0% found this document useful (0 votes)
14 views30 pages

Lecture_7-3

This lecture discusses three-phase transformers, focusing on their connections and configurations such as Delta-Delta, Delta-Wye, Wye-Delta, Wye-Wye, and Open-Delta. It covers the operational principles, advantages, and calculations associated with each connection type, including examples of load calculations. The objective is to provide a comprehensive understanding of three-phase transformer systems in power engineering.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views30 pages

Lecture_7-3

This lecture discusses three-phase transformers, focusing on their connections and configurations such as Delta-Delta, Delta-Wye, Wye-Delta, Wye-Wye, and Open-Delta. It covers the operational principles, advantages, and calculations associated with each connection type, including examples of load calculations. The objective is to provide a comprehensive understanding of three-phase transformer systems in power engineering.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 30

Lecture-7

Three Phase Transformers

Mesfin T.

Addis Ababa University


College of Technology and Built Environment
School of Electrical and Computer Engineering

Introduction Electrical Machines


ECEG-3151
April 1, 2025
Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 1 / 24
Overview

Overview

1 Overview
2 Objective
3 Introduction
4 Transformer Banks
5 Transformer Connections
Delta-Delta Connection
Delta-Wye Connection
Wye-Delta Connection
Wye-Wye Connection
Open-Delta Connection
6 Three-phase Transformers

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 2 / 24


Objective

Lecture Objectives

The objectives of this lecture are:


To discuss three-phase transformer connections and three-phase
transformers.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 3 / 24


Introduction

Introduction

In the operation of power systems, transformers are required to change


the voltage levels throughout the network.
three-phase circuits use three-phase transformers
can be achieved by using a bank of three single-phase transformers
may be a 3-phase unit having three primary windings and three
secondary windings on a 3-legged core
using a bank of three single phase transformers, the windings may
be connected in a variety of ways
the primary side may be connected in a wye or delta configuration
independent of the secondary connection
the secondary side may be connected in a wye or delta configuration
independent of the primary connection

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 4 / 24


Transformer Banks

Transformer Banks

3-phase transformer banks can be analyzed using simplifying


assumptions
excitation currents are negligible
winding impedances are negligible
total apparent input power equals the total apparent output power
Single-phase transformers connected into a 3-phase bank
retain all basic single-phase properties
individual voltage and current transformations are based on the
single- phase turns ratio
phase shift between primary and secondary is zero
3-phase transformer banks can introduce a phase shift between the
three-phase primary and the three-phase secondary
function of the primary and secondary winding connections

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 5 / 24


Transformer Connections Delta-Delta Connection

Transformer Connections
Delta-Delta (∆ − ∆) Connection

Three single-phase transformers connected delta-delta.

the H1 terminal of each


transformer is
connected to the H2
terminal of the next
transformer
the X1 terminal of each
transformer is
connected to the X2
terminal of the next
transformer Figure 1: ∆ − ∆ connection.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 6 / 24


Transformer Connections Delta-Delta Connection

the primary-side line voltage is transformed to the


secondary-side line voltage
the primary and secondary voltages and currents are in-phase

Figure 2: Schematic diagram of ∆ − ∆ connection of a transformer.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 7 / 24


Transformer Connections Delta-Delta Connection

Example (1)
Three single-phase transformers are connected in delta-delta (∆ − ∆)
configuration to step down a line voltage of 138kV to 4160V to supply
power to a manufacturing plant. If the plant draws 21M W at 0.86
power factor lagging, calculate
a) the apparent power drawn by the plant
b) currents in the HV lines and the LV lines
c) current in the primary and secondary windings of each transformer
d) the load carried by each transformer
Solution:

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 8 / 24


Transformer Connections Delta-Delta Connection

Example (1)
Three single-phase transformers are connected in delta-delta (∆ − ∆)
configuration to step down a line voltage of 138kV to 4160V to supply
power to a manufacturing plant. If the plant draws 21M W at 0.86
power factor lagging, calculate
a) the apparent power drawn by the plant
b) currents in the HV lines and the LV lines
c) current in the primary and secondary windings of each transformer
d) the load carried by each transformer
Solution:
a) The apparent power drawn by the plant is
P
S=
cos ϕ
21
= = 24.4M V A
0.86

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 8 / 24


Transformer Connections Delta-Delta Connection

Example (1)
b) Current in each HV line is

S 24.4 × 106 V A
I1 = √ =√ = 102 A
3E 3 × 138, 000 V

Current in each LV line is


S 24.4 × 106 V A
I2 = √ = √ = 3386 A
3E 3 × 4160 V

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 9 / 24


Transformer Connections Delta-Delta Connection

Example (1)
b) Current in each HV line is

S 24.4 × 106 V A
I1 = √ =√ = 102 A
3E 3 × 138, 000 V

Current in each LV line is


S 24.4 × 106 V A
I2 = √ = √ = 3386 A
3E 3 × 4160 V

c) The current in each primary winding is


102
IP = √ = 58.9 A
3
The current in each secondary winding is
3386
IS = √ = 1955 A
3
Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 9 / 24
Transformer Connections Delta-Delta Connection

Example (1)
d) Because the plant load is balanced, each transformer carries
one-third of the total load, or
24.4
M V A = 8.13 M V A
3

The individual transformer load can also be obtained by


multiplying the primary voltage times the primary current:

S= EP IP
= 138, 000 V × 58.9 A
= 8.13 M V A

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 10 / 24


Transformer Connections Delta-Wye Connection

Delta-Wye (∆ − Y ) Connection

Three single-phase transformers connected delta-wye.

the H1 terminal of each


transformer is
connected to the H2
terminal of the next
transformer.
the X2 terminals of all
transformers are
connected together to
form a neutral terminal.
Figure 3: ∆ − Y connection.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 11 / 24


Transformer Connections Delta-Wye Connection

the primary-side line voltage is transformed to the


secondary-side phase voltage
the delta-wye connection produces a 30o phase shift between
the primary and secondary voltages and currents

Figure 4: Schematic diagram of ∆ − Y connection of a transformer.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 12 / 24


Transformer Connections Delta-Wye Connection

Example (2)
Three single-phase step-up transformers rated at 40M V A,
13.2kV /80kV are connected in a delta-wye (∆ − Y ) configuration to a
13.2kV transmission line. If the 80kV load is 90M V A, calculate
a) the secondary line voltage
b) the currents in each winding of the transformer
c) the line currents in the LV and HV transmission lines
Solution:

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 13 / 24


Transformer Connections Delta-Wye Connection

Example (2)
Three single-phase step-up transformers rated at 40M V A,
13.2kV /80kV are connected in a delta-wye (∆ − Y ) configuration to a
13.2kV transmission line. If the 80kV load is 90M V A, calculate
a) the secondary line voltage
b) the currents in each winding of the transformer
c) the line currents in the LV and HV transmission lines
Solution:

The easiest way to solve this problem is to consider the windings of


only one transformer, say, transformer-P (consider figure-5, on the next
slide).

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 13 / 24


Transformer Connections Delta-Wye Connection

Example (2)

Figure 5: Figure for example-2.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 14 / 24


Transformer Connections Delta-Wye Connection

Example (2)

Figure 5: Figure for example-2.

a) The voltage across the primary winding is obviously 13.2kV . The


voltage across the secondary is, therefore, 80kV . The voltage
between the outgoing lines 1,2 and 3 is:

ES = 80kV × 3 = 138.5kV

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 14 / 24


Transformer Connections Delta-Wye Connection

Example (2)
b) The load carried by each transformer is
90
S = M V A = 30 M V A
3
The current in the primary winding is
30 M V A
IP = = 2273A
13.2 KV
The current in the seconday winding is
30 M V A
IS = = 375A
80 KV

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 15 / 24


Transformer Connections Delta-Wye Connection

Example (2)
b) The load carried by each transformer is
90
S = M V A = 30 M V A
3
The current in the primary winding is
30 M V A
IP = = 2273A
13.2 KV
The current in the seconday winding is
30 M V A
IS = = 375A
80 KV
c) The current in each incoming line A, B, C is

I = 2273 × 3 A = 3937A

The current in each outgoing line 1, 2, 3 is


I = 375A
Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 15 / 24
Transformer Connections Wye-Delta Connection

Wye-Delta (Y − ∆) Connection

The currents in a wye-delta connection are identical to those in the delta-


wye connection
the primary and secondary connections are simply interchanged
the H2 terminals of all transformers are connected together to
form a neutral terminal
the X1 terminal of each transformer is connected to the X2
terminal of the next transformer

Again, the connection results in a 30o phase shift between the primary
and secondary voltages and currents
the primary-side phase voltage is transformed to the secondary
side line voltage

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 16 / 24


Transformer Connections Wye-Wye Connection

Wye-Wye (Y − Y ) Connection

Three single-phase transformers connected wye-wye


the H2 terminals of all transformers are connected together to
form a neutral terminal
the X2 terminals of all transformers are connected together to
form a neutral terminal
the primary-side phase voltage is transformed to the
secondary-side phase voltage
the neutral terminal of the primary side of the transformer
must be connected back to the source with a low impedance
path to avoid secondary voltage magnitude distortion with
unbalanced loads

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 17 / 24


Transformer Connections Wye-Wye Connection

the connection produces no phase shifts

Figure 6: Schematic diagram of Y − Y connection of a transformer.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 18 / 24


Transformer Connections Open-Delta Connection

Open-Delta Connection

It is possible to transform the voltage of a 3-phase system using only 2


transformers.

open-delta arrangement
is identical to a
delta-delta connection,
less one transformer
limited use due to a
86.6% reduction in the
installed power
capability
Figure 7: Open − Delta connection.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 19 / 24


Transformer Connections Open-Delta Connection

two 50kV A transformers could carry 100kV A, but limited to


86.6kV A in an open-delta connection
used in emergency conditions
used in metering of power system voltages

Figure 8: Schematic diagram of Open − Delta connection of a transformer.

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 20 / 24


Transformer Connections Open-Delta Connection

Example (3)
Two single-phase 150kV A, 7200V /600V transformers are connected in
open-delta. Calculate the maximum 3-phase load they can carry

Solution:

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 21 / 24


Transformer Connections Open-Delta Connection

Example (3)
Two single-phase 150kV A, 7200V /600V transformers are connected in
open-delta. Calculate the maximum 3-phase load they can carry

Solution:

Although each transformer has a rating of 150kV A, the two together


cannot carry a load of 300kV A. The following calculations show why:

The nominal secondary current of each transformer is


150 kV A
IS = = 250A
600 V

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 21 / 24


Transformer Connections Open-Delta Connection

Example (3)
The current I, in lines 1, 2, 3 cannot, therefore, exceed 250A (figure-8 ).
Consequently, the maximum load that the transformers can carry is

S= 3EI

= 3 × 600V × 250A = 259, 800V A

= 260kV A

Thus, the ratio


maximum load = 260kV A
installed transformer rating = 300kV A

0.867 or 86.7%

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 22 / 24


Three-phase Transformers

Three-phase Transformers

A transformer bank composed of three single-phase units may be re-


placed by one 3-phase transformer.
the magnetic core has three flux-carrying legs
two yokes, bottom and top, couple the flux of the three legs
the sum of the three fluxes equals zero
each leg contains the primary and secondary windings of one of
the phases
the windings are connected delta or wye, internal to the
transformer tank
only six terminals are brought out of the tank

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 23 / 24


Three-phase Transformers

Questions?

Mesfin T. (CoTBE/SECE) Lecture-7 April 1, 2025 24 / 24

You might also like