Selection . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Selection during Deceleration . . . . . . . . 266, 444
Terminal V2 Signal Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223
Stall Prevention Selection during Run . . . . . . . . . . . . . . . 267, 444
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Standard Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119, 121, 122, 129
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Test Run Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
Starting Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Test Run with Load Connected . . . . . . . . . . . . . . . . . . . . . . . . .131
Start-Up Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Tightening Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Station Address Setting Error
Timer Function Off-Delay Time . . . . . . . . . . . . . . . . . . . . . . . .163
(CC-Link, CANopen, MECHATROLINK) . . . . . . . . . . . . . . . 324
Timer Function On-Delay Time. . . . . . . . . . . . . . . . . . . . . . . . .163
Stationary Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Too Many Speed Search Restarts. . . . . . . . . . . . . . . . . . . .308, 321
Stationary Auto-Tuning 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Top Protective Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Stationary Auto-Tuning for Line-to-Line Resistance. . . . . . . . 116
552 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Top Protective Covers, Reattaching . . . . . . . . . . . . . . . . . . . . . . 66 Unit Capacity Setting Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Top Protective Covers, Removing . . . . . . . . . . . . . . . . . . . . 65, 66 Unit Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Torque Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 Unit Selection for MEMOBUS/Modbus Register 0025H . . . . 494
Torque Compensation at Forward Start . . . . . . . . . . . . . . . . . . 183 Unstable Motor Speed when Using PM. . . . . . . . . . . . . . . . . . 347
Torque Compensation at Reverse Start . . . . . . . . . . . . . . . . . . 183 Up/Down 2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Torque Compensation Gain . . . . . . . . . . . . . . . . . . . . . . . 183, 302 Up/Down 2 Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Torque Compensation Primary Delay Time . . . . . . . . . . . 183, 302 Up/Down Command Operation . . . . . . . . . . . . . . . . . . . . . . . . 231
Torque Compensation Primary Delay Time Constant 1. . . . . . 302 Up/Down Frequency Reference Limit Selection . . . . . . . . . . . 199
Torque Compensation Time Constant . . . . . . . . . . . . . . . . . . . 184 USB Copy Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133, 376
Torque Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 USB port (type-B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Torque Control Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . 200 User Monitor Selection after Power Up. . . . . . . . . . . . . . 290, 451
Torque Control Input Value Selection . . . . . . . . . . . . . . . . . . . 201 User Parameter Automatic Selection . . . . . . . . . . . . 132, 143, 404
Torque Control Reference Sources. . . . . . . . . . . . . . . . . . . . . . 201 User Parameter Default Value . . . . . . . . . . . . . . . . . 132, 292, 452
Torque Control Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 User Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Torque Control Setting Error . . . . . . . . . . . . . . . . . . . . . . . . . . 333 User Parameters 1 to 32 . . . . . . . . . . . . . . . . . . . . . . 132, 143, 404
Torque Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271 User Set Speed Agree 1 Time Chart . . . . . . . . . . . . . . . . . . . . 239
Torque Detection Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . 273, 445 User Set Speed Agree 2 Example with a Positive L3-04
Torque Detection Level 2 . . . . . . . . . . . . . . . . . . . . . . . . . 273, 446 Value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Torque Detection Selection 1 . . . . . . . . . . . . . . . . . . . . . . 272, 445 User-Set Display Units Decimal Display. . . . . . . . . . . . . . . . . 291
Torque Detection Selection 2 . . . . . . . . . . . . . . . . . . . . . . 272, 446 User-Set Display Units Maximum Value . . . . . . . . . . . . . . . . . 291
Torque Detection Time 1 . . . . . . . . . . . . . . . . . . . . . . . . . 273, 445 Using the Pulse Train Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Torque Detection Time 2 . . . . . . . . . . . . . . . . . . . . . . . . . 273, 446 Using the Safe Disable Function . . . . . . . . . . . . . . . . . . . . . . . 530
Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274, 395 Uv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 330
Torque Limit Control Method Selection during Uv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 323
Accel/Decel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275, 446 Uv2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 323
Torque Limit Integral Time Constant . . . . . . . . . . . . . . . . 275, 446 Uv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 323
Torque Limit Process at Start . . . . . . . . . . . . . . . . . . . . . . . . . . 275 V
Torque Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Torque Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
V/f Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Torque Reference / Torque Limit Selection from Comm.
V/f Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
V/f Control Mode Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Torque Reference at Previous Fault . . . . . . . . . . . . . . . . . . . . . 459
V/f Control Mode Tuning Parameters . . . . . . . . . . . . . . . . . . . 302
Torque Reference Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . 203
V/f control using motor speed feedback . . . . . . . . . . . . . . . . . . 30
Torque Saturation Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
V/f Control with Simple Speed Feedback . . . . . . . . . . . . . . . . 254
Torque Specifications, Three Phase 200 V Class . . . . . . . . 71, 521
V/f Data Setting Error . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 332
Torque Specifications, Three Phase 400 V Class . . . . . . . . 72, 522
V/f Gain During Speed Search. . . . . . . . . . . . . . . . . . . . . . . . . 158
transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
V/f Pattern Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Traveling Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
V/f Pattern Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
V/f Pattern Display Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
Troubleshooting without Fault Display . . . . . . . . . . . . . . . . . . 342
V/f Pattern for Motor 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Tuning Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
V/f Pattern for Motor 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Types of Alarms, Faults, and Errors . . . . . . . . . . . . . . . . . . . . . 306
V/f Pattern Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206, 345
Types of Auto-Tuning for Induction Motors . . . . . . . . . . . . . . 116
vAEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Types of Auto-Tuning for Permanent Magnet Motors . . . . . . . 117
VERIFY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
U Verify Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
U Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456 Verifying Parameter Changes. . . . . . . . . . . . . . . . . . . . . . . . . . 102
U1000 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Vertical Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
U2, U3 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295, 453 vFyE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
UL Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 Vibration Suppression Gain during Acceleration
UL/cUL Mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 (with Current Limit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
UL3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 322, 330 Vibration Suppression Gain during Deceleration
UL4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 310, 322, 330 (with Current Limit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
UL5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 322 Voltage Class, Capacity Mismatch. . . . . . . . . . . . . . . . . . . . . . 339
Undertorque 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Voltage Error Compensation Time Constant . . . . . . . . . . . . . . 288
Undertorque 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 vrFy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Undertorque Detection 1 . . . . . . . . . . . . . . . . . . . . . 308, 322, 330 W
Undertorque Detection 2 . . . . . . . . . . . . . . . . . . . . . 308, 322, 330
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Undertorque Detection Operation . . . . . . . . . . . . . . . . . . . . . . 272
Water Supply Pump Application . . . . . . . . . . . . . . . . . . . . . . . 110
Undervoltage 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Watt Hour Output Example . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Undervoltage 3 (Soft-Charge Bypass Circuit Fault) . . . . . . . . 323
Watt Hour Output Unit Selection . . . . . . . . . . . . . . . . . . . . . . . 246
Undervoltage Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Watt Loss 200 V Class Three Phase Models . . . . . . . . . . . . . . 397
Unexpected Noise from Connected Machinery . . . . . . . . . . . . 346
Watt Loss 400 V Class Three Phase Models . . . . . . . . . . . . . . 397
Unidirectional Speed Limit Bias . . . . . . . . . . . . . . . . . . . . . . . 204
Wire Gauge, Three Phase 200 V Class . . . . . . . . . . . . . . . 71, 521
unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Wire Gauge, Three Phase 400 V Class . . . . . . . . . . . . . . . 72, 522
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Wire Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71, 78
transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Wiring Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 553
Wiring Diagram for 2-Wire Sequence . . . . . . . . . . . . . . . . . . . 234
Wiring Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Wiring the Control Circuit Terminal . . . . . . . . . . . . . . . . . . . . . 78
WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Writing Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Writing to Multiple Registers. . . . . . . . . . . . . . . . . . . . . . . . . . 500
Z
Z Pulse Correction Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Z Pulse Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Z Pulse Noise Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . 314
Z Pulse Offset Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Zero Servo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Zero Servo Completion Width . . . . . . . . . . . . . . . . . . . . . . . . . 177
Zero Servo Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Zero Servo Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Zero-Speed Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
554 YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual 555
YASKAWA U1000 Series
Technical Manual
EUROPEAN HEADQUARTERS
YASKAWA EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany
Phone: +49 (0)6196 569 300 Fax: +49 (0)6196 569 398
E-mail: [email protected] Internet: http://www.yaskawa.eu.com
YASKAWA ENGINEERING EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany
Phone: +49 (0)6196 569 520 Fax: +49 (0)6196 888 598
E-mail: [email protected] Internet: http://www.yaskawa-eng.eu.com
U.S.A.
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: +1 800 YASKAWA (927-5292) or +1 847 887 7000 Fax: +1 847 887 7310
Internet: http://www.yaskawa.com
JAPAN
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: +81 (0)3 5402 4502 Fax: +81 (0)3 5402 4580
Internet: http://www.yaskawa.co.jp
DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan
Phone: +81 (0)930 25 3844 Fax: +81 (0)930 25 4369
Internet: http://www.yaskawa.co.jp
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof,
the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all
procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2014 YASKAWA ELECTRIC CORPORATION. All rights reserved.