General Requirements
5 Protection class Manufacturer's standard
6 Standards IEC 60076-11
7 Marine certification NA
8 Color of enclosure RAL or Munsell color code
9 Hi-Gloss painting No
10 Warranty 24 months
Primary Side
28 Primary voltage [V] 11000
29 Vector group D
30 Cable entry Bottom
31 Cable frame MCT frame (unpainted)
32 Primary winding conductor material Copper
Secondary Side
33 No. of secondary windings 2
34 Secondary voltage 1 / 2 [V] 690 /690 (Full Load)
35 Secondary winding power 1 / 2 [kVA] 1000/1000
36 Vector group Y11d0
37 Cable entry Bottom
38 Cable frame EMC cable glands
39 Earthing (secondary side) Solid
40 Secondary winding conductor material Copper
Additional Requirements
1 Type: ONAN (oil type).
2 Insulation Class: class A.
3 Temperature Rise of Oil/Winding by Thermometer/Resistance method over specified Ambient ( 50 Deg.C) : 45° / 50°C.