ET-701 Single Phase Relay Tester
ET-701 Single Phase Relay Tester
Thank you for purchasing our ET-701 Single Phase Relay Tester.
Please read the manual in detail prior to first use, which will help you
SERIOUS COMMITMENT
All products of our company carry one year limited warranty from
the date of shipment. If any such product proves defective during this
1
SAFETY REQUIREMENTS
work.
Only use the power wire supplied by the product or meet the
When the test wire is connected to the live terminal, please do not
Grounding
2
read the instruction manual to acquire information about the ratings.
Only use the fuse with type and rating specified for the product.
equipment.
-Security Terms
3
Contents
I. Summary ............................................................................................................ 5
V. Instruction ........................................................................................................ 8
4
I. Summary
ET-701 Single-phase relay tester is newly developed calibration device. The application of the
latest AC and DC voltage technology and current power source technology to the equipment
makes its circuit design, component selection, panel layout, and the internal structure design to
meet the advanced level in china. With many excellences for example perfect functions,
excellent Components, clear measuring data, simple operation and so on, the equipment is the
Humidity:≤85 %RH
AC voltage:0~220V/3A
AC current:0~100A/7.5V
0~20A/25V
0~5A/5V
DC voltage:0~220V/3A
DC current:0~20A/25V
Measuring Relay. A Measuring Relay is provided to measure current and the start value,
return value and return coefficient/ drop-off to pick-up ratio of potential relay.
Time Relay. A Time Relay is provided to measure the start value, return value and operating
time.
5
Auxiliary Relay. An Auxiliary Relay is provided to measure the start value, return value,
holding value and operating time of all kinds of auxiliary relays with starting coil and holding
coil.
Reclosing Relay. Reclosing Relays provide tests to Capacitance in charge time, reclosing time
Differential Relay. Differential Relays provide DC excitation test, braking characteristics test
Figure (1)
(2) Function Description.
The AC and DC power supply and fixed value Note: When measuring
J1, J2, J3, J4, J5
output terminals, see the front panel. action time of the relay,
Display ammeter/ voltmeter data(such as the start value, the relay contact should
X1
return value and fixed value) be linked with neither
6
X2 Digital millisecond meter external power supply
short-circuit condition.
S2 Electrical power switch
Turn T1 to AC250V, and close the sync switch; adjust T4, J2 to 0 ~ 250V AC voltage output, X1
Turn T1 to AC5V/AC20V/AC100V, and close the sync switch; adjust T4, J1 to 0 ~ 5V/ 0~20A
/0~100A AC current output, X1 will display the current value, ACA LED will light.
Turn T1 to DC250V, and close the sync switch; adjust T4, J3 to 0 ~ 220V DC voltage output, X1
7
(4) DC current output(0~20V)
Turn T1 to DC20V, and close the sync switch; adjust T4, J4 to 0 ~ 20V DC voltage output, X1 will
Note: adjusting the current, please do not exceed the rated current, otherwise the equipment
will be damaged.
Turn T2 to 24V, and close the fixed voltage switch; J5 will output 24V DC voltage.
Turn T2 to 48V, and close the fixed voltage switch; J5 will output 48V DC voltage.
Turn T2 to 110V, and close the fixed voltage switch; J5 will output 110V DC voltage.
Turn T2 to 220V, and close the fixed voltage switch; J5will output 220V DC voltage.
V. Instruction
(About instruction you can refer to "protection relay calibration", compiled by Water Resources
and Electric Power department Electric Power Production Division, published by China Water
Power Press.)
(1) Measurement
Can be used as voltage and current source respectively, in order to avoid the equipment
damage please pay more attention to all output power. Specific operations refer to section 4.
(2) Over range and Under range
Measuring the start value, the return value, return coefficient and contact action time of relays
(including voltage relay and current relay). Over range relay is defined by the action value of
the contact close. Under range relay is defined by the action value of the contact open.
Measuring the action value, the return value, and return coefficient of relays
Reference sections 4, turn T3 to , press the sync switch, and slowly adjust T4 to the relay
action, then the LED becomes ON, X1 displays this action value. Continue to adjust T4 to the
rated value, and then slowly back to the return value, at this time the LED turns OFF, X1 displays
this return value. Return coefficient = (the return value/the action value) %
Reference sections 4, turn T3 to the relay contact, press the sync switch, and slowly adjust T4 to
the rated value, through the sync switch, relay time can be measured. Note: before test, the
milliseconds should be cleared to zero and closing switch should be in OPEN condition.
8
Relationship between sync switch and contact is as follows:
the cable form contact ZJ3 to ⑿( see "protection relay calibration" page 352), adjust T1 to
DC20A, turn the power supply ON, and turn T4 to relay rated current value. Turn OFF the
power supply, and turn T2 to relay rated voltage value. Adjust T3 to I( Relay ZJ3 is in contact
condition). Turn the power supply ON, press the fixed output switch, change for 15 to 25
seconds (the charge time will show in millisecond meter), reset the millisecond meter, press the
"reclosing switch", measuring reclosing time, then the value displayed in X2 is reclosing time
of reclosing relay.
9
(5) Auxiliary Relay
See Fig.(a), the operation method same as the operating of over range/ under range relay
measuring action values, return values, action time, and return time.
See Fig.(b), for current holding relay, adjust T2 to the relay rated voltage, turn on power switch,
press the fixed value switch, and add the rated voltage to the relay voltage coil, after relay
action, adjust T4 to enable J1 to reach the rated current. Then disconnect the voltage, adjust
the protection coil current (T4), the minimum current that relay holds is the minimum hold of
relay. For testing action time and return time refer to section 5, term 2.
in external connecting regulator and current booster condition, just can do trials at NO. ⑥,
1) Check the action voltage, action current and return current of actuator elements, wiring as
flows:
Disconnect the serial gram between terminal ⑩ and ⑾, measure the action current and
return current as the current relay operating method, then rise the AC current to just measured
action current value, record this voltage value, and the voltage between terminal
10
2) Initial ampere-turn check in no braking condition
This project is not included in routine examination. Put all the 20 working winding turns into
service, connect ⑩ ⑾ short-circuit chips, add AC current from terminal ③ ⑧, and join the
contact action signal to the contact terminal from ⑤ ⑦, verify as the current relay testing
method.
Periodic inspection, only test the action ampere-turn value when Φ = 0 ° and the braking is 280
ampere-turn.
Wiring as above. Disconnect the serial grams of ④ ⑥, adjust the action loop to 39 turns and
the brake circuit to 14 turns, make sure 220V power supply apply to the voltage regulator
(minimum capacity 5KVA) and the equipment, and adjust the brake current to the required
ampere-turns, refer to the AC relay to operate the action current. If action ampere-turns are
completely wrong, it is possible the phase angle between the braking current and action
current is 180 °, reversing the braking current phase, all will be ok. If the equipment using one
phase of the three phase current, voltage regulator using another phase current, changing
their phase position in three phase current and the positive and negative of will get 60 ° phase
AC current add to the working winding ③ ⑧, actuator elements voltage can be read out by
an multi meter from ⑨ ⑩. Adjusting J1 to AC current and boost current to 1 times, 2 times, 5
11
times ampere-turn, actuator elements voltage can be read out. See "protection relay test"
VI. Notes
(1) For security, do not turn on the power switch when the equipment and the relay are
wiring. Make sure the wire is properly connected; you can turn on the power switch.
(2) For better accuracy, please warm-up the equipment for 5 to 10 minutes before test.
(3) When measuring contact action time, the millisecond should be cleared to zero after
(4) For any reason the Equipment fails to operate properly, please check each fuse holder. If
damaged, it is recommended to replace the same model units. It still cannot operate
properly, please contact with our company timely instead repair it by yourself.
(5) The output power supply cannot short-circuit with each other. The connection between
contact terminals and the output power cannot be in short-circuiting condition. All that
(6) Please read the instruction manual carefully before using the equipment.
1 The host 1
2 Power cord 1
3 Test line 1
4 Fuse 4
5 Inspection report 1
6 Certificate 1
7 Warranty card 1
8 User manual 1
9 Packing list 1
12