Chapter 2 Remaining Notes
Chapter 2 Remaining Notes
These includes bus bars, CB, isolator with or without earthing switch, power transformer,
CTs, VTs, surge arresters, line trap unit, coupling capacitors compensating equipments, etc.
These equipments are connected in accordance with single diagram, bus bar scheme and
the substation layout.
Bus bar: bus bars are either in the form of aluminium tubes (ridged) or flexible Aluminium
Conductor Steel Reinforced (ACSR). In MV and LV indoor bus bar applications copper
(aluminium) ridged bars are used. Tubuler bus bars are mounted on post insulators, whereas
ACSR are supported on strain insulators.
The main functional requirement of bus bar system is:
- To carry 𝐼𝑟𝑎𝑡𝑒𝑑 continuously and limited over loading
- With stand 𝑉𝑟𝑎𝑡𝑒𝑑 and specified transient over voltage without flashover
- To provide low resistance path for current flow
- For HV, EHV, and UHV out door bus bars should have minimum corona losses
Circuit Breaker (CB): CB is a mechanical switching device capable of making, carrying and
breaking current under normal and abnormal (short circuit) condition for specified time. CBs
are mounted on support structures. CBs are classified on the bases of the medium used for arc
extinctions. They are: SF6, Air blast, vacuum, minimum or bulk oil, air-magnetic, miniature
CBs.
Technical particulars of a CB:
- Type of medium for arc extinction
- Rated voltage (power frequency phase-phase highest voltage)
- Rated breaking current, kA
- Rated continuous current
- Type of construction (indoor, outdoor, metal-clad, SF6 gas insulated type etc)
- Type of operating mechanism (pneumatic, spring, hydraulic)
- Total breaking time (e.g. 2, 3, 5 cycles)
- Structural form (live tank, dead tank type)
An example of bus bar specification is given in the following table.
Sample specification of CB is illustrated in Table 2.2 and photo of SF6 is shown in Fig. 2.10.
Disconnect switches are designed to continuously carry load currents and momentarily carry
higher capacity for short-circuit currents for a specified duration (typically specified in
seconds). They are designed for no load switching, opening or closing circuits where negligible
currents are made or interrupted, or when there is no significant voltage across the open
terminals of the switch. They are relatively slow-speed operating devices and therefore are not
designed for arc interruption. Disconnect switches are also installed to bypass breakers or other
equipment for maintenance and can also be used for bus sectionalizing. Interlocking equipment
is available to prevent inadvertent operating sequence by inhibiting operation of the disconnect
switch operation until the fault and/or load currents have been interrupted by the appropriate
equipment.
Disconnect switch operation can be designed for vertical or horizontal operating of the switch
blades (see Fig.2.11). Several configurations are frequently used for switch applications
including:
Vertical break
Double break switches
Center break switches
Hook stick switches
Vertical reach switches
Grounding switches
Phase spacing is usually adjusted to satisfy the spacing of the bus system installed in the
substation.
Earthing Switch is connected between the line conductor and earth. Normally it is open and
when the line is disconnected, earthing switch is closed so as to discharge the voltage trapped
on the line capacitance to earth. This voltage is significant in the high voltage system and
should be discharged to earth before proceeding maintenance work. Specification example for
Isolator is given in Table 2.3.
Load break switches: A load break switch is a disconnect switch that has been designed to
provide making or breaking of specified currents. This is accomplished by addition of
equipment that increases the operating speed of the disconnect switch blade and the addition
of some type of equipment to alter the arcing phenomena and allow the safe interruption of the
arc resulting when switching load currents.
Disconnect switches can be supplied with equipment to provide a limited load switching
capability. Arcing horns, whips and spring actuators are typical at lower voltages. These
switches are used to de-energize or energize a circuit that possesses some limited amount of
magnetic or capacitive current, such as transformer exciting current or line charging currents.
An air switch can be modified to include a series interrupter (typically vacuum or SF6) for
higher voltage and current interrupting levels. These interrupters increase the load break
capability of the disconnect switch and can be applied for switching load or fault currents of
the associated equipment.
Automatic high-speed grounding switches are applied for protection of transformer banks when
the cost of supplying other protective equipment is too costly. The switches are generally
actuated by discharging a spring mechanism to provide the “high-speed” operation. The
grounding switch operates to provide a deliberate ground on the high-voltage bus supplying
the equipment (generally a transformer bank), which is detected by protective relaying
equipment remotely, and operates the transmission line breakers at the remote end of the line
supplying the transformer. This scheme also imposes a voltage interruption to all other loads
connected between the same remote breakers. A motor-operated disconnect switch is
frequently installed along with a relay system to sense bus voltage and allow operation of a
motor-operated disconnect switch when there is no voltage on the transmission line to provide
automatic isolation of the faulted bank, and allow reclosing operation of the remote breaker to
restore service to the transmission line.
Power Fuses: Power fuses are generally accepted means of protecting power transformers in
distribution substations. The primary purpose of power fuse is to provide interruption of
permanent faults. Fusing is an economical alternative to circuit switcher or circuit breaker
protection. Fuse protection is generally limited to voltages from 34.5kV through 69kV, but has
been applied for protection of 115 – 138 kV transformers.
To provide the greatest protective margin, it is necessary to use the smallest fuse rating
possible. The advantage of close fusing is the ability of the fuse unit to provide backup
protection for some secondary faults. For the common delta-wye connected transformer, a
fusing ratio of 1.0 would provide backup protection for a phase to ground fault as low as 230%
of the secondary full-load rating. Fusing ratio is defined as the ratio of the fuse rating to the
transformer full load current rating. With low fusing ratios, the fuse may also provide backup
protection for line-to-ground faults remote to the substation on the distribution network.
Fuse ratings also must consider parameters other than the full load current of the transformer
being protected. Coordination with other overcurrent devices, accommodation of peak over-
loadings, and severe duty may require increased ratings of the fuse unit. The general purpose
of the power transformer fuse is to accommodate, not interrupt, peak loads. Fuse ratings must
consider the possibility of nuisance trips if the rating selected is too low for all possible
operating conditions.
The concern of unbalanced voltages in a three-phase system must be considered when selecting
fusing for power transformer protection. The possibility of one or two fuses blowing must be
reviewed. Unbalanced voltages can cause tank heating in three phase transformers and
overheating and damage to three phase motor loads. The potential of ferro resonance must be
considered for some transformer configurations when using fusing.
Circuit Switchers: Circuit switchers have been developed to overcome some of the limitations
of fusing for substation transformers. They are designed to provide three-phase interruption
(solving the unbalanced voltage considerations) and provide protection for transient over-
voltages and overloads at a competitive cost between the costs of fuses and circuit breakers.
Additionally, they can provide protection from transformer faults based on differential, sudden
pressure, and over-current relay schemes as well as critical operating constraints such as low
oil level, high oil or winding temperature, pressure relief device operation, and others.
Circuit switchers are designed and supplied as a combination of a circuit breaking interrupter
and an isolating disconnect switch. Later models have been designed with improved interrupter
have reduced the number of gaps and eliminated the necessity of the disconnect switch blades
in series with the interrupter. Interrupters are now available in vertical or horizontal mounting
configurations, with or without an integral disconnect switch. Circuit switchers have been
developed for applications involving protection of power transformers, lines, capacitors, and
line connected or tertiary connected shunt reactors.
Circuit switchers are an alternative to the application of circuit breakers for equipment
protection. Fault duties may be lower and interrupting times longer than a circuit breaker. Some
previous designs employed interrupters with multiple gaps and grading resistors and the
integral disconnect switch as standard. The disconnect switch was required to provide open-
circuit isolation in some earlier models of circuit switchers. Circuit switchers originally were
intended to be used for transformer primary protection. Advancements in the interrupter design
have resulted in additional circuit switcher applications, including:
Table 2.7 shows VT specification example and photo of CTs & VTs are shown in Fig. 2.13
Surge Arrester (SA) diverts the transient over voltages to earth and protect the substation
equipment from overvoltage surges. There are two types of arrestor design: a) conventional
gapped arrestors; b) Metal oxide (MOA) or zinc-oxide (ZOA) arrestor.
b) CVTs
A substation earthing is very important for safety of personal and needs careful attention while
designing, erection and routine maintenance.
All non-current carrying parts connected to the earthing system shall be uniformly at
zero potential with respect to ground.
The floor on which the operational and maintenance staff moves shall be at ground
potential. This means safe step-potential
During any earth fault in the substation, the potential of structures, tank, and other non-
current carrying parts does not rise to unsafe value (safe touch-potential).
The “step voltage” is the difference in surface potential experienced by a person bringing a
distance of 1 meter with his feet without contacting any other grounded object.
The “touch voltage” is the potential difference between the earth potential rise and the surface
potential at the point where a person is standing, which at the same time having his hand in
contact with an “earthed” structure.
The station earthing system is in the form of an earthing mat or earthing mesh level. In
addition to earthing mat a number of earthing electrodes (spikes) are driven in the ground
and connected to earthing mesh (see Figure 2.14). The earthing mesh comprises several
horizontal earthing rods placed below ground level and welded together, which gives low
earth resistance and ensures the entire substation floor level at near ground potential.
An earth mat (grid) formed by copper or mild steel bars or bare cables placed in
the ground at a depth of about 0.5m in a horizontal plane. The crossings are
welded. The grid covers the entire substation area and sometimes a few meters
beyond the fencing. The earthing rods are also run along the border of the fencing
of the substation.
Earth electrodes driven vertically into earth at several locations and connected to
earth mat. Large number of earth electrodes gives lower earth resistance.
Earth risers are used for connection between the structures, equipment bodies and
earthing mat. These usually clamped or welded or brazed (soldering is not
permitted).
Earthing strips between the transformer neutrals and the earth mat are usually in
the form of bare copper cables or strips.
Functional requirement of Earthing System
To provide earth connection for the neutral points of transformer, reactor, capacitors
banks, filter banks, generators.
To provide low resistance path to the earthing switch earthed terminals, so as to
discharge the trapped charge to charge to earth prior to maintenance or repairs.
To provide discharge path for lighting over voltage coming via surge arrestors,
shield wires etc.
To ensure safety of operating staff by limiting voltage gradient at ground level in
the substation.
The cross-section area of conductor depending on the above three of factors can be calculated
as follow:-
𝐼𝑓 √ 𝑡
𝐴= 𝐾
Since substation earthing (grounding) is related with over voltage protection system from
lighting and therefore designing aspect of substation earthing system will be covered in more
detail in course “High Voltage Engineering”.
DC Supplies
The power source for DC supply is generally obtained from storage batteries, or from AC/DC
rectifier sets. The application of substation batteries is limited because of high cost and complex
maintenance. Storage batteries are used only for essential circuits. Static rectifiers are used for
some circuits where storage batteries are not required.
- Battery room with battery/ battery charger, bus bars etc (see Fig. 2.17)
- LV DC switch board
- LV DC distribution system
All the DC distributions system are generally designed with duplication to ensure availability
and maintainability. Each battery system includes two separate battery sets with one or more
charger sets.
Separated battery charger is provided for different DC voltages battery sets. The ampere hour
capacity of batteries is selected on the bases of total loads for a period of certain autonomous
operation (3 to 6h) without the need of intermediate charging.
The battery chargers are generally static rectifiers from LV AC mains as well as additional
diesel generator sets. All the load groups connected to the DC bus bars are provided with
circuit protection with over-current tripping and alarms. Also necessary measuring instruments
are provided.
AC Supplies
Substation auxiliary AC may be derived from dedicated sources or from additional circuits on
low voltage distributing system. Three examples are shown in Fig. 2.18
Simple 380 – 415 V three phase circuit allocation fed by distribution substation
transformer(s).
Tertiary windings on substation main transformer(s) or from earthing transformer
(zigzag star-star) winding.
Dedicated substation auxiliary transformers and switchgear.
The essential factors to be considered are the level of security of supply required (duplicated
transformers, LV AC sectionalized switch board, key interlocks, etc), the fault level of the LV
AC switchgear (possible high fault level at primary substation sites) and allowance for future
substation extensions.