0% found this document useful (0 votes)
3 views

BCC.12180540

Uploaded by

Rasel Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

BCC.12180540

Uploaded by

Rasel Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

TECHNOLOGY DEPARTMENT

TECHNICAL DATA SHEET


LOW VOLTAGE BUILDING WIRE

Cable Description:
Cu / PVC 450 / 750 V H07V2-K 90 °C 2.5 mm2 (Flex) GREY

Design and Construction Data:


Reference Manufacturing Standards IEC 60228, IEC 60227-3, BS EN 50525-2-31
Max. Permissible Continuous Conductor Temp °C 90
Max. Conductor Short Circuit Temp for 5 Seconds °C 160 °C
Rated Voltage V 450 / 750
Conductor Size mm2 2.5
Conductor Material & Shape Copper & Flexible Class 5 Round Shape
Insulation Material PVC
Nominal Insulation Thickness mm 0.80
Insulation Color GREY
Approximate Wire Overall Diameter mm 4
Electrical Data:
Max Conductor DC resistance @ 20 °C ohms/km 7.9800
Max Conductor AC resistance @ 90 °C (Two/Three) Conductors ohms/km 10.1753 / 10.1753
Max Conductor Short Circuit Current @ 1 Second KA 0.25
Current Carry Capacity @ 30 °C Ambient Temperature
Enclosed in conduit(1)
Two Insulated Conductors Single Phase ac or dc A 27
Three or Four Insulated Conductors Three Phase ac A 24
Clipped direct(2)
Two Insulated Conductors Single Phase ac or dc A 31
Three or Four Insulated Conductors Three Phase ac A 28
(1) Current carrying capacity based on IEE wiring regulation method B cables single ac or dc / three phase ac,
enclosed in conduit on a wall or in trunking etc. at 30 °C ambient temperature”.
(2) Current carrying capacity based on IEE wiring regulation method C cables single ac or dc / three phase , clipped
direct at 30 °C ambient temperature”.
* ref (IEE Wiring Regulations 17th edition Table 4D1A)
The Cable shall meet all Test requirements of: IEC/BS EN 60228, IEC 60227-3, BS EN 50525-2-31, IEC 60332-1
Packing Data:
Type Coil
Length of Cable per Coil (± 2%) m 92
Gross Weight (Approximate) kg 3
Cable Marking:
BAHRA CABLES CO. KSA 2.5 MM2 CU/PVC (450 / 750 V) 90 DEG C SASO 1320- FLEX TYPE 60227 IEC 02, FR IEC 60332-1
Cable Drawing

1 2

Description Cu / PVC 450 / 750 V H07V2-K 90 °C 2.5 mm2 (Flex) GREY Approx. Diameter
1 Copper conductor with round shape 1.97
2 PVC TI-3 Insulation 3.57

Inquiry No.: EP-1000241 (126491) ksalahuddin 13/08/2023

Product ID: 12180540 Page 1 / 1