H-IM-CU
H-IM-CU
Compressor noisy or 1. Flooding of refrigerant into crankcase. 1. Check setting of expansion valves.
vibrating 2. Improper piping support on suction or liquid line. 2. Relocate, add or remove hangers.
3. Worn compressor. 3. Replace.
4. Scroll compressor rotation reversed. 4. Rewire for phase change.
Low discharge 1. Faulty condenser temperature regulation. 1. Check condenser control operation.
pressure 2. Suction shutoff valve partially closed. 2. Open valve.
3. Insufficient refrigerant in system. 3. Check for leaks. Repair and add charge.
4. Low suction pressure. 4. See corrective steps for low suction pressure.
5. Variable head pressure valve. 5. Check valve setting.
Low suction pressure 1. Lack of refrigerant. 1. Check for leaks. Repair and add charge.
2. Evaporator dirty or iced. 2. Clean.
3. Clogged liquid line filter drier. 3. Replace cartridge(s).
4. Clogged suction line or compressor suction gas strainers. 4. Clean strainers.
5. Expansion valve malfunctioning. 5. Check and reset for proper superheat.
6. Condensing temperature too low. 6. Check means for regulating condensing temperature.
7. Improper TXV. 7. Check for proper sizing.
Compressor loses oil 1. Lack of refrigerant. 1. Check for leaks and repair. Add refrigerant.
2. Excessive compression ring blow by. 2. Replace compressor.
3. Refrigerant flood back. 3. Maintain proper superheat at compressor.
4. Improper piping or traps. 4. Correct piping.
Compressor thermal 1. Operating beyond design conditions. 1. Add components to bring conditions within acceptable limits (i.e.,
protector switch 2. Discharge valve partially shut. CPR/EPR valves, additional condenser surface, liquid injection, etc.).
open 3. Blown valve plate gasket. 2. Open valve.
4. Dirty condenser coil. 3. Replace gasket.
5. Overcharged system. 4. Clean coil.
5. Reduce charge.
System does not 1. Low pressure switch not correctly adjusted. 1. Adjust low pressure switch (see page 24)
start reliably in 2. Low ambient kit not installed. 2. Install low ambient kit (low pressure switch settings can be lowered
cold weather. temporarily to allow system to start)
(Low pressure switch 3. Review " low suction pressure possible causes".
not closing 4. Call Heatcraft tech support.
28
Table 14. System Troubleshooting Chart (cont.)
System will not 1. Lack of refrigerant. 1. Check for leaks. Repair and add charge.
run reliably in 2. Head pressure builds too slowly to reach setpoint during 2. Install pressure fan cycling control to reduce the time required to
cold weather. cooling cycle. reach the head pressure valve setpoint. The control operation shall
(Head pressure does 3. Head pressure valve defective. not defeat the head pressure valve setpoint. See Table 15.
not reach minimum 3. Replace head pressure valve.
setting during
cooling cycle
Low compressor 1. Unit cooler has ice accumulation 1. Defrost unit cooler completely.
superheat observed 2. Superheat low when measured at unit cooler. 2. Raise superheat at unit cooler by 5°F (3°C).
at compressor in 3. Suction accumulator not installed. 3. Install suction accumulator
cold weather.
Slow initial room 1. Expansion valve capacity less than pull-down 1. Temporarily reduce the condenser coil face area to elevate the
pull-down in cold load. discharge pressure to equivalent 105°F condensing temperature
weather. 2. Expansion valve not sized for minimum head pressure during pull-down. (Remove blockage after pull-down).
and the installed distributor nozzle. 2. Replace expansion valve with correct size.
Head Pressure Valve Setpoint Control cut-in setting psi Control cut-out setting psi
150 psi 175 140
100 psi 125 90
NOTE: Use pressure fan cycling for fan nearest compressor. Use ambient fan cycling (see Table 1) for other fans
Replacement Parts by
Commercial Refrigeration Parts
InterLink™ Comercial Refrigeration Parts is your link to a complete line of dependable and certified commercial refrigeration parts, accessories
and innovative electronic controls for all Heatcraft Refrigeration Products (HRP) brands - including Bohn, Larkin, Climate Control and Chandler.
At InterLink, we provide our wholesalers with a comprehensive selection of product solutions and innovative technologies for the installed
customer base. And every product is built to ensure the same high performance standards with which all HRP brands are built — backed by a
dedicated team to serve every customer need, delivering at the best lead times in the industry.
Replacement parts should be obtained from your local InterLink wholesaler. Replacement parts, which are covered under the terms of the
warranty statement on page 2 of this manual, will be reimbursed for total part cost only. The original invoice from the parts supplier must
accompany all warranty claims for replacement part reimbursement. Heatcraft Refrigeration Products reserves the right to adjust the
compensation amount paid on any parts submitted for warranty reimbursement when a parts supplier's original invoice is not provided with a
claim. For more information, call 800-686-7278 or visit www.interlinkparts.com.
29