Harmonics Principle Complete
Harmonics Principle Complete
The net result is the present design practice of rating the neutral conductors for three-phase
Wye 4-wire feeders and branch circuits in IT data center environment at 173% of the phase
current. This practice is fine, if the actual load is 100% nonlinear load. While this is correct
for a high-density nonlinear distributed PC desktop or office environment, it doesn’t take into
account load diversity in an IT data center rack environment.
k = harmonic currents, i.e., triplens – 3rd (180Hz), 9th (), 15th (90540Hz 0Hz), etc.
This formula takes into account both the linear and nonlinear load effects on the neutral
conductor. It also accounts for load imbalance of either linear or nonlinear loads. Generally
it is sufficient to use the 3rd & 9th as these are two dominant triplen harmonic currents.
Where: DPF = Displacement Power Factor THDi = Circuit Current % Total Harmonic
Distortion expressed as a decimal.
Case study The effects of load diversity are best illustrated through review of actual system data
measurements. Measurements were conducted to determine the power factors, neutral
current levels, and harmonics in a typical IT data center rack environment. Two installed
InfraStruxure™ (ISX) Type B systems were used in this study. The InfraStruxure™ Type B
architecture uses three-phase 20A multi-wire branch circuits (4-wire +ground) to efficiently
feed power to high density IT rack enclosures.
The system studied is installed at OneBeacon in Foxboro MA. This system consists of a 60
kVA, K-1, 480 delta input, 208 Y/120 output transformer feeding an APC Symmetra™ PX (40
Revision 0
Harmonics overload building power transformers and cause them to wear out.
Power transformers are rated in KVA and are designed to carry currents at the power line frequency (50 or
60 Hz). The factor that limits the power handling capacity of a transformer is how hot it gets. The heat in a
transformer is caused by the inherent resistance of the transformer and the current carried by it. When a
power transformer carries harmonic currents, an effect known as the proximity effect (sometimes confused
with the eddy current effect) causes the effective resistance of the transformer to increase with frequency.
The result is that the transformer rating must be decreased if the transformer carries significant harmonic
currents, otherwise it will overheat and wear out due to insulation degradation. Transformer failures are
often catastrophic and emit noxious fumes or fire; they can result in facility closure for days and a variety of
health and safety consequences.
For this to be a problem, three things must happen together: 1) The transformer must be loaded nearly to
capacity (unusual); 2) The transformer must have a poor "K" factor rating (bad proximity effect design); and
3) The load in the building must be mainly PCs. This is a real potential problem especially in situations
where a large number of PCs have been deployed. Again, the location for concern is typically an office
environment with high PC density such as a call center. The problem is no longer of concern in the
datacenter environment as explained previously.
Correcting Harmonics
If a UPS is used in conjunction with the equipment, then in some cases the UPS can correct or eliminate
the harmonics. Some single phase UPS like the APC Symmetra eliminates neutral current entirely. If a
power factor correcting UPS is used to power clusters of PCs, the harmonics problem cannot pass
upstream to the building wiring or power transformers. This approach has the advantage that it can be
retrofit to an existing building, and used with existing loads. It also corrects both the wiring and the
2003 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or 7
stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
transformer issues. For other types of loads, such as large industrial motor drives which are not covered by
the harmonic regulations, specialized products are available that can absorb harmonics near the source.
K-rated transformers
Modern office facilities with high densities of PCs should always be specified to include transformers with a
"K" rating of at least 9. These transformers have been specially designed to withstand harmonic currents.
For datacenters, a "K" rating of 9 would be sufficient to ensure harmonic carrying capability for the fraction
of the datacenter consisting of old legacy loads, PC loads, or lighting loads.
Conclusion
International regulations have dramatically affected the power requirements for computing systems.
Networking equipment, once rightly accused of "power pollution" and of causing fires due to overheated
transformers and wiring, have transformed into one of the "cleanest" loads to be found in a modern
commercial or industrial establishment. Datacenter design standards specifying double neutrals or
transformers with K=20 ratings are driving needless expense and should be updated.
2003 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or 8
stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com
K – Factor Transformer
K-Factor Dry-Type Transformers - Type FHK
Figure 1
Application Distorted 3rd and 5th Resultant Harmonic Waveform
The Problem
The extensive utilization of solid state
power conversion technologies has
7th
created new problems for the power 5th Harmonic
industry and power engineer designer. Harmonic
This technology, called Switch Mode Resultant
Power Supply (SMPS), consists of Wave
various types of solid state switching
elements. These switching elements
(Non-linear loads can produce additive 3rd order harmonic currents which may create
overloaded neutral conductors.)
These switching devices are in
computers, copy machines, fax ma-
chines, tele-communications equip-
ment, solid-state drives and controls, What Are Harmonics (multiples of the 60 Hz fundamental
!#$& $& '*+++/49 frequency), which are all generated
numerous types of DC-Power Loads. latest edition. by the non-linear load. Figure 1 shows
These solid state elements continu- the resultants of a distorted 3rd and
ously switch on and off producing Harmonic 5th harmonic waveform. It is not un-
non-linear or non-sinusoidal wave Harmonic components are repre- common for portions of an industrial
shapes in the current supplied from sented by a periodic wave having a power system to have 15 to 25% of
the energy source. frequency that is an integral multiple Total Harmonic Distortion (THD).
of the fundamental frequency. THD is calculated as the square
While a linear load uses current from root of the sum of the squares of all
the AC source continuously over the In other words, harmonics are volt-
ages or currents at frequencies that are harmonics, divided by the normal 60
sinusoidal cycle, a non-linear load hertz value as shown in Equation 1
(such as the SMPS) uses current integer multiples of the fundamental
in large pulses from the AC source (60 Hz) frequency, e.g. 120 Hz, 180
which creates harmonic distortion. Hz, 240 Hz, 300 Hz, etc. Harmonics Equation 1
These non-linear current pulses may are designated by their harmonic RMS RMS
RMSN ]
exceed the nameplate ampere rating number, or multiple of the fundamen- THD=
tal frequency. Thus, a harmonic with RMS ]
of the power source and may cause
transformers to run hotter than ex- a frequency of 180 Hz (three times
pected, even when these transformers the 60 Hz fundamental Frequency) This yields a root-mean-square
are supplying less than 50% of their is called the 3rd harmonic. (RMS) value of distortion as a per-
rated nameplate capacity. Harmonics superimpose themselves centage of the fundamental 60 hertz
on the fundamental waveform, dis- waveform.
With non-linear loads, overloaded
neutrals are also showing up in three- torting it and changing its magnitude. Therefore, THD is the percent of odd
phase panel boards serving single- For instance, when a sine wave volt- harmonics (3rd, 5th, 7th, ..., 25th, ...)
phase loads. In some cases the neutral age source is applied to a non-linear present in the load which can affect
conductor carries 180 Hertz currents, load connected from phase-to-neutral the transformer. This condition is
rather than 60 Hertz currents. This on a 3-phase, 4-wire wye circuit, the called a "Non-Linear Load" or "Non-
phenomenon is called triplen harmon- load itself will draw a current wave Sinusoidal Load".
ics. Triplens are multiples of three, made up of the 60 Hz fundamental
which do not cancel but are additive frequency of the voltage source plus
in the neutral conductor. 3rd and higher order odd harmonic
43
(!&&+/##" #"&3!##"
! " !# # !#&&01 -#!"
$%$##&#"& "%2 1% 3 01 (!&&+#+&
"'!()*"& % 01%3 '!!#,"
(! & " !# && (!"&##!&&+/ !&"&' 1!
!#'& 1!#"'!! )/"&#"4&
&!#!#+#,!! ## " &" ! &&' !#
600 Volt Class
(A) 50% Non-Linear Load (K-4 9th harmonic plus 125% non-linear load which can
Rating) Beyond the 9th Harmonic the operate at a total (Ih(pu)2h2) K-factor
16.7% of the rated current at the percentages of the fundamen- load value of 20. See Table 1
3rd Harmonic tal current through the 25th (D) 150% Non-Linear Load (K-30
10.0% of the rated current at the Harmonic shall be equal to the Rating)
5th Harmonic reciprocal of the odd harmonic 50.0% of the rated current at the
7.1% of the rated current at the number involved times 1.0 3rd harmonic
7th Harmonic The FP Type FHK13 series trans- 30.0% of the rated current at the
5.6% of the rated current at the former is designed for 100% linear 5th harmonic
9th Harmonic load plus 100% non-linear load which 21.4% of the rated current at the
Beyond the 9th Harmonic the can operate at a total (Ih (pu)2h2) K- 7th harmonic
percentages of the fundamen- factor load value of 13.0. See Table 1 16.7% of the rated current at the
tal current through the 25th (C) 125% Non-Linear Load (K-20 9th harmonic
Harmonic shall be equal to the Rating) Beyond the 9th Harmonic the per-
reciprocal of the odd harmonic 41.7% of the rated current at the centages of the fundamental current
number involved times 0.5 3rd harmonic through the 25th Harmonic shall be
The FP Type FHK4 series transformer 25.0% of the rated current at the equal to the reciprocal of the odd
is designed for 100% linear load plus 5th harmonic harmonic number involved times
50% non-linear load which can oper- 17.9% of the rated current at the 1.50
ate at a total Ih (pu)2 h2 K-factor load 7th harmonic The FP Type FHK30 series trans-
value of 4.0. See Table 1 13.9% of the rated current at the former is designed for 100%linear
(B) 100% Non-Linear Load (K-13 9th harmonic load plus 150% non-linear load which
Rating) Beyond the 9th Harmonic the can operate at a total (Ih(pu)2h2) K-
33.3% of the rated current at the percentages of the fundamen- factor load value of 30. See Table 1
3rd harmonic tal current through the 25th 1RWH In these examples the amount of non-linear
20.0% of the rated current at the Harmonic shall be equal to the -
5th harmonic reciprocal of the odd harmonic
14.3% of the rated current at the number involved times 1.25
7th harmonic The FP Type FHK20 series transform-
11.1% of the rated current at the er is designed for 100%linear load
44
K-Factor Transformer K-20, K-30, K-40: The higher num- Theory also states that for even har-
ber of each of these K-factor ratings monics, starting with the second or-
Ratings indicates ability to handle succes- der, when balanced the even harmonic
The K-Factor rating assigned to a sively larger amounts of harmonic will cancel in the common neutral.
transformer and marked on the trans- load content without overheating. Other odd harmonics add in the com-
former case in accordance with the Table 1 Gives examples of K-factor mon neutral, but their magnitude is
listing of Underwriters Laboratories, loads. considerably less than triplens. The
<# # &- RMS value of the total current is
ity to supply harmonic content in its
45
Multiplying Effect of Calculating K-Factor Loads
Cascading Shielded 1. List the KVA value for each load 4. Next, add-up the KVA-ILK values
Transformers category to be supplied. Next, as- for all loads or load categories to
sign an ILK value that corresponds be supplied by the transformer.
Having the presence of an upline trans- to the relative level of harmonics
former with an electrostatic shield may drawn by each type of load. See 5. Divide the grand total KVA-ILK
mean that other shielded transformers Table 2. value by the total KVA load to be
47
Examples:
Problem 1
;&#"&!4&&%#4&&&
C;' %A5C- C% >%A5C%A&"
*#!'&'!' 9 - 0 > 92
?##&##" - 302 > 29
600 Volt Class
Problem 2
;&#"&!"&%3&!#+!&+ 0%A5
% 3!:%A5##
1.*!4&+&% 3%A5C%"'!C%!#
!M%#'
%A5-C%>%A5C%
:-0992>0 :%A5C%
2.*4!%A5C%+!-C%'!&+
"&
(!C%%3& 302
%A5C%&C%Q%3>-"&%A5
0 : 302>2 %A5-"&%A5
3.(!&2 %A5%3&#"&+!
(!&&'!+&"-"&
&'!
For a transformer already partially loaded, any additional KVA loading must
take into consideration the K-factor of each of the new loads to be added.
48
The following graph, taken from a draft of the IEEE 519
Application Guide (1996), shows the recommended derating rate
for a transformer supplying electronic loads:
Electronic load
Typical values:
• «Rectangular» current (spectrum in 1/h(*)): k = 0.86
• Frequency converter type current (THD ≅ 50%): k = 0.80
(*) in fact, as is the case with all rectifiers (three-phase rectifiers, induction furnaces,
etc.) the current signal closely resembles a rectangle.
T6 -3/7-
As a guideline, for a Special Losses ratio of 10% compared with
Ohmic Losses, the derating factor of power as a function of the
factor Kn, to allow for harmonics, is given in the table below:
Hence:
th th
• a "Dyd" vector group stops 5 and 7 order harmonics,
rd
• a "Dy" vector group stops 3 order harmonics (the harmonics
circulate in each phase and return via the neutral point of the
transformer).
th
• a "Dz" vector group stops 5 order harmonics, which return via
the magnetic core.
A "Dyd" transformer prevents 5th and 7th order harmonics from spreading to the
upstream network.
Filtering harmonics
T6 -4/7-
The passive filter:
Typical applications:
Operating principle:
Typical applications:
T6 -5/7-
Operating principle:
Active
compens.
The active filter injects anti-phase harmonics into the load supply to
cancel existing harmonics. As a result, the loop current is
sinusoidal.
Typical applications:
Operating principle:
T6 -6/7-
Active
comp.
T6 -7/7-
Harmonic Mitigating Transformers 7400DB0301
July 2003
Methods of Addressing Harmonics with Transformers may be used to address harmonics generated by non-
Transformers sinusoidal (non-linear) loads by providing good source impedance,
combining sine waves within the transformer, and combining sine waves at
the common bus feeding different transformers.
Source Impedance Source impedance has the effect of attenuating the crest factor created by a
non-linear load. Once the voltage rises to a specific point, the control
circuitry in the power supply allows a capacitor to be charged. With low
source impedance, the current drawn by the capacitor is high and the
duration of the charging cycle is short. Higher impedance does not allow as
much current to be drawn, and extends the time it takes to charge the
capacitor. This is how the crest factor is reduced, as well as the harmonics.
An example of how this has been done for years is the use of line reactors
or drive isolation transformers that feed drives, and, more significantly, this
is also done every time an isolation transformer is used!
Combining Sine Waves Not only do transformers improve the source impedance for non-sinusoidal
loads, but they also combine sine waves within the windings for additional
harmonic attenuation. To take it one step further, two or more transformers
of different phase angle shift(s) can be used to achieve further combination
of sine waves providing for more harmonic mitigation. The phase shifts can
be accomplished using standard NEMA wiring configurations or minor
variations thereof. Either way, it is not new technology.
Combining Sine Wave Theory The theory of combining sine waves is accomplished two ways.
• By using the inherent phase angle displacement of the electrical wave
shapes within the transformer which are then combined at the nodes, or
connection points, of the windings within the transformer.
• By combining the sine waves at the common bus feeding two
transformers of different phase shift.
This bulletin will concentrate on single-phase, line-to-neutral, non-linear
loads. Three phase non-linear loads have been successfully addressed
for over 50 years by using line reactors, drive isolation transformers, or
active filters.
Cancellation of the Triplens (3rd, 9th, 15th…) “Cancellation” of the triplen harmonics (3rd, 9th, 15th…) can be achieved if a
60º phase shift is created between the two wave shapes, and then
combined.
Figure 9: Two Single-phase Non-linear Wave Shapes With a 60º
Phase Angle Difference
3rd, 5th, 7th, 9th, 11th, 13th, 15th, 17th, 19th Harmonics
0º 60º
The resultant wave shape of Figure 10 will be referred to as wave shape “A”
throughout this paper.
The triplen harmonics are no longer part of the wave shape. More
importantly, none of the energy was removed from the wave shape. Rather,
the sine waves were simply combined. This is one step where some
mistakenly assume the triplen harmonics to be circulating in the delta
winding of a delta-wye transformer.
The “A” is found on the line side of either a standard delta-wye or a wye-
zigzag transformer that feeding single-phase, line-to-neutral non-linear
loads.
Figure 11: Delta–Wye/Wye–Zig-zag
Figure 12: Two “A” Wave Shapes With a 60º Phase Angle Difference
17th, 19th, 5th, 7th, 11th, 13th 5th, 7th, 11th, 13th, 17th, 19th
0º 60º
Figure 13: The Combination of Two (Figure 12) “A” Wave Shapes.
The Figure 13 combination is created with two “A” wave shapes and a 60º
phase shift so the new “B” wave shape can be more easily understood.
No harmonic cancellation takes place in the (“A”) + (“A”+60º) combination.
This applies to harmonic mitigation/attenuation via transformers in
two ways.
• The “B” wave shape combination (remember, no triplen harmonics
present) can be obtained through tiering of delta-wye transformers as is
commonly done in many commercial and industrial facilities. The “B”
wave shape is found on the source side of a delta-wye transformer that
is feeding another delta-wye transformer downstream that is serving
computers, fax machines, and other office equipment.
• The delta-zigzag transformer takes the single-phase, line-to-neutral non-
linear single hump sine waves and combines them to get the “B” wave
shape. Once again, no energy was removed from the wave shape. The
sine waves are combined to yield a new sine wave in which the triplen
harmonics are not present.
Cancellation of the Triplens (3rd, 9th, 15th…) When a 30º phase shift is achieved between an “A” and a “B” wave shape
(see Figure 15), and the two are combined (see Figure 16), “cancellation” of
the 5th, 7th, 17th, and 19th occurs.
Figure 15: “B” Wave Shape With No Phase Shift; “A” Wave Shape
Phase Shifted By 30º
5th, 7th, 11th, 13th, 17th, 19th Harmonics in both “B” and
0º 30º
B A
Figure 16: The Combination of The “B” And 30º Phase Shifted “A”
Wave Shapes.
A+B
The “A” wave shape is phase shifted 30º and the “B” wave shape is not. The
30º phase shift of the “A” wave shape occurs with either the standard Delta-
Wye transformer or a Wye-Zigzag transformer as noted in Figure 11. The
“B” wave shape occurs with a Delta-Zigzag transformer (see Figure 14),
which has no inherent phase shift (0º) between the primary and secondary.
This can also occur within facilities with tiered delta-wye transformers.
One Step Further Could additional transformer winding configurations and sine wave
combinations theoretically eliminate all load harmonics on the supply side of
the transformers? Theoretically, yes, though it is not at all realistic in real
world applications. That will be discussed later in this paper. Theoretically, if
two A+B wave shapes were combined with one of the wave shapes phase
shifted by 15º, all of the harmonics could be “cancelled” (as shown in
Diagram 17).
Figure 17: Combination of Two “A+B” Wave Shapes With One Of
The Two Phase Shifted By 15º
No Harmonics
While the additional harmonic mitigation achieved in this last step may
appear attractive, the additional benefit would be miniscule when compared
to the additional cost involved, especially when the chance of this actually
occurring in a realistic application is essentially zero.
Electromagnetic Flux Cancellation Some HMTs are provided with a zigzag secondary winding. The zigzag
winding has a beneficial affect on triplen harmonics (3rd, 9th, 15th,…) that
have a similar phase angle.
Components of a UPS The information presented below concerns double-conversion UPSs, the
technology most commonly used by APC by Schneider Electric for power ratings
greater than 10 kVA.
UPS connection to both the primary and standby-power sources (UPS inputs
supplied by two separate circuits from the MLVS) is recommended because overall
system reliability is increased. However, if two separate circuits from the MLVS are
not available, it is possible to have both AC inputs (normal and bypass) supplied by
primary power (second cable).
Management of transfers between the two input lines is organised as follows.
• The UPS synchronises the inverter output voltage with that of the bypass line as
long as the latter is within tolerances. It is thus possible, if necessary, for the static
switch to transfer the load to the bypass AC input, without a break (because the two
voltages are synchronised and in phase) or disturbances (because the standby
power is within tolerances) for the load.
• When standby power is not within tolerances, the inverter desynchronises and
transfer is disabled. It can, however, by carried out manually.
APC by Schneider Electric 01/2012 edition p. 16
UPS components and operation (Cont.)
Components of a UPS
Rectifier/charger (1)
Transforms the AC power from the primary-power source into DC voltage and
current used to:
• Supply the inverter,
• Charge and float charge the battery.
Inverter (2)
Using the DC power supplied by the:
• Rectifier during normal operation,
• Battery during autonomous operation,
the inverter completely regenerates a sinusoidal output signal, within strict amplitude
and frequency tolerances.
Battery (3)
Makes the UPS autonomous with respect to the utility in the event of:
• A utility outage,
• Utility-power characteristics outside specified tolerances for the UPS.
Battery backup times range from 6 to 30 minutes as standard and can be extended
on request. Depending on the duration of the backup time, the battery is housed in
the UPS cabinet or in a separate cabinet.
Filters (12)
(optional equipment)
• Upstream of the rectifier/charger, when it is of the thyristor-based Graetz bridge
type (the case for MGE Galaxy PW and 9000 UPSs), a harmonic filter (see “Key
factors in UPS installation” p. 24) reduces the current harmonics resulting from the
switching of the rectifier thyristors. This reduces the voltage distortion on the
upstream busbars resulting from the flow of harmonic currents (the level required is
generally <5%). What is more, these UPSs from APC by Schneider Electric are
equipped with an oversized neutral conductor installed as standard to overcome the
consequences of third-order harmonics and their multiples which flow in the neutral
conductor.
• All the other UPSs of the MGE Galaxy and Symmetra ranges are equipped with a
PFC-type rectifier that eliminates the need for a filter (see “Key factors in UPS
installation” p. 24).
• Downstream, UPSs implementing new PWM-chopping techniques may be directly
connected to non-linear loads. This technique makes it possible for UPSs from APC
by Schneider Electric to maintain the THDU below 3%.
Complete solutions
APC by Schneider Electric can provide complete solutions comprising all the
components listed above, including air-conditioning solutions for data centers, in
conjunction with Schneider Electric. For users, the result is a single partner and an
installation that offers optimum performance and reliability.
Main characteristics of UPS These characteristics are based on the main technical specifications presented in the
IEC 62040-3 / EN 62040-3 standards on UPS performance requirements.
components Certain terms used here differ from the common jargon and a number of new
features have not yet been assimilated by manufacturers. New terms or
characteristics used by the standard are indicated between parentheses and
preceded by an asterisk.
For example, the title of a section "input current during battery float charging", a
commonly used term, is followed by (*rated input current), the term used in the
standard.
Note that a number of numerical values are indicated as examples.
They are, for the most part, drawn from the technical characteristics of the
corresponding UPSs, indicated in chapter 4, or indicated simply for the purposes of
the example.
AC input power
Number of phases and system earthing arrangement
The AC-input supply (primary power) is three-phase + neutral. Single-phase inputs
are not used for the power levels dealt with here.
The system earthing arrangement is generally imposed by standards (IT, TT, TNS or
TNC).
Normal AC input
The normal AC input is supplied with utility power for the rectifier/charger, within the
specified tolerances.
• Example: 400 V rms ± 15% at a frequency of 50 or 60 Hz ± 5%, three-phase.
Bypass AC input
The bypass AC input is supplied with standby power. Practically speaking, this a
cable connected to a utility feeder in the MLVS other than the one supplying the
normal AC input.
In general, it supplies voltage with the same characteristics as that of the primary
power.
• Example: 400 V rms ± 15% at a frequency of 50 or 60 Hz ± 5%, and a short-circuit
current Isc2 = 12.5 kA. The short-circuit current is important information for the
downstream protection devices in the event of operation via the static or
maintenance bypass.
Supply of separate primary and standby power is recommended because it
increases overall system reliability, but is not mandatory. However, if two separate
circuits from the MLVS are not available, it is possible to have both AC inputs
(normal and bypass) supplied by primary power (second cable).
Rectifier/charger
Floating voltage
This is the voltage supplied by the rectifier/charger which keeps the battery fully
charged.
It depends on the batteries used and the manufacturer's recommendations.
Service life
This is defined as the operating period, under normal usage conditions, for which the
battery supplies at least 50% of the initial backup time.
) For example, MGE Galaxy PW is supplied as standard with sealed lead-acid
batteries with a service life of ten years or more. This type of battery, rated for 30
minutes of backup time, will contractually supply only 15 minutes at the end of the
specified service life.
It may supply more if it has been used under optimum conditions (notably concerning
the temperature). However, it is contractually guaranteed not to supply less, unless
used improperly.
Operating modes
The battery may be:
• Charging. It draws a charge current (I1 charge) supplied by the rectifier/charger.
• Float charging. The battery draws a low, so-called floating current (I1 floating),
supplied by the rectifier/charger, which maintains its charge by compensating for
open-circuit losses.
• Discharging. The battery supplies the inverter until its shutdown voltage is
reached.
When this voltage, set by the battery manufacturer, is reached, the battery is
automatically disconnected (UPSs from APC by Schneider Electric) to avoid damage
by deep discharge.
Rated voltage
This is the DC output voltage that the battery supplies to the inverter.
) Example: 450 V DC for the MGE Galaxy PW range.
Capacity
Battery capacity is expressed in ampere/hours.
) Example: for a 100 kVA MGE Galaxy PW equipped with a battery offering ten
minutes of backup time and a service life of five years, the capacity is 85 A/h.
Number of cells
Number of single battery cells making up the entire battery string.
) Example: the battery of a 100 kVA MGE Galaxy PW comprises, for a given type of
battery, 33 cells providing 13.6 V each, for a backup time of ten minutes.
Floating voltage
This is the DC voltage used to maintain the battery charge, supplied by the
rectifier/charger.
) Example: for a MGE Galaxy PW, the floating voltage is between 423 and 463 V
DC.
Inverter
Rated power (Sn)
(* rated output apparent power)
This is the maximum apparent power Sn (kVA) that the inverter can deliver to a
linear load at a power factor of 0.8, during normal operation under steady-state
conditions.
The standards also define this parameter for operation on battery power.
Theoretically speaking, it is the same if the battery is correctly sized.
) Example: a MGE Galaxy 5500 with a rated power (Sn) of 100 kVA.
Efficiency (η)
This is the ratio of active power Pu (kW) supplied by the UPS to the load to the
power Pin (kW) that it draws at its input, either by the rectifier or from the battery.
.η= Pu / Pin.
For most UPSs, efficiency is optimum at full rated load and drops sharply with lower
percent loads. Due to their low output impedance and no-load losses, the efficiency
of MGE Galaxy UPSs is virtually stable for loads from 25 to 100%. The MGE Galaxy
range offers efficiency greater than 90% starting at 25% load, up to 93% at full rated
load, as well as an ECO mode which increases efficiency by 4%, i.e. up to 97%.
Practically speaking, for MGE Galaxy UPSs, an efficiency value of 0.93 can be used
for all input-power calculations for loads from 30 to 100%.
) Example: for a 100 kVA MGE Galaxy at 75% load, 0.93 efficiency corresponds to
a UPS active input power of
Pin = Pu / η = 60/0.93 = 64.5 kW.
Output voltage Un
Number of phases
The output can be three-phase (3ph-3ph UPS) or single-phase (3ph-1ph UPS),
depending on the situation. Note that the upstream and downstream system earthing
arrangements may be different.
Static characteristics
These are the tolerances (maximum permissible variations) for the amplitude and
frequency of the output voltage under steady-state conditions. Stricter than those
applying to utility power, they are measured for normal operation on AC-input power
and for operation in battery backup mode.
• Output voltage variation
The amplitude tolerance is expressed as a percentage of the nominal rms value and
may be adjustable.
) Example: for a MGE Galaxy, the voltage 400 V rms ± 1% may be adjusted to ±
3%.
The standards also stipulate a rated peak output voltage and the tolerance with
respect to the rated value.
• Output frequency variation
The tolerance is expressed as a percentage of the rated frequency.
) Example: for a MGE Galaxy, 50 or 60 Hz ± 0.1% during normal operation on
primary power and ± 0.5% in battery backup mode.
Dynamic characteristics
These are the tolerances under transient load conditions.
MGE Galaxy UPSs are capable of withstanding the following conditions.
• Load unbalance
For unbalance in the load voltage (phase-to-neutral or phase-to-phase) of:
- 30%, the output voltage variation is less than 0.1%,
- 100% (one phase at Pn and the others at 0), the output voltage does not vary more
than 0.2%.
• Load step changes (voltage transients)
For load steps from 0 to 100% or from 100 to 0% of the rated load, the voltage does
not vary more than:
± 2% on utility power;
+ 2% to -4 % on battery power.
Fig. 5.7. Diagram showing the main characteristics (see the list below).
Normal AC input
● Voltage Un + 10% to - 15%
● Frequency f + 4% to - 6%
Bypass AC input
● Voltage Un + 10% to - 15%
● Frequency f + 4% to - 6%
● Short-circuit current Isc2 (withstand capacity of the static bypass)
Rectifier/charger
● Floating voltage
● Input currents
- rated (battery float charging)
- maximum (battery charging)
Battery
● Backup time: standard 5, 6, 8, 10, 15, 20, 30, 60 minutes, longer times on request)
● Service life: 10 years or longer
● Maximum current Ib max.
Inverter
● Apparent output power:
- rated: Sn (kVA)
- load power: Su (kVA) = Sn x Tc%
● UPS percent load Tc% = Su / Sn
● Active output power:
- rated: Pn (kW) = Sn (kVA) x 0.8
- load power: Pu (kW) = Su (kVA) x PF = Sn x Tc% x PF = Un Iu PF
● Efficiency: η Pu / Pn = 93% (97% in ECO mode).
● Static characteristics (output-voltage tolerances under steady-state conditions)
- amplitude: Un ± 1% adjustable to ± 3%
- frequency: f ± 1% during normal operation, f ± 0.5% in battery backup mode
- inverter output voltage synchronised (frequency and phase) with that of the standby
power as long as the latter is within tolerances.
● Dynamic characteristics (tolerances under transient conditions)
- maximum voltage and frequency variations for load step changes from 0% to 100%
or 100% to 0%: Un ± 2%, f ± 0.5%
● Output voltage distortion
- 100% non-linear loads THDU < 2%
● Overload and short circuit capacity:
- overloads: 1.5 In for 1 minute
- short-circuits: current limiting to 2.33 In for 1 second
Load
● Load current (Iu)
● Power factor PF
UPS operating modes Normal mode (on utility power, see fig. 5.8 on left-hand side)
The UPS draws the AC utility power required to operate via the rectifier/charger
which provides DC current.
Part of the utility power drawn is used to charge or float charge the battery:
• I1 floating, if the battery is already fully charged,
• I1 charge if the battery is not fully charged (i.e. charging following a recent
discharge).
The remaining current is supplied to the inverter with generates an output-voltage
sine-wave within the specified amplitude and frequency tolerances.
Battery backup mode (on battery power, see fig. 5.8 on right-hand side)
The battery steps in to replace primary power and supplies the power required by the
inverter for the load, with the same tolerances as in normal mode.
This takes place through immediate transfer (the battery is parallel connected) in the
event of:
• Normal AC-input failure (utility-power outage),
• Normal AC input outside tolerances (degradation of utility-power voltage).
Bypass mode (on static-bypass line, see fig. 5.9 on left-hand side)
A static switch (SS) ensures no-break transfer of the load to the bypass AC input for
direct supply of the load by standby power.
Transfer is automatic in the event of:
• An overload downstream of the UPS exceeding its overload capacity,
• An internal fault in the rectifier/charger and inverter modules.
Transfer always takes place for internal faults, but otherwise is possible only if the
voltage of the standby power is within tolerances and in phase with the inverter.
To that end:
• The UPS synchronises the inverter output voltage with that of the bypass line as
long as the latter is within tolerances. Transfer is then possible:
- without a break in the supply of power. Because the voltages are in phase, the
SCRs on the two channels of the static switch have zero voltage at the same time,
- without disturbing the load. The load is transferred to a bypass line that is within
tolerances.
• When standby power is not within tolerances, the inverter desynchronises and
operates autonomously with its own frequency. Transfer is disabled.
It can, however, by carried out manually.
Note 1. This function greatly increases reliability due to the very small probability of a
downstream overload and a standby-power failure occurring at the same time.
Note 2. To ensure correct operation of the bypass line, discrimination must be
ensured between the protection device upstream of the bypass AC input (on the
MLVS outgoer) and those on the UPS outgoing circuits (see information on
discrimination below).
APC by Schneider Electric 01/2012 edition p. 25
UPS components and operation (Cont.)
Maintenance mode (on maintenance bypass, see fig. 5.9 right-hand side)
Maintenance is possible without interrupting load operation. The load is supplied with
standby power via the maintenance bypass. Transfer to the maintenance bypass is
carried out using manual switches.
The rectifier/charger, inverter and static switch are shut down and isolated from
power sources. The battery is isolated by its protection circuit breaker.
Redundancy
Redundancy in parallel configurations can be N+1, N+2, etc.
This means that N UPS units are required to supply the load, but N+1 or N+2 are
installed and they all share the load.
See the example below.
Example
• Consider a critical load with a 100 kVA rating.
• 2+1 redundancy
- 2 UPS units must be capable of fully supplying the load if redundancy is lost.
- Each UPS unit must therefore have a 50 kVA rating.
- 3 UPS units normally share the 100 kVA load, i.e. each supplies 33.3 kVA.
- The 3 UPS units normally operate at a percent load of 33.3 / 50 = 66.6%.
- Integrated parallel UPS units are each equipped with a static bypass. Transfer is
managed such that the three UPS units transfer to the bypass simultaneously, if
necessary.
Fig. 5.10. Integrated parallel UPS units with common maintenance bypass and 2+1
redundancy. Operation with all units OK (redundancy available).
• Loss of redundancy
- One UPS unit shuts down, the two remaining units operate at 100%.
- The faulty UPS unit can be serviced due to the maintenance bypass.
Fig. 5.11. Integrated parallel UPS units with common maintenance bypass and 2+1
redundancy. Operation following loss of redundancy.
UPS UPS
Q1 Q1
Q4S Q4S
Rectifier Rectifier
charger charger
Battery QF1
Battery QF1
Static Manual
Static Manual bypass bypass Q3BP
bypass bypass Q3BP
Inverter
Inverter
K3N
K3N
Q5N
Q5N
Loads
Loads
Fig. 5.12. UPS with output transformer. Fig. 5.13. Transformerless UPS.
Advantages
This technology offers users a number of key advantages.
● Smaller footprint: less space required with no transformer
● Less weight: weight reduction by eliminating the transformer
● Higher efficiency: elimination of transformer losses
● Voltage regulation by signal modulation for better matching with the load. The
electronics act directly on the output voltage for a for faster and more precise voltage
regulation.
The trend
The use of transformerless UPSs began in the early 1990s for ratings up to a few
hundred kVA. Given their many advantages, they are now widely used up to higher
ratings, as shown in figure 5.14. The average power rating using the transformerless
technique has increased by a factor of 50 over the past 15 years.
P(kVA)
500
400
300
200
100
years
5
1990 1995 2000 2005 2010
Galvanic isolation
One of the reasons cited for using output transformers is to provide galvanic
isolation.
However, three-phase UPSs above a certain power rating are equipped with a
bypass to ensure continuity of power. The presence of a bypass means that a UPS,
with or without an output transformer, cannot provide galvanic isolation between the
source and the loads. For this reason, transformerless UPS technology is gradually
becoming the preferred solution for high ratings.
This aspect will be discussed below by comparing the use of the two technologies
depending on the system earthing arrangement encountered.
Standard IEC 60364(1) uses 2 letters to identify the different earthing arrangements.
● The 1st letter describes the earthing of the transformer neutral point:
- T: earthed,
- I: not earthed.
● The 2nd letter describes the earthing of the ECPs of load equipment:
- T: earthed,
- N: connected to the neutral which is earthed.
In this case (N), a 3rd letter indicates the relationship between the neutral (N) and
protective (PE) conductors:
- C: single conductor used for both functions,
- S: separate conductors.
(1) Replaced by the Power Transformer Loading Guide IECI 60076-7 Ed. 1.
This is generally done using PDUs (Power Distribution Units) that include an input
transformer, making it possible to obtain a reliable neutral reference potential and
ensuring galvanic isolation in all UPS operating modes (on normal AC input or
bypass).
In addition, this solution uses standard transformers that offer very high reliability,
exceeding that of UPS output transformers. This solution with an input transformers
is used widely in the USA where a 3-phase 480 V distribution system is brought to
the computer room entry to supply 480 V/208 transformer (fig. 5.16).
UPS A UPS B
. .
PDU A PDU A
Isolating
transformers
used to recreate
a TN-S system
with neutral
x x
x x
Blade server
Fig. 5.16. Example of transformers used at the PDU input to create a TN-S distribution system
with a neutral.
IT IT
TT TT
LVMS
LVMS
L1
L2 L1
L3 L2
N L3
PE N
PE
Normal AC Bypass AC
Bypass input input
transformer
UPS Q1
Normal AC BypassAC
input input
Q4S
UPS Rectifier
D1 charger
Q1
Battery QF1
Static
Q4S
bypass
Rectifier
charger
Q3BP
Inverter
Q3BP
Battery QF1
Static
bypass
K3N
Inverter
Output
transformer Q5N
K3N
LVS PE LVS
L1 L1
L2 L2
D2 L3 L3
N N
PE
) In this case, solutions using UPSs with or without a transformer are identical,
however transformerless technology offers advantages in terms of efficiency,
footprint, weight and voltage regulation accuracy.
LVMS LVMS
L1 L1
L2 L2
L3 L3
N N
UPS UPS
Q1 Q1
Q4S Q4S
D1 D1 Rectifier/
Rectifier/
charger charger
Q3BP Q3BP
Inverter
Inverter
K3N K3N
Q5N Q5N
PE LVS
PE LVS
L1
L1 L2
L2 L3
L3 N
N
Transformerless solutions
● The constraints caused by the UPS output transformer are avoided.
● A transformer is installed at the entry to the computer room, generally in a PDU.
There is no need for four-pole devices on the bypass or for upstream distribution of
the neutral.
A transformer must still be added, but there are advantages in terms of:
● UPS cost, i.e. no specific output transformer and no four-pole devices and neutral
on the bypass line,
● reduced footprint and weight,
● better output regulation for rapid load fluctuations.
A source
A natural source (atmosphere, earth, sun, etc.) or, more often, an industrial source
(electrical and electronic devices).
The source generates disturbances through sudden (pulse) variations in electrical
values (voltage or current), defined by:
• A wave form,
• A wave amplitude (peak value),
• A spectrum of frequencies,
• A level of energy.
A coupling mode
Coupling enables transmission of disturbances and may be:
• Capacitive (or galvanic), for example via transformer windings,
• Inductive, by a radiating magnetic field,
• Conducted, by a common impedance, via an earthing connection.
A victim
This is any device likely to be disturbed, and which malfunctions due to the presence
of the disturbances.
Examples
Sources
In low-voltage installations, sources include suddenly varying currents resulting from:
• Faults or short-circuits,
• Electronic switching,
• High-order harmonics,
• Lightning or transformer breakdown.
Frequencies may be low (< 1 MHz) for power frequencies and their harmonics or
high (> 1 MHz) for lightning.
Coupling
• Capacitive: transmission of a lightning wave via a transformer.
• Inductive: radiation of a magnetic field created by one of the above currents.
Radiation creates an induced electromotive force, that is an induced disturbing
current, in the loops of conductors made up of the cables supplying devices and the
earthing conductors of the devices.
As in indication, a radiation of 0.7 A/m can disturb a video monitor.
That corresponds to the field created 2.2 m around a conductor carrying a current of
10 A.
• Conducted (common impedance): increase in the potential of an earthing
connection.
Disturbance levels
Standard IEC 6100-2-4 defines a number of disturbance levels for EMC:
• Level 0: no disturbance,
• Emission level: maximum level authorised for a user on a public utility or for a
device,
• Compatibility level: maximum disturbance level expected in a given environment,
• Immunity level: level of disturbance that a device can withstand,
• Susceptibility level: level starting at which a device or system malfunctions.
Consequently, for devices and equipment that are considered:
• Sources, limits (emission levels) must be set for disturbances emitted by devices
to avoid reaching compatibility levels,
• Victims, they must also withstand disturbance levels higher than the compatibility
levels, if they are exceeded, which is permissible on a transient basis. These higher
levels are the immunity levels.
EMC standards set these levels.
Î List of EMC standards, see the section on page 34 on EMC standards.
Measured values
Devices are subjected to tests.
Five major values are measured:
• CE - conducted emissions,
• RE - radiated emissions,
• ESD - electrostatic discharges,
• CS - conducted susceptibility,
• RS - radiated susceptibility.
The tests require major resources, namely a Faraday cage for conducted emissions
and susceptibility and an anechoic chamber for radiated emissions.
APC by Schneider Electric has a certified anechoic test chambers.
CE marking
CE marking was created by European legislation.
It is mandatory for free circulation of goods in the EU.
Its purpose is to guarantee, through respect of the corresponding European
directives:
• That the product is not dangerous (Low-voltage Directive),
• That it does not pollute (Environment Directive) and its electromagnetic
compatibility (EMC Directive).
Before placing the CE marking on a product, the manufacturer must run or have run
checks and tests which ensure conformity of the product with the requirements in the
applicable directive(s).
It is NOT a certification standard or mark of conformity.
It does not signify that the product complies with national or international standards.
It is not a certification as defined by French law (law dated 3 June 1994).
What is more, the CE marking is placed on a product under the exclusive
responsibility of the manufacturer or the importer. It does not imply inspection by a
certified external organisation.
) Not all labels carry the same implications for manufacturers.
Conformity with standards and specified levels of performance must be certifiable by
an organisation. This is not the case for CE marking which authorises self-
certification.
Main standards governing UPSs from APC by Schneider Electric comply (certified by TÜV and Veritas) with the
main applicable international standards.
UPSs
Safety
• IEC 60950-1 / EN 60950-1
Information technology equipment - Safety - Part: General requirements
• IEC 62040-1/ EN 62040-1
Uninterruptible power systems (UPS) - General and safety requirements for UPS.
• IEC 62040-3 / EN 1000-3
Uninterruptible power systems (UPS) - Method of specifying the test and
performance requirements.
• IEC 60439
Low-voltage switchgear and controlgear assemblies.
• LV directive: 2006/95/EC
EMC
• EN 50091-2
UPS - EMC.
• IEC 62040-2/ EN 62040-2
Uninterruptible power systems (UPS) - Electromagnetic compatibility (EMC)
requirements.
• EMC Directive 2004/108/EC
For equipment liable to cause or be affected by electromagnetic disturbances.
Quality
• Design , production and servicing in compliance with standard ISO 9001 - quality
organisation.
Ecological environment
• Manufacturing in compliance with standard ISO 14001.
Acoustic noise
• ISO 3746
Sound power levels.
• ISO 7779 / EN 27779
Measurement of airborne noise emitted by computer and business equipment.
Table 5-B. Compatibility levels for harmonic voltages according to the type of equipment as
indicated in standard EN 50160.
(1)
Order of the voltage Class 1 Class 2 Class 3
harmonic generated (sensitive systems and (industrial and public (for connection of
equipment) % of networks) % of major polluters) % of
fundamental fundamental fundamental
2 2 2 3
3 3 5 6
4 1 1 1.5
5 3 6 8
6 0.5 0.5 1
7 3 5 7
8 0.5 0.5 1
9 1.5 1.5 2.5
10 0.5 0.5 1
11 3 3.5 5
12 0.2 0.2 1
13 3 3 4.5
TDHU 5% 8% 10%
(1)
Class 2 corresponds to the limits of Table A of standards IEC 61000-2-2 / EN 61000-2-2.
Fig. 5.21. Energy storage using a battery and an engine generator set for long backup times.
Installation modes
Depending on the UPS range, the battery capacity and backup time, the battery is:
• Sealed type and housed in the UPS cabinet,
• Sealed type and housed in one to three cabinets,
• Vented or sealed type and rack-mounted.
Cabinet mounting
This installation method (see fig. 5.15) is suitable for sealed batteries. It is easy to
implement and offers maximum safety.
Batteries installed on racks
• On shelves (figure 5.16)
This installation method is possible for sealed batteries or maintenance-free vented
batteries which do not require topping up of their electrolyte.
• Tier mounting (figure 5.17)
This installation method is suitable for all types of batteries and for vented batteries
in particular, as level checking and filling are made easy.
Fig. 5.22. Cabinet mounting. Fig. 5.23. Mounting on shelves. Fig. 5.24. Tier mounting.
Constraints on batteries
Atmospheric constraints
The batteries supplied with UPSs from APC by Schneider Electric are designed to
operate under the following conditions:
• Optimum temperature range: 15°C to 25°C,
• Optimum relative humidity range: 5% to 95%,
• Atmospheric pressure: 700 to 1060 hPa (0.7 to 1.06 bars).
For other operating conditions, please consult us.
Access
Access must be provided for testing operations.
• Battery installed in UPS cabinet or other cabinet: comply with the clearances
indicated in the "Dimensions and weights" in chapter 4.
• Battery installed on racks: select an installation method suited to the type of
battery.
• Preliminary work: this aspect is important as it involves safety. It is discussed in ”
Key factors in UPS installation” p. 49.
Service life
A battery is considered to reach the end of its service life when its real backup time
has fallen to 50% of the specified backup time.
The service life of a battery is basically enhanced by:
• Providing protection against deep discharge,
• Correct charger settings, in particular the ripple factor of the charge or float current,
• An optimum operating temperature, maintained between 15°C and 25°C.
Recharge mode
The charge cycle takes place in two steps:
• Step 1, a constant current limited to 0.1 C10 (one tenth of the battery capacity for a
ten-hour discharge),
• Step 2, a constant voltage, at the maximum permissible value. The charge current
regularly decreases and reaches the floating value.
TM
Fig. 5.26. Digibat
Temperature monitoring
TM TM
MGE Galaxy UPSs can also be equipped with the Temperature Monitoring
module used to:
• Optimise the charger voltage depending on the temperature in the battery room,
• Warn the user if preset permissible temperature limits are exceeded,
• Refine the estimate on battery backup time carried out by the standard system.
Natural ventilation of battery cabinets avoids battery temperature rise.
Environment Sensor is also a simple means to monitor temperature and humidity. It
can be used to launch shutdown when combined with software running the module.
Battery monitoring
APC by Schneider Electric also offers the B2000 and Cellwatch autonomous and
communicating battery-monitoring systems which immediately detect and locate all
battery faults. These systems monitor each battery block or cell and make possible
predictive maintenance.
) Note that the energy stored is proportional to the square of the angular velocity.
This is one of the reasons that APC by Schneider Electric proposes flywheels
spinning at relatively high speeds. This reduces both the weight and the footprint of
the energy storage system.
UPS applications
Flywheel units can replace traditional UPS batteries or work in tandem with batteries
to provide highly reliable, instantaneous backup power for today’s mission-critical
applications (data centres, hospitals, broadcast studios, casinos airports and
manufacturing plants). They interface with the DC bus of the UPS, just like a battery,
receiving charging current from the UPS and providing DC current to the UPS
inverter during discharge.
UPS
AC input Critical
loads
Rectifier Inverter
Flywheel Battery
Fig. 5.27. Simplified diagram of a UPS with a flywheel energy storage connected in parallel with
a battery.
Types of flywheels
UPS flywheels can be divided into several types depending on their speed, flywheel
material and motor generator configuration.
Flywheel speed
• Low speed flywheels
- Angular velocity <10 000 rpm
- Energy for high power requires heavy steel flywheels (heavy and bulky)
- Periodic maintenance and replacement to the mechanical bearings
- High amount of parasite energy losses
- Requires special concrete slab specifications for installation
• High speed flywheels
- 30 000 to 60 000 rpm (potentially up to 100 000 rpm)
- Much lighter for high power needs (energy stored through higher spinning velocity)
- Full magnetic levitation
- Lower periodic maintenance
- Smaller footprint and lighter weight
- Easy commissioning, start up and shutdown
Flywheel materials
• Carbon fibre flywheels
Carbon fibber flywheels are typically made by winding great lengths of carbon-fibber
on a spindle. They are held together by an epoxy resin.
Imperfections in the process and gaps between the fibbers can lead to unbalancing
of the wheel over time due to the stresses applied as the wheel is spun from high
speed to low speed and back again, which occurs during every discharge event.
Once the carbon fibber flywheel becomes unbalanced, the entire flywheel module
much be replaced, a very costly and time consuming processes.
• Steel flywheels
The flywheels supplied with APC by Schneider Electric UPSs are made of aerospace
grade 4340 steel. The material properties are very well known, available from
numerous suppliers and this material is used in many high speed rotating
applications. Most important is the integrity of the material can be measured through
core samples and ultrasound to make sure it complies with the application
specifications. The same flywheel has been used not only in UPS applications, but
also in high-cycling, regenerating applications like in electric motors for cranes and
electric rail. These applications call on the flywheel to be charged and discharged up
to 20 times per hour. These applications prove the robustness of utilising aerospace
grade steel as the preferred flywheel material.
Installation
Flywheel cabinets
Flywheel energy storage systems are supplied in separate cabinets that connect to
the DC bus just like battery cabinets. Multiple flywheel cabinets can be installed in
parallel for higher power, longer run-time or redundancy.
Site preparation
Minimal site preparation is required for installation of flywheel cabinets. Before
installation, consideration must be given to a certain aspects.
• Wiring and cabling to UPS and other equipment
• Service access
• Clearances for cooling
• Floor mounting
Constraints on flywheels
Atmospheric constraints
The flywheel energy storage systems supplied with UPSs from APC by Schneider
Electric are designed to operate under the following conditions:
• Operating temperature: -20°C to 40°C (without derating)
• Minimum cold start temperature: 0°C
• Relative humidity: up to 95% (non-condensing)
For other operating conditions, please consult us.
Service life
• The service life of a flywheel energy storage time is typically much longer than that
of lead-acid batteries.
• The flywheel energy storage systems supplied with UPSs from APC by Schneider
Electric has a service of life of 20 years for operating temperatures up to 40°C and
frequent charge-discharge cycles.
Fig. 5.29. Gradual start of the UPS rectifier during operation on generator power.
Capacitive currents
The generator can supply only relatively low capacitive currents (10 to 30 % of In).
When an LC filter is installed, the main difficulty lies in the gradual start-up of the
rectifier on generator power, when active power is equal to zero and the generator
supplies only the capacitive current for the filter. Consequently, the use of LC filters
must be correctly analysed to ensure that operation complies with manufacturer
specifications.
Use of compensated LC filters with a contactor solves this problem. For UPSs with a
PFC rectifier, compatibility is total.
Î LC filters and generators, see Ch. 1 p. 26.
Harmonics
The subtransient reactance X"d of a generator is generally higher than the short-
circuit voltage Uscx of a transformer (two to four times higher). Any harmonic
currents drawn by the UPS rectifier may have greater impact on the voltage
harmonic distortion on the upstream busbars. With PFC rectifier technology, the
absence of upstream harmonics avoids this problem.
Motors
Motors are generally of the three-phase asynchronous type (95% of all motors). The
additional power requirement corresponds to the start-up current defined by (fig. 5.30):
• Id (5 to 8 In, rated rms value) for a time td (1 to 10 seconds),
• Imax = 8 to 12 In, for 20 to 30 milliseconds.
The power drawn that must be taken into account (neglecting the peak effect of
Imax) is:
Sa (kVA) = Un Id 3 during td.
LV/LV transformers
Transformer switching produces current peaks with amplitudes that are damped
according to an exponential decay with a time constant (see fig. 5.31).
• i = I1st peak exp -t/τ where τ is a few cycles (30 to 300 ms).
• I1st peak = k In (where k is given, generally 10 to 20).
Indications generally include the number of cycles the phenomenon lasts and the
value of the various peaks as a percentage of I1st peak.
The corresponding inrush current is generally calculated on the basis of (see
example):
• Sa (kVA) = Un I1st peak 3 , i.e. Sa (kVA) = k Un In 3 during the number of cycles.
• Example of an inrush current damped in four cycles with:
1st peak (100%): k In (k from 10 to 20),
2nd peak 30 %: 0.3 k In,
3rd peak 15 %: 0.15 k In.
The total of the rms values of the currents corresponding to the various peaks (Ipeak
/ 2 ) (1) is:
k In (1 + 0,3 + 0,15 ) K In 1,45
= ≈ k In
2 2
This is roughly equivalent to the value of the first peak alone.
(1)
Considering the current peaks as sine waves; note that some manufacturers indicate an rms
value of Ipeak / 2.
Computer loads
Switch-mode power supplies are non-linear loads. The current for a single-phase
load has a wave form similar to that shown in figure 5.32. There can be a peak
during the first half wave of approximately 2 In. However, it is generally much lower
than this and can be neglected.
Fig. 5.30. Curve for direct on- Fig. 5.31. LV/LV transformer Fig. 5.32. Computer load
line starting of a three-phase switching current. starting current.
asynchronous motor.
Consequences of harmonics
Harmonics disturb, increasingly severely, all sorts of activities, ranging from factories
producing electronic components and data-processing systems to pumping stations,
telecommunications systems, television studios, etc., because they represent a
significant part of the current drawn.
There are three types of negative consequences for users:
Impact on applications
Harmonic currents circulate in the source and line impedances, thus generating
voltage harmonics which lead to voltage distortion on the busbars upstream of the
non-linear loads (figure 5.34).
The distortion of the supply voltage (upstream THDU - Total harmonic distortion in
voltage) may disturb the operation of certain sensitive devices connected to the
these busbars.
What is more, for TNC systems where N and PE conductors are combined to form a
PEN conductor, the zero-sequence third-order harmonics cumulate in the neutral
conductor. This unbalance current in the neutral can disturb circuits interconnecting
low-current devices and may require oversizing of the neutral.
Fig. 5.34. Voltage distortion due to reinjection of harmonic currents by non-linear loads.
Precautions
General
There are a number of traditional solutions to limit harmonics:
• installation of tuned passive filters,
• installation in parallel of several cables with medium-sized cross sections,
• separation of non-linear loads and sensitive loads behind isolating transformers.
However, these solutions have two major disadvantages:
• limitation of harmonics is effective only in the existing installation (the addition or
removal of loads can render it ineffective),
• implementation is difficult in existing installations.
SineWave active harmonic conditioners (see chapter 3) avoid these disadvantages.
Much more effective than other solutions, they may be used with all types of loads
and can selectively eliminate harmonics ranging from the 2nd to the 25th order.
Î Elimination of harmonics, see “eliminate harmonic currents”
UPSs
• Due to the rectifier/charger, a UPS is a non-linear load for its power source. UPSs
from APC by Schneider Electric offer perfect control over upstream harmonics by
using "clean" PFC rectifiers or filters (MGE Galaxy PW and 9000).
Upstream of the UPS, the total voltage distortion remains within limits that are
acceptable for the other devices connected to the same busbars.
where
• IH1 is the rms value of the fundamental current at frequency f (50 or 60 Hz),
• ω = 2 π f is the angular frequency of the fundamental,
• ϕ1 is the phase displacement between the fundamental current and the voltage,
• IHn is the rms value of the nth harmonic, at frequency nf,
• ϕn is the phase displacement between the nth harmonic current and the voltage.
It is important to evaluate the harmonics (n ≥ 2) with regards to the fundamental (n =
1) to determine to what degree the function differs from the fundamental.
To that end, the values below are taken into account.
∑ IH n
2
∞
⎡ IHn ⎤
2 ∞
THDI% = 100
n= 2
IH1
= 100 ∑ ⎢⎣ IH ⎥⎦
n= 2 1
= ∑ (Ih %)
n= 2
n
2
Note. Harmonic contents are sometimes expressed with respect to the complete signal Irms,
and not the fundamental (IEC documents). Here, we use the definition of the CIGREE, which
uses the fundamental.
For the low harmonic contents analysed in the following pages, the two definitions produce
virtually identical results.
∞ 2
∑
⎡ IHn ⎤
Ieff = IH1 1 + ⎢ ⎥ hence:
⎢⎣ IH1 ⎥⎦
n=2
∞
Irms = IH1 1 + ∑ Ih
n= 2
n
2
= IH1 1 + THDI2
• Ihn = Ihn% / 100 (individual level expressed as a value and not as a percentage).
• THDI = THDI% / 100 (distortion expressed as a value and not as a percentage).
The rms value of the current is that of the fundamental, multiplied by a coefficient
which is due to the harmonics and is a function of the distortion.
) One effect of harmonics is therefore to increase the rms value of the current,
which can lead to temperature rise and therefore require oversizing of conductors.
The lower the distortion, the less need for oversizing.
Example
Input current of a three-phase rectifier.
Harmonic distortion levels
Ih5 = 33%
Ih7 = 2.7%
Ih11 = 7.3%
Ih13 = 1.6%
Ih17 = 2.6%
Ih19 = 1.1%
Ih23 = 1.5%
Ih25 = 1.3%
THDI = 35%
Voltage values
At the terminals of a non-linear load, through which a distorted periodic AC current
flows, the voltage is also periodic with a frequency f and it is also distorted with
respect to the theoretical sinusoidal wave. The relation between voltage and current
is no longer governed by Ohm's linear law, because it is applicable only for
sinusoidal voltage and current. It is possible, however, to use a Fourier expansion for
the voltage and to define, similar to the current and with the same results, the
following values:
∑ UH n
2
∞
⎡ UHn ⎤
2 ∞
THDU% = 100
n= 2
UH1
= 100 ∑ ⎢
n= 2 ⎣
⎥
UH1 ⎦
= ∑ (Uh )
n= 2
n
2
) The rms value of the voltage is that of the fundamental, multiplied by a coefficient
which is due to the harmonics.
Power values
Power factor in the presence of harmonics
On the basis of the active power at the terminals of a non-linear load P (kW) and the
apparent power supplied S (kVA), the power factor is defined by:
P (kW )
λ=
S (kVA )
This power factor does not express the phase displacement between the voltage and
the current because they are not sinusoidal. However, it is possible to define the
displacement between the voltage fundamental and the current fundamental (both
sinusoidal), by:
P1(KW )
cos ϕ1 =
S1(kVA )
where P1 and S1 are the active and reactive power, respectively, corresponding to
the fundamentals.
Standard IEC 146-1 defines the distortion factor:
λ
ν=
cos ϕ1
When there are no harmonics, this factor is equal to 1 and the power factor is simply
the cos ϕ.
S = P12 + Q12 + D2
where D is the distortion power, due to the harmonics.
The inverter output is a perfect voltage source Vc = impedance across the load terminals.
V0 in series with an output impedance Zs. Vs = impedance at the inverter output.
ZL = line impedance.
Zc = load impedance.
Fig. 5.36. Equivalent diagram of an inverter output.
The switches represented here to illustrate the principle are controlled IGBTs.
Fig. 5.37. Half-bridge DC/AC converter. Fig. 5.38. Full-bridge DC/AC converter.
Practically speaking, the switches shown in figures 5.37 and 5.38 are IGBTs for
which it is possible to control the relative on and off times.
By controlling the on and off times, it is possible to "distribute" the voltage over the
reference sinusoidal wave. This principle is known as PWM (pulse width modulation).
It is shown in a simplified manner, with five square-wave pulses, in figure 5.39. The
area of the voltage sinusoidal wave is equal to that of the square-wave pulses used
to generate it. These areas represent the power supplied by the inverter to the load
T
over a given time, i.e.
∫ VIdt
0
The higher the chopping frequency (the higher the number of square-wave pulses),
the better the regulation with respect to the reference wave. Chopping also reduces
the size of the internal filter required on the LC output (see fig. 5.40).
Fig. 5.39. DC/AC converter output voltage Fig. 5.40. Inverter output filter.
with five square-wave pulses per half-wave.
PWM inverters
PWM chopping
The PWM (pulse width modulation) chopping technique combines high-frequency
chopping (a few kHz) of the DC voltage by the inverter and regulation of the pulse
width for the inverter output, to comply with a reference sinusoidal wave.
This technique uses IGBTs (insulated gate bipolar transistors) offering the
advantages of voltage control and very short commutation times. Due to the high
frequency, the regulation system can react quickly (e.g. 333 nanoseconds for a
frequency of 3 kHz) to modify the pulse widths within a given period.
) Comparison with the reference voltage wave makes it possible to maintain the
inverter output voltage within strict distortion tolerances, even for highly distorted
currents.
Z2
The ratio is the transfer function of the filter, noted H(p).
Z1 + Z 2
To simplify, C(p) x A is replaced by µ(p) which represents the transfer function of the
correction and amplification.
It is thus possible to replace fig. 5.41 by the functional diagram in fig. 5.43.
It is possible to show that the inverter output impedance Zs in this case is equal to:
Z1
Z' s ≈
µ (p)
(for further information, consult Schneider Electric Cahier Technique document no.
159).
This means that in the regulation pass band, the inverter output impedance is equal
to the filter series impedance divided by the correction and amplification gain.
Given the high gain in the regulation pass band, the output impedance is significantly
reduced compared to impedance Z1 of an inverter without this type of regulation.
Outside the regulation pass band, the inverter output impedance is equal to that of
the filter, but remains low because it corresponds to the impedance of a high-
frequency capacitor.
Consequently, the output impedance is a function of the frequency (see fig. 5.44).
) The free-frequency PWM (pulse width modulation) technique considerably limits
the output impedance.
Conclusion
The PWM inverter is the source offering by far the lowest output impedance in the
presence of harmonics. It is clearly the best source on the market in terms of its
aptitude to minimise the voltage distortion caused by non-linear loads. It is five to six
times better than a transformer with an identical power rating.
) The new generation of UPSs implementing IGBTs and the PWM chopping
technique with frequency modulation are the best sources of sinusoidal voltage,
whatever the type of current drawn by the load.
Fixed-frequency chopping
The chopping fronts occur at fixed, regular intervals corresponding to the chopping
frequency over one period.
The width of the pulses (square-wave pulses) can be modulated to conform to the
reference within the fixed time interval.
The two sine waves shown in the diagram correspond to the tolerance (< 1%)
around the reference sine wave.
Free-frequency chopping
The chopping fronts do not necessarily occur at fixed intervals. Chopping adapts to
the requirements of the regulation, i.e. the rate of change of the reference. The width
of the commutation fronts decreases (the chopping frequency increases) as the rate
of change of the reference sine wave increases. Conversely, the width of the
commutation fronts increases (the chopping frequency decreases) as the rate of
change of the reference decreases. On the whole, the average chopping frequency
is the same as that for the fixed-frequency technique (approximately 3 kHz). But
regulation is better because the commutation accelerates in the zones where the
rate of change is high (see fig. 5.46).
It can reach eight commutations per millisecond, i.e. a regulation time as low as 125
nanoseconds (compared to 300 ns for the fixed-frequency technique).
) The free-frequency technique increases the precision of the voltage regulation in
PWM inverters compared to the fixed-frequency technique.
The chopping frequency is fixed. The free chopping frequency increases where
Modulation takes place within fixed intervals, the rate of change of the reference is high.
whatever the rate of change of the reference Modulation therefore takes place within
sine wave. intervals that are shorter when the rate of
change of the reference sine wave increases.
Fixed frequency. Free frequency.
Fig. 5.45. PWM chopping with fixed-frequency and free-frequency regulation.
Free-frequency
switching
Quality
band with
variations
< 1%
Output voltage Up to 8 commutations
curve per millisecond
Fig. 5.46. Regulation employing free-frequency commutation.
Standard rectifiers
These are three-phase rectifiers incorporating SCRs and using a six-phase bridge
with standard chopping of the current.
This type of bridge draws harmonic currents with orders of n = 6 k ± 1 (where k is a
whole number), mainly H5 and H7, and to a lesser degree H11 and H13.
Harmonics are controlled by using a filter.
PFC rectifiers
Operating principle
The principle behind PFC rectifiers consists in forcing the current drawn to remain
sinusoidal. To that end, they use the PWM technique presented above.
The principle is that of a "voltage source" converter (see fig. 5.47), whereas the
SineWave active harmonic conditioner uses a "current source" converter.
The converter acts as a back-electromotive force (a "sinusoidal voltage generator")
on the distribution system and the sinusoidal current is obtained by inserting an
inductor between the utility power and the voltage source.
Even if other non-linear loads increase the voltage distortion on the distribution
system, the regulation can adapt to draw a sinusoidal current.
The frequency of low residual harmonic currents is the frequency of the modulation
and of its multiples. Frequency depends on the possibilities of the semiconductors
used.
Implementation
Single-phase rectifier
Figure 5.48 shows the operation of a single-phase rectifier.
Voltage modulation is obtained by a controller that forces the current to follow a
sinusoidal current reference.
Transistor T and diode D make up the voltage modulator. The voltage u thus
changes between 0 and Vs according to whether transistor T is in the on or off state.
When transistor T conducts, the current in inductor L can only increase as the
voltage is positive and u = 0.
Therefore:
di e
= >0
dt L
When transistor T is off, the current in L decreases, provided that Vs is greater than
V, so that:
di e − Vs
= >0
dt L
For this condition to be fulfilled, voltage Vs must be greater than the peak voltage of
V, i.e. the rms value of the AC voltage multiplied by 2
If this condition is fulfilled, the current in L can be increased or decreased at any
time. The variation of the current in L with time can be forced by monitoring the
respective on and off times of transistor T. Figure 5.49 shows the evolution of current
IL with respect to a reference value.
Three-phase rectifier/charger
The basic circuit arrangement is shown in fig. 5.50. It is similar to that in fig. 5.48,
with the inductor placed upstream of the rectifiers; the operating principle is also the
same. The monitoring system controls each power leg and forces the current drawn
on each phase to follow the sinusoidal reference.
Contents
Introduction ..................................................................... 2
Using this guide .............................................................. 3
Overview of protection solutions .................................. 4
Protection solutions ..............................................................................4
Accompanying software and services ..................................................5
UPSs in electrical installations ...................................... 6
Function of each component in the installation.....................................6
Essential installation parameters ..........................................................7
Sources of information in setting up installation specifications .............8
Basic notions on installations with UPSs ..................... 9
Need for high-quality and high-availability power .................................9
Supply systems with UPSs ...................................................................10
UPS power quality ................................................................................11
UPS power availability ..........................................................................13
Selection of the configuration ...............................................................16
Power calculations.......................................................... 17
Elements required for power calculations .............................................17
Ratings of single-UPS configurations ...................................................19
Ratings of parallel-UPS configurations .................................................22
Control of upstream harmonics ..................................... 24
UPSs and upstream harmonic currents for different input rectifiers .....24
Filtering of upstream harmonics for Graetz bridge rectifiers .................25
Selection of a filter ................................................................................27
System earthing arrangements...................................... 30
Background information on system earthing arrangements .................30
Applications in UPS installations ..........................................................32
Protection ........................................................................ 35
Protection using circuit breakers ..........................................................35
Selection of circuit breakers .................................................................38
Cables ............................................................................. 43
Selection of cable sizes ........................................................................43
Example of an installation ....................................................................44
Energy storage ............................................................... 45
Storage technologies ............................................................................45
Selection of a battery............................................................................46
Battery monitoring ................................................................................47
Human-machine interface and communication ........... 49
Human-machine interface (HMI) ..........................................................49
Communication ....................................................................................49
Preliminary work ............................................................ 51
Installation considerations ....................................................................51
Battery room .........................................................................................52
Fig. 1.4. Main parameters for the components in installations with UPSs.
Types of UPSs
The term UPS covers products with apparent power ratings from a few hundred VA
up to several MVA, implementing different technologies.
That is why standard IEC 62040-3 and its European equivalent ENV 62040-3 define
three standard types (topologies) of UPS.
UPS technologies include:
• Passive standby,
• Interaction with the distribution system,
• Double conversion.
For the low power ratings (< 2 kVA), the three technologies coexist. For higher
ratings, virtually all static UPSs (i.e. implementing semiconductor components, e.g.
IGBTs) implement the double-conversion technology.
Rotary UPSs (with rotating mechanical parts, e.g. flywheels) are not included in the
standards and remain marginal on the market.
Î Types of UPSs, see Technical review p. 9 "Types of static UPSs".
H5 = 33%
H7 = 2.7%
H11 = 7.3%
H13 = 1.6%
H17 = 2.6%
H19 = 1.1%
H23 = 1.5%
H25 = 1.3%
Power of a UPS
Rated power of a UPS
This rating, indicated in the catalogues, is in the output power. It is indicated as
an apparent power Sn in kVA, with the corresponding active power Pn in kW, for a:
• linear load,
• load with a cos ϕ = 0.8.
However, last-generation UPSs from APC by Schneider Electric can supply
loads with a cos ϕ = 0.9 leading.
Linear loads
Three-phase Single-phase
Sinusoidal voltage u(t) = U 2 sin ωt between phases v(t) = V 2 sin ωt phase to neutral
U=V 3
Displaced sinusoidal current i(t) = I 2 sin (ωt - ϕ) phase current
S= P 2 +Q 2
Non-linear loads
Sinusoidal voltage u(t) = U 2 sin ωt between phases v(t) = V 2 sin ωt phase to neutral
The regulated UPS voltage remains sinusoidal
(low THDU), whatever the type of load. U=V 3
Current with harmonics i(t) = i1(t) + Σihk(t) total phase current
i1(t) = I1 2 sin (ωt - ϕ1) fundamental current
I12 2 2 2
+ I2 + I3 + I4 + ....
THDI = Current total harmonic distortion
I1
UPS efficiency
This factor determines the power drawn by the UPS on the upstream
distribution system, i.e. the consumption. It may be calculated as:
PUPSoutput (kW )
η (%) =
PUPSinput (kW )
For a given power rating, a high level of efficiency:
• reduces power bills,
• reduces heat losses and, consequently, ventilation requirements.
It is possible to calculate the efficiency at full rated load, i.e. with a 100% load.
Pn (kW )
ηn (%) =
PUPSinput (kW )
The rated active power of the UPS is obtained by multiplying the rated
apparent power Sn (kVA) by 0.8 (if λ > 0.8) or by λ (if λ< 0.8).
The efficiency can vary significantly depending on the percent load and the
type of load.
The installation designer must therefore pay attention to two aspects of
efficiency.
Fig. 1.17. Single double-conversion static UPS unit and example of an overload curve.
4. - Percent load
The fourth step is a check to ensure that the percent load is acceptable now and in
the future, given the desired operating conditions.
The percent load is:
Load = S / Sn(kVA) .
It must be sufficient to cover any increases in the load or if there are plans to expand
the system to become redundant.
Necessary checks
It is then necessary to check that the planned UPS power rating can handle the in-
rush currents. Note that the UPS can operate for a few periods in current-limiting
mode (e.g. 2.33 In for one second for an MGE Galaxy 9000). If the UPS cannot
handle the in-rush currents, it is necessary to decide whether it is acceptable to
transfer to the Bypass AC input when the transient conditions occur. If transfer is not
acceptable, it is necessary to increase the power rating.
Î Review of in-rush currents, see Technical review p. 37.
Example
The example below is simply to illustrate the point and does not correspond to
a real situation. The purpose is to indicate the required steps. The installation
is made up of three 400 V three-phase loads connected in parallel:
• Computer system - S1 = 4 x 10 kVA (4 identical 10 kVA loads), λ = 0.6 for all the
loads, in-rush current 8 In over four periods 50 Hz (80 ms) for each load,
• Variable-speed drive - S2 = 20 kVA, λ = 0.7, in-rush current 4 In over five periods
(100 ms),
• Isolation transformer - S3 = 20 kVA, λ = cos ϕ = 0.8, in-rush current 10 In over six
periods (120 ms).
Fig. 1.19. UPS system with parallel-connected units and a static-switch cubicle (SSC).
4 - Percent load
With redundancy, the UPS units share the load according to the equation
S / (N+K). The percent load for each unit when there is redundancy is therefore:
TL = S / (N + k) Sn(kVA) .
In a non-redundant system, it is calculated as:
TL = S / N Sn(kVA).
It must be sufficient to cover any increases in the load.
Example
This example will use the results from the last example and we will suppose that the
loads are critical, i.e. redundancy is required.
• The total load is 54 kW with an overall power factor for all the loads of 0.68, i.e. S
= 54 / 0.68 = 79.4 kVA.
• If 2+1 redundancy is used, two units must be capable of supplying the load. Each
must will have to supply S / 2 = 79.4 / 2 = 39.7 kVA.
• An MGE Galaxy PW UPS with a sufficient rating should be selected. The 40 kVA
rating would not be sufficient, i.e. the 50 kVA rating should be selected or higher if a
site extension is planned.
• If redundancy is not available, the two UPS units must be capable of supplying the
load.
• This is the case because 2 x 50 x 0.68 = 68 kW > 54 kW.
• During operation, the percent load will be:
- with redundancy, i.e. with 3 UPS units sharing the load: 79.4 / 3 x 50 = 52.9%,
- without redundancy, i.e. with only 2 UPS units sharing the load: 79.4 / 2 x 50 =
79.4%.
Standard rectifiers
These are three-phase rectifiers incorporating SCRs and using a six-phase bridge
(Graetz bridge) with standard chopping of the current.
This type of bridge draws harmonic currents with orders of n = 6 k ± 1 (where k is a
whole number), mainly H5 and H7, and to a lesser degree H11 and H13.
Harmonics are controlled by using a filter (see fig. 1.20).
All high-power UPS ranges from APC by Schneider Electric (except MGE Galaxy
PW and and MGE Galaxy 9000) use PFC type controlled active rectifier technologies
and therefore do not generate harmonics.
Table 1.2. Example of harmonic-current limitations as per guide IEC 61000-3-4 / EN 61000-3-
4 for devices with an input current > 16 A/ph (stage 1, simplified connection).
Harmonic % of H1 (fundamental)
H3 21.6%
H5 10.7%
H7 7.2%
H9 3.8%
H11 3.1%
H13 2.0%
H15 0.7%
H17 1.2%
H19 1.1%
H21 ≤ 0.6%
H23 0.9%
H25 0.8%
H27 ≤ 0.6%
H29 0.7%
H31 0.7%
≥ H33 ≤ 0.6%
Even orders ≤ 0.6% or ≤ 8/n (n even order)
Passive LC filters
• non-compensated
• compensated
• non-compensated with contactor
Double-bridge rectifier
Phase-shift filter
THM active filter (Active 12-pulse technology).
Fig. 1.21. Derating curve for a generator, as a function of the installation power factor.
The curve in the figure above, provided as one example among many, shows the
power derating as a function of the operating point, for a given generator. For a
purely capacitive load (λ = 0), the power available is equal to only 30% of the rated
power (point A). If we assume an apparent power rating such that Pn generator = Pn
rectifier, the meaning of points A, B, C, D, E and F is the following:
A: reactive power corresponding to the capacitive current of a non-compensated
filter,
B: reactive power corresponding to the capacitive current of a compensated filter,
C: operating point at start-up with a non-compensated filter with contactor,
D: operating point at the rated load with a non-compensated filter,
E: operating point at the rated load with a compensated filter,
F: operating point at the rated load, without a filter or with a phase-shift filter.
Example
Consider a non-compensated filter with a 300 kVA generator and a 200 kVA MGE
Galaxy PW UPS.
The power rating of the rectifier, taking 87% as the efficiency value (1 / 0.87 = 1.15),
is 1.15 times that of the inverter, i.e. 200 x 1.15 = 230 kVA.
The capacitive current of the non-compensated filter is 230 x 30% (1) = 69 kVA.
The reactive power that the generator can handle (point A) is 300 x 0.3 = 90 kVA.
The filter is therefore compatible with the generator.
(1) The value of 30% has been determined experimentally.
Type of filter LC non- LC compensated LC with contactor Double bridge Built-in THM
Criterion compensated
Diagram
Fig. 1.22a Fig. 1.22b Fig. 1.22c Fig. 1.22d Fig. 1.22e
Reduction in distortion
THDI at 100% load 7 to 8% 7 to 8% 7 to 8% 10% 4%
THDI at 50% load 10% 10% 10% 15% 5%
Harmonics eliminated H5, H7 H5, H7 H5, H7 H5, H7, H17, H19 H2 to H25
Power factor
λ at 100% load 0.95 0.95 0.95 0.85 0.94
λ at 50% load 1 1 1 0.8 0.94
Compatibility with * ** ** ** ***
generator
Efficiency of filter *** *** *** * **
Flexibility, upgradeability * * * * ***
Cost *** *** *** * **
Dimensions *** *** *** * ***
Connection in parallel with * * * * **
UPS
Fig. 1.22f Fig. 1.22g Fig. 1.22h Fig. 1.22i Fig. 1.22j
Compliance with guide no no no no yes
IEC 61000-3-4
General comment Solution suitable for Solution suitable for Solution suitable for Solution suitable for Solution suited to
installations without installations with an installations installations with sensitive installations
an engine generator engine generator set. comprising an engine gensets or with changing load
set. The added inductor generator set with a levels. The most
load reduces the power rating lower effective and the most
capacitive power that than that of the UPS. flexible solution. Does
must be supplied by The LC line is not depend on the
the engine-generator switched in by the percent load or the
set. contactor at a preset type of upstream
value corresponding source.
to an inverter percent
load that is
acceptable for the
engine generator set.
SW
Load
The MGE Galaxy PW and MGE Galaxy 9000 ranges are designed with isolation
transformers. All the other ranges use transformless technology with the neutral
recreated electronically.
The following pages show some examples for MGE Galaxy PW and MGE Galaxy
5000, 7000 and 9000 UPSs. For other cases, contact your APC by Schneider
Electric representative to obtain the applicable diagram.
Same system upstream and downstream Same system upstream and downstream
IT or TT or TN-S. IT or TT or TN-S.
Distributed neutral on the two lines. Distributed neutral on the bypass line only.
Same system upstream and downstream Same system upstream and downstream
TN-C IT or TT or TN-S.
Distributed neutral.
MGE Galaxy PW and 9000 MGE Galaxy 5000 and 7000
Fig. 1.29. A few examples with the same system upstream and downstream.
Protection using circuit The protection system for installations with UPS units presented here will implement
circuit breakers. Below is a presentation of the main characteristics of circuit
breakers breakers and their trip units. The part number mentioned as examples pertain to
Schneider Electric circuit breakers. Other characteristics, such as limiting thermal
stress and current, are among the strong points of the Compact NSX range of circuit
breakers, but will not be discussed here.
Î For further information, see the Schneider Electric low-voltage and medium-
voltage distribution catalogue and the "Electrical installation guide".
Trip units
Technology
There are two types of trip units:
• thermal-magnetic,
• electronic.
Construction
• built-in (thermal-magnetic only).
• interchangeable.
Comparison
Thermal-magnetic trip units are simple and inexpensive.
Electronic trip units offer more precise and comprehensive settings for better
adaptation to installations and their requirements.
The table below sums up the characteristics of both types of trip units for circuit-
breakers from 1 to 630 A and should enable you to solve most of the problems
commonly encountered (from 1 to 400 kVA).
Figure 1.31 presents the characteristic curves for the trip units.
(1) Ir is the thermal protection threshold (sometimes written Ith) of thermal-magnetic trip units or
the long-delay protection threshold of electronic trip units. These thresholds are defined by an
inverse time curve that depends on the selected setting.
(2) tr is the time delay of the long-delay thermal protection for a given value of Ir.
(3) Im is the magnetic threshold of thermal-magnetic trip units and Isd the short-delay threshold
of electronic trip units.
(4) tm is the time delay (adjustable or fixed) of the magnetic protection of thermal-magnetic trip
units and tsd the time delay (generally adjustable) of the short-delay protection of electronic trip
units.
(5) Ii is the instantaneous tripping threshold.
Fig. 1.31. Circuit-breaker time/current curves (Icu is the ultimate breaking capacity).
Current limiting
When a high fault current hits the circuit breaker, the breaker contacts separate
under the electrodynamic forces, an arc is created and its resistance limits the short-
circuit energy.
Cascading
When a short-circuit occurs downstream of the installation (see fig. 1.32), the fault
current also flows through the upstream circuit breaker which current limits, thus
attenuating the current applied to the downstream circuit breaker. The breaking
capacity of the latter is thus reinforced.
Selection of Rating
circuit breakers
The selected rating (rated current) for the circuit breaker must be the one just above
the rated current of the protected downstream cable.
Breaking capacity
The breaking capacity must be selected just above the short-circuit current that can
occur at the point of installation.
Ir and Im thresholds
The table below indicates how to determine the Ir and Im thresholds to ensure
discrimination, depending on the upstream and downstream trip units.
Remark.
Time discrimination must be implemented by qualified personnel because time
2
delays before tripping increase the thermal stress (I t) downstream (cables, semi-
conductors, etc.). Caution is required if tripping of CB2 is delayed using the Im
threshold time delay.
Energy discrimination does not depend on the trip unit, only on the circuit breaker.
Example
Consider the example used to determine the UPS power rating (Ch. 1 p. 21) with a
number of parallel-connected 400 V three-phase loads, namely:
• Computer system - S1 = 4 x 10 kVA, λ = 0.6, in-rush current 8 In over four periods
(80 ms),
• Variable-speed drive - S2 = 20 kVA, λ = 0.7, in-rush current 4 In over five periods
(100 ms),
• Isolation transformer - S3 = 20 kVA, λ = 0.8, in-rush current 10 In over six periods
(120 ms).
The three loads represent 54 kW with a power factor of 0.68.
In chapter 1, p. 21, an MGE Galaxy PW was selected, with a power rating of 100
kVA, I = 100 / (400 x 3 ) = 144 A.
The goal is to select circuit breakers CB1 and CB2, and the most powerful circuit
breaker CB3 compatible with discrimination requirements, given that the upstream
installation includes the following:
• 20 kV / 400 V transformer with a power rating of 630 kVA,
• 400 V engine generator set with a power rating of 400 kVA,
• Transformer to MLVS link, five meters of aluminium cable 4 x 240 mm2 per phase,
• Busbars to circuit breaker link, four meters using three copper bars 400 mm² per
phase.
Upstream system
Ra, Xa
Sources
Rtr Xtr
Transformer
• Sn = rated apparent power 630 kVA
• In = rated current = 630 / U 3 = 630 103 / (400 x 3 ) = 909 A
• Usc = transformer short-circuit voltage = 4%
• Pcu = transformer copper losses in VA
Pcu
Rtr = transformer resistance = ≈ 20% Xtr, negligible given Ztr
3 In2
U20 2 2 3
Xtr ≈ Ztr = transformer impedance = x Usc = 410 x 0.04 / 630 10 = 10.7 mΩ
Sn
Rtr ≈ 0 and Xtr = 10.7 mΩ.
Busbars
• Xb = busbar reactance (typically 0.15 mΩ/m) = 0.15 x 4 = 0.6 mΩ
• Rb = busbar resistance = ρ L / S= 22.5 x 4 / (3 x 400) = 0.075 mΩ (negligible)
Rb ≈ 0 and Xb = 0.6 mΩ.
Selection parameters
The table below sums up the various values calculated.
Parameter Value
transformer short-circuit current 19.4 kA
generator short-circuit current 2.9 kA
rectifier current (UPS input) 173 A
continuous load current downstream of the UPS 97 A
energising current of the largest load 288 A - 120 ms
maximum static-switch current 19.4 kA
Static bypass
Negligible impedance
Temperature rise
Permissible temperature rise in cables is limited by the withstand capacity of cable
insulation.
Temperature rise in cables depends on:
• the type of core (Cu or Al),
• the installation method,
• the number of touching cables.
Standards stipulate, for each type of cable, the maximum permissible current.
Voltage drops
Maximum values
The maximum permissible voltage drops are:
• 3% for AC circuits (50 or 60 Hz),
• 1% for DC circuits.
Selection tables
The tables below indicate the voltage drop in percent for a circuit made up of 100
meters of copper cable. To calculate the voltage drop in a circuit with a length L,
multiply the value in the table by L/100.
If the voltage drop exceeds 3% on a three-phase circuit or 1% on a DC circuit,
increase the cross section of the conductors until the value is within tolerances.
Calculation example
Consider a 70-meter 400 V three-phase circuit, with copper conductors and a rated
current of 600 A.
Standard IEC 60364 indicates, depending on the installation method and the load, a
2
minimum cross section. We shall assume that the minimum cross section is 95 mm .
It is first necessary to check that the voltage drop does not exceed 3%.
The table for three-phase circuits on the following page indicates, for a 600 A current
2
flowing in a 300 mm cable, a voltage drop of 3% for 100 meters of cable, i.e. for 70
meters:
3 x 70/100 = 2.1%, less than the 3% limit.
A identical calculation can be run for a DC current of 1000 A in a 10-meter cable with
a cross section of 240 mm². The voltage drop for 100 meters is 5.3%, i.e. for ten
meters:
5.3 x 10/100 = 0.53%, less than the 1% limit.
Example of an installation
Available technologies
Comparison of technologies
Batteries are by far the most commonly employed solution today.
They are the dominant solution due to low cost, proven effectiveness and storage
capacity, but nonetheless have a number of disadvantages in terms of size,
maintenance and the environment.
Ultracapacitors do not yet offer the necessary performance levels.
Flywheels operating at high speeds constitute a possible technology in terms of their
power ratings (40 to 500 kW), for short backup times (12 seconds to 1 minute).
Figure 1.39 shows the fields of application for the different technologies.
Î For more information, see White Paper WP 65: "Comparing Data Center
See WP 65 Î Batteries, Flywheels, and Ultracapacitors".
The table below compares the different solutions in terms of their capacity to meet
the energy-storage requirements of static UPSs.
Flywheels
APC by Schneider Electric offers flywheel energy storage systems on request.
This solution is suitable to complement batteries in that it may be used to ride
through short disturbances without calling on battery power, thus preserving the
battery.
Use without a battery is possible, but the backup time is only a dozen seconds. For
certain applications, such a short backup time is insufficient to start an engine
generator set.
For use in conjunction with its UPS ranges, APC by Schneider Electric recommends
sealed lead-acid batteries.
Selection of a battery depends on the following factors:
• operating conditions and requirements (special room, battery cabinet, racks, etc.),
• required backup time,
• cost considerations.
Backup time
APC by Schneider Electric offers:
• standard backup times of 5, 10, 15 or 30 minutes,
• custom backup times that can reach a number of hours.
Selection depends on:
• the average duration of power-system failures,
• any available sources offering long backup times (engine generator set, etc.),
• the type of application.
Service life
APC by Schneider Electric offers batteries with service lives of 5 or 10 years, or
longer.
Î Battery service life, see Ch. 5 p. 33.
Vented batteries
This type of battery (lead-acid or Ni/Cad) offers certain advantages:
• long service life,
• long backup times,
• high power ratings.
Vented batteries must be installed in special rooms complying with precise
regulations (see Ch. 1 p. 51 "Preliminary work") and require appropriate maintenance.
DigiBatTM
The DigiBatTM battery-monitoring system is an assembly of hardware and software,
installed as standard on UPSs of the MGE Galaxy range from APC by Schneider
Electric and offering the following functions:
• automatic entry of battery parameters,
• optimised battery service life,
• protection against excessive discharges,
• regulation of the battery floating voltage depending on the temperature,
• limitation of the battery current,
• continuous evaluation of available power taking into account the battery age, the
temperature and the percent load,
• forecast of battery service life,
• periodic, automatic tests on the battery, including a check on the battery circuit, an
open-circuit test, a partial-discharge test, etc.
Î DigiBat, see Ch. 5 p. 34 "Battery Management".
Example
The HMI typically offers the functions listed below.
Management software
• Enterprise Power Manager & ISX Central (software & server)
Software solutions to manage all installed UPSs via IP networks, web
compatible and accessible from any web browser.
• NMS Integration kits (Network Management System)
Integration in NMSs such as HP OpenView, IBM Tivoli, CA Unicenter, etc.
• Network Shutdown Module
- Software module for safe system shutdown.
Fig. 1.40. The communication cards combined with supervision software offer a wide range of
functions.
Installation considerations The main elements that must be taken into account for the UPS installation are the
following:
• plans for site modifications, any preliminary work (notably for a battery room),
taking into account:
- the dimensions of equipment,
- operating and maintenance conditions (accessibility, clearances, etc.),
- temperature conditions that must be respected,
- safety considerations,
- applicable standards and regulations,
• ventilation or air-conditioning of rooms,
• creation of a battery room.
Dimensions
Layout of UPS cabinets and enclosures should be based on precise plans.
The physical characteristics of UPSs from APC by Schneider Electric that may be
used to prepare the plans are presented in chapter 4.
They indicate, for each range:
• the dimensions and weights of:
- UPS and centralised-bypass cabinets;
- battery cabinets,
- any auxiliary cabinets (autotransformers, transformers, filters, etc.),
• minimum clearances required for cabinets and enclosures to ensure optimal
ventilation and sufficient access.
Ventilation, air-conditioning
Ventilation requirements
UPSs are designed to operate within a given temperature range (0 to 40°C for UPSs
from APC by Schneider Electric ) that is sufficient for most operating conditions
without modifications.
However, UPSs and their auxiliary equipment produce heat losses that can, if no
steps are taken, increase the temperature of a poorly ventilated room.
What is more, the service life of a battery is heavily dependent on the ambient
temperature. The service life is optimal for temperatures between 15° C and 25° C.
This factor must be taken into account if the battery is installed in the same room as
the UPS.
A further consideration is the fact that UPSs may be installed in the same room as
computer equipment which often has more severe requirements concerning
operating-temperature ranges.
Noise level
UPSs must produce a low level of noise, suited to the room where they are installed.
Measurement conditions for the level of noise indicated by the manufacturer must
comply with standard ISO 3746 (measurement of noise).
Battery room Where possible and if desired, the battery should be installed in a cabinet.
Battery-cabinet dimensions are indicated for each UPS range, depending on the
rated power.
However, for very high-power UPSs, batteries are generally installed in special
rooms (electrical room).
Batteries must be installed in compliance with international standards, local
regulations and standard IEC 60364.
Battery on racks
The battery cells are installed on a number of different levels, off the floor.
When determining the height between each rack, it is necessary to take into account
the space required to check battery levels and fill the battery cells easily. A minimum
height of 450 mm is recommended.
Battery on tiers
This installation method is similar to the preceding. It is the most convenient method
for checking battery levels.
Battery-room features
Whatever the installation method selected, the battery installation must comply with
the following requirements (the numbers indicate the elements shown in figure 1.40).
Ventilation (2)
• calculation of throughput
The volume of air to be evacuated depends on the maximum load current and the
type of battery. In installations comprising a number of batteries, the quantities of air
that must be evacuated are cumulative.
- vented batteries
d = 0.05 x N x Im, where
d - throughput in cubic meters per hour,
N - number of battery cells,
Im - maximum load current in amperes.
- sealed battery
The ventilation conditions in a general-purpose room are sufficient.
• safety
An automatic device must stop battery charging if the ventilation system fails.
• location
Air must be drawn out from the top of the battery room.
79980
Captive installation screws
Specification Description
AC-input type Autoranging input with power factor correction (PFC)
Note Power factor correction is a standard feature on all Catalyst 6500
series AC-input power supplies. PFC reduces the reactive
component in the source AC current allowing higher power
factors (typically 99 percent or better) and lower harmonic
current components.
AC-input voltage • Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
• High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
AC-input current • 12 A @ 120 VAC
• 6 A @ 230 VAC
AC-input frequency 50/60 Hz (nominal)
Note Because of the form-factor difference, when you install an 8700 W power supply in a Catalyst 6506,
Catalyst 6509, or Catalyst 6509-NEB chassis you must relocate the system ground connection from the
chassis ground pad connection to the two system ground studs located on the 8700 W power supply
faceplate. Installing an 8700 W power supply in the other Catalyst 6500 series chassis does not require
that you move the chassis system ground connection to the power supply.
The 8700 W power supply cannot be installed in the Catalyst 6503, Catalyst 6503-E, and
Catalyst 6504-E switch chassis.
AC power
connection 1
AC power
connection 2
AC power
connection 3
Power 182076
NC RELAY
switch o INPUT
OK
FAN
OK
OUTPUT
FAIL
1
Status LEDs 2 3
220VAC
1 2 3 DEFAULT
NO RELAY
CISCO SYSTEMS, INC.
Specification Description
AC-input type 3 AC-inputs per power supply. High-line input with power factor
correction (PFC) included.
Note Power factor correction is a standard feature on all Catalyst 6500
series AC-input power supplies. PFC reduces the reactive
component in the source AC current allowing higher power
factors (typically 99 percent or better) and lower harmonic
current components.
AC-input voltage • Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
(One-phase) • High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
Software compatibility Cisco NX-OS Software Release Cisco NX-OS Software Release 4.0 Cisco NX-OS Software Release
6.1(2) and later and later 4.1(2) and later
Physical specifications ● (H x W x D): 1.6 x 3.95 x 22 in. ● (H x W x D): 8.51* x 4 x 17.5 in. ● (H x W x D): 8.51* x 4 x 17.5 in.
(4.1 x 10 x 55.9 cm) (21.6* x 10.1 x 44.5 cm) (21.6* x 10.1 x 44.5 cm)
● Weight: 5 lb (2.27 kg) ● Weight: 18 lb (8.2 kg) ● Weight: 23 lb (10.5 kg)
* *
The height of the power supply unit The height of the power supply unit
is not uniform along the entire depth. is not uniform along the entire depth.
The height at the front and rear are The height at the front and rear are
8.51 and 4.2 in. (21.6 and 10.7 cm) 8.51 and 4.2 in. (21.6 and 10.7 cm)
respectively. respectively.
Input voltage range 90 to 264 VAC 90 to 264 VAC 170 to 264V AC
Input frequency range 47 to 63 Hz 47 to 63 Hz 47 to 63 Hz
Input current 16A maximum at nominal line voltage 16A maximum at nominal line voltage 24A maximum at nominal line voltage
(each input) (110 or 220 VAC) (110 or 220 VAC) (220 VAC)
Power supply input International Electrotechnical IEC 320-C20 ● IEC 60309 for INT
receptacles Commission (IEC) 320-C20 ● NEMA L6-30 for US
Power cord rating 16A 16A 24A
British thermal units ● 11,400 BTUs per hour at 3000W ● 23,000 BTUs per hour at 6000W ● 28,500 BTUs per hour at 7500W
(BTUs) ● 5560 BTUs per hour at 1400W ● 16,500 BTUs per hour at 4200W ● 14,200 BTUs per hour at 3750W
● 11,500 BTUs per hour at 3000W
● 9900 BTUs per hour at 2400W
● 4950 BTUs per hour at 1200W
Output holdup time 20 milliseconds (ms) minimum
Cooling fan Integrated Integrated
© 2016 Cisco and/or its affiliates. All rights reserved. This document is Cisco Public Information. Page 6 of 9
IEC 61000-3-2 Harmonic
Limits
WEBPORT pour client/for customer SCHNEIDER ELECTRIC INDUSTRIES SAS le/the 26/01/2016 à/at 09:21
ELOT EN 61000-3-2 : 2014-08
3.22
variable speed drive
VSD
equipment, based on power electronics, which enables the speed and/or torque of a motor to
be continuously controlled
4 General
The objective of this standard is to set limits for harmonic emissions of equipment within its
scope, so that, with due allowance for the emissions from other equipment, compliance with
the limits ensures that harmonic disturbance levels do not exceed the compatibility levels
defined in IEC 61000-2-2.
Professional equipment that does not comply with the requirements of this standard may be
permitted to be connected to certain types of low voltage supplies, if the instruction manual
contains a requirement to ask the supply utility for permission to connect. Recommendations
concerning this aspect are contained in IEC/TR 61000-3-4 or IEC 61000-3-12.
5 Classification of equipment
Class A:
Equipment not specified in one of the three other classes shall be considered as Class A
equipment.
NOTE 1 Equipment that can be shown to have a significant effect on the supply system may be reclassified in a
future edition of the standard. Factors to be taken into account include:
– number of pieces of equipment in use;
– duration of use;
– simultaneity of use;
– power consumption;
– harmonic spectrum, including phase.
Class B:
– portable tools;
– arc welding equipment which is not professional equipment.
Class C:
– lighting equipment.
Class D:
Equipment having a specified power according to 6.2.2 less than or equal to 600 W, of the
following types:
– television receivers;
– refrigerators and freezers having one or more variable-speed drives to control compressor
motor(s).
NOTE 2 Class D limits are reserved for equipment that, by virtue of the factors listed in note 1, can be shown to
have a pronounced effect on the public electricity supply system.
6 General requirements
The following restrictions apply even to equipment to which no harmonic current limits apply as
defined in Clause 7.
The requirements and limits specified in this clause are applicable to the power input terminals
of equipment intended to be connected to 220/380 V, 230/400 V and 240/415 V systems
operating at 50 Hz or 60 Hz. Requirements and limits for other cases are not yet considered.
A simplified test method is permitted for equipment that undergoes minor changes or updates,
provided that, in previous full compliance tests, it has been shown to have current emissions
below 60 % of the applicable limits and the THD of the supply current is less than 15 %. The
simplified test method consists of verifying that the updated equipment has an active input
power within r20 % of that of the originally tested product, and that the THD of the supply
current is less than 15 %. Products that fulfill these requirements are deemed to comply with
the applicable limits, but in case of doubt the result of a full compliance test according to
Clauses 6 and 7 takes precedence over this simplified method.
a) where they are the only practical solution permitting the detection of unsafe conditions, or
b) where the controlled active input power is less than or equal to 100 W, or
c) where the controlled appliance is a portable equipment fitted with a two-core flexible cord
and is intended for use for a short period of time, i.e. for a few minutes only.
If one of these three conditions is fulfilled, half-wave rectification may be used for any purpose,
whereas asymmetrical controls may only be used for the control of motors.
NOTE 1 Such equipment includes, but is not limited to, hair dryers, electrical kitchen appliances and portable
tools.
Symmetrical control methods which are prone to produce harmonics of low order (n d 40) in the
input current may be used for the control of the power supplied to heating elements provided
that the full sine-wave input power is less than or equal to 200 W, or that the limits of Table 3
are not exceeded.
Such symmetrical control methods are also allowed for professional equipment provided that
either
Professional equipment whose primary purpose, considered as a whole, is not for heating, shall
be tested against the relevant limits.
WEBPORT pour client/for customer SCHNEIDER ELECTRIC INDUSTRIES SAS le/the 26/01/2016 à/at 09:21
ELOT EN 61000-3-2 : 2014-08
V A
400 0,4
d65°
300 0,3
Ip+
t90°
200 0,2
d60°
100 0,1
+0,05Ip(abs)
0 0
–0,05Ip(abs)
–100 –0,1
d60°
–200 –0,2
t90°
–300 d65° Ip– –0,3
–400 –0,4
V A
IEC 1461/14
For Class A equipment, the harmonics of the input current shall not exceed the values given in
Table 1.
Audio amplifiers shall be tested according to Clause C.3. Dimmers for incandescent lamps
shall be tested according to Clause C.6.
For Class B equipment, the harmonics of the input current shall not exceed the values given in
Table 1 multiplied by a factor of 1,5.
– the equipment shall be tested according to the conditions given in Clause C.5 (see the
last paragraph of C.5.3).
b) Active input power d 25 W
Discharge lighting equipment having an active input power smaller than or equal to 25 W
shall comply with one of the following two sets of requirements:
– the harmonic currents shall not exceed the power-related limits of Table 3, column 2, or:
– the third harmonic current, expressed as a percentage of the fundamental current, shall
not exceed 86 % and the fifth harmonic current shall not exceed 61 %. Also, the
waveform of the input current shall be such that it reaches the 5 % current threshold
before or at 60°, has its peak value before or at 65° and does not fall below the 5 %
current threshold before 90°, referenced to any zero crossing of the fundamental supply
voltage. The current threshold is 5 % of the highest absolute peak value that occurs in
the measurement window, and the phase angle measurements are made on the cycle
that includes this absolute peak value. See Figure 2.
If the discharge lighting equipment has a built-in dimming device, measurement is made
only in the full load condition.
For Class D equipment, the harmonic currents and the power shall be measured as defined
in 6.2.2. The input currents at harmonic frequencies shall not exceed the values that can be
derived from Table 3 according to the requirements specified in 6.2.3 and 6.2.4.
Odd harmonics
3 2,30
5 1,14
7 0,77
9 0,40
11 0,33
13 0,21
15
15 d n d 39 0,15
n
Even harmonics
2 1,08
4 0,43
6 0,30
8
8 d n d 40 0,23
n
WEBPORT pour client/for customer SCHNEIDER ELECTRIC INDUSTRIES SAS le/the 26/01/2016 à/at 09:21
ELOT EN 61000-3-2 : 2014-08
2 2
3 30 O a
5 10
7 7
9 5
11 d n d 39 3
(odd harmonics only)
a O is the circuit power factor.
3 3,4 2,30
5 1,9 1,14
7 1,0 0,77
9 0,5 0,40
11 0,35 0,33
13 d n d 39 3,85 See Table 1
(odd harmonics only) n
Quasi-stationary T obs of sufficient duration to meet the requirements for repeatability in 6.2.3.1
Short cyclic (T cycle d 2,5 min) T obs t 10 cycles (reference method) or T obs of sufficient duration or
synchronisation to meet the requirements for repeatability in 6.2.3.1 a
Random T obs of sufficient duration to meet the requirements for repeatability in 6.2.3.1
Long cyclic (T cycle ! 2,5 min) Full equipment program cycle (reference method) or a representative 2,5 min
period considered by the manufacturer as the operating period with the highest
THC
a By 'synchronization' is meant that the total observation period is sufficiently close to including an exact
integral number of equipment cycles such that the requirements for repeatability in 6.2.3.1 are met.
WEBPORT pour client/for customer SCHNEIDER ELECTRIC INDUSTRIES SAS le/the 26/01/2016 à/at 09:21
ELOT EN 61000-3-2 : 2014-08
Annex A
(normative)
The measured harmonic values shall be compared with the limits given in Clause 7. The
harmonic currents of the equipment under test (EUT) shall be measured in accordance with the
circuits given in the following figures:
Measurement equipment complying with Annex B shall be used. Test conditions for the EUT
are given in Annex C.
While the measurements are being made, the test voltage (U) at the terminals of the
equipment under test, when operated according to Annex C, shall meet the following
requirements.
a) The test voltage (U) shall be the rated voltage of the equipment. In the case of a voltage
range, the test voltage shall be 230 V or 400 V for single-phase or three-phase supplies
respectively. The test voltage shall be maintained within r2,0 % and the frequency within
r0,5 % of the nominal value.
b) In the case of a three-phase supply, the angle between the fundamental voltage on each
pair of phases of a three-phase source shall be 120° r 1,5°.
c) The harmonic ratios of the test voltage (U) shall not exceed the following values with the
EUT connected as in normal operation:
0,9 % for harmonic of order 3;
0,4 % for harmonic of order 5;
0,3 % for harmonic of order 7;
0,2 % for harmonic of order 9;
0,2 % for even harmonics of order from 2 to 10;
0,1 % for harmonics of order from 11 to 40.
d) The peak value of the test voltage shall be within 1,40 times and 1,42 times its r.m.s. value
and shall be reached within 87° to 93° after the zero crossing. This requirement does not
apply when Class A or B equipment is tested.
WEBPORT pour client/for customer SCHNEIDER ELECTRIC INDUSTRIES SAS le/the 26/01/2016 à/at 09:21
ELOT EN 61000-3-2 : 2014-08
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-3-2 has been prepared by sub-committee 77A: Low-
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
This fourth edition cancels and replaces the third edition published in 2005, Amendment 1:
2008, Amendment 2:2009 and Corrigendum of August 2009.
This edition includes the following significant technical changes with respect to the previous
edition:
0RGHO OLVW
7KH 0*( *DOD[\ 836 LV DYDLODEOH LQ WKH IROORZLQJ PRGHOV
(I¿FLHQF\
7KH WDEOH EHORZ SURYLGHV DYHUDJH V\VWHP HI¿FLHQFLHV RQ D GRXEOH FRQYHUVLRQ VLQJOH XQLW ZLWK D EDODQFHG
OLQHDU ORDG 3) $& LQSXW YROWDJH 9 $& RXWSXW YROWDJH 9
(I¿FLHQF\ RQ ORDG 3) RU IRU RWKHU ,QSXW RU 2XWSXW $& YROWDJH LV YHU\ FORVH WR WKH YDOXHV JLYHQ EHORZ
IRU 3) YROWDJH LQSXW 9 RXWSXW 'LIIHUHQFH LV OHVV WKDQ
0LQLPXP V\VWHP HI¿FLHQF\ LV YHU\ FORVH WR DYHUDJH V\VWHP HI¿FLHQF\ 7KH GLIIHUHQFH LV PD[LPXP
$OO WKHVH PHDVXUHV DUH FRPLQJ IURP WKH SURGXFWLRQ OLQH $7( VWDWLVWLFV SHUIRUPHG RQ RYHU XQLWV
1RPLQDO
LQSXW FXUUHQW
$
&RQQHFWLRQ ±ZLUH 3+
W\SH
,QSXW +] WR +]
IUHTXHQF\
+]
7+', ORDG
DW IXOO ORD
,QSXW
S SRZHU
S ! DW ORDG !
IDFWRU
FRUUHFWLRQ
1RWH )RU 9 LQWHUSKDVH YROWDJHV DQG D ORDG ZLWK D SRZHU IDFWRU RI
1RP LQSXW FXUUHQW
$
&RQQHFWLRQ W\SH +DUG :LUH ZLUH 3+ 1 3(
,QSXW IUHTXHQF\ +] WR +]
+]
1RP RXWSXW FXUUHQW
$
&RQQHFWLRQ W\SH +DUG :LUH ZLUH 3+ 1 3(
2XWSXW FDSDFLW\ IRU VHFRQGV QRUPDO RSHUDWLRQ
IRU PLQXWHV QRUPDO RSHUDWLRQ
2XWSXW IUHTXHQF\ +] +]
V\QF WR PDLQV
6OHZ UDWH +]6HF
7RWDO +DUPRQLF
7 SKSK
'LVWRUWLRQ 7+'8
2XWSXW
S SRZHU
IDFWRU
'\QDPLF ORDG
UHVSRQVH
2XWSXW
S YROWDJH
UHJXODWLRQ
&UHVW IDFWRU
%DWWHU\ 6SHFL¿FDWLRQV
7
7\SH 6HDOHG OHDGDFLG 9HQWHG OHDGDFLG
9 1L&DG
0LQ0D[ QXPEHU RI FHOOV
)ORDWLQJ YROWDJH SHU FHOO 9 9 9
0LQ0D[ ÀRDWLQJ 9 9 9 9 9 9
YROWDJH
(TXDOLVLQJ YROWDJH SHU FHOO 1RW DSSOLFDEOH 9 9
%RRVW YROWDJH SHU FHOO 1RW DSSOLFDEOH 9 9
0LQ YROWDJH SHU FHOO 9 WR 9 9 WR 9 9
5HFKDUJH FXUUHQW [ & [ & &
1RWH %DWWHU\ FDEOH VL]HV DUH GHWHUPLQHG IRU &RSSHU VLQJOHFRUH FDEOHV W\SH 8 59
PD[LPXP OHQJWK P ZLWK D OLQH YROWDJH GURS
1RWH $& FDEOH VL]HV DUH GHWHUPLQHG IRU 7KH 716 V\VWHP IRU FRSSHU VLQJOHFRUH FDEOHV
W\SH 8 59 P ORQJ ZLWK D OLQH YROWDJH GURS LQVWDOOHG RQ SHUIRUDWHG FDEOH
WUD\V ;/3(W\SH LQVXODWLRQ VLQJOHOD\HU WUHIRLO IRUPDWLRQ 7+', EHWZHHQ DQG
& DW 9 JURXSHG LQ IRXU WRXFKLQJ FDEOHV
1RWH %DWWHU\ FDEOH VL]HV DUH GHWHUPLQHG IRU &RSSHU VLQJOHFRUH FDEOHV W\SH 8 59
PD[LPXP OHQJWK P ZLWK D OLQH YROWDJH GURS
1RWH ,PSRUWDQW )RU ! N9$ 836V WKH RXWSXW FDEOHV PXVW EH DW OHDVW PHWUHV ORQJ
/P
3DUDOOHO &DSDELOLWLHV
836 FDELQHW
3)& UHFWL¿HU PRGXOH $
,QYHUWHU PRGXOH %
%DWWHU\ FKRSSHU &
%DWWHULHV
66&
6WDWLFVZLWFK RQ $& E\SDVV
OLQH '
they add together to create a new harmonic current and PF profile. Because this example
exhibits high power factor and relatively low current THD we can deduce that the majority
load on this circuit is linear (PFC). The circuit load diversity can be defined as the ratio of
linear load to nonlinear load. For example, 1200 VA linear and 300 VA nonlinear would be
1200:300 = 4:1 ratio. A diversity of greater than one indicates that the linear loads dominate
and dramatically reduce the effect of the non-linear load. A diversity of zero is a pure non-
linear load. Any diversity of greater than zero provides some mitigation from the theoretical
problems associated poor power factor and current harmonics.
1 A 4.48 120.5 0.97 0.98 540 524 20 19 2.6 3.3 2.5 2.2 0.7
B 2.49 121.6 0.93 0.99 303 282 34.2 32.1 4 7.1 7.4 5.4 2.9
C 2.45 120.6 0.93 0.98 295 275 31.5 27.1 10.6 10 4.8 2.3 1
N 3.04
2 A 8.64 121.8 0.96 0.96 1052 1010 6.1 5.2 2.4 1 1.2 0.4 0.3
B 4.6 121.4 0.95 0.95 558 531 5.9 5 2.3 0.9 1.3 0.2 0.6
C 4.45 121.9 0.96 0.95 542 521 7 6.2 2.3 0.9 1.5 0.3 0.1
N 4.01
3 A 5.56 120.5 0.97 0.98 670 650 12.7 12.5 1.2 1.3 1.4 0.8 1.6
B 2.54 121.6 0.97 0.98 309 300 18.4 18.1 2.2 1 1.6 1.2 1.6
C 6.28 121.9 0.98 0.98 766 750 10.3 10.1 0.9 0.8 0.7 0.3 0.7
N 1.96
4 A 0.89 121.8 0.98 0.98 108 106 11.8 10.9 1.1 1.6 0.2 2.5 2.2
B 3.73 121.7 0.97 0.97 454 440 8 7.5 1.5 1.3 0.9 1.1 0.7
C 0.97 122 0.98 0.97 118 116 11.6 10.1 1.6 1.6 2.6 2.9 1.9
N 2.82
5 A 2.77 121.7 0.98 0.98 337 330 7.3 6.8 1.7 1.1 0.9 0.8 0.4
B 2.09 121.6 0.97 0.99 254 247 23.7 17.7 11.1 8.5 5 3.2 0.9
C 2.47 120.7 0.98 0.98 298 292 7.3 6.9 1.4 0.4 1 0.3 0.4
N 1.12
Figure 4 6 A 3.74 121.8 0.99 0.96 456 451 6.7 6.3 1.7 0.5 0.9 0.2 0.4
B 3.05 121.7 0.95 0.95 371 353 7.8 1 7.2 1.7 0.6 1.2 0.7
Results of C 1.95 121.9 0.97 0.98 238 231 6.5 6.1 1.5 0.6 1.6 0.4 0.7
N 1.8
harmonics study 7 A 3.24 121.7 0.97 0.99 394 382 20.6 18.8 6.4 4.1 2.5 1.1 1.8
B 6.4 121.6 0.98 0.99 778 763 16.1 14.8 4.7 3.3 1 0.8 1.1
C 4.44 120.6 0.97 0.98 535 519 17.2 15.9 5.1 3.3 1 1.1 1.4
N 3.55
8 A 0.12 121.8 0.65 0.68 15 10 23 17.5 2.3 2.2 4.1 2.2 2
B 0.1 121.7 0.91 0.94 12 11 83 65.1 21.1 18.3 25.2 19.1 16.9
C 0 121.9 N/A N/A 0 N/A N/A N/A N/A N/A N/A N/A N/A
N 0.1
9 A 1.67 121.8 0.94 0.99 203 191 31.6 22.2 13.6 14.4 7.6 6.3 3.5
B 1.31 120.5 0.99 0.99 158 156 12.7 7.2 1.1 4.6 3.1 3.3 2.9
C 1.07 121.9 0.57 0.98 130 74 81.5 48.1 42 35 27.2 19.4 12.5
N 1.69
10 A 0.8 121.8 0.65 0.99 97 63 75.4 50.4 38.2 29.7 20.7 12.6 0.04
B 0.75 121.7 0.6 0.99 91 55 79.5 56.4 46.3 29.7 21.9 12.1 4.2
C 1.45 121.9 0.67 0.99 177 118 73.9 57.4 37.3 27.5 13.3 6 1.9
N 1.76
11 A 0 121.8 N/A N/A 0 0 N/A N/A N/A N/A N/A N/A N/A
B 0.11 121.7 0.62 0.78 13 8 56.7 12.3 26.7 19.3 16.4 17.4 14.3
C 0.11 120.6 0.17 0.25 13 2 73.7 69.3 8.3 7 8.3 1.4 2.7
N 0.13
12 A 4.66 121.8 0.97 0.98 568 551 11.2 10.5 2.8 1.2 0.4 0.9 0.8
B 3.95 121.7 0.96 0.98 481 461 17.5 16.5 4 3.1 0.7 1.9 1.7
C 6.72 120.8 0.96 0.97 812 779 12 11.2 3.3 1.7 0.6 0.9 0.7
N 2.97
13 A 2.99 121.7 0.96 0.99 364 349 7.3 6.9 1.7 1 0.7 0.3 0.5
B 3.78 120.5 0.97 0.95 455 442 29.3 6.9 9.3 5.1 2.9 2.4 0.8
C 4.27 121.8 0.97 0.99 520 504 13.7 12.9 2.7 1.3 2.4 1.6 0.8
N 2.13
14 A 1.34 121.7 0.96 0.98 163 157 17.8 17.6 1.9 1.3 0.3 2.6 0.9
B 3.54 121.7 0.97 0.98 431 418 15.7 15.1 1.5 2.1 1.6 1.8 0.6
C 3.2 120.6 0.97 0.98 386 374 13.9 13.3 0.9 2.5 0.1 1.3 1.2
N 2.25
Using the raw branch circuit data from the chart above, analysis was done and bar charts
were created to provide better visualization of the circuit conditions.
Figure 5
Fundamental
(60Hz) currents
The circuit numbers 1-48 correspond to the individual breaker poles in the main PDU panel
board as shown in the previous data chart. Therefore, “1, 2, 3 are multi-wire branch circuit #1
in the above analysis chart, i.e., A, B, and C phases respectively. This data shows that none
of the 16 three-phase multi-wire branch circuits are carrying balanced load.
Figure 6
% of phase
conductor rating
(16A)
This chart shows the branch circuit loads relative to the 16A conductor rating for each branch.
Once again there is no balance indicated for any of the three-phase multi-wire circuits and
the highest % load is ~ 55% on branch # 4 (CB #2- A Phase). The majority circuit loading is
under 30% of the conductor rating.
Figure 7
Current % total
harmonic distortion
This chart is the analysis of the percent total harmonic distortion for the currents (% THDi) on
each branch circuit. This shows us that the majority of branch circuits are loaded with less
than 20% THDi. If we compare this to the previous charts we can see a pattern developing,
i.e., the loads with the highest THDi (circuits 21-33) have some of the lowest branch circuit
loading, i.e., ~ 10% or less of the circuit rating.
Figure 8
Total circuit power
factor
This chart shows the total power factor of all branches. We can see that the majority load is
.95 or better and also has same pattern as the previous charts, i.e., lowest power factor is the
lightest loaded circuits. The overall power factor of the system will be higher than the
average of these power factors, because the data shows that the circuits with low power
factor also have low current, and therefore the circuits with low power factor make a low
contribution to the total reactive power.
Figure 9
% of neutral rating
(20 A)
This is the key chart that summarizes the implications regarding the sizing of neutral wires.
The chart shows the neutral load current versus 20A branch rating for all 16 multi-wire branch
circuits. Legacy design guidelines would predict that these neutral currents would be as
much as 170% of rating, whereas the data shows actual currents in a real installation are on
the order of 20%. Furthermore, the dominant source of the observed neutral currents is
actually load imbalance between phases, and not harmonic currents. These results are
expected when an understanding of modern computer power supplies is applied to the
analysis, and they clearly show that the legacy approach of oversizing neutrals in this
application is unwarranted.
System phase loading in all branch circuits is under 60% and is under 20% for the majority of
the 48 branch circuits studied. The circuits with highest ITHD percentage exhibit the lowest
circuit loading. These same circuits also exhibit the lowest neutral currents and poorest
power factor. The reason for this is that they represent a very small fraction of the modern IT
data center load.
Legacy design guidelines would predict that the K-factor requirement would be as much as
21, whereas the data shows the actual K-factor requirement is approximately 1. These
results are expected when an understanding of modern computer power supplies is applied
to the analysis, and they clearly show that the legacy approach of specifying high K-factors of
15 or 21 in this application is unwarranted.
Conclusion The power characteristics of the modern IT data center rack environment are very different
from the computer room of the early 1980’s. Dramatic improvements in IT equipment power
factor and harmonics have lead to corresponding improvements in the overall system power
factor along with a large harmonic current reduction. Actual measurements of real systems
demonstrate these improvements. K-factor specifications of 15 or 21 drive unnecessary cost
when the actual K-factor of real installation is approximately 1. Neutral oversizing of 170% to
200% drives unnecessary costs when the actual neutral current is only 20% of circuit rating.
Legacy design practices and specifications for data center power systems should be updated
to reflect the actual requirements of modern data centers.
Neil holds 19 patents related to high-efficiency and high-density data center power and cooling
infrastructure, and has published over 50 white papers related to power and cooling systems,
many published in more than 10 languages, most recently with a focus on the improvement of
energy efficiency. He is an internationally recognized keynote speaker on the subject of high-
efficiency data centers. Neil is currently working to advance the science of high-efficiency,
high-density, scalable data center infrastructure solutions and is a principal architect of the APC
InfraStruXure system.
Prior to founding APC in 1981, Neil received his bachelors and masters degrees from MIT in
electrical engineering, where he did his thesis on the analysis of a 200MW power supply for a
tokamak fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel
energy storage systems and solar electric power systems.
Variable Speed Drives are non linear loads thus increase voltage distortion
by injecting harmonic currents into the main supply.
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
The current absorbed by a Variable Speed Drive is not sinus, it's not a
linear load
• In steady state the filtering capacitors are charged only on the peak of the supply voltage
• The current in a phase is a succession of impulses, corresponding to the reloading of the DC bus
capacitors on the peaks of the line voltage (voltage between phases).
DC bus voltage U
DC bus capacitor
current Ic
Supply voltage V
V E Z I
• The current impulses in the phase 1 correspond to the peak of the voltage between phases U12 and
U13, in the 2 directions. Each current impulse starts when the line voltage is higher than the voltage
at the capacitor terminals.
600
Vc
400 The current is almost in
U 13 U 12
phase with the simple
main voltage
So the Cos Phi is near
200
from 1
I main
0
V1
-200
-400
- Vc
-600
0.04s 0.05s 0.06s 0.07s 0.08s
18/01/2017 Bertrand Guarinos STIE VSD and harmonics V3 Summary 7
Generalities
h
I RMS I h2
h 1
The effective current is equal to
the square root of the sum of
the harmonics squared.
h
I h2
h 2
THD
I1
Ratio of the r.m.s. value of the sum of
all the harmonic components up to a
specified order to the r.m.s. value of
the fundamental component .
I 22 I 32 I 42 ... I n2
THD% * 100
I1
Supply 1 ph 3 ph
Pulses 4 6
THDI 98% 145%
Freq Row I RMS % 140 176
50 1 100 100
150 3 80
250 5 51 90
350 7 23 81
450 9 5
550 11 6 58
650 13 5 46
750 15 2
850 17 2,5 23
950 19 2 14
1050 21 1,2
1150 23 1,4 5
1250 25 1 5
1350 27 0,8
1450 29 0,9 6
1550 31 0,7 3,5
1650 33 0,5
1750 35 0,6 3
1850 37 0,4 2,2
1950 39 0,4
2050 41 0,4 2,4
Cos
The power factor is
P UI 3 * D
Voltage harmonics
• RMS current and ripple higher => Overload of the rectifier bridge and
the drive capacitors
U n2
Ssc
• Short circuit power (Ssc) ZT
I sc
* Rsce is define in IEC 61000-3-4 (-12) Rsce
IEEE519 gives Isc/Iload in fact it's the same value IL
• Within an installation, the PCC is defined as the connection point between the
non-linear load and other loads.
• In the standard the Total Harmonic Distortion limits are tabulated as function of
the short circuit ratio (Rsce) at PCC
Ssc I sc
Rsce
SL IL
IL or Sl
Rsce is an image of
PCC the supply impedance
U n2
Ssc
ZT
Rated power
Transformer
(impedance)
Cable length
At PCC2 THDI THDU
PCC2*
Transformer size (Rsce)
Cable length
Linear loads/VSD kVA
Technology VSD impedance
VSD* of the VSD VSD rectifier pulses
Linear Motor load
loads
THDI (%)
ATV71 3ph 22kW
140
THDI increase when With choke
motor load decrease
Without choke
120
100
80
60
40
20
0 Motor load
0% 20% 40% 60% 80% 100%
50
THDI decrease when
45 linear loads inrease
40
THDI at PCC %I
35
30
25
VSD with 3% choke
20
15
10
5
0
0 10 20 30 40 50 60 70 80 90 100
Ratio VSD load / Linear loads at PCC %
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
Generic
Standards and guidelines ...
or reference
standards
IEC/EN 61800-3
• International standard for Power Drives Systems
• It refers to IEC 61000-3-2 , technical report IEC 61000-3-4 and IEC 61000-3-12
IEEE 519
• Recommended Practices and Requirements for Harmonic Control in Electrical
Power Systems
• Us guide line
In fact these are guide lines and recommendations are not mandatory but
many manufacturer and drive users refer to them.
The CE marking indicates that the product works in conformity with the
directives that are valid for the product.
EN61800-3 is the EMC product standard for Power Drive Systems* (PDS).
The current harmonic values shall be given at least up to the 40th row.
For calculations, the PDS is connected to a supply with short circuit power
Rsce = 250 and with initial voltage distortion less than 1%.
The high-frequency component of the THD call PWHD shall be also given.
A device can have a very low THD for the first rows but a lot of high
frequency distortion which is not good for certain installation.
2
In
PWHD n 14 n
40
I1
For example the PWHD with DC inductance is worse than with AC inductance
and yet the THDI is quite the same.
• All those standards are applicable for the first environment “ residential “
• There is no standard for the 2nd environment “industrial”
Residential Industrial
directly connected onto the public network MV/LV transformer
Professional equipment Non professional equipment
I line VSD Standard THDI Rsce Standard THDI Rsce
<= 16A IEC 61000-3-12 <=48% >=120 IEC 61000-3-2 <5% NS no requirment
16A < I <= 75A IEC 61000-3-12 <=48% >=120 IEC 61000-3-12 <=48% >=120 no requirment
>=75A IEC 61000-3-4 <=48% >=350 IEC 61000-3-4 <=48% >=350 no requirment
• To conform to this standard the drive must be equipped with a specific filter,
inductors are not sufficient. The THDi must be less than 5%
• This standard is not easy to respect at reasonable cost for little variable speed
drive (the filter has the price of the drive).
• At the moment Telemecanique doesn't conform this standard even with option
filters
Always:
• If the drive is declared as professional equipment, which does not conform to the
standard IEC 61000-3-2 then : the recommendations of the standard IEC 61000-3-
12 apply
• In this case, the builder (STIE) must warn the user in the product notices :
“ The installation of this product can be done only with the authorization of the
public energy utility, because this product does not conform to the standard
IEC 61000-3-2 ”.
• If the phase shift of the 5th harmonic of the line current with Up1
- 180°
120 40 25 15 10 48 46
* I1 = reference fundamental current; In = harmonic current component.
This standard gives 3 cases for connection of the equipment and then 3 table
of THD limits :
The standard does not give limits for individual equipment, but for
individual customers.
IEEE 519 THDI limits at PCC function of short circuit ratio Isc/IL
Where:
ISC = Maximum short circuit current at the point of common connection(PCC).
IL = Maximum current drawn by the installation (fundamental) at PCC.
To have no trouble with the energy supplier, the customer generally consider
the all installation is connected to the public network (including
transformer).
The customer voice is often to follow the standard requirements even for
industrial network.
Telemecanique offer :
• Harmonic current available in the catalogues
• Different solutions for harmonic mitigation in accordance with the standards
• Tools for THDU evaluation of installation with drives.
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
• Both users and non linear load manufacturers have to limit them in order to
guaranty the quality of the energy of the network.
• Standards give recommendation in order to not pass the limit acceptable for
other equipment and the energy provider.
• The best economical and technical choice need an analyze of the installation
some tools more or less evolved allows to do it.
• Industrial user : the supplier can have influence with the end user
• As there is no drive standard for industrial network, the limits are a commitment
of best practice with eventually respect of guide lines .
Public Plant
network MV network LV
sensitive
loads
Harmcalc V4
Harmcalc V4
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
• In the DC bus
• Onto the main supply
30
30
THDI = 150% 25,94
THDI = 40%
25,16 25
25 22,88
20,77
Irms = 45A Irms = 28A -60%
20
20
I (A)
15,32
I (A)
15
15
12,36
9,38
10 10
6,77
4,51 5
5 3,20
1,54 1,21 1,80
0,87 0,74 0,49 0,35 0,30
0 0
1
11
13
15
17
19
21
23
25
1
11
13
15
17
19
21
23
25
Z R L
L I ZI THD Motor Losses
voltage
ZI
Z%
U sup
120%
100%
5
Harmonics levels
80%
7
11
60%
13
40%
17
19
20%
THD
0%
0,0% 1,0% 2,0% 3,0% 4,0% 5,0% 6,0%
Impedance Z%
20 20
I (A)
I (A)
15 15
9,38
10 10
6,65
5 3,20 5 4,14
1,80 2,23
0,87 0,74 0,49 1,73 1,39 1,12
0,35 0,30 0,99 0,81
0 0
15
1
7
3
11
17
21
23
13
19
25
11
17
13
15
19
21
23
25
1
9
5
Advantages Disadvantage
ATV11
ATV31
ATV71
ATV71
ATV71
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
The broad band filter able to lower harmonics on the all spectrum
• Can be put directly on the inputs of the variable speed drives
• Has to used if no global solution is possible
With simple choke THDI 48% With passive filter THDI 10%
16
10% f ilter
14
16% f ilter
ISC/IL <20
12
ISC/IL 20<50
10 ISC/IL 50<100
ISC/IL 100<1000
8 ISC/IL >1000
0
ISC/IL >1000
5
7
11 ISC/IL 50<100
13
17
19 ISC/IL <20
23
25
29
31 10% f ilter
35
37
41
10% filter
20 16% filter
15
THDI
10
0
45 55 65 78 90 100 125 150
Load pow er % 160
Advantages Disadvantage
• Line chokes protects the drive • Designed for full load capacity to
front end, limits voltage spikes obtain effective impedance.
and short circuit current Ineffective at no load
• Reliable
• Good EMC
• Working temperature :
– 5°C…40°C without derating
– 55°C with derating
• CE marking
• IP20
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
Then :
• 2 rectifier sections phase shifted by 30° result in 12-pulse row up H7 are slightly
reduced
Delta
H5 and H7 attenuated 6 pulses
rectifier M
Inverter
6 pulses
rectifier
Star
+L
Advantages Disadvantage
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
It's cost make it rather dedicated for very severe requirements (THD<5%)
The solution use an active rectifier bridge made with IGBT (in fact an
inverter) instead of the standard 6 diodes rectifier.
The rectifier is controlled in order to absorb a sinus current onto the
network (THDI <5%)
It has the advantage to be reversible and allows to feedback energy onto
the network when the PDS is generator (slow down or braking phase).
+L
Advantages Disadvantage
Active filter
Active filter
+ =
Active filter
Advantages Disadvantage
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
• A DC capacitance link provides voltage to the inverter between the peaks of the mains voltage
waveform.
• Current only flows from the mains into the DC link when the mains voltage exceeds that of the
capacitor. Current only flows when the mains voltage is near its peak, as shown.
• The larger the DC link capacitor, the shorter the period of current flow, and the higher the
peak current.
V Single or +
Three
Phase Power C C
Current
-
Rectifier D C Link Inverter
Advantages Disadvantage
I. Generalities
II. The standards
V. Passive filters
IX. Synthesis
Current distortion THDI >80% <48% <5%-16% <30% <5%-10% <5% <5%
Meet IEEE519 gen. app. no to be evaluated yes to be evaluated yes (18p) yes yes
Meet IEC 61000 3-12 no yes yes yes yes yes yes
Meet IEC 61000 3-2 no no no no no yes yes
Cost effective very good good <100kW very good >200kW If regen needed for installation
Price ratio /drive cost 100% 110%-120% 150%-200% 95% 200%-250% 250% 250%
Foot print ration/drive 100% 120% 200% 100% 350% 150%-200% 300%-500%
300
5
250 5-10
200
5-16
THDI
150 %
35-48
60-130 30-35
100
50
0
6 Pulse Drive C-Less DC chokes Passive Filters Multi-Pulse Active
AC chokes 12p, 18p Filters
Market trends
• In this case we suggest to use passive filter or a global passive or active solution
for the all installation
• Some competitors pushes active front end in standard VSD (ABB) but the
overcost is not justified if regenerative mode is not necessary (95% of the
cases).
• We prefer a targeted approach with a wide offer of options.
The VSD manufacturer must help and lead the customer in harmonic
mitigation
Thanks
for your attention
• The THDI with a choke is 45% for Rsce (Isc/Il) =120 and Isc max=22kA
• Calculate the minimum transformer power corresponding
• The maximum short circuit current of the drive is 22kA what is the maximum
transformer power possible