intelinano-nt-plus-2.4.1 new features list
intelinano-nt-plus-2.4.1 new features list
Plus
Firmware version for
InteliNanoNT Plus HW 2.0
SW version 2.4.1
1 General information 2
2 Changes in the version 2.4.1 3
3 Changes in the version 2.4.0 4
4 Changes in the version 2.3.0 5
5 Changes in the version 2.2.1 7
6 Changes in the version 2.2.0 8
7 Changes in the version 2.1.0 9
8 Changes in the version 2.0.1 10
9 Changes in the version 2.0.0 11
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
Nominal Cooling is performed at Nominal speed and generator protections are active.
Idle Cooling is performed at Idle speed and generator protections are not active.
Note: When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note: Binary output IDLE/NOMINAL must be configured and connected to engine speed governor.
Engine Idle speed must be adjusted on speed governor.
Idle/Nominal (O18)
Description
This output is used for switching between Idle and Nominal speed of the engine during the Startup and
Cooling phase, if this feature (input) is available on the particular engine. The output is opened when the
engine is required to run at Idle speed and it is closed when the engine is required to run at Nominal
speed.
In the case of some EFI engines, the idle/nominal switching is performed over the communication bus.
Cranking Attempts
Setpoint group Basic settings Related FW 2.2.0
Range [units] Yes / No [-]
Default value Yes Related applications PLUS
Step -
Description
Use this setpoint to suppress showing any current related information on controller screens when no CT is
used.
When CT Connected setpoint is set to No value, following steps are taken:
CT symbol is not shown on main screen.
Value of apparent power is not shown on main screen.
Values of current and apparent power are not shown on generator screen.
Nominal Current (B09) setpoint is hidden.
CT Ratio (B10) setpoint is hidden.
Generator Short Circuit Shutdown (G05) setpoint is hidden.
Generator Short Circuit Delay (G06) setpoint is hidden.
Note: No changes to the protections subsystem are introduced. So, it is strongly recommended to not
connect CT when CT Connected setpoint is set to No to prevent unexpected controller behavior.
Cranking Attempts
Engine parameters and
Setpoint group Related FW 2.1.0
protections
Range [units] 1 ... 10 [-]
Default value 6 Related applications PLUS
Step 1
Description
This setpoint defines maximal number of cranking attempts.
Starting RPM
Engine parameters and
Setpoint group Related FW 2.0.1
protections
Range [units] 5 ... 60 [%]
Default value 25 Related applications PLUS
Step 1%
Description
When starting RPM are reached controller stops cranking. (Starter is disengaged.)
8.2 Repairs
Glow Plugs
LBO GLOW PLUGS now works according to the description in Reference Guide.
User Curves
A few points definitions have been corrected in curves VDO 120-300 °F, Datcon Low °F and Datcon
Level %.
Event log
A problem with display of confirmed External Shutdown 2 and External Shutdown 3 on event log has
been solved.
Auto button behavior
A problem with repetitive changeover between "Auto mode" and "Manual mode" when button "Auto" is
long pressed has been solved.
Archives (*.ain)
NT
For InteliNano Plus
IN-NT-PLUS-2.4.1.1.ain
User texts(*.xml)
NT
For InteliNano Plus
NE-UserTexts.xml
Note: All aforementioned files are part of the latest InteliNano Installation Suite.