Lecture_7-3
Lecture_7-3
Mesfin T.
Overview
1 Overview
2 Objective
3 Introduction
4 Transformer Banks
5 Transformer Connections
Delta-Delta Connection
Delta-Wye Connection
Wye-Delta Connection
Wye-Wye Connection
Open-Delta Connection
6 Three-phase Transformers
Lecture Objectives
Introduction
Transformer Banks
Transformer Connections
Delta-Delta (∆ − ∆) Connection
Example (1)
Three single-phase transformers are connected in delta-delta (∆ − ∆)
configuration to step down a line voltage of 138kV to 4160V to supply
power to a manufacturing plant. If the plant draws 21M W at 0.86
power factor lagging, calculate
a) the apparent power drawn by the plant
b) currents in the HV lines and the LV lines
c) current in the primary and secondary windings of each transformer
d) the load carried by each transformer
Solution:
Example (1)
Three single-phase transformers are connected in delta-delta (∆ − ∆)
configuration to step down a line voltage of 138kV to 4160V to supply
power to a manufacturing plant. If the plant draws 21M W at 0.86
power factor lagging, calculate
a) the apparent power drawn by the plant
b) currents in the HV lines and the LV lines
c) current in the primary and secondary windings of each transformer
d) the load carried by each transformer
Solution:
a) The apparent power drawn by the plant is
P
S=
cos ϕ
21
= = 24.4M V A
0.86
Example (1)
b) Current in each HV line is
S 24.4 × 106 V A
I1 = √ =√ = 102 A
3E 3 × 138, 000 V
Example (1)
b) Current in each HV line is
S 24.4 × 106 V A
I1 = √ =√ = 102 A
3E 3 × 138, 000 V
Example (1)
d) Because the plant load is balanced, each transformer carries
one-third of the total load, or
24.4
M V A = 8.13 M V A
3
S= EP IP
= 138, 000 V × 58.9 A
= 8.13 M V A
Delta-Wye (∆ − Y ) Connection
Example (2)
Three single-phase step-up transformers rated at 40M V A,
13.2kV /80kV are connected in a delta-wye (∆ − Y ) configuration to a
13.2kV transmission line. If the 80kV load is 90M V A, calculate
a) the secondary line voltage
b) the currents in each winding of the transformer
c) the line currents in the LV and HV transmission lines
Solution:
Example (2)
Three single-phase step-up transformers rated at 40M V A,
13.2kV /80kV are connected in a delta-wye (∆ − Y ) configuration to a
13.2kV transmission line. If the 80kV load is 90M V A, calculate
a) the secondary line voltage
b) the currents in each winding of the transformer
c) the line currents in the LV and HV transmission lines
Solution:
Example (2)
Example (2)
Example (2)
b) The load carried by each transformer is
90
S = M V A = 30 M V A
3
The current in the primary winding is
30 M V A
IP = = 2273A
13.2 KV
The current in the seconday winding is
30 M V A
IS = = 375A
80 KV
Example (2)
b) The load carried by each transformer is
90
S = M V A = 30 M V A
3
The current in the primary winding is
30 M V A
IP = = 2273A
13.2 KV
The current in the seconday winding is
30 M V A
IS = = 375A
80 KV
c) The current in each incoming line A, B, C is
√
I = 2273 × 3 A = 3937A
Wye-Delta (Y − ∆) Connection
Again, the connection results in a 30o phase shift between the primary
and secondary voltages and currents
the primary-side phase voltage is transformed to the secondary
side line voltage
Wye-Wye (Y − Y ) Connection
Open-Delta Connection
open-delta arrangement
is identical to a
delta-delta connection,
less one transformer
limited use due to a
86.6% reduction in the
installed power
capability
Figure 7: Open − Delta connection.
Example (3)
Two single-phase 150kV A, 7200V /600V transformers are connected in
open-delta. Calculate the maximum 3-phase load they can carry
Solution:
Example (3)
Two single-phase 150kV A, 7200V /600V transformers are connected in
open-delta. Calculate the maximum 3-phase load they can carry
Solution:
Example (3)
The current I, in lines 1, 2, 3 cannot, therefore, exceed 250A (figure-8 ).
Consequently, the maximum load that the transformers can carry is
√
S= 3EI
√
= 3 × 600V × 250A = 259, 800V A
∼
= 260kV A
0.867 or 86.7%
Three-phase Transformers
Questions?