System Design Report

The document provides a detailed air system sizing summary for a climatization project in Malaga, Spain, with a total cooling load of 3.6 kW and a maximum heating load of 2.2 kW. It includes specific data on central cooling and heating coil sizing, supply fan sizing, and outdoor ventilation air data, along with hourly load analysis for cooling and heating. The air system is designed for a floor area of 56 m², with calculations covering the entire year from January to December.

Uploaded by

dcabreri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

System Design Report

The document provides a detailed air system sizing summary for a climatization project in Malaga, Spain, with a total cooling load of 3.6 kW and a maximum heating load of 2.2 kW. It includes specific data on central cooling and heating coil sizing, supply fan sizing, and outdoor ventilation air data, along with hourly load analysis for cooling and heating. The air system is designed for a floor area of 56 m², with calculations covering the entire year from January to December.

Uploaded by

dcabreri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Air System Sizing Summary for Climatizacion

Project Name: Practica 1 Instalaciones 03/09/2022


Prepared by: Universidad Carlos III Ingeniería Térmica 11:34

Air System Information


Air System Name Climatizacion Number of zones 1
Equipment Class UNDEF Floor Area 56,0 m²
Air System Type SZCAV Location Malaga, Spain

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3,6 kW Load occurs at Oct 1600
Sensible coil load 3,5 kW OA DB / WB 31,4 / 18,8 °C
Coil L/s at Oct 1600 255 L/s Entering DB / WB 26,2 / 18,3 °C
Max block L/s 255 L/s Leaving DB / WB 14,9 / 14,1 °C
Sum of peak zone L/s 255 L/s Coil ADP 13,6 °C
Sensible heat ratio 0,966 Bypass Factor 0,100
L/(s kW) 70,5 Resulting RH 49 %
m²/kW 15,5 Design supply temp. 14,4 °C
W/m² 64,6 Zone T-stat Check 1 of 1 OK
Water flow @ 5,6 K rise 0,16 L/s Max zone temperature deviation 0,0 K

Central Heating Coil Sizing Data


Max coil load 2,2 kW Load occurs at Des Htg
Coil L/s at Des Htg 255 L/s W/m² 38,4
Max coil L/s 255 L/s Ent. DB / Lvg DB 19,1 / 26,1 °C
Water flow @ 11,1 K drop 0,05 L/s

Supply Fan Sizing Data


Actual max L/s 255 L/s Fan motor BHP 0,00 BHP
Standard L/s 255 L/s Fan motor kW 0,00 kW
Actual max L/(s·m²) 4,56 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 24 L/s L/s/person 6,00 L/s/person
L/(s·m²) 0,43 L/(s·m²)

Hourly Analysis Program 5.11 Page 1 of 3


Air System Design Load Summary for Climatizacion
Project Name: Practica 1 Instalaciones 03/09/2022
Prepared by: Universidad Carlos III Ingeniería Térmica 11:34

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 18,8 °C HEATING OA DB / WB 3,9 °C / 0,4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 2429 - 12 m² - -
Wall Transmission 61 m² 73 - 61 m² 336 -
Roof Transmission 56 m² 44 - 56 m² 276 -
Window Transmission 12 m² 245 - 12 m² 836 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 20 - 2 m² 68 -
Floor Transmission 56 m² 0 - 56 m² 181 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 74 W 75 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 74 W 75 - 0 0 -
People 4 280 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3241 240 - 1698 0
Zone Conditioning - 3331 240 - 1667 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 255 L/s 0 - 255 L/s 0 -
Ventilation Load 24 L/s 165 -118 24 L/s 485 0
Supply Fan Load 255 L/s 0 - 255 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3496 122 - 2151 0
Central Cooling Coil - 3496 122 - 0 0
Central Heating Coil - 0 - - 2151 -
>> Total Conditioning - 3496 122 - 2151 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 2 of 3


Hourly Air System Design Day Loads for Climatizacion
Project Name: Practica 1 Instalaciones 03/09/2022
Prepared by: Universidad Carlos III Ingeniería Térmica 11:34

Data for October

Total Cooling Total Heating


3,5

3,0

2,5
Load ( kW )

2,0

1,5

1,0

0,5

0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 3 of 3