SCROLL CHILLER
Appearance
Model Heat pump LSQWRF65M/NaD-M LSQWRF80M/NaD-M LSQWRF130M/NaD-M LSQWRF160M/NaD-M
kW 60/65 71/79.5 120/130 145/170
Classic D Series Capacity Cooling/Heating
RT 17.0/18.5 20.2/22.6 34.1/37.0 41.2/48.3
Capacity steps % 0-50-100 0-50-100 0-25-50-75-100 0-25-50-75-100
EER/COP W/W 2.84/3.09 2.76/2.94 2.84/2.93 2.74/3.04
Power supply Ph/V/Hz 3/380-415/50 3/380-415/50 3/380-415/50 3/380-415/50
Cooling kW 21.1 25.7 42.3 53.0
Power input
Heating kW 21.0 27.0 44.4 56.0
Type Hermetic scroll Hermetic scroll Hermetic scroll Hermetic scroll
Compressor Starting mode Direct starting Direct starting Direct starting Direct starting
Quantity 2 2 4 4
Type High-efficient shell and tube heat exchanger
L/s 2.9 3.4 5.7 6.9
Water side heat Water flow volume
GPM 45.0 54.0 91.0 110.0
exchanger kPa 15 20 30 35
Pressure drop
ft.WG 4.9 6.6 9.8 11.5
65/80kW 130/160kW 249/280/320/325kW Connection pipe DN65 DN65 DN80 DN80
Type High-efficient fin tube type heat exchanger
Air side heat Fan type and quantity axial×2 axial×2 axial×4 axial×4
exchanger Total fan air flow
L/s 0.75×104 0.83×104 1.5×104 1.67×104
CFM 1.59×104 1.76×104 3.18×104 3.53×104
Total fan motor power kW 0.65×2 0.95×2 0.65×4 0.95×4
Sound pressure level dB(A) 70 71 72 74
Outline(W×D×H) mm 2040×1000×2230 2040×1000×2230 2226×1650×2230 2226×1650×2230
Dimension
Package(W×D×H) mm 2120×1080×2230 2120×1080×2230 2306×1730×2230 2306×1730×2230
Golden fin Inner groove Modular Comprehensive Self-diagnosis Easier Memory Easier 24 hour timer Net/Gross/Operating weight kg 710/715/781 760/765/836 1256/1261/1382 1440/1445/1584
condenser copper structure protection maintainability function maintainability
Loading quantity 40'GP/40'HQ set 10/10 10/10 6/6 6/6
Note: The specification is tested under the connection pipe of 7.5 meters.
4
CFM 8x0.82×10 8x0.92×104 8x0.92×10
4
01/02
AIR COOLED CHILLERS
Dimensions Dimensions
SCROLL CHILLER
LSQWRF65M/NaD-M, LSQWRF65M/NaD-M(FB01), LSQWRF80M/NaD-M (Unit: mm)
LSQWRF249M/NaD-M, LSQWRF280M/NaD-M, LSQWRF320M/NaD-M, LSQWF325M/NaD-H (Unit: mm)
2200
2160
2410
238
A
319
967(Anchor bolt) 543 2894 2152 Anchor Bolt M16
1396
1750(Anchor bolt 4-M12) 1000 600 1390 Anchor bolt M16 1390 Anchor bolt M16 2260
2040 3980
Model A
LSQWRF249M/NaD-M 411
LSQWRF130M/NaD-M, LSQWRF130M/NaD-M(FB01), LSQWRF160M/NaD-M, LSQWRF160M/NaD-M(FB01) (Unit: mm) LSQWRF280M/NaD-M 445
LSQWRF320M/NaD-M 445
Model A B
2160
LSQWRF130M/NaD-
366 323
M(FB01)
LSQWRF160M/NaD-
403 337 B
A
M(FB01)
1676 1617(Anchor bolt 4-M12)
2026(Anchor bolt 4-M12) 1650
2226
03/04
AIR COOLED CHILLERS
Large Capacity Modular Air-cooled Scroll Chillers High-end and high-quality configuration
SCROLL CHILLER
Appearance Condenser:
New V-shaped fin heat
exchanger, utilizing CFD
simulation to optimize
the angle, resulting in
more uniform airflow
organization and a 30%
increase in efficiency.
Condenser:
New V-shaped fin heat exchanger,
utilizing CFD simulation to optimize the
angle, resulting in more uniform airflow
organization and a 30% increase in
efficiency.
Product Overview
1.Functionality:
Space-saving, simplified installation
Utilizes air as the heat/cold source and water as the heat transfer medium.
Replaces traditional boilers, providing cooling in summer and heating in winter. Compared with traditional modular air-cooled chiller (heat pump) units, scroll air-cooled chiller (heat pump) units offer
2.Design Advantages: larger single unit capacity and more compact structure, saving over 100% of floor space and significantly reducing the
number of piping connections for equipment installation.
Flexible layout, space-saving, and aesthetically pleasing.
Low operating noise, making it suitable for central air conditioning systems. 40%
Saved
3. Flexible Investment and Installation:
Offers flexible equipment investment and simple engineering installation, ideal for central air
conditioning projects.
4.Improved Capacity and Efficiency:
New generation design with larger cooling capacity per single unit, reducing the number of units
needed for installation in space-constrained projects.
5. Modular Combination and Scalability:
Supports up to 8 units for free combination, meeting diverse cooling capacity needs.
Allows phased equipment installation, enabling easy expansion for future requirements.
Small Capacity Modular Air Cooled Chillers Large Capacity Modular Air Cooled Chiller
Formed Group
05/06
AIR COOLED CHILLERS
Partial load, higher efficiency Stable and Reliable Air volume adopts intelligent adjustment, Ultra-wide operatition range from -15°C to 48°C.*
A single module has multi-level energy adjustment, Based on the system load, the unit rotates and priori-
SCROLL CHILLER
allowing for expansion of 1 to 8 modules. The system tizes the startup of module units, evenly distributing *For T series 340/460kW Models Only
automatically calculates the operating load, matches the operating time of each module unit, which greatly The unit utilizes internationally renowned brand multi-speed adjustable
the operating capacity, humanizes the allocation of improves the reliability and hardware lifespan of the low-noise axial fans, enabling intelligent air volume adjustment. This
the operating time of each system, ensures that the unit. allows it to quickly match load changes, effectively preventing frequent
system maintains the best operating state, and starts and stops of the fan, and ensuring stable and efficient system
improves the reliability and efficiency of the unit. operation. The unit breaks through the operating range limit of tradition-
al four-pipe systems in the industry and can operate stably in ambient
temperatures ranging from -15°C to 48°C.
Output capacity
1~8 units
Ambient temperature
48℃ 48℃ 48℃
Ambient temperature
During heating operation, through the independently developed "SD" (SELF-DEFROSTING) self-learning system, the
frosting condition of the intelligent modular unit is accurately judged, and an automatic defrosting effect is achieved, ensur-
25℃
Ultra Wide opearation temperature range Opearation temperature range (480/550kW Model)
Heating capacity output, kW
Time, sec
*For S series 340/410/480/550kW Models Only
temperature, evaporation temperature, and running time during heating pipelines and power supplies need to be connected. It can be
operation, ensuring efficient defrosting when there is frost and stable powered up and used within two or three days, with less
heating when there is no frost. The heating operation rate of the unit
workload, simple installation, low overall installation cost,
reaches over 90%, and the heating energy efficiency ratio is significantly
improved. shortened commissioning time, and more than 40% reduction
in equipment room land investment costs. For energy-saving
Time
renovation of old equipment projects, it can easily achieve
rapid replacement.
07/08
AIR COOLED CHILLERS
SCROLL CHILLER
The unit program comes with multiple protection functions to ensure its stable and reliable operation. Full range of environ- The optional intelligent cloud system features diverse control methods. Users can monitor the unit's operating status and
mentally friendly modular units are equipped with water flow switches as standard, eliminating the installation and commis- parameters in real-time through a mobile app. It has functions such as automatic protection, remote detection, remote
sioning of water flow switches in the project. This not only brings higher guarantees for the safe operation of the unit, but control, and self-diagnosis, reducing economic losses caused by downtime risks during user operation. It adopts the
also simplifies the relevant work and expenses in the project, bringing benefits and convenience to customers. RS485 standard communication interface and open protocol, enabling remote modular monitoring and control through the
network, and can be easily integrated into building automation systems.
Interactive interface
Adopting a user-friendly human-machine interaction control interface, a 7-inch full touch screen, intuitive parameters,
simple operation, and complete control functions: it achieves energy control, automatic operation, intelligent defrosting,
balanced operation, power-off memory, and other controls. RS485
T Series
Interactive interface
Water side (water temperature) Air side (outdoor temperature)
The unit can automatically memorize and store the Item Nominal operating condition Operating range Nominal operating condition Operating range
data and operating status before power failure. After Inlet(℃) Outlet(℃) Outlet(℃) I/O difference(℃) DB(℃) WB(℃) DB(℃)
Cooling 12 7 5~20 2.5~6 35 -15~48 Ultra Wide
the power is restored, the unit will automatically
Heating 40 45 30~50 2.5~6 7 6 -15~48 Ultra Wide
resume the operating status before power failure
without resetting, which is convenient for users to use
and manage. S Series
Water side (water temperature) Air side (outdoor temperature)
Item Nominal operating condition Operating range Nominal operating condition Operating range
Inlet(℃) Outlet(℃) Outlet(℃) I/O difference(℃) DB(℃) WB(℃) DB(℃)
Cooling 12 7 5~20 2.5~6 35 10~48
Heating 40 45 30~50 2.5~6 7 6 -15~25
09/10
AIR COOLED CHILLERS
T Series Dimensions
Technical Specifications
SCROLL CHILLER
CTAS340BHA-TM
Quantity - 3 4
Type Axial fan Axial fan
760
Fan Air flow m /h 123000 164000 90.00
°
90.00
°
Remarks:
1. The nominal cooling capacity and nominal cooling input power are tested at the rated water flow, water outlet temperature of 7°C, and outdoor dry-bulb
temperature of 35°C.
The nominal heating capacity is tested at the rated water flow, water outlet temperature of 45°C, outdoor dry-bulb temperature of 7°C or outdoor wet-bulb
temperature of 6°C.
2. About 6% loss caused by system pipelines, water pumps, valves, and dirt after unit installation shal be considered for the cooling heating capacity in actual
application.
3. Cooling temperature range: -15°C-48°CCTAS340BHA/460BHA
Heating temperature range -15°C-48°C CTAS340BH/460BH/340BHA/460BHA .
4. The specifications above are based on a single module. Multiple modules can be used in combination. A maximum of 8 modules can be combined.
5. As a separate item, control accessory box contains a wired controller, a wired controller communication cable, user manual, and temperature sensor. The
configuration is subject to changes, so please refer to actual unit upon delivery.
11/12
AIR COOLED CHILLERS
S Series, Standard Model S Series, With Built-in Hydraulic Module
SCROLL CHILLER
Cooling Only Model CKAW-340A2C-SHM CKAW-410A2C-SHM CKAW-480A2C-SHM CKAW-550A2C-SHM
Cooling Only Model CKAW-340A2C-SM CKAW-410A2C-SM CKAW-480A2C-SM CKAW-550A2C-SM Model Number
Model Number Heat Pump Model CKAW-340A2R-SHM CKAW-410A2R-SHM CKAW-480A2R-SHM CKAW-550A2R-SHM
Heat Pump Model CKAW-340A2R-SM CKAW-410A2R-SM CKAW-480A2R-SM CKAW-550A2R-SM
Cooling Capacity kW 340 410 480 550
Cooling Capacity kW 340 410 480 550
Cooling Power Input kW 104 125.8 146.5 168
Cooling Power Input kW 104 125.8 146.5 168
EER W/W 3.27 3.26 3.28 3.27
EER W/W 3.27 3.26 3.28 3.27
Heating Capacity kW 365 440 515 590
Heating Capacity kW 365 440 515 590
Heating Power Input kW 105 127.8 149.6 172
Heating Power Input kW 105 127.8 149.6 172
COP W/W 3.45 3.44 3.11 3.43
COP W/W 3.45 3.44 3.11 3.43
Power Supply Format - 380V/3N ~ 50Hz
Power Supply Format - 380V/3N ~ 50Hz
Compressor Type - Scroll Type Compressor
Compressor Type - Scroll Type Compressor
Compressor Quantity Pcs 5 6 7 8
Compressor Quantity Pcs 5 6 7 8
Refrigerant Type - R410A
Refrigerant Type - R410A
Air Side Heat Exchange Type - Aluminum Copper Heat Exchanger
Air Side Heat Exchange Type - Aluminum Copper Heat Exchanger
Fan Motor Quantity Pcs 5 6 7 8
Fan Motor Quantity Pcs 5 6 7 8
Water Volume m /h 58.5 70.5 82.6 94.6
Water Volume m /h 58.5 70.5 82.6 94.6
Water Pressure Drop kPa 67 69 72 75
Water Pressure Drop kPa 67 69 72 75
Max Water Pressure Durability Mpa 1
Max Water Pressure Durability Mpa 1
Connection Method - Flanged Connection
Connection Method - Flanged Connection
Water Connection Pipe Size mm DN125 DN125 DN150 DN150
Water Connection Pipe Size mm DN125 DN125 DN150 DN150
Throttling Device Type - High Precision Electrical Expansion Valve
Throttling Device Type - High Precision Electrical Expansion Valve
Width, mm 3280 3280 4370 4370
Width, mm 3280 3280 4370 4370
Outline Dimensions Depth, mm 2300 2300 2300 2300
Outline Dimensions Depth, mm 2300 2300 2300 2300
Height, mm 2450 2450 2450 2450
Height, mm 2450 2450 2450 2450
Transportation Weight kg 3000 3250 4000 4250
Transportation Weight kg 3000 3250 4000 4250
Operation Weight kg 3150 3415 4200 4470
Operation Weight kg 3150 3415 4200 4470
Noise Level dB(A) 82 83 84 85
Noise Level dB(A) 82 83 84 85
Water Pump Qty 1 1 1 1
Water Pump
Hydraulic Module 11 11 11 15
Power Input
Unit External
20 25 21 26
Pump Head Lift
Remarks:
1. Rated cooling capacity test conditions: water flow rate 0.172m³/(h·kW), outlet water temperature 7°C, outdoor dry-bulb temperature 35°C;
2. Rated heating capacity test conditions: water flow rate 0.172m³/(h·kW), outlet water temperature 45°C, outdoor dry-bulb/wet-bulb temperature 7°C/6°C; Remarks:
3. The above parameters are for a single unit and can be used individually or in combination. The number of units in combination can be 1 to 8. Specifications are 1. Rated cooling capacity test conditions: water flow rate 0.172m³/(h·kW), outlet water temperature 7°C, outdoor dry-bulb temperature 35°C;
subject to change without notice due to improvements. 2. Rated heating capacity test conditions: water flow rate 0.172m³/(h·kW), outlet water temperature 45°C, outdoor dry-bulb/wet-bulb temperature 7°C/6°C;
3. The above parameters are for a single unit and can be used individually or in combination. The number of units in combination can be 1 to 8. Specifications are
subject to change without notice due to improvements.
13/14
AIR COOLED CHILLERS
SCROLL CHILLER
340/410kW Outline Dimension(Standard Model) 340/410kW Outline Dimension(With Hydraulic Module)
Water
Inlet
Water
Water Water Outlet
Inlet Outlet
Water
Inlet
Water
Outlet
Water Water
Inlet Outlet
15/16
AIR COOLED CHILLERS
Air Screw Chillers (Fix Speed, Heat Pump) Intelligent and reliable oil lubrication system
●In addition to the built-in oil separation screen of the compressor, the unit is also equipped with an external vertical oil separator to ensure the
efficiency of oil separation.
Appearance
Screw Chillers
●Vapor injection oil return will be automatically initiated to ensure the oil return from the external oil separator when needed, to ensure sufficient
oil lubrication for critical components inside the compressor.
Modular design
Different models with different capacities (modules) can be seamlessly integrated into one system by connecting the shell and tube heat exchanger,
LMP Series(50Hz) to expand the cooling capacity. The modular design facilitates lifting and transportation, and reduce the installation space as well. Each module can
be set as the master unit, and when one fails, the other remains operational.
Control panel
90RT 449RT
7 inch key screen or 10 inch touch screen be selected and the display screen provides Chinese and English interface switching function to meet
different needs, the display parameters are as follows:
Chilled water inlet and outlet temperature Suction and exhaust temperature
Evaporation pressure Condensing pressure
Compressor start times Cumulative compressor running time
Contactor status Solenoid valve status
Water temperature setting value Etc.
Golden fin Inner groove Modular Comprehensive Self-diagnosis Easier Memory Easier 24 hour timer
condenser copper structure protection maintainability function maintainability Multiple protection functions
The unit has several protection functions, such as for high exhaust temperature protection, safety valve protection, motor winding overheating
protection, low pressure protection, high pressure protection, anti-freeze protection, on/off protection of water flow, lack of reverse phase, sensor
Features failure protection and fan overcurrent protection to ensure stable operation under various conditions and to avoid damage caused.
High-accuracy electronic expansion valve (EXV) control LWT: Leaving water temperature
EWT: Entering water temperature
3810 pulses EXV which combines coarse and fine adjustment for precisely adjusting flow of refrigerant to maintain the correct superheat, thus
to improve heat exchanging efficiency under deviation and especially part-load working condition.
17/18
AIR COOLED CHILLERS
Technical Specifications
Screw Chillers
LMPB54NG2E/ LMPB55NH1E/ LMPB33LF550LE7E/ LMPB33LF533LF5E/ LMPB33LF543LG3E/ LMPB43LG343LG3E/
Model Cooling only LMPA30JD4E/Nb-M LMPB30JD3E/Nb-M LMPA40JE2E/Nb-M LMPB40JE1E/Nb-M LMPA50LE8E/Nb-M LMPB50LE7E/Nb-M Model Cooling only
Nb-M Nb-M Nb-M Nb-M Nb-M Nb-M
kW 315 340 400 445 505 550 kW 1000 1120 1240 1380 1480 1580
Cooling Cooling
TR 89.6 96.7 113.7 126.5 143.6 156.4 TR 284.4 318.5 352.6 392.4 420.8 449.3
Capacity Capacity
kW 320 335 410 430 520 545 kW 980 1075 1230 1370 1470 1570
Heating Heating
TR 91.0 95.3 116.6 122.3 147.9 155.0 TR 278.7 305.7 349.8 389.6 418.0 446.4
Capacity steps % 25%,50%~100% 25%,50%~100% 25%,50%~100% 25%,50%~100% 25%,50%~100% 25%,50%~100% Capacity steps % 12.5%,25%~100% 12.5%,25%~100% 8.3%,16.7%~100% 6.25%,12.5%~100% 6.25%,12.5%~100% 6.25%,12.5%~100%
COPC W/W 3.21 3.21 3.23 3.22 3.22 3.25 COP W/W 3.25 3.24 3.23 3.21 3.22 3.22
COPH W/W 3.23 3.22 3.25 3.21 3.25 3.22 COP W/W 3.23 3.22 3.24 3.25 3.24 3.23
Power supply V/Ph/Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz Power supply V/Ph/Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz 380V/3N~/50Hz
Cooling kW 98 106 124 138 157 169 Cooling kW 308 346 384 430 460 490
Power input Power input
Heating kW 99 104 126 134 160 169 Heating kW 303 334 380 422 454 486
Type - Semi-hermetic screw Type - Semi-hermetic screw
Compressor Starting mode - Star delta start Star delta start Star delta start Star delta start Star delta start Star delta start
Compressor Starting mode - Star delta start Star delta start Star delta start Star delta start Star delta start Star delta start
Quantity - 2 2 3 4 4 4
Quantity - 1 1 1 1 1 1 Refrigerant Type - R134a R134a R134a R134a R134a R134a
Refrigerant Type - R134a R134a R134a R134a R134a R134a Type - Flooded evaporator
Type - Flooded evaporator m3/h 172.0 192.6 213.3 237.4 254.6 271.8
m3/h 54.2 58.5 68.8 76.5 86.9 94.6 rate GPM 758 849 940 1047 1122 1198
Water side heat
rate GPM 239 258 303 337 383 417 kPa ≤70 ≤55 ≤55 ≤60 ≤60 ≤60
Water side heat exchanger Pressure drop
kPa ≤35 ≤35 ≤45 ≤45 ≤45 ≤45 ft.WG ≤23.0 ≤18.0 ≤18.0 ≤19.7 ≤19.7 ≤19.7
exchanger Pressure drop
ft.WG ≤11.5 ≤11.5 ≤14.8 ≤14.8 ≤14.8 ≤14.8 Connection
- DN150 DN150+DN125 DN150+DN125 2×DN150 2×DN150 2×DN150
Connection pipe
- DN100 DN100 DN125 DN125 DN125 DN125
pipe Type -
Type - Total fan air m3/h 21500×18 21500×20 21500×22 21500×24 21500×26 21500×28
Air side heat
Total fan air m3/h 19500×6 21500×6 19500×8 21500×8 19500×10 21500×10 CFM 12654×18 12654×20 12654×22 12654×24 12654×26 12654×28
Air side heat exchanger
exchanger CFM 11477×6 12654×6 11477×8 12654×8 11477×10 12654×10 Total fan motor
kW 1.8×18 1.5×20 1.5×22 1.5×24 1.5×26 1.5×28
Total fan motor power
kW 1.5×6 1.8×6 1.5×8 1.8×8 1.5×10 1.8×10
power Dimension Outline mm 11000×2250×2550 12230×2250×2550 13450×2250×2550 14670×2250×2550 15890×2250×2550 17120×2250×2550
Dimension Outline mm 3670×2250×2550 3670×2250×2550 4890×2250×2550 4890×2250×2550 6110×2250×2550 6110×2250×2550 (W×D×H) Package mm 11150×2330×2550 12380×2330×2550 13600×2330×2550 14820×2330×2550 16040×2330×2550 17270×2330×2550
(W×D×H) Package mm 3820×2330×2550 3820×2330×2550 5040×2330×2550 5040×2330×2550 6260×2330×2550 6260×2330×2550 Net/Gross/Operting Weight kg 12380/12420/12628 13160/13200/13423 15000/15040/15300 16820/16860/17156 18485/18525/18855 20150/20190/20553
Net/Gross/Operting Weight kg 4570/4610/4661 4600/4640/4692 5435/5475/5544 5500/5540/5610 6450/6495/6584 6590/6630/6722
Note: LMPB33LF550LE7E/Nb~LMPB43LG343LG3E/Nb can be splitted into two parts and transported separately.
19/20
FAN COIL UNITS (FCU)
Condensate Tray:
The two-row series uses a small enthalpy difference design, ideal for applications requiring high comfort and precise
Appearance
regulation.
The four-row series features a larger enthalpy difference design, providing enhanced dehumidification.
The four-pipe models (three rows for cooling, one row for heating) are designed for four-pipe air conditioning
Quiet function
systems, offering both cooling and heating to meet diverse needs.
Inner thread copper
Series Layout
12Pa FP-__WAS/G-K
Anti-corrosion Plastic Fan:
FP-__WAHS/G-K
30Pa FP-_WAHT/BHL-K
Lightweight, delivering higher air volume with the same motor. FP-__WAS-R
Consistent design of the vane and volute casing ensures quiet operation.
50Pa FPE-__WAUS/G(T)-K FPE-__WAUF/G(T)-K DC fan motor
CFD-optimized airflow passage and vane angle for improved efficiency.
Divided volute casing allows easy maintenance. Ultra high airflow and
130Pa FP-___B/U-K
ESP
Quiet and Comfortable:
Tangential arc + straight line + helix design for uniform airflow, reducing noise Technical Specifications
and improving comfort.
G Series Concealed Ceiling FCU 50Hz (3 rows(2 pipes), ESP: 12Pa)
High-quality and Reliable:
Model FP-34WAS/ FP-51WAS/ FP-68WAS/ FP-85WAS/ FP-102WAS/ FP-136WAS/ FP-170WAS/ FP-204WAS/
G-K G-K G-K G-K G-K G-K G-K G-K
Comprehensive motor testing (harmonic, sweep, winding temperature rise)
ensures electrical safety. m3/h 340/248/173 510/394/263 680/495/330 850/638/425 1020/788/525 1360/1095/730 1700/1275/850 2040/1575/1050
Optimized motor structure enhances performance in drop, stacking, and CFM 200/146/102 300/232/155 400/291/194 500/375/250 600/464/309 800/644/430 1000/750/500 1201/927/618
vibration tests, ensuring reliability.
ESP Pa 12 12 12 12 12 12 12 12
Easy Installation Capacity Cooling/Heating kW 2.25/3.60 3.30/5.30 4.30/6.93 5.00/8.05 6.30/10.10 8.20/13.20 9.80/15.80 11.25/18.6
V/Ph/
Power supply 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz
Fan mounting panel: its special design can meet bottom air return or rear air return. Power Hz
system
Installation switchover: the left-hand or right-hand installation can be switched over on site quickly. Input kW 0.035 0.052 0.062 0.075 0.096 0.134 0.148 0.189
Specially-designed electric box structure: for fan coil units with AC motor, the motor is separated with the capacitor, which can facilitate
L/s 0.09 0.14 0.17 0.21 0.27 0.4 0.5 0.55
after-sales replacement and maintenance.
volume
GPM 1.43 2.22 2.70 3.33 4.29 6.35 7.94 8.73
kPa 20 21 22 30 35 40 33 40
Heating pressure
drop
Ft.WG 6.56 6.89 7.22 9.84 11.48 13.12 10.82 13.12
Net weight/Gross weight kg 11.6/14.6 13.4/16.9 14.7/18.4 16.0/19.9 17.4/21.4 24.0/29.0 26.6/32.2 28.5/34.0
The air return plenum can be integrated or separated from the unit.
Nylon or aluminum filters (G2/G4) and metallic fan options available. Water inlet &
Inch Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4
Connection outlet(inner thread)
pipe
diameter Condensed water
Inch R23/4 R23/4 R23/4 R23/4 R23/4 R23/4 R23/4 R23/4
drain(outer thread)
21/22
FAN COIL UNITS (FCU)
G Series Concealed Ceiling FCU 50Hz (3 rows(2 pipes), ESP: 12Pa) G Series Concealed Ceiling FCU 50Hz (3 rows(2 pipes), ESP: 30Pa)
FP-34WAS/ FP-51WAS/ FP-68WAS/ FP-85WAS/ FP-102WAS/ FP-136WAS/ FP-170WAS/ FP-204WAS/ Model FP-34WAHS/ FP-51WAHS/ FP-68WAHS/ FP-85WAHS/ FP-102WAHS/ FP-136WAHS/ FP-170WAHS/ FP-204WAHS/
Model GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K GHL-K
m3/h 340/248/173 510/394/263 680/495/330 850/638/425 1020/788/525 1360/1095/730 1700/1275/850 2040/1575/1050 m3/h 340/248/173 510/394/263 680/495/330 850/638/425 1020/788/525 1360/1095/730 1700/1275/850 2040/1575/1050
CFM 200/146/102 300/232/155 400/291/194 500/375/250 600/464/309 800/644/430 1000/750/500 1201/927/618 CFM 200/146/102 300/232/155 400/291/194 500/375/250 600/464/309 800/644/430 1000/750/500 1201/927/618
ESP Pa 12 12 12 12 12 12 12 12 ESP Pa 30 30 30 30 30 30 30 30
Capacity Cooling/Heating kW 2.25/3.60 3.30/5.30 4.30/6.93 5.00/8.05 6.30/10.10 8.20/13.20 9.80/15.80 11.00/18.00 Capacity Cooling/Heating kW 2.25/3.60 2.25/3.60 4.30/6.93 5.00/8.05 6.30/10.10 8.20/13.20 9.80/15.80 11.00/18.00
V/Ph/ V/Ph/
Power supply 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz Power supply 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50H 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz
Power Hz Power Hz
system system
Input kW 0.035 0.052 0.062 0.075 0.096 0.134 0.148 0.189 Input kW 0.042 0.053 0.072 0.082 0.104 0.156 0.174 0.212
L/s 0.09 0.14 0.17 0.21 0.27 0.4 0.5 0.55 L/s 0.09 0.14 0.17 0.21 0.27 0.4 0.5 0.55
volume volume
GPM 1.43 2.22 2.70 3.33 4.29 6.35 7.94 8.73 GPM 1.43 2.22 2.70 3.33 4.29 6.35 7.94 8.73
kPa 22.00 31.00 31.00 42.00 47.00 47.00 38.00 41.00 kPa 31.00 30.00 31.00 43.00 49.00 47.00 40.00 42.00
Heating pressure Heating pressure
drop drop
Ft.WG 7.22 10.17 10.17 13.78 15.42 15.42 12.46 13.45 Ft.WG 10.17 9.84 10.17 14.10 16.07 15.42 13.12 13.78
Outline mm 680×520×235 800×520×235 900×520×235 1000×520×235 1080×520×235 1380×520×235 1520×520×235 1620×520×235 Outline mm 680×520×235 800×520×235 900×520×235 1000×520×235 1080×520×235 1380×520×235 1520×520×235 1620×520×235
Dimension Dimension
(W×D×H) (W×D×H)
Package mm 773×603×325 893×603×325 993×603×325 1093×603×325 1173×603×325 1473×603×325 1608×603×325 1713×603×325 Package mm 773×603×325 893×603×325 993×603×325 1093×603×325 1173×603×325 1473×603×325 1608×603×325 1713×603×325
Net weight/Gross weight kg 14.9/19.6 17.4/22.3 19.3/24.4 21.3/26.7 22.7/28.3 30.9/36.9 34.5/42.0 38.0/44.5 Net weight/Gross weight kg 14.9/19.6 17.4/22.3 19.3/24.4 21.3/26.7 22.7/28.3 30.9/36.9 34.5/42.0 38.0/44.5
Loading
40'GP/40'HQ Set 324/432 273/364 249/332 225/300 210/280 168/224 150/200 138/184
quantity
G Series Concealed Ceiling FCU 50Hz (3 rows(2 pipes), ESP: 30Pa) G Series Concealed Ceiling FCU 50Hz (3 rows(2 pipes), ESP: 50Pa)
FPE- FPE- FPE- FPE- FPE- FPE- FPE- FPE-
Model FP-34WAHS/ FP-51WAHS/ FP-68WAHS/ FP-85WAHS/ FP-102WAHS/ FP-136WAHS/ FP-170WAHS/ FP-204WAHS/ Model 51WAUS/ 68WAUS/ 85WAUS/ 102WAUS/ 136WAUS/ 170WAUS/ 204WAUS/ 238WAUS/
G-K G-K G-K G-K G-K G-K G-K G-K G(T)-K G(T)-K G(T)-K G(T)-K G(T)-K G(T)-K G(T)-K G(T)-K
m3/h 340/248/173 510/394/263 680/495/330 850/638/425 1020/788/525 1360/1095/730 1700/1275/850 2040/1575/1050 m3/h 510/394/264 680/495/340 850/638/425 1020/788/525 1360/1095/730 1700/1275/850 2040/1575/1050 2380/1850/1250
CFM 200/146/102 300/232/155 400/291/194 500/375/250 600/464/309 800/644/430 1000/750/500 1201/927/618 CFM 300/231/155 400/291/170 500/375/250 600/464/309 800/644/429 1000/750/500 1200/926/618 1400/1088/735
ESP Pa 30 30 30 30 30 30 30 30 ESP Pa 50 50 50 50 50 50 50 50
Capacity Cooling/Heating kW 2.25/3.60 3.30/5.30 4.30/6.93 5.00/8.05 6.30/10.10 8.20/13.20 9.80/15.80 11.25/18.60 Capacity Cooling/Heating kW 3.15/5.30 4.20/6.93 5.00/8.05 6.30/10.10 8.20/13.20 9.80/15.80 11.25/18.60 13.20/22.00
V/Ph/ 220-240V 220-240V 220-240V 220-240V 220-240V 220-240V 220-240V 220-240V V/Ph/
Power supply Power supply 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz 220-240V ~50Hz
Power Hz ~50Hz ~50Hz ~50Hz ~50Hz ~50Hz ~50Hz ~50Hz ~50Hz Power Hz
system system
Input kW 0.042 0.053 0.072 0.082 0.104 0.156 0.174 0.212 Input kW 0.04 0.049 0.061 0.08 0.101 0.125 0.173 0.208
L/s 0.09 0.14 0.17 0.21 0.27 0.4 0.5 0.55 L/s 0.16 0.21 0.24 0.28 0.39 0.47 0.54 0.64
volume volume
GPM 1.43 2.22 2.70 3.33 4.29 6.35 7.94 8.73 GPM 2.54 3.33 3.81 4.44 6.19 7.46 8.57 10.16
L/s 0.09 0.14 0.17 0.21 0.27 0.4 0.5 0.55 L/s 0.16 0.21 0.24 0.28 0.39 0.47 0.54 0.64
volume volume
GPM 1.43 2.22 2.70 3.33 4.29 6.35 7.94 8.73 GPM 2.54 3.33 3.81 4.44 6.19 7.46 8.57 10.16
Water Water
system system
kPa 20 21 22 30 35 40 33 40 kPa 21 22 30 35 40 33 40 50
Cooling pressure Cooling pressure
drop drop
Ft.WG 6.56 6.89 7.22 9.84 11.48 13.12 10.82 13.12 Ft.WG 6.89 7.22 9.84 11.48 13.12 10.82 13.12 16.4
kPa 20 21 22 30 35 40 33 40 kPa 21 22 30 35 40 33 40 50
Heating pressure Heating pressure
drop drop
Ft.WG 6.56 6.89 7.22 9.84 11.48 13.12 10.82 13.12 Ft.WG 6.89 7.22 9.84 11.48 13.12 10.82 13.12 16.4
Outline mm 680×490×235 800×460×235 900×490×235 1000×490×235 1080×490×235 1380×490×235 1520×490×235 1620×490×235 Outline mm 800×460×235 900×490×235 1000×490×235 1190×490×235 1520×490×235 1620×490×235 1770×490×235 1950×560×285
Dimension Dimension
(W×D×H) (W×D×H)
Package mm 788×258×570 908×258×570 1008×258×570 1108×258×570 1188×258×570 1488×258×570 1623×258×570 1728×258×570 Package mm 905×255×555 1005×255×555 1105×255×555 1295×255×555 1625×255×555 1725×255×555 1875×255×555 1970×350×640
Net weight/Gross weight kg 11.6/14.6 13.4/16.9 14.7/18.4 16.0/19.9 17.4/21.4 24.0/29.0 26.6/32.2 28.5/34.0 Net weight/Gross weight kg 14.2/16.9 16.2/19.4 17.4/21.0 18.8/22.7 27.6/33.6 30.3/35.8 32.8/38.3 40.0/47.0
Net weight/Gross weight kg 18/22 20.5/24 22/27 24.5/28 35/42 38.5/43 41/46 46.5/54.5
25/26
FAN COIL UNITS (FCU)
Concealed Ceiling Type (Duct Type), High Airflow Vol and ESP Series Remarks for High Airflow Vol and ESP Series
1. Cooling capacity test conditions: Supply and return water temperature 7/12°C; Return air conditions: Inlet air dry-bulb temperature 27°C,
Appearance wet-bulb temperature 19.5°C;
2. Heating capacity test conditions: Water supply temperature 60°C, water flow rate the same as during cooling; Return air conditions: Inlet air
dry-bulb temperature 21°C;
3. The air volume in the table is measured when the unit is operating in a dry state with a dry-bulb temperature of 20°C;
4. Water entrainment may occur if the duct static pressure loss is less than 80Pa;
5. The unit is equipped with a bottom return air box as standard unless otherwise specified;
6. The noise level in the table is measured in a semi-anechoic chamber with a background noise level of 11.5dB(A);
7. Specifications are subject to change without notice due to product improvements. Please refer to the unit nameplate for details;
Model Number: CTFM 800B 1000B 1200B 1600B 1800B 2000B 3000B Dimensions
H 1265 1510 1925 2490 2945 3880 5500
Airflow Vol, m
M 1015 1215 1540 1990 2360 3100 4395 Water Out
/h
L 815 970 1230 1595 1890 2485 3520
ESP, Pa H 130 130 130 130 130 130 130
H 8.29 9.87 12.04 15.93 19.11 24.26 34.41
Cooling
M 6.64 7.9 9.63 12.75 15.29 19.39 27.51 Water In
capacity, kW
L 5.3 6.31 7.7 10.2 12.22 15.53 22.01
H 6.11 7.39 8.75 11.87 14.28 17.62 25
Sensible cooling
M 4.89 5.91 6.99 9.51 11.42 14.09 19.98
capacity, kW
L 3.92 4.73 5.6 7.61 9.14 11.29 15.99
Condensate Water
H 12.37 15.19 19.6 24.56 28.66 39.47 55.99
Heating
M 9.89 12.51 15.68 19.65 22.93 31.58 44.79
capacity, kW
L 7.91 9.72 12.54 15.73 18.34 25.29 35.84
Power input, W H 280 370 600 700 750 1200 1800
Nosie, dB(A) H 62 63 64 63 64.5 65 66
Modle CTFM Water In/outlet size Condensate Water
Fan Type Forward-curved multi-blade centrifugal double-suction fan
Fan motor Type Single-phase capacitor motor
Type Aluminum finned copper tube
Max operating
1.6MPa
Heat pressure, Mpa
exchanger Water inlet/outlet R1 1/2 (Tapered pipe
R1(Tapered pipe external thread)
size external thread)
Water flow, m /h 1.6 1.88 2.39 3.08 3.65 4.5 6.16
Water resistance, kPa 6 14 25 20 25 35 45
Condesate water
Water tray R1 (Tapered pipe external thread)
pipe size
Width, mm 860 860 960 1110 1260 1560 2010
Outline
Depth, mm 820 820 820 820 820 820 820
dimensions
Height, mm 430 430 430 430 430 430 430
Net weight kg 50 50 56 65 76 94 126
27/28
FAN COIL UNITS (FCU)
Concealed Ceiling Type (Duct Type) FCU With Healthy Functions Our TiO2 photocatalytic sterilization fan coil unit has the following advantages:
Equipped with multiple high-power UV-A germicidal lamps and metal plate TiO2 filter screens, with a single
UV lamp power not less than 8W, ensuring effective purification throughout the entire air conditioning box;
Nano-grade high-strength titanium dioxide (TiO2) is used as the photocatalytic raw material, and
CMCW Series: Sterilization / Haze Removal high-temperature film coating technology is adopted to fully utilize the photocatalytic effect;
The UV lamp of the unit can not only provide a control access point for users to wire and control
Appearance themselves, but also achieve linkage control with the fan.
Base Unit
Remark:can only choose one.
Metal filter
Ionizer box
Electrostatic dust collector
cover
Access panel
Dust and pollutants in the air become ionized when passing through a high-voltage electric field, causing them to
change their direction of movement and become trapped. At this point, positively charged ions move towards the
Working
cathode plate (negative electrode) under the influence of the electric field force. Based on the principle of opposites
Principle
attract, the particulate matter is captured and adsorbed onto the collection plate by the energy instantly released by the
high-voltage charge, thus achieving the effect of dust removal and sterilization.
Our TiO2 photocatalytic sterilization fan coil unit has the following advantages:
With UV generator and Plenum Box, Fabric filter.
High-efficiency purification, PM2.5 single-pass purification efficiency ≥ 90%.
Adopting a direct-discharge ion sheet, Resistance ≤ 10Pa, compared with traditional HEPA, the resistance
Healthy functions explained is lower, it can be repeatedly cleaned, no need to replace it repeatedly, and the maintenance cost is low;
The unit can provide control access points For users to wire and control by themselves, it can also realize
Sterilization Option (TiO2, Photocatalytic Sterilization) linkage control with the fan.
29/30
FAN COIL UNITS (FCU)
Technical Speficiations
TCR Series: F7 High-Medium Filter / Micro-electrostatic filter module
CMCW Series: Sterilization / Haze Removal, 4 Pipes (3+1 Rows)
F7 High-Medium Filter Module
Model with Sterilization CMCW200VH/S CMCW300VH/S CMCW400VH/S CMCW500VH/S CMCW600VH/S CMCW700VH/S CMCW800VH/S CMCW1000VH/S CMCW1200VH/S CMCW1400VH/S
Model Number
Model with Haze removal CMCW200VS/H CMCW300VS/H CMCW400VS/H CMCW500VS/H CMCW600VS/H CMCW700VS/H CMCW800VS/H CMCW1000VS/H CMCW1200VS/H CMCW1400VS/H Appearance
H 340 510 680 850 1020 1170 1360 1700 2040 2380
Airflow Volume, m /h
M 279 418 510 660 836 900 1115 1394 1600 1785
(12/30/50Pa ESP)
L 170 255 340 425 510 585 680 850 1020 1190
Full cooling capacity H 2100 3200 4100 4850 5600 6300 7800 9000 10800 12600
Cooling capacity, W
Heating capacity, W H 2000 3000 3600 4450 5100 5600 7000 8000 9500 10000
L 23 23 21 25 28.5 29 28.5 33 30 32
The high-efficiency filter uses low wind resistance melt-blown PP material. It
H 39 40.5 42.5 43.5 45.5 46 45.5 48 49 50.5
adopts a folded filter paper structure to increase the filtration area, extend the
50Pa ESP M 32 36 39 39 38.5 39 39 42 43.5 45 filter's service life, and reduce the replacement frequency.
L 24 26.5 39.5 28 29.5 32 32 34 38.5 38
Cooling mode 0.36 0.55 0.7 0.83 0.96 1.08 1.34 1.54 1.85 2.16 The high-efficiency antibacterial filter is coated with silver ions, which have an
Water flow vol, m /h oxidizing effect and can be used for sterilization and disinfection. It is currently
Heating mode 0.17 0.26 0.31 0.38 0.44 0.48 0.6 0.69 0.81 0.94
the safest sterilizing agent.
Cooling mode 20 26 22 30 26 32 32 40 32 45
Water resistance, kPa
Heating mode 30 13 20 28 38 18 30 35 25 35
Protection Class (AC) IP20 Silver ions interfere with nucleic acid synthesis, hindering the
replication of genetic information, including the synthesis of DNA and
Insulation Class B
RNA, and the transcription of DNA templates to mRNA, etc.
Water inlet/outlet pipe Connection size Cooling coil: Rc 3/4; Heating coil: Rc 1/2 (Tapered Pipe Internal Thread)
Condenstate water pipe Connection size Rc 3/4 (Tapered Pipe External Thread)
Width mm 625 815 865 945 1045 1095 1425 1475 1675 1825
Outline Dimension Depth mm 465 465 465 465 465 1095 465 465 465 465
Height mm 235 235 235 235 235 235 235 235 235 235
Unit Net Weight (AC) kg 10.2 13 14.2 15.3 16.5 18 24.3 26.4 30.1 35.3
31/32
FAN COIL UNITS (FCU)
Micro-electrostatic filter module Technical Speficiations
CTCR Base Models
Appearance
Model CTCR
H
Airflow Vol M
L
H
Cooling Capacity, W M
L
H
Sensible Cooling, W M
L
Heating Capacity(60℃ water inlet), W H
33/34
FAN COIL UNITS (FCU)
Capacity Amendment Factors
Cassette Type FCU
Amendment factor when selector F7 High-Medium filter module
Appearance
Mode Number
H
Amendment
M
Factor
L
Outline Dimension
Water Out
Enhanced Fan Efficiency and Reduced Noise: The fan coil unit features an optimized airflow passage
design, significantly improving fan efficiency while minimizing operational noise.
44
Four-Way Airflow Distribution: Provides uniform temperature distribution across the space, ensuring
Note: Parameters for 1200/1400 are in parentheses.
consistent comfort.
Auto Evaporator Cleaning: Automatic moisture cleaning after power-off prevents mildew buildup,
Model Plenum Box
Width
maintaining a hygienic environment.
Emergency High-Speed Fan Mode: A forced high-speed fan operation is activated in emergency
Wiring box situations to ensure rapid response.
Comfortable and Safe Air Supply: The unit incorporates a metallic electric box and sealed motor holes,
offering enhanced fire protection and safer operation.
Efficient Condensate Drainage: The drain pump with a 1200mm lift capacity efficiently removes
M
condensate, ensuring smooth drainage across various applications.
Smart Control System: The integrated display and standard controller allow easy monitoring and
Dimension for unit with Micro-electrostatic filter module adjustment of key functions such as the ON/OFF timer, fan speed, operation mode (cooling, dehumidifying,
fan, and cooling), and temperature settings.
Improved Electric Box Design for Maintenance: For cassette-type FCUs with AC motors, the motor is
Water In
separated from the capacitor, simplifying maintenance and after-sales service.
302(322)
Water Out
76
Item ℃ ℃
Note: Parameters for 1200/1400 are in parentheses.
35/36
FAN COIL UNITS (FCU)
2 pipes, 50Hz Model FP-85XD/B-T FP-102XD/B-T FP-125XD/B-T FP-140XD/B-T
Model FP-51XD/A-K FP-68XD/A-K FP-85XD/B-T(E) FP-102XD/B-T(E) FP-125XD/B-T(E) m 3/h 800/650/550 1020/950/900 1180/1000/900 1400/1250/1150
Air flow volume(H/M/L)
m 3/h 510/400/300 660/560/460 800/665/590 940/770/670 1090/860/760 CFM 471/382/324 600/599/529 694/588/529 824/735/676
Air flow volume(H/M/L)
CFM 300/235/176 388/330/270 471/385/347 470/453/394 641/506/447 Capacity Cooling/Heating kW 4.5/5.6 5/6.5 6/7.8 8/9
Water inlet & outlet Water inlet & outlet Inch Rc3/4 Rc3/4 Rc3/4 Rc3/4
(inner thread) Inch Rc3/4 Rc3/4 Rc3/4 Rc3/4 (inner thread)
Connection pipe Connection pipe
diameter diameter
Condensed water drain Condensed water drain mm 31 31 31 31
(outer thread) mm 31 31 31 31 (outer thread)
mm 950×950×85 950×950×85 950×950×85 950×950×85 mm 950×950×85 950×950×85 950×950×85 1040 ×1040 ×85
Dimension Dimension
(W×D×H) (W×D×H)
mm 1033×1038×133 1033×1038×133 1033×1038×133 1033×1038×133 mm 1033×1038×133 1033×1038×133 1033×1038×133 1134 ×1134 ×125
Panel Panel
Net weight/Gross Net weight/Gross
kg 7/11 7/11 7/11 7/11 kg 7/11 7/11 7/11 8/12
weight weight
37/38
FAN COIL UNITS (FCU)
4 pipes, 50Hz
Model FP-68XDT/B-K(E) FP-85XDT/B-K(E) FP-125XDT/B-K(E) FP-180XDT/B-K(E) Model FP-125XDT/B-K FP-140XDT/B-K FP-180XDT/B-K FP-200XDT/B-K
3
3
m /h 680/618/571 850/764/697 1250/1108/1014 1700/1525/1421 m /h 1250/1108/1014 1400/1250/1100 1800/1525/1421 2000/1700/1500
Air flow volume(H/M/L) Air flow volume(H/M/L)
CFM 400/364/336 500/450/410 736/652/597 1000/897/836 CFM 736/652/597 824/736/647 1059/897/836 1177/1000/883
Capacity Cooling/Heating kW 3.5/5.8 4.5/6.8 6/9.2 8/12 Capacity Cooling/Heating kW 6/9 6.4/9.5 8/11.5 9/12.5
V/Ph/ V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz Power supply 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz
Hz Hz
Power system Power system
Input kW 0.082 0.09 0.135 0.191 Input kW 0.135 0.140 0.191 0.200
L/s 0.21 0.24 0.29 0.44 L/s 0.29 0.3 0.44 0.45
Cooling water flow Cooling water flow
volume volume
GPM 3.3 3.8 4.6 7 GPM 4.6 4.8 7 7.1
L/s 0.17 0.19 0.27 0.36 L/s 0.22 0.23 0.27 0.3
Heating water flow Heating water flow
volume volume
GPM 2.7 3 4.3 5.7 GPM 3.5 3.7 4.3 4.8
Water system Water system
Water inlet & outlet Inch Rc3/4 Rc3/4 Rc3/4 Rc3/4 Water inlet & outlet
(inner thread) (inner thread) Inch Rc3/4 Rc3/4 Rc3/4 Rc3/4
Connection pipe Connection pipe
diameter diameter
Condensed water drain mm 31 31 31 31 Condensed water drain
(outer thread) (outer thread) mm 31 31 31 31
Power supply
V/Ph/
Hz
220-240V~50Hz 220-240V~50Hz 220-240V~ 50Hz 220-240V~ 50Hz Nominal Operating Condition
Power system
Input kW 0.082 0.082 0.082 0.105
Notes:
L/s 0.15 0.21 0.24 0.27 1. The data are tested under these testing conditions as below
Cooling water flow
volume
GPM 2.4 3.3 3.8 4.3
kPa 70 76 86 70 Cooling 27 19 7 12
Heating pressure drop 2 PiPes
Ft.WG 23 25 28.2 23 50Hz
Heating 20 ≤15 45 40
Sound pressure level dB(A) 39 39 40 39
39/40
FAN COIL UNITS (FCU)
50Hz
Floor & Ceiling Type FCU
Model(B Series) FP-34ZD/B-K *3 FP-51ZD/B-K *3 FP-68ZD/B-K *3 FP-85ZD/B-K *3 FP-102ZD/B-K *3
V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Power Hz
system
Input kW 0.04 0.045 0.06 0.07 0.095
kPa 20 20 30 30 40
Heating pressure drop
Ft.WG 6.6 6.6 9.8 9.8 13.1
Auto clean Multi fan speed Self-diagnosis Compact design
Sound pressure level dB(A) 34 34 41 41 43
Condensed water
mm 17 17 17 17 17
drain(outer thread)
Features
Outline mm 870×235×665 870×235×665 870×235×665 1200×235×665 1200×235×665
The fan will operate only if the chilled water inlet temperature is lower than the setting value to avoid warm
Model(B Series) FP-119ZD/B-K *3 FP-136ZD/B-K *3 FP-170ZD/B-K *3 FP-204ZD/B-K *3
air under cooling condition.
m 3 /h 1200/950/700 1360/1100/800 1800/1400/1000 2040/1700/1200
Specially-designed electric box structure: for the floor ceiling type with AC motor, the motor is separated Air flow volume(H/M/L)
CFM 706/559/412 800/647/471 1059/824/589 1201/1000/706
with the capacitor, which can facilitate after-sales replacement and maintenance.
Capacity Cooling/Heating kW 5.9/6.6 6.6/7.5 9/11 10/12.5
V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Power Hz
system
Input kW 0.11 0.14 0.145 0.195
Condensed water
mm 17 17 17 17
drain(outer thread)
Loading
40'GP/40'HQ Set 189/216 147/168 147/168 147/168
quantity
41/42
FAN COIL UNITS (FCU)
Model FP-34ZD-K(E) FP-51ZD-K(E) FP-68ZD-K(E) FP-85ZD-K(E)
3
Nominal Operating Condition
m /h 400/300/210 510/400/310 680/550/450 690/570/485
Air flow volume(H/M/L)
CFM 235/176/124 300/235/182 400/324/265 406/335/285
Notes:
Capacity Cooling/Heating kW 1.9/2.4 2.8/3.4 3.5/4.1 3.6/4.2 1. The data are tested under these testing conditions as below
V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Power Hz
system Nominal test condition (temperature)
Input kW 0.046 0.065 0.076 0.084
Item Inlet Air ℃ Water ℃
L/s 0.09 0.13 0.17 0.17
Cooling water flow
volume DB WB Inlet Outlet
GPM 1.4 2.1 2.7 2.7
Condensed water
mm 17 17 17 17
drain(outer thread)
Loading
40'GP/40'HQ Set 224/267 224/267 224/267 224/267
quantity
3
m /h 910/756/600 1030/854/700 1800/1260/850 1940/1500/1050
Air flow volume(H/M/L)
CFM 535/445/353 606/502/412 1059/741/500 1141/882/618
V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Power Hz
system
Input kW 0.095 0.096 0.152 0.2
Condensed water
mm 17 17 17 17
drain(outer thread)
Loading
40'GP/40'HQ Set 220/244 220/244 111/117 111/117
quantity
43/44
FAN COIL UNITS (FCU)
Water system Cooling water flow L/s 0.07 0.09 0.14 0.16 0.21
Inner thread Washable filter Quiet function volume
copper GPM 1.1 1.4 2.2 2.5 3.3
Features
Model FP-102LM/D-K FP-119LM/D-K FP-136LM/D-K FP-170LM/D-K FP-204LM/D-K
Easy installation and convenient maintenance. Capacity Cooling/Heating kW 5/5.9 5.3/6.45 5.9/6.8 9.2/10.7 10.1/11.5
DB WB Inlet Outlet
Cooling 27 19 7 12
2 PiPes
50Hz
Heating 20 ≤15 45 40
45/46
FAN COIL UNITS (FCU)
3
m /h 340/255/170 510/382/255 680/510/340 850/637/425
Air flow volume(H/M/L)
CFM 200/150/100 300/225/150 400/300/200 500/375/250
Appearance
Capacity Cooling/Heating kW 2.2/2.4 2.7/2.9 3.6/3.9 4.3/4.7
V/Ph/
Power supply 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Hz
Power system
Input kW 0.012 0.018 0.029 0.043
kPa 24 35 55 65
Heating pressure drop
Ft.WG 7.9 11.5 18 21.3
Water inlet & outlet(inner thread) Inch 1/2 1/2 1/2 1/2
Inner thread Washable filter Anti-cold Quiet function Auto clean Multi fan speed Compact design Connetion pipe
Condensed water drain(outer
copper function mm 15.6 15.6 15.6 15.6
thread)
Loading
40'GP/40'HQ Set 604/682 604/682 604/682 461/525
quantity
Optimized Airflow Design for Enhanced Efficiency and Low Noise: The advanced airflow passage design
significantly improves fan efficiency and reduces operational noise for quieter performance.
Air Vent for Enhanced Reliability: The unit is equipped with an air vent, ensuring more reliable and efficient
operation.
Optimized Electric Box Structure for Easy Maintenance: In wall-mounted units with an AC motor, the motor Nominal Operating Condition
is separated from the capacitor, allowing for easier maintenance and after-sales replacement.
Notes:
1. The data are tested under these testing conditions as below
47/48
FAN COIL UNITS (FCU)
YB1FA(MOTO)
Wireless remote
controller
XE7A-17/E(M)
Wired remote
controller
XE70-17/E(M)
(with BMS
interface)
WK-011PM
WK-011PN
WK-010PM
Features
WK-010PN
High-sensitivity capacitive touch keys
Digital
thermostat Built-in Wi-Fi and RS-485 interfaces
WK-010PR
WK-010PS
Note:
means optional
49/50
Compact Air Handling Units
Compact Air Handling Units Ceiling Mounted (Horizontal) Type
Appearance
Compact air handling unit provides you an energy efficient large capacity
multi-functional terminal device of superior performance, better reliability
with lower installation cost. The product was designed with features of
c o n f i g u r a t i o n f l e x i b i l i t y, i n t e g r a t e d c o n t r o l o p t i o n s , a n d p r o v e n
performance to bring you the optimal system with function of filtering,
humidifying, and cooling(heating) for your building.
Compact AHU
Series Features
A large drain pan is designed under the heat exchanger,motor and fan to gurantee all drainage water will
be efficiently collected.
Nominal Condition
* : These series models are basic models. They may not have the required certificate in your targeted market.
For more information, please consult your regional sales manager.
51/52
Compact Air Handling Units
Fresh air
A Series
Integral frame structure casing with double skin panels made of galvanized Model G-1.5WDX(I)(Y)/A-M G-2WDX(I)(Y)/A-M G-2.5WDX(I)(Y)/A-M G-3WDX(I)(Y)/A-M G-4WDX(I)(Y)/A-M G-5WDX(I)(Y)/A-M
steel sheet.
Air flow volume m3/h 1500 2000 2500 3000 4000 5000
4-row and 6-row coil optional.
Airflow range:1500-12000m3/h. ESP range (4/6 rows) Pa 50~350/50~350 50~600/50~600 50~600/50~600 50~400/50~350 50~450/50~450 50~600/50~600
Designed excellently against air leakage and surface water condensation.
Cooling capacity
kW 20.6/25.8 27.5/33.5 33/41.6 40.7/50.2 55.3/66.6 66.3/82.4
(4/6 rows)
Model G-1.5WD(I)(Y)/A-M G-2WD(I)(Y)/A-M G-2.5WD(I)(Y)/A-M G-3WD(I)(Y)/A-M G-4WD(I)(Y)/A-M G-5WD(I)(Y)/A-M Water flow volume
L/s 0.99/1.25 1.28/1.6 1.57/2.1 1.9/2.4 2.63/3.2 3.17/4
(4/6 rows)
3
Air flow volume m /h 1500a 2000 2500 3000 4000 5000 Pressure drop
kPa 30.3/30.4 40.5/22.3 25.4/35.6 46.6/42.5 30.8/50.8 56.9/35.6
(4/6 rows)
ESP range (4/6 rows) Pa 50~350/50~350 50~600/50~600 50~600/50~600 50~400/50~350 50~450/50~450 50~600/50~600
Water inlet pipe
mm 25 25 25 25 32 32
diameter
Cooling capacity
kW 9.8/11.96 12.5/14.26 15.6/19.2 18.7/22.13 24.9/30.18 31/35.4
(4/6 rows) Water outlet pipe
mm 25 25 25 25 32 32
diameter
Heating capacity
kW 15.8/17.12 21.4/22.62 27.3/25.8 33.5/33 43.2/44.2 56.1/53.1
(4/6 rows) Condensed water
mm 25 25 25 25 25 25
drain pipe diameter
Water flow volume
L/s 0.43/0.57 0.53/0.65 0.66/0.88 0.79/1.03 1.1/1.44 1.3/1.71
(4/6 rows)
Sound pressure level dB(A) ≤58 ≤58 ≤58 ≤58 ≤60 ≤62
Pressure drop
kPa 6.5/5.25 9.2/7.85 16.3/15.4 26.2/19.92 20.1/24.6 35.3/34
(4/6 rows) Outline
Compact AHU
cm 103×100×57 103×100×57 123×100×57 103×100×67 123×100×77 143×100×77
dimension(W×D×H)
Water inlet pipe
mm 25 25 25 25 32 32
diameter Package
cm 133×130×87 133×130×87 153×130×87 133×130×97 153×130×107 173×130×107
dimension(W×D×H)
Water outlet pipe
mm 25 25 25 25 32 32
diameter
Condensed water
mm 25 25 25 25 25 25 Model G-6WDX(I)(Y)/A-M G-7WDX(I)(Y)/A-M G-8WDX(I)(Y)/A-M G-9WDX(I)(Y)/A-M G-10WDX(I)(Y)/A-M G-12WDX(I)(Y)/A-M
drain pipe diameter
Sound pressure level dB(A) ≤58 ≤58 ≤58 ≤58 ≤60 ≤62 Air flow volume m 3 /h 6000 7000 8000 9000 10000 12000
Outline
cm 103×100×57 103×100×57 123×100×57 103×100×67 123×100×77 143×100×77 ESP range (4/6 rows) Pa 50~500/50~450 50~350/50~350 50~400/50~400 50~600/50~600 50~600/50~600 50~600/50~600
dimension(W×D×H)
Cooling capacity
kW 79.6/98.8 92.9/112.3 106.3/129.7 119.5/148.9 134.9/165.2 159.3/198.8
(4/6 rows)
Heating capacity
kW 80.7/96.5 89.5/113.6 108.8/124.1 121.4/142.6 138.6164.5 160.9/197.1
(4/6 rows)
Model G-6WD(I)(Y)/A-M G-7WD(I)(Y)/A-M G-8WD(I)(Y)/A-M G-9WD(I)(Y)/A-M G-10WD(I)(Y)/A-M G-12WD(I)(Y)/A-M
Water flow volume
L/s 3.8/4.7 4.43/5.4 5.1/6.1 5.7/7.3 6.4/8.4 7.6/9.5
(4/6 rows)
Air flow volume m 3 /h 6000 7000 8000 9000 10000 12000
Pressure drop
kPa 45.8/29.4 50.5/31.5 55.1/40.4 45.2/42.5 47.4/46.8 50.8/48.7
ESP range (4/6 rows) Pa 50~500/50~450 50~350/50~350 50~400/50~400 50~600/50~600 50~600/50~600 50~600/50~600 (4/6 rows)
Pressure drop Sound pressure level dB(A) ≤62 ≤64 ≤64 ≤66 ≤66 ≤68
kPa 38.9/34.1 49.7/17.3 53.5/20.8 34/14.3 48.9/16.5 37.3/25.6
(4/6 rows)
Outline
cm 143×100×77 163×100×77 183×100×77 203×100×77 213×100×77 253×100×77
Water inlet pipe dimension(W×D×H)
mm 40 40 40 50 50 50
diameter
Condensed water
drain pipe diameter
mm 25 25 25 25 25 25 Control System DDC Starting Cabinet Wired Controller
WK-E00110A
Sound pressure level dB(A) ≤62 ≤64 ≤64 ≤66 ≤66 ≤68 Model / /
WK-E00000A
Outline
cm 143×100×77 163×100×77 183×100×77 203×100×77 213×100×77 253×100×77
dimension(W×D×H)
Package
cm 173×130×107 193×130×107 213×130×107 233×130×107 243×130×107 283×130×107
dimension(W×D×H)
53/54
Compact Air Handling Units
Jet Series
3 No cold bridge, no rust
The Jet-type AHU is a compact air handling unit designed for efficient space
utilization. It features a ceiling-mounted structure and adjustable spherical nozzles The cabinet interior is insulated from the exterior through high-pressure
for direct, ductless air supply, reducing installation costs and ceiling height. This polyurethane foam and a specially designed rubber sealing strip, effectively
unit ensures precise temperature control and is ideal for supermarkets, commercial preventing cold bridging. The cold bridge factor meets the AHRI1350 CB2
buildings, workshops, and large venues. standard. Additionally, the external metal plate is enclosed by an aluminum
frame, with its corners sealed off from exposure to humid air, ensuring
For installations near corrosive environments (e.g., seashores, paper mills, steel complete dust prevention and maintaining optimal performance.
mills, or chemical plants), consult the relevant plant(s) to ensure stable operation.
Copact AHU
4 Excellent Thermal Insulation
Jet Series Features & Advantages
The cabinet panels are constructed using one-time foam molding of
polyurethane, featuring a low heat conductivity coefficient and both external
A labyrinth sealing structure, with the concave and
1 Labyrinth-type sealing structure convex modules interlocked and internal metal plates. With a foaming density of ≥ 50 kg/m³, the panels
provide excellent heat preservation, thermal insulation, shock absorption, and
The cabinet panel utilizes advanced overall foam molding technology, encased
Compact AHU
noise reduction. The thermal insulation performance meets the AHRI1350 CT2
in an aluminum alloy profile frame with concave and convex grooves. Upon standard, ensuring superior energy efficiency and operational stability.
installation, these grooves interlock to form a tenon-style labyrinth sealing
structure. Secured by bolts and embedded nuts, this design creates a robust,
torsion-resistant sealing cabinet. The cabinet’s mechanical strength meets the
5 Clean & hygienic, quiet operation
AHRI1350 CD4 standard, while its air leakage rating achieves the AHRI1350
CL1 standard, ensuring superior durability and airtight performance. The unit features an integral drain pan with corrosion protection through static
plastic spraying, ensuring heat preservation. The drain pan is positioned on the
bottom of the cabinet, and a water discharge slope is created during
installation to ensure proper drainage of condensate, preventing bacteria
buildup. The unit is enclosed with double-wall foaming boards, providing
2 High Efficiency Heat Exchanger
excellent thermal insulation and reducing operational noise.
The heat exchanger is designed using AHRI-certified professional selection software,
ensuring that the model parameters accurately reflect the performance of the actual
heat exchanger. This allows the heat exchanger to meet diverse model selection
requirements for customers under various operating conditions.
The coil features high-quality, RoHS-certified copper tubes and hydrophilic aluminum
fins, integrated through an advanced mechanical tube expansion process. Each coil
undergoes an air tightness test before delivery, guaranteeing zero leakage and reliable 6 Intelligent integrated control
operation.
The unit features mechanical and electrical integrated control, allowing seamless management of the
fan, motor, and water valve. The control system uses low-voltage devices and temperature controllers
from internationally recognized brands. With a communication-enabled temperature controller, the unit
can connect to third-party systems like building automation and control systems for remote and
network-based monitoring.
The control cabinet includes multiple protection features, such as short-circuit, power loss, and overload
protection, ensuring stable operation. Additionally, the unit provides external interlocking options for fire
valves, fresh air valves, and switching-type water valves.
This integrated control system optimizes chiller energy efficiency while maintaining a comfortable indoor
temperature.
55/56
Compact Air Handling Units
Based on the performances of the unit and the spherical nozzle, the recommended horizontal air supply range (unit: m) of various types of air
Compact AHU
Note:
handling units is as follows:
3. The unit is not equipped with external static pressure. If a return air duct is required, please clarify the requirement when you make the order.
supply volume, cold water supply volume is provided in the table for your reference to select the water pump.
32 66.3
32
3N-
060 6000 Belt
2.2 2.2 drive
2.2 3.0
3.0 60.2 3.0
3.0 3.0
Note: Notes
supply volume, cold water supply volume is provided in the table for your reference to select the water pump.
57/58
Compact Air Handling Units
Comparison Between Air Pressures and Motor Powers Chilled water outlet pipe
Compact AHU
N 0.32 0.32 0.32
H 0.32 0.32
Lifting hole
N 0.32 0.32
020 2000
H 0.32
N
H
N
030 3000
H
Air Return
N M N Number Unit Weight
Model Outer Inner
A B C D E L P Q R of Air
H Normal Highly Normal Highly Size Diameter Diameter Normal Highly
S T Outlets
Cold Cold Cold Cold Cold Cold
N
H
020
N 2.2
060 6000
H 2.2 2.2 030 230
Note:
2. The above weight and size do not include the built-in control cabinet.
59/60
Compact Air Handling Units
Features
Concise Air Handling Units
1 Labyrinth-type sealing structure
Appearance The overall foamed box panel is surrounded by aluminum alloy profiles with
concave and convex grooves, forming a mortise-and-tenon type male and
female interlocking labyrinth seal structure during installation. The connection
method is secured by bolts and embedded nuts, forming a labyrinth sealed box
with strong torsional resistance. The mechanical strength of the box can reach
AHRI1350 CD4 level, and the air leakage rate can reach AHRI1350 CL2 level.
Compact AHU
rusting.
CTAD Series
3 High Efficiency Heat Exchanger
The heat exchanger is designed with AHRI-certified software, ensuring accurate model
Series Overview performance and meeting diverse customer needs under various conditions.
Frame Structure: The coil uses high-quality, RoHS-certified copper tubes and hydrophilic aluminum fins,
> Labyrinth-style internal and external frame box structure.
assembled via advanced mechanical tube expansion. Each coil is air-tightness tested
> Characteristics: low air leakage rate, high strength, and no thermal bridges.
before delivery to ensure zero leakage and reliable operation.
Customization and Combinations:
> Units are divided into 11 combination types based on functional section combinations and structure variations.
Innovative Maintenance: 4 Excellent Thermal Insulation
> Improved structure design for more convenient maintenance of filters and coils.
Air Volume and Pressure Options: The cabinet panels are constructed using one-time foam molding of
> Air volume range: 2000-60000 m³/h. polyurethane, featuring a low heat conductivity coefficient and both external
> Multiple external pressure options available. and internal metal plates. With a foaming density of ≥ 50 kg/m³, the panels
Compact and Efficient Performance: provide excellent heat preservation, thermal insulation, shock absorption, and
> Compact structure with excellent cooling and heating performance.
noise reduction. The thermal insulation performance meets the AHRI1350 CT2
> Can be equipped with hot water coils and wet film humidifiers per customer requirements.
Cost-Performance Advantage: standard, ensuring superior energy efficiency and operational stability.
> Higher cost-performance advantage compared to modular air conditioning units.
61/62
Compact Air Handling Units
Vertical type V1 Vertical type V2 Vertical type V3
6 Optimized Fan and Motor Design for Low Noise and High Efficiency Pre-filter+Cooling coil +Fan Return Grill+Cooling coil +Fan Return Grill+Cooling coil +Fan
section section + Air outlet Grille section + Jet Air Outlet
The fan impeller and pulley undergo precise static and dynamic balancing,
while the fan is rigorously tested for vibration during operation to ensure stable
performance. A shock absorber is integrated into the shared base of the fan
and motor, and a flexible connector between the fan outlet and the AHU body
effectively isolates moving parts, minimizing vibration and ensuring smooth,
quiet operation.
Compact AHU
8 Labyrinth-type sealing structure
Horizontal type H4 Horizontal type H5 Horizontal type H6
Achieve integrated control of the fan motor and water valve, the system is Mix + Pre-filter + Cooling coil + Dry Steam Mix + Pre-filter + Medium Filter+ Cooling coil + Mix + (Pre-filter + Static Dedust+ Cooling coil +
composed of low-voltage electrical appliances and thermostats from Humidifying + Fan section Dry Steam Humidifying + Fan section Fan section
UF UF UR FT FB
63/64
Compact Air Handling Units
Base Units Technical Specifications
Standard Capacity (4 Rows) Hight Capacity (6 Rows) Standard Capacity (4 Rows) Hight Capacity (6 Rows)
Base Base
Airflow Cooling Heating Water Water Chilled Condensate Cooling Heating Water Water Chilled Condensate Airflow Cooling Heating Water Water Chilled Condensate Cooling Heating Water Water Chilled Condensate
Model Model
Capacity Capacity Flow Resistance Water Pipe Water Pipe Capacity Capacity Flow Resistance Water Pipe Water Pipe Capacity Capacity Flow Resistance Water Pipe Water Pipe Capacity Capacity Flow Resistance Water Pipe Water Pipe
CTAD CTAD
Compact AHU
Notes: Notes:
1. Cooling: Inlet air dry-bulb temperature 27°C, wet-bulb temperature 19.5°C, inlet/outlet water temperature 7°C/12°C; Heating: Inlet air 1. Cooling: Inlet air dry-bulb temperature 35°C, wet-bulb temperature 28°C, inlet/outlet water temperature 7°C/12°C; Heating: Inlet air
dry-bulb temperature 15°C, hot water inlet temperature 60°C, water flow rate is the same as chilled water flow rate; dry-bulb temperature 7°C, hot water inlet temperature 60°C, water flow rate same as cooling water flow rate;
2. When the unit is in actual use, if the fresh air volume is increased, the cooling capacity of the unit will change. For details, please 2. * indicates that the inlet/outlet water temperature difference is greater than 5°C to control the refrigerant water pipe pressure drop;
consult TICA; 3. For parameters corresponding to other coil configurations and inlet air conditions, please refer to the product selection software;
3. For parameters corresponding to other coil configurations and inlet air conditions, please refer to the product selection software; 4. The header pipe diameter configuration of some vertical and horizontal units is different. The configuration outside the parentheses is
4. The header pipe diameters of some vertical and horizontal units are different. The values outside the brackets are for horizontal units, for horizontal units, and the configuration inside the parentheses is for vertical units.
and the values inside the brackets are for vertical units.
65/66
Compact Air Handling Units
Extra Componets Specifications
Wet film features and specifications
A wet film humidifier utilizes a hydrophilic material that evenly distributes absorbed water across its surface,
Standard Condition(Extra Heating Coil Specs for a 4 Pipes AHU) creating a water vaporization layer. As air flows over the material's surface, it evaporates and absorbs the water
Base
Base
Airflow
1 Row 2 Rows from this layer, humidifying the air. This principle is used to design evaporative humidifiers. The thickness of the
Model
Model Heating Capacity Water Flow Water Resistance Water Pipe Size Heating Capacity Water Flow Water Resistance Water Pipe Size
wet film is selected based on the desired humidification capacity, with the water supply being three times the
CTAD
humidification rate.
Compact AHU
Airflow Wet film face dimension Max humidifying Volume(kg/h) Weight(kg)
Base
Model Height,mm Width,mm
Notes:
When the unit is equipped with a wet film humidifier, the internal resistance of the unit should be increased accordingly: 50mm-20Pa;
Notes:
100mm-30Pa; 150mm-45Pa; 200mm-60Pa.
Heating (Return Air Mode): Inlet dry-bulb temperature 15°C, hot water inlet temperature 60°C, outlet temperature 50°C;
Heating (Fresh Air Mode): Inlet dry-bulb temperature 7°C, hot water inlet temperature 60°C, outlet temperature 50°C.
67/68
Modular Air Handling Units
Introduction
Modular Air Handling Units
As a result, Condor offers superior energy efficiency and reliability, perfectly tailored
to meet the specialized needs of various professional scenarios.
Modular AHU
Casing thickness: sandwich insulation panel 25mm
Seies A - CTAC 3
Commercial building
Convenient installation
economical design application
69/70
Professional Design
A labyrinth sealing structure, with the concave
and convex modules interlocked Reduced internal resistance, good energy
saving property
and hard co-extrusion sealing strip
Our modular air handling unit features a patented casing structure and meticulous design, delivering exceptional
performance in key areas such as mechanical strength, air tightness, thermal insulation, and cold bridge prevention.
Built to meet the EN1886 standard for casing performance, it has also earned certification from recognized industry
authorities, reflecting its superior quality and reliability.
Modular AHU
Access door
3
high-density polyurethane
Lower heat loss, high strength without Cleaner without volute and belt dust
copper pipe deformation
operation safety
reliability
71/72
Modular Air Handling Units
Core Components
Filter section
Fan section
Intelligent selection of optimal model, speed, and motor
in the unit height direction
balance before delivery, and operate stably.
Centrifugal fan
Modular AHU
Coil section
The requirement of healthy ventilation in public places can be
ll coils will undergo a pressure test before delivery to ensure worry-free
operation.
due to uncompleted drainage in winter. prevent secondary pollution from bacterial reproduction.
—— TICA 20 73/74
Modular Air Handling Units
Core Components
Heat recovery
· Temperature control
· Applicable to commercial
ecological protection. applications
fan section
Commercial
unit
· Temperature control
· Apply to 4-pipe commercial
applications
Modular AHU
and humidity · Applicable to process
unit
treatment
unit · Applicable to air-
conditioning systems in
75/76
Modular Air Handling Units
(unit in mm)
(unit in mm)
Section’s Name Symbol Specifications (for reference only)
Section’s Name Symbol Specifications (for reference only)
Modular AHU
•
L = 600
L = 700 - 3500 Access Door Access Door can be added before Filter Section,
Fan Section Details refer to Sections Length Table. Section Cooling Coil Section, Heating Coil Section, Sound
Attenuator Section, etc to ease maintenance works.
• •
Model L
0607-1117 600
Model L(1R-4R) L(5R-6R) L(8R-12R) Supply Air
1217-2126 800
Cooling Coil Section 0607-2940 600 700 900 Section
2227-2534 1000
3141-4565 1000 1000 1200 • 2834-4565 1200
•
Model L( 1 R-2R)
0607-2940 De-Humidifier L must be determined by the actual De-Humidifier
300
3141-4565 used.
600 Section
Heating Coil Section For model smaller than 3141, if heating coil is located
L
after cooling coil which is not larger than 8 rows, the
heating and cooling coil can be located in L the same
• drain pan. Total length is 900mm.
Sound Attenuator
T L L = 500,800,1100 for option
Section
<4 300
Electric Heater
700 •
Section
T = Electric Power (W) / Air Flow (CMH) Gas Heater Section L = 3000
•
L = 1 800
Moisture Eliminator Share length with cooling coil section
Steam L = 600 Evaporative Cooling Section L = 900
If it is located after Fan, L = 900.
77/78
Modular Air Handling Units
CTAC/CTBC
As a professional clean processing system integrator and service provider, we provide air treatment design and product custom-
-
ments, fully covering common needs. We are committed to providing users with the optimal clean environment solutions.
Modular AHU
Output of professional model selection reports
The model selection results can be output through a complete
set of reports, including the technical parameter detail list of each
function section of the unit, the coil model selection detail list,
79/80
Modular Air Handling Units
Cooling Coil Performance Chart Heating Coil Performance Chart
CTAC/CTBC CTAC/CTBC
Modular AHU
Notes: Notes:
Note Note
1.Fresh Air Condition: entering air temperature 35°CDB/28°CWB. 1.Fresh Air Condition: entering air temperature 7°CDB.
2.Return Air Condition: entering air temperature 27°C DB/19.5°CWB. 2. Return Air Condition: entering air temperature 15°C DB.
3.Chilled water entering/leaving temperature, 7°C/12°C.Coil face velocity is 2.5m/s. 3.Hot water entering/leaving temperature,60°C/50°C.Coil face velocity is 2.5m/s.
4.Manufacturer reserves the rights to change the data without prior notice. 4.Manufacturer reserves the rights to change the data without prior notice.
5.Abbreviations:SC - Sensible Cooling Capacity, TC - Total Cooling Capacity. 5.Abbreviations:TH - Total Heating Capacity.
81/82
Application features
Modular AHU
is to deliver highly efficient, clean, and energy-saving solutions tailored
energy-saving system with temperature and humidity control typically used in hospitals.
to meet the unique demands of every application.
is easy to clean, splicing is smooth which means can provide good dehumidifying
* Some functions are optional. Consult TICA factory for detailed configuration.
13 TICA —— 83/84
Application features Application features
Large air flow and high air
The demand for fresh air is
controlled in the production pressure fresh air devices are
whole-process supervision
process requirements strictly controlled complex and changeable
equipped
·
electronics plants.
Modular AHU
·
working conditions and meet indoor constant temperature and humidity requirements.
·
120,000 m3
Inverter motor
Large-capacity and multi-stage heat exchanger
* Some functions are optional. Consult TICA factory for detailed configuration.
* Some functions are optional. Consult TICA factory for detailed configuration.
85/86
Modular Air Handling Units
Sample Configuration: For Medical Operation Rooms
Sample Configuration: Large air flow MAU for Semiconductor factories
Energy-saving Fresh Air + Circulating Air Conditioning Section Arrangement
Fresh Air Unit Primary filter + Fan Motor + Air Evening + Medium filter + Heating + Cooling + Deep dehumidifying + Air outlet
Circulating Air
Air Mixing + Fan motor + Air evening + Medium filter + HEPA filter + Cooling + Heating + Humidifying + Air outlet
Conditioning Unit
Deep Air
Air inlet Air evening Heating dehumidifying Air mixing Air evening Sub-HEPA Heating Outlet
medium
section section section section Air supply fan section Air outlet
Cooling Heating
(Surface cooling/ Outline Dimensions
Type Deep dehumidifying) Capacity
(WxDxH, mm)
Fresh Air
Unit Re-cooling Reheating
Unit dimensions
capacity capacity capacity capacity
(m3
Modular AHU
40000 800 45 550 340 610 105 12900×3007×2085
45000 800 55 610 380 700 115 12900×2854×2442
50000 800 75 685 425 770 130 12900×3160×2442
55000 800 75 750 467 850 145 13900×2905×2697
60000 800 75 810 500 920 155 14000×3313×2697
70000 800 90 950 590 1080 180 14000×3619×2850
80000 800 90 1090 680 1240 205 14000×3874×2850
100000 800 110 1370 850 1550 260 15200×3772×3717
Circulating Air 120000 800 132 1630 1010 1850 310 15200×4486×3717
Conditioning 140000 800 160 1900 1150 2100 360 15400×4690×4074
Unit 180000 800 200 2450 1520 2750 450 15400×5098×4686
Notes:
1.The above configuration is a full fresh air unit designed for a chip manufacturing plant. For other tailored solutions, please consult with us.
2.The motor power listed is an estimated value, accounting for a reserved margin. The actual motor power is calculated based on the resistance created by the final-stage H13
high-efficiency filter.
3.The unit size provided is an estimate. Ensure that the machine room space is no smaller than the required size. For precise dimensions and selection assistance, contact the TICA
factory.
4.The air inlet conditions are 38°C/60% for the cooling season and -6°C/50% for the heating season.
Notes: 5.The inlet and outlet temperatures for cold water are 14/20°C (pre-cooling) and 7/13°C (re-cooling), while for hot water, both the inlet and outlet temperatures are 38/32°C.
1. The above are four-pipe fresh air handling units and four-pipe recirculating air handling units. For other solutions, please consult our local office.
6.For optimal performance, it is recommended that the air velocity across the coil does not exceed 2.5 m/s.
2. The unit dimensions are estimated values. It is recommended that the equipment room space should not be less than the required dimensions.
3. For fresh air units, the summer inlet air is 38°C 160%, chilled water inlet/outlet temperature is 7°C/12°C, and the outlet air temperature after deep dehumidification is 10°C; the
winter inlet air is -12°C, hot water inlet/outlet temperature is 45°C/40°C; the fluorine system cooling capacity is the rated cooling capacity under national standard conditions, not the
actual required dehumidification cooling capacity.
4. For recirculating air units, the return air is 24°C/50%, chilled water inlet/outlet temperature is 7°C/12°C, and hot water inlet/outlet temperature is 45°C/40°C.
5. The motor power is an estimated value with reserved margin. The current motor power is based on the resistance brought by the unselected F8 level (fresh air unit) and H12 level
(recirculating air unit) filters.
6. The principle of size selection recommendation is that the face velocity of the coil shall not exceed 2.5m/s (fresh air) / 2.7m/s (recirculating air).
87/88
Direct Expansion (DX) Air Handling Units
The outdoor unit adopts world-renowned inverter compressors complemented by The units have a wide range of applications, in addition to conventional commercial
our unique design to achieve powerful cooling and heating output for the unit. The buildings and other comfortable places, they are mainly used in pharmaceutical
compressor operates within an ultra-wide range, enabling precise energy factories, medical and health, bioengineering, food and beverage, electronics
regulation, eliminating energy waste, and contributing to carbon neutrality. industry and other places that require air cleanliness and temperature and humidity
control functions. They are suitable for air conditioning and purification areas
The indoor unit is based on our expertise and unique air handling unit, which can ranging from tens to thousands of square meters. Compared with water system
be tailored to customer needs to meet a wide variety of application scenarios, truly design, they have the advantages of simple system, convenient installation, and
creating the most suitable solution for customers. low cost.
89/90
DX Air Handling Units
Features and Advantages
Frequency (Hz)
Efficiency (%)
Stepless speed regulation. DC inverter fan motor Protection
100
DC motor
80
The fan performs stepless speed regulation according to the Innovative Refrigerant Cooling Technology · Micro-HEX
60
AC motor 45% outdoor environment and air conditioning load status, and
40 cooperates with the DC inverter compressor for precise control
High Temp.
Operation
Adopts a unique all-aluminum integrated plate heat dissipation
20
Motor speed (rps) and temperature control; the outdoor unit fan adopts a DC technology, utilizing condensed refrigerant (generally 30~55°C)
variable speed motor, which improves efficiency by 45% to exchange heat with the drive module (maximum 90°C),
150 1000
compared with an AC motor, and Effectively reduce operating Ambient Temp. significantly reducing the drive module's temperature. This
noise. Refrigerant cooling ensures that, under harsh conditions, the compressor can
Air cooling maintain optimal operating temperatures.
Cooling demand %
Full inverter design for significant energy savings
Stepped regulation
DX AHU
Wide Operating Range, Stable And Reliable
Cooling
Patented Constant Temperature And Humidity Control
Professional Design, Superior Performance Technology
Utilizing advanced DC inverter technology and a professionally Fast, precise, and energy-efficient.
designed heat exchanger, the equipment operates across a Original constant temperature and humidity control logic
Ambient Temp. wide ambient temperature range, from a high of 48°C to a low adjusts the control target under different temperature deviation
of -15°C. conditions to achieve fast and precise humidity control effect.
Heating
91/92
DX Air Handling Units
DX AHU Applications
Technologically advanced, with superior performance
DX AHU
processing methods based on capacity requirements, achieving precise energy regulation with a cost-effective configuration. This perfectly
adapts to the constant temperature requirements of fresh air systems.
93/94
DX Air Handling Units
Control Functions System Application Solution Types
Fully Functional, Easy To Operate Type 1: All circulated air Type 2: All fresh air
Set value
Operating status
visible, such as fan,
Actual value compressor, electric
display
Operating parameters
Model: Inverter circulating air purification type DX AHU Model: Inverter all fresh air purification type DX AHU
The curve diagram describes the set temperature and historical fault information
humidity and measured temperature and humidity changes
Type 3: Primary return air with fresh air DX solution/Secondary return air with fresh air DX solution
Notes:
1. Heat pump unit: Cooling / Heating / Ventilation / Electric heating modes, switched through a 7-inch LCD control panel.
2. Temperature / Humidity setting range: 8~45°C, 35~90%.
3. Timing on/off function: Supports setting by day of the week (Monday to Sunday) and time (24-hour format, adjustable to the minute).
4. Preheating function: When the intake air temperature is below 0°C, preheating is activated to ensure normal system operation;
typically configured with a 1:2:4 ratio.
DX AHU
5. Auxiliary electric heating function: When the direct expansion coil heating capacity is insufficient, auxiliary heating is activated to
ensure the unit's heating capacity.
6. Standard equipped with a 7-inch LCD control panel, which can be installed in the local control cabinet or the user's centralized
control room, with a standard cable length of 30m (or 100m) optional.
The display can show set temperature and humidity, actual temperature and humidity, operating mode, system real-time clock, day of
the week, on/off status, fault display, etc.
7. Rotating defrost function: Multi-system units can achieve alternating defrost function, so that when the unit is defrosting, the indoor
temperature and humidity requirements remain stable.
8. Defrost compensation function: When the outdoor unit is defrosting, the preheating electric heater (if any) and the reheating electric Primary air return Secondary air return
heater (if any) will operate for compensation according to the indoor temperature demand.
9. Reserved Modbus communication interface, which can transmit unit operating status, fault alarms and other information, and
Model: Inverter Air Purifying Air Conditioning Unit/Inverter Circulated Air Constant Temperature and Humidity Air
supports on/off, mode setting, temperature and humidity setting functions. It also supports centralized control for multiple systems on
site. Conditioning Unit
Application: Places with partial fresh air usage. The primary return air scheme is suitable for places with a small
number of air changes, and the secondary return air scheme is suitable for places with a large number of air changes or
where the selected air volume is much larger than the nominal air volume.
95/96
DX Air Handling Units
Technical Specifications
Type 4: Primary air return + Fresh air pre-handling solution
Fresh air
DX AHU
Inverter Split Type Deep Dehumidifying DX AHU ---P103
Fresh air unit: Inverter all fresh air Constant Temperature and Humidity DX AHU
Circulated air unit: Inverter circulated air purifying DX AHU,
Inverter circulated Air Constant Temperature and Humidity DX AHU
Applicable to: Locations requiring temperature and humidity control.
97/98
DX Air Handling Units
Technical Specifications
Width Width
Dimension Depth
Dimension Depth
(Single unit) (Single unit)
Height Height
Cooling Cooling
Type
Refrigerant
Charge Volume
DX AHU
Connection method Welded connection
Notes: Notes:
1. The nominal cooling capacity is measured under the conditions of indoor dry/wet bulb temperature 27/19°C and outdoor dry/wet bulb temperature 35/-°C. 1. The nominal cooling capacity is measured under the conditions of indoor dry/wet bulb temperature 27/19°C and outdoor dry/wet bulb temperature 35/-°C.
2. The nominal heating capacity is measured under the conditions of indoor dry/wet bulb temperature 20/15°C and outdoor dry/wet bulb temperature 7/6°C. 2. The nominal heating capacity is measured under the conditions of indoor dry/wet bulb temperature 20/15°C and outdoor dry/wet bulb temperature 7/6°C.
3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions. 3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions.
4. Piping conditions for unit performance testing: equivalent refrigerant length 7.5m (horizontal). 4. Piping conditions for unit performance testing: equivalent refrigerant length 7.5m (horizontal).
5. Operating ambient temperature range of the unit: cooling: -10~48°C, heating: -15~25°C. 5. Operating ambient temperature range of the unit: cooling: -10~48°C, heating: -15~25°C.
6. Specifications are subject to change without prior notice due to product improvement. Please refer to the unit nameplate for details. 6. Specifications are subject to change without prior notice due to product improvement. Please refer to the unit nameplate for details.
7. For the outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current during 7. For the outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current during
wiring. wiring.
DX Air Handling Units
Cooling Cooling
Type Type
Refrigerant Refrigerant
Charge Volume Charge Volume
DX AHU
Connection method Welded connection Connection method Welded connection
Condensate water tray connection pipe Condensate water tray connection pipe
Notes: Notes:
1. Nominal cooling capacity is measured under the condition of indoor dry/wet bulb temperature 24/17°C and outdoor dry/wet bulb temperature 35/-°C; 1. Nominal cooling capacity is measured under the condition of indoor dry/wet bulb temperature 24/17°C and outdoor dry/wet bulb temperature 35/-°C;
2. Nominal heating capacity is measured under the condition of indoor dry/wet bulb temperature 20/15°C and outdoor dry/wet bulb temperature 7/6°C; 2. Nominal heating capacity is measured under the condition of indoor dry/wet bulb temperature 20/15°C and outdoor dry/wet bulb temperature 7/6°C;
3. Rated cooling capacity does not consider the heat loss of the fan motor, and nominal air volume refers to the operating air volume under standard conditions; 3. Rated cooling capacity does not consider the heat loss of the fan motor, and nominal air volume refers to the operating air volume under standard conditions;
4. Piping conditions for unit performance test: equivalent refrigerant length 7.5m (horizontal); 4. Piping conditions for unit performance test: equivalent refrigerant length 7.5m (horizontal);
5. Ambient temperature range for unit operation: cooling: -10~48°C, heating: -15~25°C; 5. Ambient temperature range for unit operation: cooling: -10~48°C, heating: -15~25°C;
6. If the local water source conductivity exceeds the conductivity range required by the electrode humidifier, please select an electric heating humidifier; 6. If the local water source conductivity exceeds the conductivity range required by the electrode humidifier, please select an electric heating humidifier;
7. Specifications are subject to change without notice due to product improvements. Please refer to the unit nameplate; 7. Specifications are subject to change without notice due to product improvements. Please refer to the unit nameplate;
8. For outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when wiring; 8. For outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when wiring;
9. Conventional constant temperature and humidity air conditioning unit control can only guarantee the temperature and humidity control accuracy of the return air. 9. Conventional constant temperature and humidity air conditioning unit control can only guarantee the temperature and humidity control accuracy of the return air.
DX Air Handling Units
Throttling type Elecrical Expansion Valve Throttling type Elecrical Expansion Valve
Width Width
Dimension Dimension
(Single unit) Depth Depth
(Single unit)
Height Height
Weight(Single unit) Weight(Single unit)
Outdoor
Power supply Power supply
Outdoor Unit
Unit Cooling Cooling
Cooling Cooling
Rated current Rated current
(Single unit) Heating (Single unit) Heating
Max Max
Type Type
Refrigerant Refrigerant
Charge Volume Charge Volume
DX AHU
Notes: Notes:
1. The nominal cooling capacity is measured under outdoor dry/wet bulb temperature of 35/28°C. 1. The nominal cooling capacity is measured under outdoor dry/wet bulb temperature of 35/28°C.
2. The nominal heating capacity is measured under outdoor dry/wet bulb temperature of 7/6°C. 2. The nominal heating capacity is measured under outdoor dry/wet bulb temperature of 7/6°C.
3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions. 3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions.
4. Piping conditions for unit performance test: equivalent refrigerant length of 7.5m (horizontal). 4. Piping conditions for unit performance test: equivalent refrigerant length of 7.5m (horizontal).
5. The ambient temperature range for unit operation: cooling: 13~48°C, heating: -15~25°C (with electric preheating). When the outdoor ambient temperature is below 0°C and 5. The ambient temperature range for unit operation: cooling: 13~48°C, heating: -15~25°C (with electric preheating). When the outdoor ambient temperature is below 0°C and
heating operation is required, electric heating preheating of fresh air is needed. The electric preheating capacity should be selected based on preheating the minimum outdoor heating operation is required, electric heating preheating of fresh air is needed. The electric preheating capacity should be selected based on preheating the minimum outdoor
ambient temperature to above 5°C. ambient temperature to above 5°C.
6. Specifications are subject to change due to product improvement without prior notice. Please refer to the unit nameplate. 6. Specifications are subject to change due to product improvement without prior notice. Please refer to the unit nameplate.
7. For outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when wiring. 7. For outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when wiring.
99/100
DX Air Handling Units
Cooling Cooling
Max Max
Type
Refrigerant
Charge Volume
Connection method Welded connection Connection method Welded connection
DX AHU
Connection Liquid pipe Connection Liquid pipe
Size Size
Gas pipe Gas pipe
Condensate water tray connection pipe Condensate water tray connection pipe
Notes: Notes:
1. The nominal cooling capacity is measured under the outdoor dry/wet bulb temperature of 35/28°C; 1. The nominal cooling capacity is measured under the outdoor dry/wet bulb temperature of 35/28°C;
2. The nominal heating capacity is measured under the outdoor dry/wet bulb temperature of 7/6°C; 2. The nominal heating capacity is measured under the outdoor dry/wet bulb temperature of 7/6°C;
3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions; 3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions;
4. Piping conditions for unit performance test: equivalent refrigerant length of 7.5m (horizontal); 4. Piping conditions for unit performance test: equivalent refrigerant length of 7.5m (horizontal);
5. Ambient temperature range for the operation of the fresh air unit: cooling: 13~48°C, heating: -15~25°C (with electric preheating); 5. Ambient temperature range for the operation of the fresh air unit: cooling: 13~48°C, heating: -15~25°C (with electric preheating);
When the outdoor ambient temperature is lower than 0°C and heating operation is required, electric heating preheating of fresh air is required; the electric preheating capacity is When the outdoor ambient temperature is lower than 0°C and heating operation is required, electric heating preheating of fresh air is required; the electric preheating capacity is
selected based on preheating the lowest outdoor ambient temperature to above 5°C; selected based on preheating the lowest outdoor ambient temperature to above 5°C;
6. If the conductivity of the local water source exceeds the conductivity range required by the electrode humidifier, please choose an electric heating humidifier; 6. If the conductivity of the local water source exceeds the conductivity range required by the electrode humidifier, please choose an electric heating humidifier;
7. Specifications are subject to change without notice due to product improvement, please refer to the unit nameplate; 7. Specifications are subject to change without notice due to product improvement, please refer to the unit nameplate;
8. For the outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when 8. For the outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when
wiring; wiring;
9. The conventional constant temperature and humidity air conditioning unit can only achieve the temperature and humidity control accuracy at the location where the room sensor is 9. The conventional constant temperature and humidity air conditioning unit can only achieve the temperature and humidity control accuracy at the location where the room sensor is
installed. For the sensor installation location, please refer to the installation and operation manual. installed. For the sensor installation location, please refer to the installation and operation manual.
101/102
DX Air Handling Units
Inverter Split Type Deep Dehumidifying DX AHU Inverter DX AHU Outdoor Unit (Long Connection Piping) Technical Specifications
HP (1HP = 2.5kW) Outdoor Model *Qty CTSAV
Outdoor Model *Qty CTSAV Capacity in HP
Model Indoor Frame CTAC/ (1HP = 2.5kW)
Size CTBC Cooling Capacity 1
Cooling Capacity
Airflow Volume ³ Heating Capacity 1
Airflow Volume Range ³
Water coil optional rows Cooling Capacity 2
Inlet air dew point
Deep
temperature range Heating Capacity 2
Total length of water
Dehumidifying coil + Refrigerant coil
Indoor
Unit
Coil resistance Compressor type DC Inverter Compressor
Power supply Throttling type
Compressor type Elecrical Expansion Valve
DC Inverter Compressor
Throttling type Elecrical Expansion Valve Width
Width Dimension
Dimension (Single unit) Depth
Depth
(Single unit)
Outdoor Height Height
Unit Weight(Single unit) Weight(Single unit)
Power supply
Power input Rated Power supply
(Single unit)Max Cooling
Rated current Rated Power input
(Single unit) Max Heating
(Single unit)
Type Max
Refrigerant
Charge Volume
Connection method Welded connection Cooling
Rated current
Connection Liquid pipe (Single unit) Heating
Size
Gas pipe
Max
Condensate water tray connection pipe
Refrigerant Type
DX AHU
Throttling type Elecrical Expansion Valve
Dimension
Width C
Depth
(Single unit)
Outdoor Height
C
Unit Weight(Single unit)
Power supply
Rated C
Max
Rated current Rated
(Single unit) Max
Refrigerant
Type Notes:
Charge Volume 1. Cooling capacity 1 is measured under outdoor dry/wet bulb temperature conditions of 35/28°C; heating capacity 1 is measured under outdoor dry/wet bulb temperature conditions
Connection method Welded connection of 7/6°C;
Connection Liquid pipe 2. Cooling capacity 2 is measured under indoor dry/wet bulb temperature conditions of 24/17°C and outdoor dry/wet bulb temperature conditions of 35/-°C; heating capacity 2 is
Size
Gas pipe measured under indoor dry/wet bulb temperature conditions of 20/15°C and outdoor dry/wet bulb temperature conditions of 7/6°C;
Condensate water tray connection pipe 3. The rated cooling capacity does not consider the heat loss of the fan motor, and the nominal air volume refers to the operating air volume under standard conditions;
4. Piping conditions for unit performance testing: equivalent refrigerant length 7.5m (horizontal);
5. For 32HP, 64HP, and 96HP cooling capacity, if the equivalent length of connecting pipes needs to reach 50~100m, TSAVO320CRCX single-module and multi-module direct
Notes: expansion can be used to meet the requirements;
1. Piping conditions for unit performance test: equivalent refrigerant length 7.5m (horizontal); 6. The specifications of the outdoor unit wiring are shown in the sample "Electrical Parameter Table". Be sure to refer to the maximum power and maximum current when wiring;
2. Ambient temperature range for fresh air unit cooling operation: 13~48°C; 7. When the ambient temperature and unit supply air temperature deviate from the rated operating conditions, or the length of the connecting pipe is greater than 7.5m, the cooling
3. For outdoor unit wiring specifications, please refer to the "Electrical Parameter Table" in the brochure. Be sure to refer to the maximum power and maximum current when wiring; capacity correction factor can be found in the performance variation table.
4. The diameter of the refrigerant connecting pipe between the indoor and outdoor units is the same as the diameter of the refrigerant pipe of the outdoor unit.
103/104
DX Air Handling Units
Single ODU
Single ODU
Single ODU
Single ODU
Single ODU
Single ODU
Two ODUs
Single ODU
3 ODUs Two ODUs
Single ODU
Two ODUs
Two ODUs
3 ODUs
Single ODU
Two ODUs
3 ODUs
3 ODUs
DX AHU
Two ODUs
3 ODUs
Two ODUs
3 ODUs
105/106
DX Air Handling Units
Performance Deviation
4. Outdoor unit electrical specifications (single module or multi module units)
Communication
Power Supply Power cord current
Outdoor power cord recommendation Cable
Outdoor Model
1. Outdoor Ambient Temperature and Supply Air Temperature Correction Factor Type Voltage
recommendation, A Sectional
area, mm2
pcs Length, m
Sectional
area, mm2
When the ambient temperature or the unit's supply air temperature deviates significantly from the rated value, find the correction factor in the following
table to correct the outdoor unit's cooling performance. C
Example: If the actual operating ambient temperature of an outdoor unit is 30°C, and the indoor unit requires a supply air temperature of 18°C, then the actual cooling capacity correction factor of the outdoor unit = K1 0.75-1.25 mm2
C 5 pcs
× K2 = 1.08 × 1.12 = 1.21 Polyethylene
shielded
twisted pair
When the length of the connecting pipe between the indoor and outdoor units is too long or the height difference between the two units is too large, the
cooling capacity will be affected (refer to the attached table for the maximum pipe length). The correction coefficient of the cooling capacity is shown in the
C
table below:
C
Total equivalent length of single-way horizontal interconnected pipes (meters)
Amendment
Factor
Notes:
The recommended power cable specifications are based on the copper core cable specifications selected for single-core PVC insulated cables for fixed installation, laid in the air
and with an ambient temperature of 40°C. If the on-site installation conditions change, please refer to the power cable specification provided by the cable manufacturer and consider
2. Elbows and Oil Trap equivalent lengths compatible use as appropriate.
Connection pipe
outer diameter, mm
Elbow, m Electrical Schematic Diagram
Oil trap, m
DX AHU
copper pipe 1 ODU power supply
Note that for some models, when using long connecting pipes, the diameter of the connecting pipes needs to be expanded according to the following table
and the corresponding amount of refrigerant needs to be added. 2 IDU power supply
Electric heater power
Power 3
distribution
supply
Evaporator
Connection Pipe Length/ Indoor Outdoor Connection Pipe Size Addtional refrigerant charge volume
Heater
Outdoor Model when pipe length > 7.5 meters
cabinet Fan 4
Height Diff. Limits Liquid pipe Gas pipe
5 Motor power supply
C 6 Communication
C 7
Differential pressure and
other protection
C Constant
8 Air outlet temperature
C
temperature Indoor temperature and
and humidity 9
humidity
control
C cabinet
C
Notes: 1. This diagram is intended to guide on-site wiring in the case of one ODU;
2. Power distribution cabinet, power for on-site wiring and signal cable are not provided with the unit.
107/108
Air Curtains
Powerful isolation, Efficient and energy saving
Air Curtains
109/110
Air Curtains
Our Air Curtains adopt non-isometric quiet impellers to avoid the maximum
noise frequency area. Combined with scientific airflow design, it can reduce
noise effectively under stable operation. The working noise is around 50 dB
which is as quiet as the office.
Air Curtains
111/112
Air Curtains
NEW
S7 AIR CURTAIN S5 ALUMINUM
S5 ALUMINUM SERIES
Air Curtains
Model Unit Voltage Frequency Air velocity Air volume Noise Power Net weight Unit size
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm)
Unit Voltage Frequency Air velocity Air volume Noise Power Net weight Unit size CA-3509-L/Y S5 900 220-240 50/60 16 1100 52 230 13.5 900X220X240
Model
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm) CA-3510-L/Y S5 1000 220-240 50/60 16 1200 52 250 14 1000X220X240
CA-3512-L/Y S5 1200 220-240 50/60 16 1500 53 290 16 1200X220X240
CA-3209-L/Y 900 220-240 50 14.5 11.5 950 750 200 170 12 900x198x215 CA-3515-L/Y S5 1500 220-240 50/60 16 1900 55 380 20.5 1500X220X240
CA-3210-L/Y 1000 220-240 50 14.5 11.5 1050 850 210 180 12.5 1000x198x215 CA-3518-L/Y S5 1800 220-240 50/60 16 2280 57 450 24 1800X220X240
CA-3520-L/Y S5 2000 220-240 50/60 16 2520 58 470 27.5 2000X220X240
CA-3212-L/Y 1200 220-240 50 14.5 11.5 1350 1050 260 230 14.5 1200x198x215
CA-4009-L/Y S5 900 220-240 50/60 20 1400 57 300 13.5 900X220X240
CA-3215-L/Y 1500 220-240 50 14.5 11.5 1700 1350 330 300 18 1500x198x215 CA-4012-L/Y S5 1200 220-240 50/60 20 1900 58 400 16 1200X220X240
CA-3218-L/Y 1800 220-240 50 14.5 11.5 2050 1600 390 360 21.5 1800x198x215 CA-4015-L/Y S5 1500 220-240 50/60 20 2300 61 500 20.5 1500X220X240
CA-3220-L/Y 2000 220-240 50 14.5 11.5 2250 1750 400 370 24 2000x198x215
113/114
Air Curtains
5G SERIES
Model Unit Voltage Frequency Air velocity Air volume Noise Power Net weight Unit size
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm)
Air Curtains
CA-1209T5G 900 220-240 50/60 11 1400 55 160 10 900X190X225
CA-1212T5G 1200 220-240 50/60 11 1900 56 200 12.5 1200X190X225
CA-1215T5G 1500 220-240 50/60 11 2500 57 230 15.5 1500X190X225
CA-1218T5G 1800 220-240 50/60 11 3200 58 300 18 1800X190X225
CA-1220T5G 2000 220-240 50/60 11 3600 59 350 20 2000X190X225 Model Unit
(mm)
Voltage
(V~) (Hz)
Air velocity
Frequency
(m/s)
Air volumeNoise Power Net weight
(m3/h) (dB) (W) (kg)
Unit size
(mm)
115/116
Air Curtains
T2
Model Voltage Frequency Air volume Noise Power Net weight Unit size
Model Unit Voltage FrequencyAir velocityAir volume Noise Power Net weight Unit size (V~) (Hz) (m3/h) (dB) (W) (kg) (mm)
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm) CA-2512LK 380 50 1300 70 600 21.5 1600x420x370
CA-2515LK 380 50 1550 70 670 23 1900x420x370
CA-1209T2 900 220 50 11 1400 160 10.5 900X190X205 CA-2518LK 380 50 1950 71 740 24.5 2200x420x370
CA-1212T2 1200 220 50 11 1900 200 13 1200X190X205 CA-2520LK 380 50 2100 72 800 25.5 2400x420x370
CA-2525LK 380 50 2300 72 900 27 2900x420x370
CA-1215T2 1500 220 50 11 2500 230 16 1500X190X205 CA-2815LK 380 50 2600 73 1000 27.5 1940x450x380
CA-1218T2 1800 220 50 11 3200 300 18.5 1800X190X205 CA-2818LK 380 50 3000 73 1170 28.5 2240x450x380
CA-2820LK 380 50 3300 74 1280 30 2440x450x380
CA-1209T2/Y 900 220 50 11 1400 160 10.5 900X190X205 CA-2825LK 380 50 3700 74 1400 32.5 2940x450x380
CA-1212T2/Y 1200 220 50 11 1900 200 13 1200X190X205
CA-1215T2/Y 1500 220 50 11 2500 230 16 1500X190X205
CA-1218T2/Y 1800 220 50 11 3200 300 18.5 1800X190X205
Air Curtains
Model Unit Voltage FrequencyAir velocityAir volume Noise Power Net weight Unit size
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm)
Model Unit Voltage FrequencyAir velocityAir volume Noise Power Net weight Unit size CA-1209SK 900 220 50/60 12 1530 57 160 8.5 900x180x180
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm) CA-1212SK 1200 220 50/60 12 2070 58 200 11 1200x180x180
CA-1215SK 1500 220 50/60 12 2730 59 230 12 1500x180x180
CA-3009F/Y 900 220 50 8-10 1250-1100 53 100 7 900X200X156
CA-3012F/Y 1200 220 50 8-10 1700-1550 54 140 8.2 1200X200X156
CA-3015F/Y 1500 220 50 8-10 2200-1950 55 180 9.5 1500X200X156
CA-3018F/Y 1800 220 50 8-10 2650-2400 56 200 11 1800X200X156
117/118
Air Curtains
Model Unit Voltage FrequencyAir velocityAir volume Noise Power Net weight Unit size
(mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm)
Model Unit Frequency Voltage Power Air volume Air velocity Noise Net weight Unit size
(mm) (Hz) (V~) (W) (m3/h) (m/s) (dB) (kg) (mm)
Air Curtains
CA-6010A 1000 50 220/380 1000 4150 25 66 32.5 1000x306x352
CA-6012A 1200 50 220/380 1550 5640 25 69 45 1200x306x352
CA-6015A 1500 50 220/380 1950 7520 25 70 55.5 1500x306x352
CA-6018A 1800 50 220/380 2000 8500 25 70 61 1800x306x352
CA-6020A 2000 50 220/380 2450 9400 25 72 71.5 2000x306x352
CA-6509A 900 50 380 1400 4510 30 70 32.5 900x306x352
CA-6510A 1000 50 380 1450 4950 30 70 36 1000x306x352
Model Unit Voltage FrequencyAir velocityAir volume Noise Power Net weight Unit size
CA-6512A 1200 50 380 2300 6760 30 71 47 1200x306x352 (mm) (V~) (Hz) (m/s) (m3/h) (dB) (W) (kg) (mm)
CA-6515A 1500 50 380 2800 9000 30 72 57.5 1500x306x352 CAB-1509S 900 3N 380 50/60 14 2800 62 270 25.5 970X265X352
CA-6518A 1800 50 380 2900 10000 30 73 63 1800x306x352 CAB-1512S 1200 3N 380 50/60 14 3900 64 350 31 1270X265X352
CA-6520A 2000 50 380 3700 11200 30 74 73.5 2000x306x352 CAB-1515S 1500 3N 380 50/60 14 5000 65 430 38 1500X352X265
119/120
Air Curtains
6G NEW
5G HEATING
Air Curtains
Model Unit Voltage Frequency Motor power PTC heater Power Air velocity Air volume Rising temp Noise Net weight
Model Unit Frequency Voltage Motor power PTC heater Power Rising temp Air volum Air velocity Noise Net weight
(mm) (V~) (Hz) (W) (kW) (m/s) (m3/h) (K) (dB) (kg)
(mm) (Hz) (V~) (W) (kW) (K) (m3/h) (m/s) (dB) (kg)
H L H M L H L H L H L
H L H M L H L H L
14 CARM-1209S-3D/Y5G 900×190×260 380 50 160 110 6 4 2 9.5 8.5 1200 1000 35-45 13.5
CARM-1209T6G-D/Y 900x218 x247 50 220 250 220 8 5.5 2.5 35-40 1300 1150 9 8
CARM-1212T6G-D/Y 1200 x218 x247 50 220 290 260 10 7 3.5 35-40 1900 1750 9 8 17.5 CARM-1212S-3D/Y5G 1200×190×260 380 50 200 150 8 5 3 9.5 8.5 1700 1500 35-45 16
CARM-1209T6G-3D/Y 900x218 x247 50 380 250 220 8 5.5 2.5 35-40 1300 1150 9 8 14 CARM-1215S-3D/Y5G 1500×190×260 380 50 230 180 10 7 3 9.5 8.5 2200 1900 35-45 18.5
CARM-1212T6G-3D/Y 1200 x218 x247 50 380 290 260 10 7 3.5 35-40 1950 1750 9 8 17.5 CARM-1218S-3D/Y5G 1800×190×260 380 50 300 250 12 8 4 9.5 8.5 2700 2400 35-45 24
CARM-1215T6G-3D/Y 1500 x218 x247 50 380 350 320 12 8 4 35-40 2600 2300 9 8 21 CARM-1209S-D/Y5G 900×190×260 220 50 160 110 6 4 2 9.5 8.5 1200 1000 35-45 13.5
CARM-1218T6G-3D/Y 1800 x218 x247 50 380 500 470 16 10 5 35-40 2600 2300 9 8 27 CARM-1212S-D/Y5G 1200×190×260 220 50 200 150 8 5 3 9.5 8.5 1700 1500 35-45 16
CARM-1220T6G-3D/Y 2000 x218 x247 50 380 580 450 16 10 5 35-40 2900 2600 9 8 29 CARM-1215S-D/Y5G 1500×190×260 220 50 230 180 10 7 3 9.5 8.5 2200 1900 35-45 18.5
121/122
Air Curtains
Summer Winter
Model Power Input Air speed Air volume Noise Net SIZE
power level weight
(V/Hz) (w) (m/s) (m3/h) (dB) (kg) (mm)
H L H L
CARM-1210-S/Y 220/50 180/130 9 7 1500 1150 <57 18 1000x227x310
CARM-1215-S/Y 220/50 230/180 9 7 2250 1750 <59 28 1500x227x310
CARM-1220-S/Y 220/50 350/300 9 7 3250 2550 <61 34 2000x227x310
VERCIAL TYPE AIR CURTAIN / HEATING AIR CURTAIN
Model Voltage / Height of cool Height of heated Power Air velocity of Air velocity of Air volume Noise Size (L*W*H) Remark
Frequency air section air section (kW) cool air section heated air section (m³/h) (dB) (mm)
(V /Hz) (m) (m) Motor PTC (m/s) (m/s)
CFM-LC2000S 220/50 2 0 0.85 / 18 0 6790 480x330x2000 cool air only
CFM-LC2500S 220/50 2.5 0 1.1 / 18 0 8450 480x330x2500 cool air only
CFM-LC3000S 220/50 3 0 1.25 / 18 0 10230 480x330x3000 cool air only
CFM-LC3500S 220/50 3.5 0 1.55 / 18 0 11860 480x330x3500 cool air only
CFM-LC4000S 220/50 4 0 1.7 / 18 0 13580 480x330x4000 cool air only
CFM-LC4500S 220/50 4.5 0 2.1 / 18 0 15280 480x330x4500 cool air only
CRM-LC2000S-3D 380/50 0 2 0.85 24 0 11 4150 480x330x2000 2.0m heated
CRM-LC2500S-3D 380/50 0 2.5 1.1 24 0 11 4500 480x330x2500 2.5m heated
CRM-LC3000S-3D 380/50 1 2 1.25 24 11 11 6250 480x330x3000 2.0m heated+1.0m cool air
CRM-LC3500S-3D 380/50 1.5 2 1.55 24 11 11 7250 480x330x3500 2.0m heated+1.5m cool air
CRM-LC4000S-3D 380/50 2 2 1.7 24 11 11 8300 480x330x4000 2.0m heated+2.0m cool air
CRM-LC4500S-3D 380/50 3 2 2.1 24 11 11 8500 480x330x4500 2.0m heated+1.5m+1m cool air
Air Curtains
Model Voltage Noise Power Air velocity Air volume Heat dispersal capacity
Net weight Unit size
(V~) (dB) (w) (m/s) (m3/h) (Kw) (kg) (mm) Model Voltage Frequency Power PTC heater Power Air velocity Air volume Rising temp Noise Net weight Unit size
H L H L (V~) (Hz) (w) (kW) (m/s) (m3/h) (K) (dB) (kg) (mm)
CARM-5009A-S 220 630 21 17 2750 2320 28 23.5 21 36 900x351x376
H L H M L H L H L
CARM-5012A-S 220 850 21 17 3500 2920 36 30 27 43 1200x351x376
CARM-5015A-S 220 1050 21 17 4250 3550 44 37 33 51.5 1500x351x376 CARM-1209CS-3D/Y 380 50 160 110 8 5.5 2.5 10 8 1200 900 35-45 19 900X235x320
CARM-5018A-S 220 1300 21 17 5000 4150 52 43.5 39 58.5 1800x351x376
CARM-1212CS-3D/Y 380 50 200 150 10 7 3.5 10 8 1700 1300 35-45 22 1200x235x320
CARM-1215CS-3D/Y 380 50 230 180 12 8 4 10 8 2200 1650 35-45 25 1500x235x320
123/124
Water Valves
Selected C
MOTORIZED 2/3 WAYS VALVES ro
m
Our ert
if
ie
F
dS
tion
upp
Collec
Premium
liers
CDYH01-A Series Brands
FCU Motorized Valves
Water Valves
one-control customizable)
Operating Time: 30 seconds for opening valve, 30
seconds for closing valve
125/126
Water Valves
Selected C
Our ert
m if
MOTORIZED 2/3 WAYS VALVES ro
STATIC BALANCING VALVES
ie
F
dS
tion
upp
Collec
Premium
liers
CHVC Series Brands
Series Introduction
The CYHV series static balancing valve is a static hydraulic balancing valve with a straight flow valve body
structure, which can reasonably distribute the flow and effectively solve the problem of uneven room
temperature in heating (air conditioning) systems. At the same time, it can accurately adjust the pressure
drop and flow to improve the liquid flow state in the pipeline network system, so as to achieve the purpose
of pipeline network liquid balance and energy saving. The valve is equipped with an opening degree
indicator and a pressure measuring interface for flow measurement. As long as appropriate specifications of
balancing valves are installed at the branch pipes and user inlets, the total water volume of the system can
be controlled within a reasonable range, overcoming the unreasonable phenomenon of "large flow and
small temperature difference".
General Specifications
Balancing valve with precise design, simple structure, accurate parameters,
large flow capacity and pressure measuring holes located on the same side for
convenient measurement and energy saving.
The product is applied in the fields of HVAC cihlled water system, chemical industry, petroleum, mining, electric power, food,
pharmaceuticals, water supply and drainage, municipal, and mechanical equipment systems for liquid flow and temperature
regulation control.
Water Valves
127/128
Water Valves
VS9 Series
Basic Specifications
Motor part
Power supply
Control Method Switch type, with spring return function, always closed when power is off.
Power Input
Opening: s20s
Action Time
Closing: ≤15s
Protection Grade
Temp. range
Product operation
temp. range
Product operation
RH. range
Product storagte
temp. & RH. range -2065 ℃10~90% RH No Condenstate water
Nominal Pressure
Leakage rate
Valve body: HPb59-2
Materials Valve stem: HPb59-2
Sealing valve shaft: EPDM
Water Valves
129/130
Water Valves
Temperature
Technical Specifications Model Number
Model Number ML8824A0620 ML8824A1820 ML8824A1840
Leakage Rate
≤0.02% of Kvs Safety
Rated Stroke 20mm 20mm 40mm
Materials
Medium
Top Cover PC Plastic Factory settings.
Medium Cold/hot water Installation Requirements
Reverse action can be
Shell Body 600N: Plastic; 1800N: Cast aluminum
Medium Temp. Range +130 C · The water medium must meet VDI2035 achieved through the 5th
requirements. Bracket Cast aluminum
DIP switch on the PCB.
Materials · The valve stem position must not be below
the horizontal plane. Wiring
Valve Body Ductile Iron GGG40 · The fluid flow direction should be
consistent with the direction of the arrow on Wiring Terminals 1.5mm 2
Valve Seat Stainless Steel the valve body.
· It is strongly recommended to install a filter
PG13.5
Water Valves
Cable Connection
Valve Stem Stainless Steel
before the valve. Reserve PG13.5 and PG9 interfaces.
Valve Core Stainless Steel
131/132
Water Valves
VSHC Series
H
Applications
D
Honeywell VSBC series static balancing valves achieve Kv value adjustment by
manually adjusting the valve opening degree. When used with dedicated balancing
valve commissioning instruments, they can achieve accurate flow presetting.
Installing static balancing valves in the water systems of central air conditioning
systems allows for precise setting of the maximum flow rate of the pipelines through L
commissioning. This avoids pipeline overflow or underflow, achieving static balance
of the water system, and ultimately realizing comfort and energy saving in central air
conditioning systems.
Honeywell VSBC series static balancing valves are mainly installed on the branch
pipes or terminal branch pipes of central air conditioning water systems. They can
also be applied to other occasions with the same or similar functional requirements.
DN15 3.4
DN20 6.2
DN25 9.7
DN32 15.2
DN40 20.6
DN50 33.0
Water Valves
133/134
Water Valves
Water Valves
Screw: (
Flange: (
135/136
Water Valves
Selected C
Our
ro
m ert
if Notes
ie
F
dS
MANUAL VALVES
tion
upp
Collec
Premium
liers
Brands
CYH.Z11F Series
Manual Gate Valves
CYH.J11F Series
Manual Stop Valves
Valve Body Material: Forged Brass
Handle: Cast Iron Valve Body Material: Forged Brass
Sealing Material: Nitrile Rubber Handle: Cast Iron
Nominal Pressure: 1.6MPa Sealing Material: Nitrile Rubber
Applicable Medium: Cold and Hot Water Nominal Pressure: 1.6MPa
Operating Temperature: 0~95°C Applicable Medium: Cold and Hot Water
Working Temperature: 0~95°C
Valve Body Material: Forged Brass Connector: Forged steel (chrome plated)
Sealing Material: PTFE Corrugated pipe: 304 stainless steel
Nominal Pressure: 1.6MPa Sealing material: Nitrile rubber
Applicable Medium: Cold and hot water Nominal pressure: 1.6MPa
Working Temperature: 0~95°C Applicable medium: Cold and hot water
Working temperature: 0~95°C
Water Valves
137/138