AHU-003 R
AHU-003 R
: 10
Unit
Unit color || Insulation || Hygienic ZincMagnesium || 60 mm mineral wool / Density 60 kg/m3 || Standard
Control system Without control system
Power supply Unit L1 + L2 + L3 + N + PE (3x400V) 50 Hz / 20.5 A
Sound break out || Supply air 68 dB(A) || 89 dB(A)
Supply Air/fan data Air density 1.205 kg/m³
Airflow || Face velocity || Ext. p 22000 m³/h || 2.54 m/s || 450 Pa AIR HANDLING UNIT
AHU
SF DVH CW1
SF
Outdoor 82 89 Supply
Air dB(A) dB(A) Air
Winter Temperature after [°C] -8.0 -8.0 -8.0 -7.4 20.0 20.0 20.0 20.0
Humidity after [%] 77 77 77 74 11 11 11 11
Pressure drop [pa] 100 4 128 61 28 4 115 350
Pressure after function [pa] -100 -104 -232 498 498 494 378 -
F7 - ePM1 60% Efficiency 65.3%
201.92 kW
Filter (Total Pressure)
Summer Temperature after [°C] 34.0 34.0 34.0 34.6 34.6 34.6 27.0 27.0
Humidity after [%] 75 75 75 73 73 73 89 89
158.77 kW
Ecodesign
2018 Value Limit
Non-residential - Unidirectional Approved
Fan with multispeed or Var.Speed Drive Approved
Pressure gauge Warning
SFP internal in W/(m³/s) Approved 127 230
Total check Approved
Supply
Manufacturer Systemair
Model Geniox SBS 3216.16
Typology NRVU;UVU
Drive Type EC Bluefin VSD Ok
Type of Heat Recovery System (HRS) None
Non Residential unit - flow rate 6.11 m³/s
Effective electric power input incl. clean filters and variable drive 6.55 kW
SFP internal in W/(m³/s) 2018 127 127 W/(m³/s)
Face velocity 2.54 m/s
Nominal external pressure 450.00 Pa
Internal pressure drop of ventilation components 78.36 Pa
Overall static pressure drop with clean filter 528.36 Pa
Total fan efficiency by static pressure incl. motor and speed control 61.81 %
Maximum external leakage rate @ ± 400 Pa Leakage is less than 7.1 l/s -> Leakage rate is less than 0.1 %
Maximum internal leakage rate (EATR, ?p = 250 Pa) Leakage rate is 0%.
Energy class for filters B No filter
Visual filter warning description Must be installed with control system
Internet address with information about disassembly techdoc.systemair.dk
Sound power level Supply air Outdoor air Sound break out
Total 89 dB(A) 82 dB(A) 68 dB(A)
Ecodesign is calculated for a reference configuration with ePM1 60% (F7) filter in supply and ePM10 60% (M5) filter in extract.
Technical specification
Unit
Casing
Panels Steel sheets coated with ZM310, corrosion class C5
Frame profiles Steel profiles coated with z225 painted, corrosion class C4
Mullion profiles Steel profiles coated with ZM310, corrosion class C5
Corners PA6 fiber reinforced
Insulation 60 mm mineral wool / Density 60 kg/m3
Corrosion protection Class C4 according to EN ISO 12944-2:2018
Operating pressure 0 - 2000 Pa (Geniox10 - Geniox31)
Operating temperatures -40/+40 °C (Standard)
-40/+60 °C (Special design)
Classifications EN 1886, 2. edition 2008
Mechanical Strength Class D1(M)*
Casing air leakage -400 Pa: Class L1(M)* and standard L2(RU)**
+700 Pa: Class L1(M)* and standard L2(RU)**
Filter by-pass leakage -400 Pa: Class G1-F9
+400 Pa: Class G1-F9
Thermal transmittance Class T2(M)*
Thermal bridging factor Class TB2(M)*
Filter
Dimensioning pressure drop 128 Pa
Initial pressure drop/Final pressure drop 78/178 Pa
Velocity, face area 2.82 m/s
Velocity, filter area 0.16 m/s
Filter class F7 - ePM1 60%
Filter size 4x[592x592x25] + 2x[592x287x25] + 2x[287x592x25] + 1x[287x287x25]
Filter length 520 mm
Filter description Camfil Hi-Flo II XLT
Material ZincMagnesium
Fan
Air flow 22000 m³/h
External pressure 450 Pa
Pressure drop 61 Pa
Static pressure (Designed at wet conditions) 791 Pa
Total pressure 836 Pa
Fan speed 2559 RPM
Maximum fan speed 2860 RPM
Total efficiency by static pressure, incl. motor and speed control 61.8 %
Total efficiency by total pressure, incl. motor and speed control 65.3 %
K-factor (p=1.2 kg/m³) (3 x 180) 540
Fan type - 3xMedium - Impeller ZAmid GR40I-ZID.GG.CR
ErP efficiency n(stat,A) 72.7 %
ErP efficiency class N(actual)/ N(target) 77.3 / 62
ErP-conformity Yes
Direct drive
Motor
Motor types EC motor
Motor types-size ZID.GG.CR
Motor protection
Total power (3 x 3.70 kW) 11.10 kW
Speed (nominal) 2860 RPM
Total current, Amp. (3 x 5.80 A) 17.40 A
Voltage 3x400 V
Consumed power from mains power supply, including speed control 7.82 kW
SFPv, clean filters including speed control 1.20 kW/(m³/s)
Winter: Temperature before / after -8.0 / -7.4 °C
Summer: Temperature before / after 34.0 / 34.6 °C
Winter: Humidity before / after 77 / 74 %
Inspection section
Pressure drop 4 Pa
Length 300 mm
Cooling coil
Air flow 22000 m³/h
Pressure drop air, wet coil with condensate droplets 78 Pa
Pressure drop air, dry coil 51 Pa
Air temperature before/after 34.6/27.0 °C
Air relative humidity before/after 73/89 %
Total cooling capacity 158.77 kW
Sensible cooling in % of total cooling 36 %
Face velocity 3.10 m/s
Condensate 2.4 l/min
Fluid type Water
Fluid temperature inlet/outlet 7.0/12.0 °C
Fluid flow rate 7.62 l/s
Fluid pressure drop 23.8 kPa
Fluid velocity 1.47 m/s
Feet or baseframe
Feet or baseframe Feet
Height of feet or baseframe 118 mm
Corrosion protection Surface protection of Magnelis
Duct connections
Product Dimensions (width x height)
Outdoor 1500x1600 mm
Supply 1500x1600 mm
Weights