Power Factor Measurement and Correction Techniques
Power Factor Measurement and Correction Techniques
Abstract
The prevailing method of power factor measurement is debatable. Certain methods are suggested in this paper with hints to
improve power factor measurement and correction.
series also becomes significant as the impedance is kWh and kVArh. It is also assumed here that the
dependent upon the frequency. The power factor in energy consumed per unit time is constant. Then,
establishments using such devices is normally low, p.f. = AB/AD
about 0.4-0.6. The penalty attracted is high, and nor-
mal correction methods become defunct. The power factor determined by the supply authori-
ties is a stretched hypotenuse, i.e. the scalar addition of
the instantaneous kVAh values. The above value of the
3. Power factor measurement power factor could at times go below the mandatory
statutory limit of 0.85, thereby attracting a penalty.
The supply authorities take the cumulative monthly It is generally seen that there is an initial high power
readings of the kWh and kVAh meters. factor operation with reduced power factor at the end
Let the kWh reading be x, the kVAh reading be h, of the day. This usually occurs in medium-size indus-
and the kVArh reading be y (if any). The power factor tries where one or two shifts are operating. When the
(taken over a month) is given by load in the third shift is less, the power factor is low.
Even under such situations the power factor determined
P-f. = (x2 - x l )/(h2 - hi ) by the supply authorities is questionable.
It is generally seen that It can therefore be concluded that the best way to
determine the power factor is as follows:
H 2 _~ x 2 + y 2
p.f. = x / ( x 2 + y2)1/2
The industries which have attracted penalties have In other words, the power factor should only be
raised doubts about the method of determination of the related to the amount of reactive kVA supplied (re-
power factor. The various methods suggested for the ceived) by the supply authorities per unit kW of load
measurement of the power factor, they argue, could be over a specified time. It is therefore very important
any one of the following: to take the readings on exact specified dates to arrive at
(a) p.f. = ~ p.f.,/n an unquestionable value of the power factor for any
industry.
(b) 1/p.f. = (l/n) ~ (1/p.f.,) It is therefore obvious that supply authorities should
only instal two meters, a kWh and a kVArh meter, if
(c) p.f. = x2 - Xl trivector meters are used the power factor should only
[(x2 - x , )2 + (y2 - y , )2],/2
be determined by the kWh and kVArh meters; the
The question that arises, therefore, is how to arrive kVAh meter should only serve the purpose of obtaining
at a justifiable value of the power factor. the kVA MD.
Referring to Fig. l(a), it is tacitly assumed here that Generally speaking, if the machines of a factory run
the power factor over a period of time from tl to t2 has on full load, its power factor is best. The method of
remained constant at all loads. In this case, connecting capacitors on the main line and hoping
for the best is basically unscientific for varying load
p.f. = AB/AC conditions.
Referring to Fig. l(b), over the period of time from All phase correction devices should be connected on
t~ to t 2 the power factor of the load is varying. AB the load itself with the axiom 'load on, capacitor on'.
indicates the recorded kWh, AD the recorded kVAh,
5.1. M o t o r s
and BC the recorded kVArh. AC is the kVAh based on
It is best to correct the power factor of any motor at
no-load/dead-load conditions. The power factor at load
c / will be looked after by itself. The reason for this
// technique lies in the fact that magnetizing current
causes low power factor, whereas the load part of the
current has essentially a high power factor.
In star-delta starters, phase correction devices have
to be connected on the star side so that initially a lower
Fig. 1. Measurement of the power factor where (a) the power factor voltage is impressed and the initial current jerk is low,
is constant at all loads between t~ and t 2 and (b) it is varying. thereby reducing the chances of damage to capacitors.
C.S. Prasanna Kumar et al, Eleclric Power Systems Research 32 (1995) 141 143 143