The document provides detailed specifications and calculations for the HUS-H 6 anchor type, including load combinations, anchor forces, and failure modes. It emphasizes the importance of checking input data for agreement with existing conditions and highlights installation requirements and warnings related to the design. The calculations indicate that the anchor design meets the necessary criteria for a service life of 50 years.

Uploaded by

kumaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

Report

The document provides detailed specifications and calculations for the HUS-H 6 anchor type, including load combinations, anchor forces, and failure modes. It emphasizes the importance of checking input data for agreement with existing conditions and highlights installation requirements and warnings related to the design. The calculations indicate that the anchor design meets the necessary criteria for a service life of 50 years.

Uploaded by

kumaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

www.hilti.com Profis Anchor 2.8.

8
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

Specifier's comments:

1 Input data
Anchor type and size: HUS-H 6
Return period (service life in years): 50
Effective embedment depth: hef = 42 mm, hnom = 55 mm
Material: 1.5523
Approval No.: ETA 08/0307
Issued I Valid: 23/08/2018 | -
Proof: Design method ETAG (No. 001 Annex C/2010)
Stand-off installation: eb = 0 mm (no stand-off); t = 4 mm
Baseplate: lx x ly x t = 200 mm x 40 mm x 4 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc,cube = 32.00 N/mm2; h = 220 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to ETAG 001, Annex C, 5.2.2.6 present.

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. [%]
1 Combination 1 Vx = 0.400; Vy = 0.400; N = 0.400; no no 11
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Combination 2 Vx = 0.400; Vy = 0.400; N = -0.400; no no 7


Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.400 0.566 0.400 0.400
1 x
max. concrete compressive strain: - [‰]
Tension
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.400 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

3 Tension load (ETAG, Annex C, Section 5.2.2)


Load [kN] Capacity [kN] Utilisation bN [%] Status
Steel failure* 0.400 17.857 3 OK
Pull-out failure* 0.400 3.771 11 OK
Concrete cone failure** 0.400 6.159 7 OK
Splitting failure** N/A N/A N/A N/A
* most unfavourable anchor **anchor group (anchors in tension)

3.1 Steel failure


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
25.000 1.400 17.857 0.400

3.2 Pull-out failure


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
6.000 1.131 1.800 3.771 0.400

3.3 Concrete cone failure


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm]
15,876 15,876 63 126
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.200 11.086 1.800 6.159 0.400

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

4 Shear load (ETAG, Annex C, Section 5.2.3)


Load [kN] Capacity [kN] Utilisation bV [%] Status
Steel failure (without lever arm)* 0.566 8.333 7 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout failure** 0.566 11.086 6 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* most unfavourable anchor **anchor group (relevant anchors)

4.1 Steel failure (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
12.500 1.500 8.333 0.566

4.2 Pryout failure


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] k-factor
15,876 15,876 63 126 1.500
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
11.086 1.500 11.086 0.566

5 Combined tension and shear loads (ETAG, Annex C, Section 5.2.4)

Steel failure
bN bV a Utilisation bN,V [%] Status
0.106 0.068 1.500 6 OK
baN + baV ≤ 1.0

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.296 [kN] dN = 0.012 [mm]
VSk = 0.419 [kN] dV = 0.133 [mm]
dNV = 0.133 [mm]
Long term loading:
NSk = 0.296 [kN] dN = 0.074 [mm]
VSk = 0.419 [kN] dV = 0.196 [mm]
dNV = 0.209 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid baseplates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the baseplate is assumed to
be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required
baseplate thickness with FEM to limit the stress of the baseplate based on the assumptions explained above. The proof if the rigid baseplate
assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions
and for plausibility!
• In general, the conditions given in ETAG 001, Annex C, section 4.2.2.1 and 4.2.2.3 b) are not fulfilled because the diameter of the clearance
hole in the fixture acc. to Annex 3, Table 3 is greater than the values given in Annex C, Table 4.1 for the corresponding diameter of the
anchor. Therefore the design resistance for anchor groups is limited to twice the steel resistance in accordance with the approval.
• Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the baseplate without creating air voids and before application of the loads.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

8 Installation data
Baseplate, steel: - Anchor type and size: HUS-H 6
Profile: no profile Installation torque: 0.025 kNm
Hole diameter in the fixture: df = 9 mm Hole diameter in the base material: 6 mm
Plate thickness (input): 4 mm Hole depth in the base material: 65 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions
for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Hilti SIW 22T-A impact screw driver
• Properly sized drill bit

100 100

20

20

1 x
20

20

100 100

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 0 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 7/20/2020
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan