Unit-1_Representation Of Power System Components
Unit-1_Representation Of Power System Components
LT 13.2 KV
KVb(new) on LT side = KVb(new) on HT side x = 230 KV x = 13.8 KV
HT 220 KV
PU reactance of Generator(G),
2
20 300
X PU ( new) 0.2 X X
20 300 = 0.2 PU
j 32
= = 0.1815 PU
176.33
PU reactance of Transformer 2(T2),
2
220 300
X PU ( new) 0.1X X
230 300 = 0.0915 PU
NB-Reactance diagram is useful in load flow analysis and short circuit analysis.
Example,
Obtain the per unit impedance diagram of the power System shown in figure. Assume a
base of 30 MVA, 33 kv on the transmission line
Say,
Base MVA = MVAb(new)=30MVA
Base KV = KVb(new)=33KV on the transmission line
LT 11KV
KVb(new) on LT side of T1 = KVb(new) on HT side x = 33 KV x = 11 KV
HT 33KV
LT 6.2 KV
KVb(new) on LT side of T2 = KVb(new) on HT side x = 33 KV x = 6.2 KV
HT 33KV
Now ,
PU reactance of Generator 1(G1),
Re ac tan ce Re ac tan ce 16 16
zb ( KVb ,new ) 2 (33) 2 36.3 = 0.44 PU
MVAb ( new) 30
V2 112
Actual load impedance ( Z L ) * , ZL
121
= 3.02∠25.8 ohm
SL 40 25.8 40 25.8
KVb 2 112
Base load impedance ( Zb ) 4.03
MVAb 30
ZL 3.02 25.8
Z L , pu Z
, L , pu = 0.74∠25.8 = 0.66+j0.32
Zb 4.03
V2 6.62
Actual load impedance ( Z L ) * , ZL
43.56
= 1.08∠31.7 ohm
SL 40 31.7 40 31.7
KVb 2 6.22
Base load impedance ( Zb ) 1.28
MVAb 30
ZL 1.08 31.7
Z L , pu , Z L, pu = 0.84∠31.7 = 0.71+j0.44
Zb 1.28
[NB.
(1)Case-1 Load =62 MVA ,0.8 PF lagging at 10.5 KV
V2 10.52
Actual load impedance ( Z L ) * =1.423+j1.0667
SL 62 36.86
KVb 2 112
Base load impedance ( Zb ) 1.21
MVAb 100
ZL 1.423 j1.0667
Z L , pu , Z L, pu =1.176+j0.88 pu
Zb 1.21
V2 2002 2002
Actual load impedance ( Z L ) * = 500∠59.03
SL 48 j 64 80 59.03
KVb 2 2002
Base load impedance ( Zb ) = 400
MVAb 100
ZL 500 59.03
Z L , pu , Z L, pu = 1.25∠59.03 = 0.75+j1 pu ]
Zb 400
Example,
The single line diagram of an unloaded power system is shown in Fig.The generator
transformer ratings are as follows.
G1=20 MVA, 11 kV, X’’=25%
G2=30 MVA, 18 kV, X’’=25%
G3=30 MVA, 20 kV, X’’=21%
T1=25 MVA, 220/13.8 kV (Δ/Y), X=15%
T2=3 single phase units each rated 10 MVA, 127/18 kV(Y/Δ), X=15%
T3=15 MVA, 220/20 kV(Y/Δ), X=15%
Draw the reactance diagram using a base of 50 MVA and 11 kV on the generator1.
Solution,
Draw the reactance diagram of given power system using common base of 100 MVA and
20 KV on the generator side. All the impedance including load impedance is in PU.
G= 85 MVA , 20 KV , 16%
T1= 60 MVA , 20/220 KV , 10 %
T2 = 50 MVA , 220/11KV , 5%
T3 = 50 MVA , 20/110 KV , 7%
T4 = 40 MVA , 110/11KV , 9%
M = 65 MVA , 10.5 KV , 17%
Load = 62 MVA , 10.5 KV at 0.8 power factor lagging.
Line 1 and Line 2 have reactance of 45 ohm and 60 ohm respectively
Solution,
HT 220 KV
KVb(new) on HT side = KVb(new) on LT side x = 20 KV x = 220 KV
LT 20 KV
Z ( KVb,new )2 2202
Z pu ( new) actual , and zb = 484 ohm
zb MVAb ( new) 100
j 45
= = 0.093 PU
484
PU impedance of Transformer 2 (T2),
2
220 100
Z pu ( new) j 0.05 X X j 0.1 pu
220 50
PU impedance of Transmission line 2 (TL2),
HT 110 KV
KVb(new) on HT side = KVb(new) on LT side x = 20 KV x = 110 KV
LT 20 KV
Z ( KVb,new )2 1102
Z pu ( new) actual , and zb = 121 ohm
zb MVAb ( new) 100
j 60
= = 0.496 PU
121
11
KVb(new) on LT side of T4 = 110 X = 11 kv
110
2
10.5 100
Z pu ( new) j 0.17 X X j 0.238 pu
11 65
PU impedance of Load ,
KVb 2 112
Base load impedance ( Zb ) 1.21
MVAb 100
ZL 1.423 j1.0667
Z L , pu , Z L, pu =1.176+j0.88 pu
Zb 1.21
This sequence has components that are also equal in magnitude and displayed from each other
by 1200 similar to the positive sequence components. However, it has an opposite phase
sequence from the original system. The negative sequence is identified as the "acb" sequence
and usually denoted by the symbol "-" or "2" . The phasors of this sequence are shown in Fig
where the phasors rotate anti- clockwise. This sequence occurs only in case of an
unsymmetrical fault in addition to the positive sequence components.
a2 = 1∠2400 = -0.5-j0.866
a3 = 1∠3600 = 1
1+a+a2 = 0
EXAMPLE
The symmetrical components of a phase –a voltage in a 3-phase unbalanced system are
Va0 =10∠1800 v , Va1 = 50∠00 v and Va2 = 20∠900 v
Solution,
THREE-SEQUENCE IMPEDANCES AND SEQUENCE NETWORKS
The analysis of unsymmetrical faults in power systems is carried out by finding the symmetrical
components of the unbalanced currents.
Since each sequence current causes a voltage drop of that sequence only, each sequence current
can be considered to flow in an independent network composed of impedances to current of that
sequence only. The single phase equivalent circuit composed of the impedances to current of
any one sequence only is called the sequence network of that particular sequence. The sequence
networks contain the generated emfs and impedances of like sequence. Therefore for every
power system we can form three- sequence networks. These sequence networks, carrying
current Ia1, Ia2 and Ia0 are then inter-connected to represent the different fault conditions.
Power system is a balanced device. In a balanced system we will have only positive sequence
networks, but when faults are introduced in the system the system becomes unbalanced. When
power system becomes unbalance the negative sequence and zero sequence also introduce in the
system along with positive sequence.
In = Ia1+Ib1+Ic1 Ia1
=0
Hence neutral current will be zero. That is why no neutral connection is drawn in Positive
sequence network.
=0
Hence neutral current will be zero. That is why no neutral connection is drawn in negative
sequence network.
In = Ia0+Ib0+Ic0
As transformer is a static element, the sequence in which the currents are rotating does not
affect the impedance of the network. That is why Positive sequence network and negative
sequence network is same in case of transformer.
2.Zero sequence impedance is approximately 2.5 times that of positive or negative sequence
impedance in the case of single circuit lines. For double circuit lines, the order will be more.
Example