Please observe the following precautions for safe use of the products.
• Do not reverse connection of DC power supply polarity.
Model E3AS-HF6000@M@ • Do not short-circuit the load.
• Insulate unused input/output wires individually.
• Never use this product with AC power supply. Otherwise it may
explode.
TOF Laser Sensor • The maximum power supply voltage is 30 VDC. Before turning on the
product's power, make sure that the supply voltage does not exceed
INSTRUCTION SHEET the maximum power supply voltage.
Thank you for selecting OMRON product. This sheet primarily describes precautions
• Do not use the product in environments where flammable or explosive
required in installing and operating the product. gases are present.
Before operating the product, read the sheet thoroughly to acquire sufficient knowledge • Please assess the safety beforehand when using the product in
of the product. For your convenience, keep the sheet at your disposal. chemicals and/or oil environments.
TRACEABILITY INFORMATION: • Do not disassemble or remodel the product.
Importer in EU: Manufacturer: • Do not touch the metal surface with your bare hands when the
Omron Europe B.V. Omron Corporation, temperature is low. Touching the surface may result in a cold burn.
Wegalaan 67-69 Shiokoji Horikawa, Shimogyo-ku,
NL-2132 JD Hoofddorp, Kyoto 600-8530 JAPAN • Burn injury may occur. The product surface temperature rises
The Netherlands depending on application conditions, such as the ambient temperature
Importer in UK: and the power supply voltage. Attention must be paid during operation
OMRON Electronics Ltd. or cleaning.
Opal Drive, Fox Milne, • When the product is used at an ambient temperature of -10°C or less, a
Milton Keynes MK15 0DG, warm-up time of 10 minutes maximum is required. The output remains
U.K.
ON and does not change during warming up.
The following notice applies only to products that carry the CE mark. • To prevent an accident due to the product falling, wear appropriate
Notice:
This is a Class A product. In residential areas it ma cause radio protective gear when performing installation work in a high location.
interface, in which case the user may be required to be take adequate • Do not use the product while the case is damaged.
measures to reduce interference. • Do not use the product while the cord is pinched.
• In the event that you notice an abnormality, immediately stop use, turn
© OMRON Corporation 2024 All Rights Reserved. * 3 6 4 4 1 1 6 - 4 A *
off the power, and contact your Omron representative.
Package contents
Instruction sheet this sheet , Compliance sheet, Index list (attached for
IO-Link type only), FDA certification label
1
Using Pin2 (white wire) as monitor current "3-5 monitor current" ( page 4).
1 Installation
Model Method Input/Output circuit diagram
1-1 Mounting of the Sensor
+V
Brown
<Size of installation holes (Unit: mm)> Black Load 100 mA
E3AS- OUT1 or less 10 to 30 VDC
□□N□ NPN Monitor White
49.9 Reference Current
4.2 34.1 surface Blue Load 3.8 to 20.5 mA
0V
Brown
+V
26.55
PNP Black
OUT1 10 to 30 VDC
Standard I/O White
Monitor
53.9
Mode Current 100 mA or less
Blue Load Load
20.7
0V
E3AS- 3.8 to 20.5 mA
□□T□ Brown
+V +V
2-φ3 Reference Black
Through hole surface PNP C/Q 3.8 to
C/Q IO-Link
Monitor White 20.5 mA master
IO-Link Mode Current
Blue Load
0V 0V
Mounting brackets are sold separately.
@@T@ +V
Brown
+V 2-3 Cable Allowable Bending Radius
Black
PNP C/Q C/Q
White IO-Link Master
IO-Link Mode DO DI
Blue
0V 0V Length not allowed to bend
Length not
allowed to bend:
Note 1. The standard I/O mode is used as PNP ON/OFF output. 5 mm
Note 2. The IO-Link mode is used for communications with the IO-Link master.
The C/Q is used for IO-Link communications. The sensor output DO is
used for ON/OFF output.
Note 3. For detailed information on models, ratings, and performance, refer to Minimum
bending radius Minimum
"8 Ratings and Specifications" ( page 12). R13 mm bending radius
Using Pin2 (white wire) as external input "3-4 External Input" ( page 4).
2
Spot variable dial operation
3 Settings
The spot can be adjusted in 3 levels for each type by the spot variable dial.
Diffuse spot type E3AS-HF6000DM□
3-1 Operation/Display Lookup Table
This type can prevent chattering when there is space between objects by
Name and function of each part widening the spot.
0
Operation indicator
+1
(orange) Screen [UP] button
display
+2
Changes the threshold
value or set value. Approx.
40 mm
0
Power &
Communication [TEACH] button T
+1
6000 mm
indicator (green) Executes various
+2
teaching.
*Flashes during
IO-Link Approx.
[DOWN] button 40 mm
communication
0
Changes the threshold
+1
value or set value. 3000 mm
To switch between the
+2
Bottom indicator main screen and menu
setting screen, press Diffused light
(green/orange) and hold this button for
over 3s. Small spot type E3AS-HF6000SM□
This type detects an object deep in a narrow hole by condensing the spot.
Bottom indicator Parallel light
Approx. 9 mm
0
The bottom indicator is linked with the operation indicator, and lights in
either green or orange.
+1
+2
Operation indicator Bottom indicator
Lights in orange Lights in orange
0
Off Lights in green
+1
+2
Main screen 3000mm
Zero reset indicator
Turned ON when the zero
0
Threshold value indicator
reset function is enabled. Displays the set value of the threshold
+1
value in [mm]*1.
+2
Small spot 1500mm
Setting
Error Output
Main Screen
Monitor current
+1
Window FGS
+1
MODE
3s
Window BGS
Threshold value setting screen Input External input is accepted.
"4-3 Threshold Value Manual
Turns ON when there is a system error, output 1 has a
or Press for less Operations" ( page 7) Error
than 1s load short-circuit error, or in the low temperature state.
UP DOWN
0
3
3-4 External Input 3-5 Monitor Current
External input can be selected from the menu setting screen. Current is output according to the detected value.
External Input in "6 Detailed Settings External Input" ( page 8) The relationship between the detected value and current can be freely set
The external input of "Output 2 Function" cannot be used in IO-Link mode. by changing Scaling High/Low. In addition, Scaling High/Low can be taught
using actually detected values.
Laser OFF "6-6 Monitor Current Scaling Value Teaching Function" ( page 10)
Laser emission is turned OFF. When the laser emission is stopped, the
intensity is insufficient. Scaling function initial operation
20.5mA
(Monitor current upper limit value)
20 mA
ON
Monitor current
OFF
Output1 Output before zero reset execution Output after zero reset execution
Monitor current
4 mA
Zero reset cancel
3.8 mA
(Monitor current lower limit value)
ON 40 mm 2000 mm 6200 mm
External (Detected value (Detected value
Input External input OFF External input OFF 3000 mm
input ON upper limit value) lower limit value)
OFF Detected value
20.5mA
(Monitor current upper limit value)
Sensor response time 20 mA
Note: When the power is turned off after zero reset is executed, zero reset
Monitor current
is canceled. To retain the result of a zero reset, use the zero reset
memory function.
"5-3 Zero reset memory" ( page 7)
4 mA
3.8 mA
(Monitor current lower limit value)
1000 mm 6000 mm
40 mm 6200 mm
(Detected value (Detected value
upper limit value) Detected value lower limit value)
If Scaling High and Scaling Low are the same, the scaling setting
is ignored and the operation is the same as with the initial values
(Low: 50, High: 6000).
4
3-6 Output Mode Window BGS mode
Factory default (initial setting) Rated sensing distance range
Single operation Near-side Far-side
The output is inverted when the detected value falls below the threshold value (SP1).
threshold threshold
This mode is selected automatically when 2-point teaching and object teaching are executed.
"4-1 Basic Teaching" ( page 5)
Power/Communication ON
indicator (green) OFF
ON
Standard Operation Indicator (orange)
OFF
Near I/O Bottom indicator Lights in orange
Lights in green
Mode Output1 ON
ON OFF OFF
Output2 ON
Threshold value OFF
Near
Power/Communication ON
indicator (green) OFF
ON
OFF ON Standard Operation Indicator (orange) OFF
I/O Bottom indicator
Lights in orange
Near-side threshold Lights in green
Mode ON
(SP2) Output1
OFF
ON OFF
Output2 ON
Far-side threshold
OFF
(SP1) Power/Communication Flashing
indicator (green) (1second cycle)
OFF ON ON
Operation Indicator (orange) OFF
Lights in orange
Far IO-Link Bottom indicator Lights in green
N.O. setting N.C. setting Mode 1
Communication Output1 (PD3 bit0)
Window FGS 0
1
The output is inverted when the detected value is between the far side Communication Output2 (PD3 bit1)
0
(SP1) and near side (SP2) threshold values. This mode is selected Output2 *1 ON
OFF
automatically when background reference teaching is executed.
"4-1 Basic Teaching" ( page 5) *1 In IO-Link mode, output 2 can also be used in addition to communication output.
The mode is suitable for when the object has a mirror-surface, level difference,
or low reflectance since an object nearer than the set distance and an object 4 Teaching
with a reflected light intensity lower than the specified value are not detected.
When the light intensity is insufficient and when out of the detection distance 4-1 Basic Teaching
range, output is ON when N.O. is set, and OFF when N.C. is set.
2-point Teaching Single
Use to detect an object and a background.
Near 1. Press the T button quickly without any objects (longer than 25 ms and shorter than 1s).
TEACH
Use this mode when you want to perform teaching using the two points of the object and background.
ON OFF
Near-side threshold
(SP2)
OFF ON Teaching waiting status
Far-side threshold Alternate
(SP1) lighting
ON OFF
Far
N.O. setting N.C. setting
Note: Single point mode and window BGS mode perform the BGS operation, 2. Press the T button quickly with an object (longer than 25ms and shorter than 1s).
so they can be used regardless of whether there is a background, but TEACH
1. Press the T button quickly with an object (longer than 1s and shorter than 5s).
1.Press and hold the Tbusson with an object (longer than 1s and shorter than 5s).
TEACH
Release the button when [Object Teach] is displayed on the display TEACH
Release the button when [Window Obj. Teach] is displayed on the display
OFF
ON
Margin Near-side threshold value
Object Threshold value Margin
ON
OFF Background Margin
Object Far-side threshold value
The threshold value is set on the near side to the object.
OFF Background
If teaching is performed without a detected object or background, the maximum
detection value (6,000 mm) is set as the threshold. The threshold value is set with ± margin to the background.
Margin is set automatically to the optimal value depending on the received light Margin is fixed to 50.
intensity. Shown above is applicable to the case of N.O. output logic. In the case of N.C.,
Shown above is applicable to the case of N.O. output logic. In the case of N.C., this is inverted.
this is inverted.
The output target for teaching can be switched to output 1 or output
2 in the setting menu.
Background Reference Teaching "6-2 Teaching Target Selection" ( page 10)
This is suitable for when you want to detect an Window FGS
object that is not stable (mirror-surface, level
difference, or low reflectance) in object teaching.
4-2 Teaching Display
1. Press the T button quickly without any objects (longer than 25ms and shorter than 1s).
TEACH Teaching cancel display
Indicator
Display Power/ Operation Bottom Description
communication indicator indicator
Teaching waiting status indicator (green)*1 (orange) (green/orange)
Alternate
lighting Teaching If the Teach button is pressed
Cancelled Normal Normal and held for 5s or more
during teaching, [Teach
operation operation
Lighting Cancel] is displayed and
teaching can be canceled.
Teaching
succeeded
6
4-3 Threshold Value Manual Operations 5 Useful Functions
The threshold value can be adjusted using the [UP] button and the
[DOWN] button. 5-1 Key Lock
The threshold value increases. Quick adjustment is Acceptance of button operations can be disabled to prevent incorrect operations.
UP
usable by pressing and Key lock execution
The threshold value decreases.
DOWN holding the button.
Setting completed
The key lock icon is displayed on the main screen.
or Short press for 1s or less
UP DOWN
Output 1 Output 2 The screen is returned to the main screen after the
T elapse of a certain time.
TEACH
If buttons are operated in the key lock state, the key lock icon is
displayed on the main screen.
T 5-2 Initialization
Threshold value setting screen TEACH
Settings are initialized and returned to the factory settings.
Output 1 near side Output 1 far side Output 2 near side Output 2 far side After initialization, language setting is required as the initial setting.
"3-2 Initial Setup" (page 3)
T T T
TEACH TEACH TEACH
Releasing completed
The zero reset icon on the main screen is turned OFF.
The screen is returned to the main screen after the Zero reset memory
elapse of a certain time. The result of zero resetting can be saved even turning OFF the power after
The main screen displays only the threshold value of executing zero resetting by the external input or the communication
output 1.
commands of the IO-Link mode, only when the zero reset memory is set as
When “Off” is selected, the operation is the same as for single. [Off] described in "6 Detailed Settings Zero Reset Memory"(page 9).
The threshold value of output 2 is not displayed when “Invert,” When the sensor is operated using the buttons, the result is saved
“Input,” “Error,” or “Current” is selected for the output swichpoint regardless of the setting of zero reset memory.
mode of output 2.
7
6 Detailed Settings
Transition of the setting screen when Japanese is selected in the initial screen
Numerical value settings can be adjusted quickly by pressing and holding a button.
Main screen
[UP] Left shift / Numerical value +
3s
Teach Select Teach Select T * Displayed only when the Output 2 Mode ≠ Input, Current
Y
Advanced
Settings=ON
Advanced N
Settings=Off
Advanced Settings=On
Initialization Initialize?
T
5-2 (page 7) No No Yes
* If the Initialize? = Yes and transiting to item setting,
initialization is executed and the screen moves back to the initial screen.
8
* Displayed only when the Response = 10 ms, 50ms or 200 ms
Sensitivity Sensitivity T
6-10 (page 10) Very High Very High High Middle Low Very Low
Mutual Interference
Prevention
Interference T
Auto Auto Manual
6-12 (page 10)
Mutual Interference
Channel Selection
Manual ch. T
Channel1 Channel1 Channel2 Channel3 Channel4
6-12 (page 10) * Displayed only when the
Interference = Manual
Language Language T
6-15 (page 11) English English Spanish Italiano Deutsch
9
The screen transitions automatically to the main screen, and output is as follows.
6-1 Response Time
20.5 mA
Response time can be changed. (Monitor current upper limit value)
Detection becomes more stable as increasing response time. 20 mA
Execute teaching again or set the threshold again after changing the
Monitor current
response time.
+1
T *1
3s
ON
MODE
On delay
OFF
T *2 T MODE
3s +1
ON
0 +2
Hysteresis Width
The point at which the output turns from OFF to ON is called the operating
point and the point at which it turns from ON to OFF is called the return point. An error occurred Initialize the settings
on the memory by pressing and
The distance between the operating and return points is called hysteresis width. Data (EEPROM) error inside the sensor. holding the [UP] button
For this sensor, threshold value is equal to operating point, so the for 3s and restarting
The definition of hysteresis width for each output mode is shown on the figure below. the power.The sensor
OFF Quick flashing is out of order if the
Single Point Mode error is still not
(at 0.2s intervals) fixed.Replace the
●Operating point
sensor.
Near ○Return point
The output line is Check the wiring
Load short-circuit error short-circuited. and connecting.
Hysteresis width
Threshold value (SP1)
Quick flashing OFF
(at 0.2s intervals)
Detected value
Far
State Display
ON
Output *1 State name /
Possible causes Action and correction
OFF
display
The intensity of light received Delay the response time or
Insufficient intensity
*1. This is a graph when the output logic is N.O. It is inverted in the case of N.C. from the object is insufficient or decrease the distance between
Far state the object is farther than the the sensor unit and object to
detection distance range. enable detection by the sensor.
Window BGS mode
Near
Near side threshold Hysteresis width Near state The object is nearer than the Increase the distance between
value (SP2) detection distance range of the the sensor unit and object to
Far side threshold sensor. enable detection by the sensor.
value (SP1) Hysteresis width
Far
Detected value Low temperature state The sensor temperature is low. Allow the sensor to warm up for
ON 10 min maximum while the
Output *1
power is turned on.
OFF
*1. This is a graph when the output logic is N.O. It is inverted in the case of N.C.
Back-to-box This is displayed when the Removal of the sensor is
back-to-box command (IO-Link) possible. Reconnecting
Window FGS mode is received. enables communication.
This is the IO-Link
Near
communication prohibited state.
Near side threshold
value (SP2) Hysteresis width The key lock function enabled. If a button operation is required,
Key lock
release the key lock.
"5-1 Key Lock" ( page 7)
Far side threshold Hysteresis width
value (SP1)
Far
Detected value Laser emission OFF Pin2 terminal (white) might Check the wiring and external
ON have been short-circuited input setting.
Output *1
OFF
*1. This is a graph when the output logic is N.O. It is inverted in the case of N.C.
11
8 Ratings and Specifications
Sensing method Time-of-Flight (TOF) system
NPN output E3AS-HF6000DMN@ series E3AS-HF6000SMN@ series
Model
PNP output/COM3 E3AS-HF6000DMT@ series E3AS-HF6000SMT@ series
Sensing distance 50 to 6,000 mm
Spot size Variable (used with diffusion and Φ40 or less) Variable (used with condensation and Φ40 or less)
Light source (wavelength) Red laser (660 nm)
Power supply voltage 10 to 30 VDC, (including ripple (p-p) 10%), Class2
Consumption current 150 mA max. *1
Load power supply voltage 30 VDC max. (Class2), Load current 100 mA max.
Control output Residual voltage (Load current 10 mA max.: 1 VDC max., Load current 10 to 100 mA: 2 VDC max.)
Open collector output type (Depends on the NPN/PNP output type) N.O.(Normally Open) / N.C.(Normally Close) selectable
Monitor current 4 to 20 mA, maximum load resistance 500 Ω
Laser OFF / Teaching / Zero reset selectable
External input
For the applied voltage, refer to "2-1 Input/Output Circuit Diagram" ( page 2). For the input time, refer to "3-3 External Input" ( page 3).
Reversed power polarity protection, Power surge protection, Output short-circuit protection,
Protection circuits
Output reverse polarity protection, and Output surge protection
OLED Display(White), Power/Communication indicator (Green *1), Operation indicator (Orange),
Indicator
and Bottom indicator (green, orange)
Response time 2 ms / 10 ms / 50 ms / 200 ms selectable
Mutual interference prevention Auto setting / User channel setting: 4 units
Ambient illumination Incandescent lamp / Sunlight: 100,000 lx max.
Ambient temperature Operating: -30 to +55 (with no icing or condensation) *2, Storage: -30 to +70 (with no icing or condensation)
Ambient humidity Operating: 35 to 85%RH, Storage: 35 to 95%RH (with no condensation)
Insulation resistance 20 MΩ min. at 500 VDC
Dielectric strength 1,000 VAC at 50 / 60 Hz for 1 min
Vibration resistance 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance 500 m/s2 for 3 times each in X, Y, and Z directions
Enclosure ratings IP67 (IEC60529), IP69K (ISO20653)
Dimensions 58.6×51.2×26.5 mm (W×H×D)
Case Aluminum die cast (Nickel plating)
Material Indicator Polyethersulfone (PES)
Lens cover and Display Methacrylic resin (PMMA), Antifouling coating (Lens cover)
IO-Link specification Ver.1.1
Communication Baud rate COM3: 230.4 kbps
specifications Data length PD size: 4 byte, OD size: 2 byte (M-sequence type : TYPE_2_V)
Minimum cycle time COM3: 1.2 ms
Conformity standards UL/CSA Certification, CE Marking, RCM, UKCA, Various laser standards (details are provided on the cover), Ecolab, RoHs2, WEEE2
Note: 1.Altitude: Up to 2000m, Pollution degree: 3, Enclosure type: Type1.
*1. 300 mA max. when -10°C max.
*2. When the product is used in an environment with a temperature of -10°C or less, a warm-up time (10 min maximum) is required.
6000 Sensing distance 6,000 mm NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO
LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS
D Diffusion BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS
Emission spot shape
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
S Condensation EQUIPMENT OR SYSTEM.
Blank Light source Red OMRON Corporation Industrial Automation Company
Kyoto, JAPAN
M Case material Metal Contact: www.ia.omron.com
N NPN open collector Regional Headquarters
Output method OMRON EUROPE B.V.
T PNP open collector/COM3 Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Blank Pre-wired Tel: (31)2356-81-300/Fax: (31)2356-81-388
- M1TJ Connection method Pre-wired M12 Smartclick Connector OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
M1 M12 Connector Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
alphanumerical character Optional suffix Special specification OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Blank M12 Connector Alexandra Technopark,
Singapore 119967
2M 2 m+150/-0 mm(Pre-wired) Tel: (65) 6835-3011/Fax: (65) 6835-3011