Chloride CEP DS en Emea Rev1 1909
Chloride CEP DS en Emea Rev1 1909
Power DC - Rectifier
1
CE-P
Power DC - Rectifier
Voltage Signaling
Code Reference Output current (A)
Input (Vac) Output (Vdc) LED Contact 58 311
6011054 CE-P 2.5 12 187 to 305 V 12 V (10 - 15) 2.5 A 2 No No
6011060 CE-P 08 12 50/60Hz 12 V (10 - 15) 8A 4 Yes Yes
6007024 CE-P 05 12/24 12 V (10 - 15) 5A 4 Yes Yes
24 V (24 - 30)
6011062 CE-P 2.5 30/48 30 V (30 - 38) 2.5 A 4 Yes Yes
48 V (48 - 60)
Functions
Boost For the commissioning of NiCd batteries and to accelerate the charging of the batteries, it is necessary to apply a higher voltage for a few
hours.
voltage for a few hours. The charger has a boost function that increases the charging voltage by 3.8%. It is activated by connecting two
terminals of a connector with a Strap. The voltage automatically returns to the initial
The voltage automatically returns to the initial voltage after 12 hours of boosting (manual return on 6011054).
Battery test The test verifies that the battery is capable of powering the application and that the battery fuse is in order.
The operator can perform a test at any time by connecting two terminals of a connector with a Strap. Function not
available on 6011054.
Signalling The status of the charger is indicated by a LED :
• Chargeur in perfect condition : Led ON
• Mains failure and Mains fuse failure : Led OFF
Addional signalling (not available on 6011054) : Fault summary signalling contact
• Minimum battery voltage : Ledflashes rapidly
• Maximum charger voltage: Led flashes rapidly
Charger stop in case of loss regulation to protect all connected equipment:
• Battery test (on battery fault) : Led flashes rapidly
Option CF IP31 enclosure with display: 300 x 333 x 203 mm (HLP)
General Features
Input power supply 187 to 305 Vac - 47 to 63 Hz
Stability regulation ±1% cumulative change
Output current ±5%
Operating/storage temperature -20 to +50 °C / - 45 to +85 °C
Relative humidity < 95 % at 20 °C - Cooling: Natural convection
Insulation Classe I
Protection IP 20
Weight 0.5 kg
Dimension 155 x 112 x 65 mm
Standards
Compliance • Product: NF C 58-311 / NF EN 61204 (except 6011054)
• ECM n°2004/108/CE
• NF EN 61000-6-2 / NF EN 61000-6-4
• Complies to (LV Safety Compliance) n°2006/95/CE
• NF EN 50178 - complies to SELV
• Transformers comply to NF EN 61558-2-17
Chloride SAS, 30, Avenue Montgolfier, BP 90 - 69684 Chassieu - France T: +33 (0)4 78 40 13 56 [email protected]
To find contact in your region, please visit www.Chloride.com
© 2022 Chloride SAS. All rights reserved. Chloride, the Chloride logo are trademarks or registered trademarks of Chloride SAS. All other names and logos
referred to are trade names, trademarks or registered trademarks of their respective owners. Whilst every precaution has been taken to ensure accuracy and
completeness herein, Chloride SAS assumes no responsibility for, and disclaims all liability for, damages resulting from the use of this information or for any
errors or omissions. Specifications are subject to change without notice.