The 4010ES Fire Control Units are UL, ULC, and CSFM listed addressable fire detection systems designed for mid-range applications, featuring compatibility with Simplex ES Net and 4120 networks. They support up to 1000 addressable IDNet points, enhanced power delivery, and modular design for various operational needs, including TrueAlarm sensors and IDNAC notification appliances. The units include advanced diagnostics, programmable functions, and options for remote communication and control, ensuring effective fire alarm management and system reliability.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views18 pages

Ft-Panel de Incendio-4010-9721

The 4010ES Fire Control Units are UL, ULC, and CSFM listed addressable fire detection systems designed for mid-range applications, featuring compatibility with Simplex ES Net and 4120 networks. They support up to 1000 addressable IDNet points, enhanced power delivery, and modular design for various operational needs, including TrueAlarm sensors and IDNAC notification appliances. The units include advanced diagnostics, programmable functions, and options for remote communication and control, ensuring effective fire alarm management and system reliability.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

4010ES Fire Control Units

UL, ULC, CSFM Listed; FM Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories
Approved*

Features
Compatible with Simplex ES Net and 4120 fire alarm networks

Basic system includes:


• Models available with Color ES Touch Screen Display or Monochrome 2
line x 40 Character Display
• Capacity for up to 1000 addressable IDNet points, up to 127 VESDA
Air Aspiration Systems interface points and up to 254 addressable
notification appliances with up to 2000 points of Annunciation; and up
to 20 internal and external card addresses
• CPU assembly includes dedicated compact flash memory for on-site Figure 1: 2-Bay Cabinet with 2x40 LCD Monochrome Display
system information storage and convenient Ethernet service port
access

Includes an Enhanced System Supply (ESS) that provides power


and battery charging (6 A output):
• Dual 3 A on-board IDNAC SLCs (signaling line circuit) provide enhanced
power delivery to addressable notification appliances
• With an IDNAC SLC, a constant 29 VDC source voltage is maintained Figure 2: 1-Bay Cabinet with 2x40 LCD
during alarm, even during battery operation, allowing strobes to Monochrome Display and LED Annunciation
operate at higher voltage with lower current and ensuring a consistent
current draw and voltage drop margin under both primary power and
secondary battery standby
• Efficiencies include lower strobe currents, wiring distances up to two
to three times farther than with conventional notification, support for
more appliances per IDNAC SLC, ability to use smaller gauge wiring,
all providing installation and maintenance savings with high assurance
that appliances that operate during normal system testing will operate Figure 3: 1-Bay Cabinet with 2x40 LCD Monochrome Display
during worst case alarm conditions
Optional ESS mounted modules, door mounted modules, and
• IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert other options include:
addressable notification appliances, and remote 4009 IDNAC
• City Connect (with or without disconnect switches)
Repeaters to extend power and wiring distance even farther and
extends supervisory capacity by up to 139 additional unit loads or 3 A • Alarm Relay Module
• Addressable initiating device control is provided by on-board IDNet • Battery brackets for seismic area protection
2 dual loop SLCs that provide two electrically isolated channels that Optional block space modules include:
support TrueAlarm analog sensors and IDNet communications
monitoring and control devices with an electrically isolated output • Fire Alarm Network Interface Card for ES Net or 4120
channel allowing use with either shielded or unshielded, twisted or • Peer-to-Peer Network Communications supports either Class B or
untwisted single pair wiring; and providing dual short circuit isolating Class X operation
output loops • Modem or TSP/IP Physical Bridge Network Modules, Class B or Class X
• Battery charger for up to 110 Ah batteries (UL) or up to 50 Ah batteries operation
(ULC) (33 Ah max in control unit cabinet for 1 Bay Systems, 50Ah for 2 • Ethernet connectivity options include ES Net Network Interface Card,
Bay systems) Building Network Interface Card (BNIC), SafeLINC Internet Interface,
• 2 A programmable function auxiliary output and BACpac Ethernet Portal
• Remote annunciator module support via RUI communications port, • Dual Class A IDNAC Isolator (DCAI)
Class A or B operation • Dual RS-232 Module (for printer or third party interface)
• 48 LED panel mount annunciation provides 40 Red and 8 Yellow • VESDA Air Aspiration High Level Interface
pluggable LEDs(select models, meets ULC requirements), optional LED • Serial DACT
kits are available to change individual LED color to Green or Blue to
• 8-Point Zone/Relay Module
meet specific site requirements
• 4-Point Auxiliary Relay Module with Feedback
• Additional IDNet and MX Loop addressable channels

Compatible with Simplex remotely located


• 4098-9757 QuickConnect2 and legacy 4098-9710 QuickConnect
TrueAlarm smoke sensors
• 4003EC Small Voice Control Units
• 4009 IDNet NAC Extenders and IDNAC Repeaters
• 4081 Series, 110 Ah Battery Chargers
• 4100-7400 Series Graphic Annunciators

* These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0383 for allowable
values and/or conditions concerning material presented in this document. At the time of publication only UL and ULC listings are applicable to ES Net network products. Additional listings may be
applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.

S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

• 4190 Series Fiber Modems and Physical Bridges Other 4010ES Options:
• 4606-9102 Remote LCD Annunciator, 4100-9400 Series Remote ES • The 4010ES City Connect module or the optional Alarm Relay module
Touch Screen Displays, 4100-9400 Series Remote InfoAlarm Command mount directly to the ESS. These options are mutually exclusive.
Centers, and 4602 Series Status Command Units (SCU) and Remote • The battery compartment is located in the bottom of the 4010ES
Command Units (RCU) Annunciators cabinet. The cabinet allows for up to 33 Ah battery capacity for 1 bay
• IP communicator compatibility systems, and 50 Ah for 2 bay systems. 50 Ah batteries also require the
use of 4100-0650 battery shelf.
4010ES Agency listings
• UL 864 - Control Units, System (UOJZ); Control Unit Accessories, Software Feature Summary
System, Fire Alarm (UOXX); Control Units, Releasing Device Service • TrueAlarm individual analog sensing with front panel information and
(SYZV); Smoke Control System Equipment (UUKL) selection access
• UL 1076 - Proprietary Alarm Units (APOU) • "Dirty" TrueAlarm sensor maintenance alerts, service and status
• UL 1730 - Smoke Detector Monitors and Accessories (UULH) reports including "almost dirty"
• UL 2017 - Emergency Alarm System Control Units, CO detection (FSZI); • TrueAlarm magnet test indication appears as distinct "test abnormal"
Process Equipment Management (QVAX) message on display when in test mode
• ULC-S527 - Control Units, System, Fire Alarm (UOJZC); Control Unit • TrueAlarm sensor peak value performance report
Accessories, System, Fire Alarm (UOXXC); Control Units, Releasing • "Install Mode" allows grouping of multiple troubles for uninstalled
Device Service (SYZVC); Smoke Control System Equipment (UUKLC) modules and devices into a single trouble condition (typical with future
• ULC-S559 - Central Station Fire Alarm System Units (DAYRC) phased expansion); with future equipment and devices grouped into
• ULC/ORD-C1076 - Proprietary Burglar Alarm System Units (APOUC) a single trouble, operators can more clearly identify events from the
commissioned and occupied areas
• ULC/ORD-C100 - Smoke Control System Equipment, UUKLC
• Module level ground fault searching assists installation and service by
locating and isolating modules with grounded wiring
Introduction
• "Recurring Trouble Filtering" allows the control unit to recognize,
4010ES Series Fire Detection and Control Units process, and log recurring intermittent troubles such as external wiring
4010ES Series Fire Detection and Control Units provide leading edge ground faults, but only sends a single outbound system trouble to
installation, operator, and service features for customer applications avoid nuisance communications
in the mid-range addressable fire alarm systems market. An onboard • WALKTEST silent or audible system test performs an automatic self-
Ethernet port provides fast external system communications to expedite resetting test cycle
installation and service activity. Dedicated compact flash memory
archiving provides secure on-site system information storage of IDNet Addressable Device Control
electronic job configuration files.
The 4010ES with ESS provides an IDNet 2 addressable device SLC with
Modular design two isolated loops that supervise wiring connections and the individual
A variety of functional modules are available to meet specific system device communications status on the SLC. With 2-wire IDNet 2 SLCs,
requirements. Selections allow control units to be configured for either initiation, monitoring, and control devices such as manual fire alarm
Stand-Alone or Networked fire control operation. stations, TrueAlarm sensors, control relays, and sprinkler waterflow
switches can communicate their identity and status and receive fire
alarm system control. Additional addressable interface modules include
Mechanical Description circuit isolators, conventional IDC zone adapters, and interface to other
• Mounting box provides convenient stud markers for drywall thickness system circuits such as fans, dampers, and elevator controls.
and nail-hole knockouts for quicker mounting
• Smooth box surfaces are provided for locally cutting conduit entrance IDNet 2 Addressable Device Operation
holes exactly where required Each addressable device on the IDNet communication channel
• The hinged User Interface panel easily opens for internal access is continuously interrogated for status condition such as: normal,
• Modules are power-limited (except as noted) off-normal, alarm, supervisory, or trouble. Both Class B and Class A
• Doors include tempered glass inserts, boxes and doors are available in operation is available. Sophisticated poll and response communication
platinum or red techniques ensure supervision integrity and allow for "T-tapping" of
the circuits for Class B operation. Devices with LEDs pulse the LED to
• Box and door/retainer assemblies are included with Basic Control Unit
indicate receipt of a communications poll and can be turned on steady
assemblies
from the control unit. With addressable devices, the location and status
• Cabinet assemblies are rated NEMA 1 and IP 30 of the connected device is monitored, logged, and displayed on the
• Cabinet assembly design is seismic tested and is certified to IBC and operator interface LCD with each device having its own 40 character
CBC standards as well as to ASCE 7 categories A through F, requires custom label for precise identification.
battery brackets as detailed on data sheet S2081-0019
TrueAlarm Addressable Sensor Operation
Control Unit Hardware Addressable initiating device communications include operation
• The Master Controller and Enhanced System Supply (ESS) are mounted of TrueAlarm smoke and temperature sensors. Smoke sensors transmit
in the upper section of the 4010ES cabinet (refer to Cabinet One and an output value based on their smoke chamber condition and the CPU
Two Bay Loading Reference) maintains a current value, peak value, and an average value for each
• 4010ES Block Space Option Cards mount to the left of the 4010ES sensor. Status is determined by comparing the current sensor value to
ESS. In 2-bay cabinets block space option cards also mount below the its average value. Tracking this average value as a continuously shifting
4010ES ESS. reference point filters out environmental factors that cause shifts in
sensitivity.

Page 2 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Table 1: TrueAlarm Addressable Sensor Reference Table 2: IDNet 2 and IDNet 2+2 SLC Wiring Specifications
Specification Rating
Maximum capacitance between
1 µF
IDNet channels
Figure 4: TrueAlarm Figure 5: TrueAlarm Photo/ 0.8 mA supv., 1 mA alarm; 2 mA
Loading per device
Photo Sensor with Base Heat Sensor in CO Base per activated device LED
Shielded or unshielded, twisted or
Programmable sensitivity of each sensor can be selected at the Wire type and connections
untwisted wire*
control unit for different levels of smoke obscuration (shown directly in
Connections Terminal blocks for 18 to 12 AWG
percent) or for specific heat detection levels. To evaluate whether the
sensitivity should be revised, the peak value is stored in memory and can Note: Compatibility includes: IDNet communicating devices and
be easily read (or downloaded as a report) and compared to the alarm TrueAlarm sensors including QuickConnect and QuickConnect2 sensors.
threshold directly in percent. See data sheet S4090-0011 for additional reference.
CO sensor bases combine an electrolytic CO sensing module with a
Note: * Some applications may require shielded wiring. Review your
TrueAlarm analog sensor to provide a single multiple sensing assembly
system with your local Simplex product supplier.
using one system address. The CO sensor can be enabled/disabled, and
can be used in LED/Switch modes and custom control. Refer to data
sheet S4098-0052 for details.
TrueAlarm heat sensors can be selected for fixed temperature
detection, with or without rate-of-rise detection. Utility temperature
sensing is also available, typically to provide freeze warnings or alert to
HVAC system problems. Readings can selected as either Fahrenheit or
Celsius.

TrueSense Early Fire Detection


Multi-sensor 4098-9754 provides photoelectric and heat sensor data
using a single 4010ES IDNet address. The control unit evaluates smoke
activity, heat activity, and their combination, to provide TrueSense
early detection. For more details on this operation, refer to data sheet
S4098-0024 .

Diagnostics and Default Device Type


Sensor Status
TrueAlarm operation allows the control unit to automatically indicate
when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72
requirement for a test of the sensitivity range of the sensors is fulfilled
by the ability of TrueAlarm operation to maintain the sensitivity level of
each sensor. CO Sensors track their 10 year active life status providing
indicators to assist with service planning. Indicators occur at: 1 year, 6
months, and end of life.

Modular TrueAlarm sensors


Modular TrueAlarm sensors use the same base and different sensor
types smoke or heat sensor and can be easily interchanged to
meet specific location requirements. This allows intentional sensor
substitution during building construction when conditions are
temporarily dusty. Instead of covering smoke sensors causing them
to be disabled, heat sensors may be installed without reprogramming
the control unit. The control unit will indicate an incorrect sensor type,
but the heat sensor will operate at a default sensitivity to provide heat
detection for building protection at that location.

IDNet Device Wiring Reference


IDNet 2 SLCs support up to 250 addressable monitor and control points
intermixed on the same pair of wires. The ESS IDNet 2 provides two
electrically isolated SLCs, and IDNet 2+2 provides four isolated SLCs that
are isolated from other system reference voltages to reduce common
mode noise interaction with adjacent system wiring.
Table 2: IDNet 2 and IDNet 2+2 SLC Wiring Specifications
Specification Rating
Maximum Distance 0 to 125 4000 ft (1219 m); 50 ohms
from control unit per
126-250 2500 ft (762 m); 35 ohms
device load
Total wire length allowed with "T"
Up to 12,500 ft (3.8 km); 0.60 µF
taps for Class B wiring

Page 3 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

IDNAC SLC Control of TrueAlert and TrueAlert ES appliance within the selected VNAC group will briefly operate and then
Addressable Notification report its Self-Test status to the control unit, all within several seconds.
Silent Self-Test can be selected to test only visible appliance if desired.
Addressable notification appliance communications The control unit is in a trouble condition during testing and in the event
Addressable notification appliance communications include operation of of an alarm, Self-Test is automatically terminated. Additionally, Automatic
TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, Self-Test can be scheduled to occur at a convenient time on a regular
horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible basis.
(S/V) notification appliances. (S/V appliances require separate speaker Automatic Self-Test results are communicated to the control unit with
wiring.) IDNAC SLC addressable communications allow each horn and a time and date stamp and are stored in memory. Results are viewable
strobe to be individually controlled using a single two-wire circuit, at the front panel display and printed reports can be generated from the
confirms the wiring connections to the individual notification appliance's control unit service port.
electronic circuit, and confirms communications between each appliance Individual Self-Test is selected from the control unit when individual
and the fire alarm control unit. Addressable communications increases appliances need to be observed to operate. Each appliance in the
supervision integrity versus conventional notification systems by selected VNAC group will turn on its LED until individually activated by
providing supervision beyond the circuit wiring to each individual applying a magnet. After performing the individual test, the appliance
appliance and by constantly verifying the ability of each appliance to LED turns off to indicate completion. Results are recorded the same as
communicate with the control unit. during the automatic test.
Individual Appliance Status and Settings
The fire alarm control unit monitors and records each addressable IDNAC SLC Hardware Reference
notification appliance status, type of appliance, and its configured The Enhanced System Supply provides two, 3 A IDNAC SLCs for control
appliance settings. A fault in any individual appliance automatically and power to TrueAlert ES and TrueAlert addressable notification
reports a trouble condition to the control unit. appliances. Both power supplies incorporate an efficient switching
design that provides a regulated output of 29 VDC, even during battery
Virtual NACs provide control convenience operation. With 29 VDC minimum output at the control unit, addressable
For control convenience, IDNAC notification appliances can be grouped notification SLCs can support wiring distances 2 to 3 times farther than
into Virtual NACS (VNACs) for group control, grouping that can be made available with conventional notification, or support more appliances
across SLCs, not defined by their wiring connection. per SLC, or work with smaller gauge wiring, or combinations of these
benefits. The result is installation and maintenance savings with high
Panel Control Convenience
assurance that appliances that operate during normal system testing will
Applicable operation settings for each appliance can be programmed operate during worst case alarm conditions.
without having to replace appliances or remove them from the wall or
ceiling. An appliance's VNAC notification zone can be easily changed
IDNAC SLC Appliance Wiring Reference
through programming without having to add additional circuits, conduit,
and wiring. Audible and visible appliances for non-fire emergency IDNAC SLC Capacity: Up to 127 addresses and up to 139 unit loads
communications notification can be programmed to operate separately (appliances are typically one unit load, devices such as Isolators may
on the same pair of wires as the fire alarm notification appliances. The require more than one load, refer to individual device data sheet for
result is lower installation, retrofit, and overall life-cycle cost of ownership specific information)
compared with traditional conventional notification systems Table 3: IDNAC SLC Appliance Wiring Reference

Installation, Retrofit, and Life-Cycle Cost Benefits Recommended Wire Type UTP, unshielded twisted pair
With each addressable appliance capable of being controlled separately Maximum wire length allowed with 10,000 ft (3048 m)
on the same two-wire IDNAC SLC, installation time and expense for “T-Taps” for Class B wiring, per SLC
both retrofit and new construction can be significantly reduced. When Maximum wire length per SLC to 4000 ft (1219 m)
Class B wiring is used, wiring can be "T-tapped" allowing more savings any appliance
in distance, wire, conduit (size and utilization), and overall installation Appliance Supervisory Current 1 unit load = 0.8 mA per appliance
efficiency. Wiring Connections Terminals for 20 to 12 AWG (0.52
mm² to 3.31 mm²)
Location Information, Diagnostics and Troubleshooting
Each addressable notification appliance has its own 40 character
custom label to identify the location of the appliance and to aid in
troubleshooting fault conditions. In conventional notification systems,
conventional appliances are not capable of communicating with the
control unit. Fault reporting on a conventional system is limited to the
circuit wiring and the entire area (zone) covered by appliances on the
notification appliance circuit (NAC) making it much more difficult and
costly to locate and correct the source of a problem. Using the TrueAlert
magnet test allows each appliance to individually identify its candela
setting and address and to briefly operate if desired, and using the
TrueAlert ES Appliance Self-Test feature provides detailed performance
verification per appliance.

TrueAlert ES Appliance Self-Test Operation


On-Board Test Sensors
TrueAlert ES appliances are equipped with on-board sensors to detect
strobe and/or horn output allowing efficient and unobtrusive Self-
Testing. When Automatic Self-Test is initiated from the control unit, each

Page 4 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Color ES Touch Screen Display


The Color ES Touch Screen Display interface offers intuitive operation similar to a tablet or smart phone. With a larger area format versus an individual
text line display, more information is available at a glance, and minimal key presses are needed to access detailed information.

Figure 6: ES Touch Screen Display Operator Interface

Features
ES Touch Screen Displays provide customized operating experience
• Event activity display choices include: First 8 Events; or First 7 Events with emphasis on Most Recent; or First 6 Events with emphasis on First and
Most Recent (individually selectable for each event type)
• System reports are easily viewable; logs can be read with minimal scrolling
• Up to two languages are available per system, easily selected by programmable key press
• Information sent to Remote ES Touch Screen Displays can be vectored by point or zone
• Both Hard and Soft keys available for critical functions: Event Acknowledge, Alarm Silence, and Reset Functions
• Resistive touchscreen technology allows operation with or without gloves
• Seven programmable RGY LEDs available for user-defined display status (up to 2 status conditions per LED)
• Seven programmable Soft keys available for user-defined control or maintenance functions
• PRI2 Soft key label can be changed to CO to annunciate Carbon Monoxide detection status
• ES Touch Screen Display can be programmed to report individual points or groups of points as a single zone
• Supports ability to display a custom watermark background file of a company logo or other desired display content

Page 5 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Display properties
• 8 inch (203 mm) diagonal, 800 x 600 resolution color touch screen display capable of annunciating up to 8 active events without scrolling
• Bright white LED backlighting provides efficient and long lasting illumination; backlight is dim in quiescent state, automatically switches to full power
on touch or on event activity in system.

Description
ES Touch Screen Displays for 4100ES fire alarm systems provide a large display with extended information content, dual language support including
UTF-8 character languages, and an intuitive control key interface per the following:
• Up to 10 ES Touch Screen Displays are supported per 4100ES control panel; able to allow one ES Touch Screen Display to take-control and to
designate access levels for interfaces not in-control; programmable LEDs can be assigned to in-control status indications
• Menu-driven format conveniently prompts operators for the next action required
• Direct point callup displays individual points alphabetically and then homes in on the logical choice as more point information is entered
• Event categories are color coded for quick visual representation; Red for Alarm and Priority 2 Events; Yellow for Supervisory and Trouble events
• Date formats are either MM/DD/YY or DD/MM/YY
• Time formats are either 24 hour or 12 hour with AM/PM
• System Normal screen supports a color background (watermark) for company name, company logo, or other desired display content

Page 6 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Example Display Screens

Figure 8: Main Menu


Figure 7: First and Most Recent Alarm Display

Figure 9: First Eight Active Trouble Events List Figure 10: Direct Point Callup

Figure 11: Alarm History Log Figure 12: Detailed Point Status
Screen for TrueAlert ES Appliance

Page 7 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Specifications
Table 4: General ES Touch Screen Display Specifications
Specification Rating
Resolution 800 x 600 Pixels (RGB)
Size / Type 8 inch (203 mm) Diagonal / Color Touch Screen
Touch Screen Technology Resistive
Event Display Up to 8 Events without scrolling
Normal Screen Custom Watermark File Format 680 x 484 Pixels: BMP, JPG, TIFF, GIF or PNG file format
Environmental Operating Temperature: 32°F to 120°F (0°C to 49°C)
Operating Humidity: Up to 93% RH, non-condensing @ 90°F (32°C)
maximum

© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4010-0012 Rev. 16 08/2020
Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Operator Interface with Monochrome 2x40 Display Features


• Convenient and extensive operator information is provided using a logical, menu-driven display:
• Multiple automatic and manual diagnostics for maintenance reduction
• Convenient PC programmer label editing
• Password access control
• Alarm and Trouble History Logs (up to 2000 total events) are available for viewing on the LCD screen, printing on a connected printer, or downloading
to a service computer

Figure 13: Operator Interface Features

Master Controller (CPU)


• The 4010ES Master Controller includes dedicated compact flash Mass Storage memory for on-site system information storage and convenient
Ethernet service port access
• Convenient front panel accessed Ethernet port for quick and easy download of site-specific programming and firmware enhancements. Firmware
enhancements are made via software downloads to the on-board flash memory
• Every downloaded job is automatically stored to Compact flash without overwriting earlier versions providing a means for recovering previous
configurations

Page 9 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

• Downtime is reduced because the system stays running during download


• Modifications can be uploaded as well as downloaded for greater service flexibility
• Mass Storage allows job specific files to be stored in the control unit such as test and inspection reports, record drawings, specifications, and more
• RUI (Remote Unit Interface) communications port supports either Class B or Class A operation for remote annunciation equipment

Basic Control Unit Description


4010ES Control Units with ESS include:
• An Operator Interface, Master Controller with Compact Flash, IDNet 2 addressable device SLCs configurable with short circuit isolating loop outputs
for Class B or Class A operation, and 6 A Enhanced System Supply (ESS)
• RUI Class B or Class A communications port for remote annunciation devices
• Support for up to 20 internal and external card addresses
• Other standard features may be provided depending on model (see model selection below for additional details on specific models)
• Cabinet and door

6 A Enhanced System Supply details:


• Two, 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances; Class A operation is available using the 4010-9930 Dual Class A IDNAC
Isolator (DCAI) module
• Up to 2 A of auxiliary power
• 110 Ah (UL)/50 Ah (ULC) battery charger (33 Ah max in 1 bay cabinet, 50 Ah max with 4100-0650 battery shelf in two bay control cabinet)
• Low Battery Voltage Cutout is selectable when required (required for ULC listing applications)
• 2 A Auxiliary Output (AUX/SNAC) can be selected either as s resettable auxiliary power of 2 A @ 24 VDC, or selected to be a simple NAC (SNAC) for
non synchronous 24 VDC reverse polarity NAC operation

8-Point Zone/Relay Module Details


• Select as IDC or Relay; configure up to eight Class B IDCs, or up to four Class A IDCs; or up to eight Relay outputs rated 2 A resistive @ 30 VDC (N.O.
or N.C.); or combinations of IDCs and Relays; each zone is separately configurable as an IDC or Relay output
• IDC Support: each IDC supports up to 30, two-wire devices. Zone relay modules may be powered directly from the control unit power supply or
through the optional 25 VDC regulator module where required for 2- wire detector compatibility (refer to 2-Wire Detector Compatibility document
579-832 for additional details).
• IDC EOL resistor values are selectable as: 3.3 kΩ, 2 kΩ, 2.2 kΩ, 3.4 kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ, 6.34/6.8 kΩ, and 3.6 kΩ + 1.1 kΩ; see
instructions for more details

Basic Control Unit Model Selection – 1 Bay Control Unit


Table 5: 1 Bay Control Unit Model Selection
Model* Color Language & Listings Features Supv. Alarm Available
Voltage Current Current Option
Blocks
4010-9601 Red English UL, CSFM, FM Basic 1- Bay Control Unit with 336 mA 540 mA Three
4010-9602 Platinum 120 VAC 2x40 LCD Operator Interface, 4 in. x 5 in.
4010-9602-BA 6 A ESS/battery charger, (1) blocks
Two-loop Isolated IDNet 2
4010-9701 Red English UL, FM
Communications Channel, Class
4010-9702 Platinum 220 to 240 A or Class B, with support for
VAC up to 250 addressable IDNet
points; and two, 3 A, Class B,
IDNAC SLCs with support for up
to 254 addressable notification
appliances
4010-9603 Red English UL, ULC, CSFM, FM Same features as above with 48 356 mA 605 mA
4010-9604 Platinum 120 VAC LED annunciation; alarm current
includes 24 annunciator LEDs
activated

Note: Model numbers ending in BA are assembled in the USA.

Page 10 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Current Notes:
1. Basic control unit current does not subtract from the 6 A output rating.
2. Supervisory and alarm current specifications are for determining battery standby requirements.
3. Current specifications include an active RUI channel.
4. IDNet channel device current is not included, see Block Space Option Card Selection for details.
5. IDNAC channel notification appliance current is not included, calculate separately per connected devices.

Basic Control Unit Model Selection - 2 Bay Control Units


Note: Supervisory and Alarm current specifications are for determining battery standby requirements. Current specifications include an active RUI
channel. Models with IDNet channels include 20 IDNet device LEDs activated in alarm per channel.
Table 6: 2 Bay Control Units Model Selection
Language & Supv. Alarm Available
Model Color Listings Features
Voltage Current Current Option Blocks
4010-9621 Basic control unit with 2x40 LCD
Red
4010-9621BA English, UL, CSFM, Operator Interface, 6 A ESS/battery
4010-9622 120 VAC FM charger, (1) Two-loop Isolated IDNet
Platinum 2 Communications Channel and
4010-9622BA
4010-9721 (1) Four-loop Isolated IDNet 2+2
Red Communications Module, Class A or 411 mA 655 mA
4010-9721BA
Class B, with support for up to 500
English, 220 to addressable IDNet points; and two, 3
UL, FM
4010-9722 240 VAC
Platinum A, Class B, IDNAC SLCs with support
4010-9722BA for up to 254 addressable notification
appliances
4010-9609 Red UL, ULC Same features as above with 48 LED
CSFM, annunciation; alarm current includes 431 mA 720 mA
4010-9610 Platinum
FM 24 annunciator LEDs activated
English, 120
4010-9623 VAC Basic control unit with InfoAlarm
Red
4010-9623BA UL, CSFM, Operator Interface, 6 A ESS/battery
4010-9624 FM charger, (1) Two-loop Isolated IDNet
Platinum 2 Communications Channel and
4010-9624BA
4010-9711 (1) Four-loop Isolated IDNet 2+2 493 mA 721 mA
Red Communications Module, and two, 3
4010-9711BA
English, 220 to A, Class B, IDNAC SLCs with support
UL, FM
4010-9712 240 VAC for up to 254 addressable notification Ten
Platinum
4010-9712BA appliances 4 in. x 5 in.
Basic control unit with ES Touch blocks
120 VAC Screen Operator Interface, 6 A ESS/
(multiple battery charger, (1) Two-loop Isolated
languages IDNet 2 Communications Channel
available, and (1) Four-loop Isolated IDNet 2+2
4010-9633 Red contact your UL/ULC Communications Module, Class A or 506 mA 771 mA
local Simplex Class B, with support for up to 500
product addressable IDNet points; and two, 3
supplier for A, Class B, IDNAC SLCs with support
details) for up to 254 addressable notification
appliances
Basic control unit with ES Touch
Screen Operator Interface, 6 A ESS/
240 VAC
battery charger, (1) Two-loop Isolated
(multiple
IDNet 2 Communications Channel
languages
and (1) Four-loop Isolated IDNet 2+2
available,
4010-9731 Red UL, ULC Communications Module, Class A or 506 mA 771 mA
contact your
Class B, with support for up to 500
local Simplex
addressable IDNet points; and two, 3
dealer for
A, Class B, IDNAC SLCs with support
details
for up to 254 addressable notification
appliances

Note: Model numbers ending in BA are assembled in the USA.

Current Notes:
1. Basic control unit current does not subtract from the 6 A output rating.
2. Supervisory and alarm current specifications are for determining battery standby requirements.

Page 11 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

3. Current specifications include an active RUI channel.


4. IDNet channel device current is not included, see Block Space Option Card Selection for details.
5. IDNAC channel notification appliance current is not included. Control unit current assumes 20 LEDs activated in alarm on each IDNet channel.

Addressable Device Load Specifications for Battery Standby


Supervisory
Addressable Channel Loading Reference Device Load Alarm Current
Current
IDNet 2 and IDNet 2+2 Communications Channel 1 mA per device in alarm; 2 mA per
for every 50 Devices 40 mA
Output activated device LED
IDNAC Communications Channel Output for every 50 Appliances 40 mA Calculate per selected appliances

Page 12 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Block Space Option Card Selection


Maximum block option module quantities may require 2 bay cabinets, 1 bay cabinets are limited to three option block spaces total. See Cabinet One
and Two Bay Loading Reference for option module availability. Supervisory and Alarm current specifications are for determining battery standby
requirements.
Table 7: Single Block Option Modules
Model Features Supervisory Current Alarm Current Option Block Usage
Serial DACT, includes two 2080-9047 cables, 14 ft (4.3 m) 1 block (must mount
4010-9912 30 mA 40 mA
long, RJ45 plug and spade lugs in top bay, block D)
4010-9908 4 Point Aux Relay Module 15 mA 60 mA 1 block (11 maximum)
Voltage Regulator Module, 22.8 to 26.4 VDC (25 VDC
3 A maximum with 2.5 4.9 A maximum with 1 block
4010-9916 nominal); isolated and resettable output; includes earth
A load 4 A load (1 maximum)
detection circuit and trouble relay for status monitoring
4010-9918 Dual RS-232 Module 60 mA 1 block (3 maximum)
Dual Class A IDNAC Isolator (DCAI); converts a single
Class B IDNAC SLC input to two Class A or two Class B
SLC outputs; provides short circuit isolation between
each Class A or B output circuit; requires up to two
IDNAC addresses; the total current remains controlled by A 1 block, (4
the Class B input source SLC at 3 A maximum; select up maximum, 2 per
4010-9930 to two per IDNAC SLC; each isolated loop supports up to 12.7 mA 25 mA IDNAC channel), 1 can
30 device addresses be mounted on the
ESS
Note: up to 30 additional device addresses may be
installed between each 4905-9929 TrueAlert Addressable
Isolator+ Module, not to exceed the maximum address
and unit loading specifications for the IDNAC channel
BACpac Ethernet Portal Module; requires 4010-9918
4010-9915 123 mA 123 mA 1 block (3 maximum)
RS-232 Module (no address required)
4010-9901 VESDA HLI 60 mA 1 block (1 maximum)
4 DPDT Auxiliary Relays with Feedback, contacts rated
for 2A Resistive/0.5A Inductive @ 30 VDC or 0.5A
4010-9936 18 mA 65 mA 1 block (11 Maximum)
Resistive/0.5A Inductive @ 120VAC (see 579-1306
installation instructions for additional information)
8 point zone/relay 4 in. x 5 in. flat module. Supports
eight Class B or four Class A IDCs. Mounts in any open
block in a master controller or expansion bay. Alarm
current shown is for eight Class B IDCs using 3.3K end-
4010-9935 of-line-resistors with four IDCs in alarm and four IDCs in 83 mA 295 mA 1 block (11 maximum)
standby. Standby current shown is for all eight IDCs in
standby. Detector current is added separately. Refer to
579-1236 Zone/Relay Module Installation Instructions for
more information
25V regulator harness for 8 point zone/relay module.
One required for each 8 point zone/relay module to be
4010-6305 powered by the 4010-9916 25V regulator module. A N/A
maximum quantity of five 8 point zone/relay modules can
be powered from the 4010-9916 25V regulator module.
IDNet 2+2 Module, 250 point No device 50 mA 60 mA
capacity; electrically isolated output 50 devices 90 mA 150 mA
with four short circuit isolating 125 devices 150 mA 225 mA
Class B or Class A output loops;
4010-9929 1 block (3 maximum)
alarm currents for 50 and above
devices includes 20 device LEDs 250 devices 250 mA 350 mA
in alarm; see above for individual
device currents

Note: For single block option modules, select three maximum if no dual block module is selected; select one maximum if a dual block module or the
module bracket is selected.

Page 13 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Table 8: Dual Vertical Block (Flat) Modules**


Alarm
Model Features Option Block Usage Supervisory Current
Current
For 1-Bay Units Only: Dual
Vertical Block Card Mounting Kit,
allows selecting two, dual Vertical Two vertical blocks (must mount in blocks
4010-9928 N/A
Block (flat) modules from the list A & B)
below; mounts at right angle to
chassis (note block usage details)
4010-9923 * SafeLINC Internet Interface Two vertical blocks (one maximum) 115 mA

Note:

*UL, ULC, and CSFM listed.

** For details on other dual vertical block network options refer to data sheets S4100-0029, S4100-0056, S4100-0057, S4100-0076, and S4100-0061.

Additional Control Unit Option Selection


Table 9: Additional Control Unit Option Selection when block space is not used
Supervisory Alarm
Model Features Mounting Requirements
Current Current
4010-9909 City Connect Module with disconnect switches
20 mA 36 mA
4010-9910 City Connect Module Select one maximum, mounts on ESS
4010-9911 Alarm Relay Module 15 mA 37 mA
Battery Distribution Terminal Block, mounts to side of box, required when battery connection leaves the 4010ES box (also used in
4100-5128
the 4100ES fire alarm control unit)

Miscellaneous Accessories
Table 10: LED Kits (LEDs are pluggable, use to change color for local application requirements)
Model Description
4100-9843 8 Yellow LED Kit
4100-9844 8 Green LED Kit
4100-9845 8 Red LED Kit
4100-9855 8 Blue LED Kit
4100-0650 Battery Shelf, required for 50 Ah batteries (2 Bay cabinets only)
4010-9831 French Applique Kit for ES Touch Screen Display Panels (order separately as required for Canadian French
panels)
Table 11: End User and Factory Programming Tools
Model Description
4100-8802 End User Programming Unit Software
4100-0292 Custom Label Editing (USB Dongle)
4100-0295 Port Vectoring Setup and Control (USB Dongle)
4100-0296 Access Level/Passcode Editing (USB Dongle)
4100-0298 WalkTest Configuration Setup and Control (USB Dongle)
4010-0831 Custom Labels and Programming (requires 4010-8810)
4010-8810 Factory Programming (select)

Network Interface and Network Media Card Product Selection


4010ES fire alarm control units are compatible with Simplex ES Net network or 4120 network fire alarm products.
• Refer to datasheet S4100-0076 for additional information on compatible ES Net fire alarm products.
• Refer to datasheet S4100-0056 for additional information on compatible 4120 network fire alarm products.
• Refer to datasheet S4100-0061 for additional information on the Building Network Interface Card.

Page 14 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Cabinet One and Two Bay Loading Reference

Figure 14: Cabinet One and Two Bay Loading Reference

Note: Some spaces may be used by basic control unit features.

Cabinet Dimension Reference

Figure 15: Cabinet dimension reference

Note:
1. Side View dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 in. stud construction with minimum
protrusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must
be a minimum of 3 in. (76 mm) for both 4 in. and 6 in. stud construction.

Page 15 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

General Specifications
Table 12: 4010ES General Specifications
Specification Rating
AC Input Current 120 VAC Models 4 A maximum, 120 VAC @ 60 Hz nominal
AC Input Current 220 to 240 VAC Models 2 A maximum, 220/230/240 VAC @ 50 or 60 Hz
6 A output for "Special Application" appliances
Power Supply Output Note: The 6 A output rating of the ESS was determined such
Rating that optional module currents, and external device and appliance
currents can be directly added together, not to exceed 6 A total.
3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit Output switches to battery
ESS Power Supply IDNAC SLC Ratings loads; DC-DC converter circuit is >92% efficient over operating backup during mains
Output Ratings range AC failure or brownout
Output terminals are rated for 20 to 12 AWG with duplicate conditions
output terminals rated for two wires each, allowing up to
IDNAC SLC Wiring four Class B branch circuit T-taps to be made in the cabinet;
additional T-taps may be made in external wiring junction
cabinets or boxes
Auxiliary Power Tap 2 A maximum, rated 19.1 to 31.1 VDC
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex
Compatible Special Application Appliances
product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 110 Ah; ULC listed for charging up to 50 Ah
batteries; For 1 bay cabinets, battery capacity above 33 Ah requires a separate cabinet. For
Battery Charger Battery capacity range
2 bay cabinets, battery capacity above 50 Ah requires a separate cabinet. See data sheet
Rating (sealed lead
S2081-0012 for further details.
acid batteries)
Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL
performance Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Operating Temperature 32°F to 120°F (0°C to 49°C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90°F (32°C) maximum
Additional Technical Installation Instructions 579-1150
Reference Operating Instructions 579-969

4010ES Card Address Allocation


The 4010ES has a maximum Internal and External Card Address Limit of 20 Card Addresses. Use the Table below to calculate 4010ES card address
allocation.
INSTRUCTIONS: Below is a list of 4010ES equipment and the quantity of card addresses they consume
1. For the applicable control unit, write in the Card Address Consumption value in the Card Address Allocation column.

Note: Only select one control unit

2. For the option cards to be installed on the 4010ES, write in the Card Address Consumption value in the Card Address Allocation column.
3. Total the Card Address Allocation column (total must not exceed 20).

Card Address Card Address


Model Description Notes
Consumption Allocation
Control Units (Select One)
4010-9601
4010-9602
2x40 Display, (1) IDNet 2 Communications Channel, Single Bay Box 2
4010-9701
4010-9702
4010-9603 2x40 Display, (1) IDNet 2 Communications Channel; 48 Pluggable LED
3
4010-9604 Module, Single Bay Box
4010-9609 2x40 Display, (1) IDNet 2 and (1) IDNet 2+2 Communications Channel,
4
4010-9610 48 Pluggable LED Module, Two-Bay Box
4010-9621 2x40 Display, (1) IDNet 2 and (1) IDNet 2+2 Communications Channel,
4010-9621BA Two-Bay Box
4010-9622 2x40 Display, (1) IDNet 2 and (1) IDNet 2+2 Communications Channel,
4010-9622BA Two-Bay Box
3
4010-9721 2x40 Display, (1) IDNet 2 and (1) IDNet 2+2 Communications Channel,
4010-9721BA Two-Bay Box
2x40 Display, (1) IDNet 2 Communications Channel and (1) IDNet 2+2
4010-9722
Communications Channel, Two-Bay Box

Page 16 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Card Address Card Address


Model Description Notes
Consumption Allocation
4010-9623
4010-9623BA InfoAlarm Display, (1) IDNet 2 and (1) IDNet 2+2 Communications
4010-9624 Channel, Two-Bay Box
4010-9624BA
4010-9711
4010-9711BA InfoAlarm Display, (1) IDNet 2 and (1) IDNet 2+2 Communications 4
4010-9712 Channel, Two-Bay Box
4010-9712BA
4010-9633 ES Color Touch Screen Display, (1) IDNet 2 Communications Channel
4010-9731 and (1) IDNet 2+2 Communications Channel, 2 Bay Box
Control Unit Option Cards (Select As Required)
4010-9901 Flat VESDA HLI Card
4010-9922 Flat 4120 Network Interface Card
4010-6310 Flat ES Net Network Interface Card
4010-9908 4 Point Flat Aux Relay Module
4010-9912 Serial DACT
4010-9923 SafeLINC Internet Interface Card 1
4010-9914 Building Network Interface Card
4010-9918 Dual RS-232 Module
4010-9935 8 Zone Initiating Device Circuit - Class B
4010-9936 4-Point Auxiliary Relay Module with Feedback
4010-9929 IDNet 2+2 Communications Module
Remote Annunciation (Select As Required)
4100-9401 Red Cabinet, English
4100-9403 Platinum Cabinet, English
Red Cabinet, with blank inserts Remote InfoAlarm Command Center 2
4100-9441
for key labels
Platinum Cabinet, with blank
4100-9443
inserts for key labels
4100-9404 Red Cabinet
Remote ES Touch Screen Display 1
4100-9405 Platinum Cabinet
4606-9102 4010ES RUI LCD Annunciator, English
4602-9101 Status Command Unit (SCU) LED Annunciator
4602-9102 Remote Command Unit (RCU) LED Annunciator w/control
4602-9150 Graphic I/O RCU/SCU Assembly for custom annunciator
4602-7101 Graphic I/O RCU/SCU Assembly for custom annunciator
4602-7001 RCU for cabinet mount 1
4602-6001 SCU for cabinet mount
4100-7401 24 Point I/O Graphic Module for custom annunciator
4100-7402 64/64 LED Switch Controller for custom annunciator
4100-7403 32 Point LED Driver Module for custom annunciator
4100-7404 32 Point Switch Input Module for custom annunciator
Total Card Addresses (Not to Exceed 20) TOTAL

Page 17 S4010-0012 Rev. 16 08/2020


Addressable Fire Detection with IDNAC, Fire Alarm Control Unit and Accessories

Additional 4010ES and Network Product Reference


Table 13: Additional 4010ES and Network Product Reference
Subject Data Sheet
Serial DACT (SDACT) for 4100ES, 4010ES, 4007ES S2080-0009
Seismic Battery Brackets Reference S2081-0019
4003EC Voice Control Unit S4003-0002
4009 IDNet NAC Extender S4009-0002
4009 IDNAC Repeater S4009-0004
4010ES Panels with Conventional Notification S4010-0004
4010ES Extinguishing Release Applications S4010-0005
InfoAlarm Command Center for the 4010ES Panels S4010-0008
InfoAlarm Command Center for the 4010ES Panels (INTL) S4010-0009
4010ES Panels with Addressable Notification S4010-0011
4010ES Panels with Addressable Notification (INTL) S4010-0012
External 110 Ah Battery Charger for 4100ES, 4010ES S4081-0002
Graphic I/O Modules for 4100ES, 4010ES, 4007ES S4100-0005
Interface to VESDA Air Aspiration Detection Systems S4100-0026
Multiple Signal Fiber Optic Modems for 4120 Networks S4100-0049
BACpac Ethernet Module S4100-0051
4120 Network Products and Specifications S4100-0056
Building Network Interface Card (BNIC) S4100-0061
SafeLINC Internet Interface S4100-0062
ES Net Network Products and Specifications S4100-0076
NDU with ES-PS Power Supplies for 4120 Network S4100-1036
Remote ES Touch Screen Displays for 4100ES and 4010ES Panels S4100-1070
NDU with ES-PS Power Supplies for ES Net S4100-1077
TrueSite Workstation S4190-0016
TrueSite Incident Commander S4190-0020
24-Pin Dot Matrix Fire Alarm System Remote Printer S4190-0027
SCU/RCU Annunciators S4602-0001
4606-9102 Remote LCD Annunciator S4606-0002

© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4010-0012 Rev. 16 08/2020