Topic 2
Topic 2
1 Introduction
Differential protection is based on the fact that any fault within an electrical equipment
would cause the current entering it, to be different, from that leaving it. Thus, we can
compare the two currents either in magnitude or in phase or both and issue a trip output
if the difference exceeds a predetermined set value. This method of detecting faults is very
attractive when both ends of the apparatus are physically located near each other. A
typical situation, where this is true, is in the case of a transformer, a generator or a
busbar. In the case of transmission lines, the ends are too far apart for conventional
differential relaying to be directly applied.
Induced
current
Induced
current
9c
Therefore, B2 will have the same polarity as that of A,. Thus, dot marks can be put on
Al and B2 as shown in Figure. 3.3 to signify that these two terminals will be similarly
phased.
Similar arguments show that current must leave terminal C1 at the instant under
consideration. Thus, C1 will be similarly phased as Al. We, therefore, put dot marks on
terminals Al, B2, and C1.
A little thought will convince the reader that we can instead put dot marks on
terminals .42, B,, and C,, as shown in Figure 3.3.
Dot mark
A2
Dot mark
From the above discussion, we can generalize the following properties of dot
markings:
When current enters the dot mark on the primary side of a C r the current must leave the
similarly marked dot mark on the secondary side.
If currents are made to enter dot marked terminals on two or more coupled coils then the
fluxes produced by these currents are such that they add up.
n
L
0
a
Instantaneous OC relay d
Spill current = 0 Plug setting = I,,
I .
< I
Figure 3i4 Simple differential protection.
The following rule can be applied in order to trace the currents in the circuit:
When current enters the dot mark on the primary side of the C q the current must lea.
the similarly marked dot mark on the secondary side.
For the operating condition of normal load flow shown in Figure 3.4, the currents
transformed by the two CTs, being equal in magnitude as well as in phase, just circulate
on the secondary side. There is no tendency for the current to spill into the over-current
relay. The over-current relay connected in the spill path is wired to trip the two circuit
breakers on either side of the equipment being protected.
Assuming that the protected equipment is either a 1 : 1 ratio transformer or say a
generator winding or a busbar, the two currents on the primary side will be equal. Hence
the ratios of the two protective CTs will also be identical. The CT secondary circuits are
so connected that in case the conditions are normal, the secondary currents simply
circulate through the 'pilot' leads connecting the two secondary windings. For the
operating condition of normal load flow, there is no current through the 'spill path' where
an over-current relay is located. Hence, the OC relay will not trip the two CBs. Thus, the
simple differential relay meets the first and foremost requirement that it remains stable
during normal operating conditions.
from the figure, current in the spill path is now (If,i,,ln), where n is the CT ratio.
Assuming that the spill current is more than the pick-up value of the over-current relay,
both the circuit breakers will be tripped out. Thus, the scheme meets the basic
requirement of clearing internal faults.
1 Internal fault
The minimum internal fault current that will cause the tripping, is given by
If,min
= (CT ratio) (Plug setting of the OC relay) = nIp,
In the preceding analysis, we have assumed a single-end-fed system. How does the
differential scheme behave in case of a double-end-fed system?
A double-end-fed system is shown in Figure 3.7, the internal fault is now fed from
both sides. The internal fault current, If,,nt, is now equal to (I, + I z )Again, we see that
the spill current is equal to (IC,,,In).
-
a rn Equipment under
protection
,\
\I rn
U -
41
,,- '2
n
,,
Internal fault
Assuming that the splll current is greater than I,,, the plug setting of the OC relay,
the relay will operate and trip out the circuit breakers on either side of the protected
equipment.
Zone of differential
Equipment uqder
External fault
I 1 External fault
/P = lr, eil
n:1
-
Equipment under
protection
,,
A .-
Ip
- --
=
n :I
If, ex1
U
7
.
Spill current
External
\
?
.
?
fault
11, ext
n = nominal CT ratio
n, and n, = actual CT ratios
!
Ideal positions of I,, and Is2
'P
Primary current
current
External fault
characteristics
So Pick-up value of OC
E relay in spill path
/
1/ Trip f' , /'
-1 Through fault current -2 <
/rob
Through fault stability
L
Figure 3.10 Characteristics of simple differential relay.
Compare this with the situation of an internal fault. The minimum internal fault
current required for the scheme to operate, correctly in this case, is decided by pick-up
value of the over-current relay in the spill path. To signify the spread between the
minimum internal fault current at which the scheme operates and the maximum 'through
f a a t ' current beyond which the scheme (mal)operates, we define a term called stability
ratio as:
Stability ratio = maximum 'through fault' current beyond which scheme (ma1)operates
minimum internal fault cur;ent required for tripping
The higher the stability ratio, the better is the ability of the system to discriminate
between external and internal faults. The stability ratio can be improved by improving
the match between the two CTs.
3.5.2 Equivalent Circuit of CT
F i g r e 3.11 shows the equivalent circuit of the CT as referred to the secondary side.
H Burden
' ( -b
h Excitation characteristic of CT
b
>
I Magnetizing current. I,
(C)
I
RLri and LLri arc the resistance and the leakage inductance of the prlmary windir,g as '
referred to. the secondary side. R,,,,, and Lmugform the shunt magnetizing branch. The
magnetizing inductancc is highly nonlinear. R,,, and I,,,, are the resistance and leakage
inductance of the secondary winding. The impedance Zhlllilenincludes the resistance and
the inductance of the relay coils and rcsistance of the pilot wire (leads). Also shown in
Figure 3.11(c) is a sketch of the magnetization characteristic of the CT (also known as
open-circuit characteristic).
Out of the current Ipln transformed by the ideal CT, the magnetizing branch draws
the magnetization current I,. It is to be noted that the magnetizing current is a nonlinear
function of the excitation voltage V,,,. During normal operating conditions, when V,, is
small, the current I, can be safely neglected. However, at higher values of primary
current, (and therefore secondary current), as in case of 'through faults', the secondary
voltage, Vse,, which is equal to I,(Z,,, + Zburden) increases and causes I, to become an
appreciable fraction of the current transformed by the ideal CT. Thus, we can no longer
ignore I,.
,:j
-1
Differential scheme considering CT equivalent circuit
Figure 3.12 shows the simple differential scheme in which CT equivalent circuit has been
explicitly included. The various currents shown in Figure 3.12 are those that result
during an external fault condition. Assuming that both CTs have the same nominal ratio
of transformation n, we see that a spill current equal to the difference of the two
magnetizing currents results. Since the magnetizing currents of the two CTs will
generally vary widely, there is a substantial spill current during 'through fault'
conditions. This results into loss of stability and maloperation of the simple differential
scheme. Thus, the simple differential scheme, which looks attractively simple, cannot be
used in practice without further modifications.
This is especially true in case of transformer protection. The CTs on the two sides of
the transformer have to work at different primary system voltage. Because the currents
on the two sides of the transformer are, in general, different, the ratios of transformation
of the CTs are also different. Their designs are therefore different, making it impossible
.d
to get a close match between their characteristics. This explains why the spill current
goes on increasing as the 'through fault' current increases.
In case of busbar protection, the primary voltages of the two CTs are the same, and
the CT ratios are also the same. However, busbars are subjected to very heavy 'through
fault' currents, which tend to magnify the differences between the characteristics of the
two CTs. Thus, for busbar protection too, the simple differential scheme needs to be
further modified.
Both these aspects have been dealt with in detail in subsequent chapters.
'P
-*
CT
n : l CB
Equipment under
CB
\
,
n
rn
:
-
~ 1,
>
T I / Trip protection ?
Trip,
T Spring
Armature
rid output
Similarly,
Operating torque = M [ N , ( I l - 1211"
The relay trips if the operating torque is greater than the restraining torque. The relay
will be on the verge of operation when the operating torque just balances out the
restraining torque, i.e. when:
where X = N,IN,,.
I,-i,=K
I
(I?+ I,)
) '
However, if we take into account the effect of control spring, the above equation can
be written as
Dzflerenrial Prctection 69
Il - I2 = K
where KO accounts for the effect of spring.
Thus, the operating characteristics of this relay will be a straight line with a slope of
(N,IN,) and an intercept KOon the y-axis. All points above the straight line will represent
the condition where the operating torque is greater than the restraining torque and hence
will fall in the trip region of the relay. All points below the straight line belong to the
restraining region. The operating characteristics of the percentage differential relay are
shown in Figure 3.14.
Internal fault
:.. ,.. characteristic External fault
200% slope characteristic
-
I I
!
,
I
!
I
Maximum through fault current, I,,,,,.,,
I
I
Thus, the spill current must be greater than a definite percentage of the 'through
fault' current for the relay to operate. Hence, the name percentage differential relay. The
slope of the relay is customarily expqessed as a percentage. Thus, a slope of 0.4 is
expressed as 40% slope.
The percentage differential relay does not have a fixed pick-up value. The relay
automatically adapts its pick-up value to the 'through fault' current. As the 'through fault'
current goes on increasing, we are in effect asking the relay to take it easy, by introducing
a restraining torque proportional to the circulatillg current. I t can be seen from
Figure 3.14,that the 'through fault' stability and the stability ratio of the percentage
70 F~lrrdar~~etitnls
of Power Svsterrr Prutecriun --
--
.
differential relay is substantially better than that of the simple differential relay. The
restraining winding is also known as the biasing winding because we bias the relay
towards restraint. The slope of the characteristic is also known as percentage bias.
The characteristic of the percentage differential relay, superimposed on the 'through
fault' characteristic, and the internal fault characteristic are shown in Figure 3.14. The
slope of the internal fault characteristic can be found as follows:
Consider an internal fault in the case of a single-end-fed system. Since CT2 will not
contribute any current, i.e., I2 = 0, the spill current, ( I , - I;), will be equal to I I . The
+
circulating current which is [ ( I 1 12)121 will be equal to (1,121. ~ h u s ,the following
currents will exist during an internal fault:
Spill current I l - I2 = I I
11 + I,
Circulating current T - 11
- -
- A
5
' I
Thus, during internal faults the spill current will be two times the circul'ating current, a ,'
giving a slope of 2, which is expressed as 200%. :
'5
The minimum internal fault current below which the scheme will not respond is seen . ,
.
to be Ir,,in,int and the maximum 'through fault' current above which the scheme will ,
maloperate is seen to be If,,,,,,,, as shown in Figure 3.14. Thus, the stability ratio is given ,. -.
by
;-
3 + 40% slope
1
Figure 3.15 Block diagram of percentage differential relay showing its settings.
3.7 Elarfh leakage ProSecfion
Many times because of insulatior~failure the chassis of the equipment becomes live. This
causes a leakage of current to earth from the chassis as the chassis is always connected
t o earth. However, the leakage current may be too small for an over-current relay to
operate. This poses danger to the personnel who come in contact with the chassis. A
special type of differential relay known as the earth leakage relay or current balance relay
can easily detect such faults.
In case the chassis of the equipment is not earthed, the relay will not trip because of
leakage. However, as soon a person whose body is in contact with earth, touches the
chassis, a path to earth becomes available, and assuming that the leakage current is of
suficient magnitude, the OC relay trips. The person will, of course, receive an electric
shock before the circuit is tripped out.
The relay consists of a toroidal corson which two identical windings A and B, each
having N number of turns are wound in close proximity. A third coil C, known as the pick-
up coil, is also wound and connected across an OC relay as shown in Figure 3.16. The
phase and neutral leads are connected to these windings as shown in the figure so that
windings A and B carry the currents in the phase wire and the neutral wire, respectively.
t Under normal operating conditions, the current through the phase wire (and coil A)
is exactly the same as that through the neutral wire (and coil B). Thus, there is no net
72 F~~i~da~~ierltols
01- Power S v ~ r r ~Protect~orr
r~
magnetomotive force (mmf) acting on the toroidal core. The flux linked with the pick-up
coll is therefore zero, and thus no voltage is induced in the pick-up coil and the OC relay
remains unenergzed.
Now consider the situation of earth leakage as shown in Figure 3.16. The current in
the phase wire is now greater than that in the neutral wire, as part of the current returns
to the supply vla the earth. The mmf acting on the toroid is now equal to [N(Iyh- I,)]
or equal to [N(Il,,)]. This rnmf sets u p flux in the core causing a voltage to be Induced
by the pick-up coil. The OC relay connected to the pick-up coil, therefore, gets energized,
and trips the circuit.
I
During the normal balanced operating condition, the phasor sum of the three-phase
currents is zero. Therefore, there is no net mmf acting on the core and the OC relay
remains unenergized.
However, during the earth leakage situation s h w n in Figure 3.17, the net mmf acting
on the core is (Ileak)ampere-turns. This causes a flux to be produced. A voltage is induced
in the pick-up winding causing the OC relay connected across it to operate.
Review Questions
1. Fiow will :iou check the polarity marks on a protection CT with the help of a
1.5 volt battery and a centre-zero voltmeter?
2. What do you mean by CT saturation?
3. Explain the following terms with respect to the simple differential scheme:
Circulating current, spill current, internal fault, external fault, through fault,
'through fault' stability limit and stability ratio.
4. What are the drawbacks of the simple differential scheme?
5. What is the effect of the resistance of the pilot (lead) wires on the CT errors?
6. As the burden on a CT secondary goes on increasing, what happens to the
magnitude and waveform of current delivered to the burden?
7. Explain how the percentage differential relay overcomes the drawbacks of the
simple differential relay.
8. Prove that the slope of the internal fault characteristics for a single-end-fed
system is 200%.
9. How do you adjust the slope of the percentage differential relay?
10. Show that the slope of the simple differential relay characteristics is zero.
11. Prove that the slope of the internal fault characteristics for a double-end-fed
system is greater than 200%.
12. Higher slopes are required in cases where there is a lot of mismatch between the
CTs at various terminals. Explain.
13. Which elements of the power system are ideal candidates for applying differential
protection?
14. What problems, if any, do you anticipate in applying conventional differential
protection to a transmission line?
Problems
1. For a 5 A CT, the total impedance of the secondary winding and leads is 0.01 ohm.
Determine the VA capacity of the CT secondary at (a) the rated secondary current
and (b) the maximum fault current of 20 times the rated CT secondary current.
2. In a simple differential scheme, the two CTs have a nominal ratio of 100 : 1. The
CT errors for a 'through fault' current of 1000 A are as follows:
CTI CT2
Ratio error
.- 5% + 6%
Phase angle error 2% -4%
Determine the pick up of the OC relay in the spill path so that the scheme
remains stable.