CHINT Manual_CONTACTOR_NCH8 Series

The NCH8 Series Modular AC Contactor is designed for use in AC power systems with a voltage up to 400V and current up to 63A, primarily for remote switching and control applications. It includes safety warnings for installation and maintenance, as well as technical parameters and installation guidelines. Regular maintenance checks are recommended, and environmental protection measures for disposal are outlined.

Uploaded by

Cao Văn Duy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views

CHINT Manual_CONTACTOR_NCH8 Series

The NCH8 Series Modular AC Contactor is designed for use in AC power systems with a voltage up to 400V and current up to 63A, primarily for remote switching and control applications. It includes safety warnings for installation and maintenance, as well as technical parameters and installation guidelines. Regular maintenance checks are recommended, and environmental protection measures for disposal are outlined.

Uploaded by

Cao Văn Duy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

NO:2020.

04

NCH8 Series
Modular AC Contactor

User Instruction

Standard:IEC/EN 61095
Safety Warning

1 Only professional technicians are allowed for installation and


maintenance;

2 It is strictly prohibited to install in the environment containing


inflammable, explosive gas and moist condensation.

3 Power must be turned off when installing, maintaining and


maintaining the product.

4 Do not touch the conductive part of the product during


working.
1 Purpose of Use and Range of Application
NCH8 series modular AC contactor is mainly used in AC 50Hz (60Hz)
power systems with rated operating voltage up to 400V and rated operating
current up to 63A. The product is used as remote switch and control circuit
under AC-1/AC-7a application category (non-inductive or low inductive
load/resistance furnace,domestic appliance and low inductive load of similar
applications). The contactor can also be used for AC-7b application category
(household motor load), but it must be derated.
The contactor is not designed to break short circuit current, therefore it
should be used with a matching short circuit protector.

2 Main Technical Parameters and Performance


Table 1 Main parameters and technical
performance index of the contactor

NCH8 NCH8 NCH8 NCH8 NCH8 NCH8 NCH8 NCH8


Model
-20 2P -20 4P -25 2P -25 4P -40 2P -40 4P -63 2P -63 4P

Rated insulation
500
voltage Ui(V)
Rated impulse withstand
4
voltage Uimp(kV)
Conventional thermal
25 63
current Ith(A)
Rated AC-1/AC-7a 20 25 40 63
operating
current Ie(A) AC-7b 9 9 15 20
Rated voltage Ue(V) 230 400 230 400 230 400 230 400
Operation AC-1/AC-7a 360
frequency
(time/h) AC-7b 360 180
Electrical life
AC-1/AC-7a 10
(10000 times)
Mechanical life
100
(10000 times)

01
NCH8 NCH8 NCH8 NCH8 NCH8 NCH8 NCH8 NCH8
Model
-20 2P -20 4P -25 2P -25 4P -40 2P -40 4P -63 2P -63 4P

Coil control power


24、220/230、240
voltage Us(V)
Pick-up
85%~110%Us
Operation voltage
range Release
20%~75%Us
voltage
Enclosure protection
IP20
degree
Rated duty system 8-hour duty, uninterrupted duty, intermittent periodic duty

Ambient temperature -5℃~+40℃


Humidity relative humidity<50% at +60℃; up to 90% at +20℃

Altitude No influence below 2000m

Pollutin class Class 2

Installation category II

3 Installation
1) See Table 2 for outline and installation dimensions.

Table 2 Overall and installation dimensions of NCH8


Unit:mm

D
Model L L1 L2 H H1
2 poles 4 poles

NCH8-20~25 18 36 85 35.5 45 66.5 50

NCH8-40~63 36 54 85 35.5 45 66.5 50

02
Unit:mm

H1
L

L2

L1
D H

Figure 1 NCH8

Unit:mm
D 9

Figure 2 Installation dimensions of partition

03
2) Installation method: use TH35-7.5 steel mounting rail, see Figure 3
below.

① ②

NCH8-20~25 2P

Figure 3 NCH8 installation diagram

3) Wire selection and connection method: applicable to copper wire


connection, please refer to Table 3 below for wire category, sectional area,
strip length and tightening torque, see Figure 4 below for connection
method.

04
Table 3 Connection requirements for copper wire
Unit:mm2

12mm
B
C D E F G H
A1
M3.5

10.5mm
A2 0.8N.m 1~4 1~2.5 1~4 1~2.5 1~4 1~2.5
Model A B C D E F G H
Code
NCH8-20
M3.5 0.8N.m 1~4 1~2.5 1~4 1~2.5 1~4 1~2.5
NCH8-25
NCH8-40
M5 2.0N.m 2.5~16 2.5~6 2.5~16 2.5~6 2.5~16 2.5~6
NCH8-63

Note: You can connect up to 2 wires with same type and sectional area.

A1 1 3 A1 1 R1
A1 1 3 1 3

A2 2 4
A2 2 4 A2 2 R2
NCH8-20~63/20 NCH8-20~63/11

A1 R1 R3 A1 1 3 5 7 A1 R1 1 3 R3

A2 R2 R4 A2 2 4 6 8 A2 R2 2 4 R4
NCH8-20~63/02 NCH8-20~63/40 NCH8-20~63/22

4 A1 R1 A1 1 A1 R1 1 3 5
2

A2 R2 A2 2 A2 R2 2 4 6
NCH8-20~25/01 NCH8-20~25/10 NCH8-20~63/31

Figure 4 NCH8 connection method

05
4 Maintenance
Check the operation of the contactor every month. Method: The
contactor should incline 5° forward upon picking up and 5° backward upon
release; check if the contactor can operation smoothly.
Conduct inspection and maintenance every month. Note: The product
should not be assembled, disassembled or maintained at will. Please
replace the product if it is damaged.

Table 4 Analysis and Troubleshooting of Faults

Symptoms Cause analysis Troubleshooting method

The control power voltage does Use control power that has the
not comply with coil voltage. same voltage as the coil
No operation Insufficient operation circuit
Check the circuit to ensure correct
or operation power capacity; disconnection or
connections
is not reliable wrong connection occured.
Coil is burnt; movable
Replace the product
mechanical parts are jammed
There is foreign objects on the
polar face of magnet yoke ora Replace the product
Noise rmature
The control power voltage is too Use control power that has the
low. same voltage as the coil
The contactor Contact welding Replace the product
does not
release or There is stain or dust on the
Replace the product
release slowly polar face of the iron core.

5 Environmental Protection
In order to protect the environment, the product or product parts
should be disposed of according to the industrial waste treatment process,
or be sent to the recycling station for assortment, dismantling and recycling
according to local regulations.

06
QC PASS
NCH8 Series
Modular AC Contactor
IEC/EN 61095

Check 10

Test date: Please see the packing

ZHEJIANG CHINT ELECTRICS CO., LTD.

07
NCH8 Series
Modular AC Contactor
User Instruction

Zhejiang Chint Electrics Co., Ltd.


Add: No.1, CHINT Road, CHINT Industrial Zone,North Baixiang,
Yueqing, Zhejiang 325603,P.R.China
E-mail: [email protected]
Website: http://en.chint.com