Eaton Ats Power Frame Design Guide Dg140003en
Eaton Ats Power Frame Design Guide Dg140003en
Low-voltage power distribution and control systems > Automatic transfer switches >
Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-6
Magnum DS Power Switch/Circuit Breaker. . . . . . . . . 25.3-6
Digitrip RMS Trip Units. . . . . . . . . . . . . . . . . . . . . . . . . 25.3-9
ATC-900 Automatic Controller. . . . . . . . . . . . . . . . . . . 25.3-10
HMi Remote Annunciator Controller . . . . . . . . . . . . . . 25.3-14
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-14
Advanced Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-15
Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-15
Control Power Transformer. . . . . . . . . . . . . . . . . . . . . . 25.3-15
Thermographic Imaging. . . . . . . . . . . . . . . . . . . . . . . . 25.3-15
Synchroscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-16
Protective Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25.3-16
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
General Description 25.3-3
■ Certifications:
❏ UL1008 Listed
❏ CSA 22.2, No. 178 Listed
❏ Seismic – OSHPD, IBC, CBC, UBC
zone 4
q NEMA 1, 3R
a 3200 A and below
b UL 891/UL1066 at 5000 A Removing the Upper Side Cover,
Lifting Brackets can be Seen at the Top NEMA 1—Through-the-Door
c UL 891/UL1066 at 4000 and 5000 A
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
General Description 25.3-4
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
General Description 25.3-5
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-6
Three-Piece Construction
The 3-piece construction (rear housing, front housing and cover)
provides support while isolating and insulating power conductors.
■ A 2-piece case encloses current paths and arc chambers.
Chambers act to channel arc gases up and out during
interruption
■ The operating mechanism and accessories sit on the front of
the case. Only the insulating front cover needs to be removed
to access mechanism and/or accessories
■ The operating mechanism achieves a longer life as a result of
reduced frame deflection during operation along with stiff
Magnum DS Power Switch (No Trip Unit) component mounting
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-7
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-8
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-9
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-10
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-11
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-12
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-13
Load Management
The ATC-900 includes several features,
enhancing a user’s ability to manage load.
■ Integral load metering: Monitor load
power utilization and compare to
baseline measurements
■ Selective load shed: Drop and pickup
non-essential loads when programmed
kW threshold levels are reached
■ Emergency inhibit/load shed: Inhibit
or disconnect the load connection to
emergency source
■ Pre-/post-transfer: Control select loads
during the transfer process
■ Load bank control: Disengage a load
bank connection from the emergency
source upon loss of the normal source
■ Normal source disconnect/reconnect:
When an abnormal power condition
is present at the normal source,
disconnect the load to prevent
potential damage
■ Emergency source disconnect/
reconnect: When an abnormal power
condition is present at the emergency
source, disconnect the load to prevent
potential damage
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-14
System Architecture
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-15
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Devices 25.3-16
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Layouts and Dimensions 25.3-17
Standard Layouts
Figure 25.3-1. Power Frame Transfer Figure 25.3-3. Power Frame Bypass Isolation Transfer Switch—Drawout
Switch—Fixed
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Layouts and Dimensions 25.3-18
Figure 25.3-4. NEMA 1 (up to 3200 A) Figure 25.3-5. NEMA 3R (up to 3200 A)
200–2000 2 90.00 (2286.0) 32.00 (812.8) 48.00 (1219.2) 1050 (476) 60.00 (1524.0) 1600 (726) 63.00 (1600.2) 1600 (726) 75.00 (1905.0) 2100 (953)
3 90.00 (2286.0) 32.00 (812.8) 48.00 (1219.2) 1050 (476) 60.00 (1524.0) 1600 (726) 63.00 (1600.2) 1600 (726) 75.00 (1905.0) 2100 (953)
4 90.00 (2286.0) 32.00 (812.8) 48.00 (1219.2) 1250 (567) 60.00 (1524.0) 1900 (862) 63.00 (1600.2) 1800 (817) 75.00 (1905.0) 2400 (1089)
2500–3200 2 90.00 (2286.0) 44.00 (1117.6) 48.00 (1219.2) 1900 (862) 60.00 (1524.0) 2500 (1134) 63.00 (1600.2) 2400 (1089) 75.00 (1905.0) 3000 (1361)
3 90.00 (2286.0) 44.00 (1117.6) 48.00 (1219.2) 1900 (862) 60.00 (1524.0) 2500 (1134) 63.00 (1600.2) 2400 (1089) 75.00 (1905.0) 3000 (1361)
4 90.00 (2286.0) 44.00 (1117.6) 48.00 (1219.2) 2000 (907) 60.00 (1524.0) 2800 (1270) 63.00 (1600.2) 2500 (1135) 75.00 (1905.0) 3300 (1498)
a Seismic mounting brace adds an additional 3 inches (76.2 mm) to each side—front left and front right side and 3 inches (75.6 mm) additional to rear side.
b Dimensions and weights shown are approximate and subject to change. Reference product outline drawings for the latest information.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Layouts and Dimensions 25.3-19
4000 2 or 3 90.00 (2286.0) 86.00 (2184.4) 68.00 (1727.2) 4400 (1998) 80.81 (2052.6) 5400 (2542)
4 90.00 (2286.0) 86.00 (2184.4) 68.00 (1727.2) 5100 (2315) 80.81 (2052.6) 6100 (2769)
5000 2 or 3 90.00 (2286.0) 86.00 (2184.4) 68.00 (1727.2) 4900 (2225) 80.81 (2052.6) 5900 (2679)
4 90.00 (2286.0) 86.00 (2184.4) 68.00 (1727.2) 5600 (2542) 80.81 (2052.6) 7100 (3223)
a Seismic mounting brace adds an additional 3 inches (76.2 mm) to each side—front left and front right side and 3 inches (76.2 mm) additional to rear side.
b Dimensions and weights shown are approximate and subject to change. Reference product outline drawings for the latest information.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Layouts and Dimensions 25.3-20
Figure 25.3-8. NEMA 1 (up to 3200 A) Figure 25.3-9. NEMA 3R (up to 3200 A)
200–2000 2 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 3100 (1407) 75.00 (1905.0) 4100 (1861)
3 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 3100 (1407) 75.00 (1905.0) 4100 (1861)
4 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 3700 (1680) 75.00 (1905.0) 4700 (2134)
2500–3200 2 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 4700 (2134) 75.00 (1905.0) 5700 (2588)
3 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 4700 (2134) 75.00 (1905.0) 5700 (2588)
4 90.00 (2286.0) 64.00 (1625.6) 60.00 (1524.0) 5400 (2452) 75.00 (1905.0) 6500 (2951)
Note: Seismic mounting brace adds an additional 3 inches (76.2 mm) to each side—front left and front right side and 3 inches (76.2 mm) additional
to rear side. Dimensions and weights shown are approximate and subject to change. Reference product outline drawings for the latest information.
4000 2 or 3 90.00 (2286.0) 137.00 (3479.8) 60.00 (1524.0) 6900 (3133) 75.00 (1905.0) 7900 (3587)
4 90.00 (2286.0) 137.00 (3479.8) 60.00 (1524.0) 7600 (3450) 75.00 (1905.0) 8600 (3904)
5000 2 or 3 90.00 (2286.0) 137.00 (3479.8) 60.00 (1524.0) 7900 (3587) 75.00 (1905.0) 8900 (4041)
4 90.00 (2286.0) 137.00 (3479.8) 60.00 (1524.0) 8600 (3904) 75.00 (1905.0) 9600 (4358)
Note: Seismic mounting brace adds an additional 3 inches (76.2 mm) to each side—front left and front right side and 3 inches (76.2 mm) additional
to rear side. Dimensions and weights shown are approximate and subject to change. Reference product outline drawings for the latest information.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Data 25.3-21
Relative Humidity
■ Operation: up to 90% (noncondensing)
■ Altitude: Product voltage and current ratings are applicable where:
up to a maximum altitude of 2000 meters (6562 feet) above Ia is the derated continuous current (Amps) at the special
sea level ambient temperature
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-22
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-23
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-24
Closed Transition
A closed transition is a “make before
break” transfer, in that the transfer switch
makes a connection to a second power
source before breaking its connection
with the first power source. As there’s
no gap between disconnection and
connection, downstream loads receive
continuous power throughout the
transfer process.
Switches configured for closed
transition transfer power automatically
as soon as both power sources are
closely synchronized in phase, voltage
and frequency. The overlap period during
which both sources are simultaneously
connected, or “paralleled,” usually
lasts no more than 100 milliseconds to Power Frame Switching Mechanisms are Available up to 5000 A
comply with local utility interconnect and Utilize Stored Energy Technology
requirements.
Low-voltage switching mechanism The linkage can be driven manually
technology comes in two basic varieties, or automatically. When overcurrent
Modes of Operation commonly referred to as “contactor type” protection is needed, molded case
Power transfers involve two processes: and “circuit breaker type”. Circuit breaker circuit breakers equipped with a
initiation and operation. Initiation is what switching mechanisms can be further thermal-magnetic or electronic trip
starts the transfer. Operation is what divided into two sub-types: molded case element are used.
completes it. Most transfer switches can and power frame.
support multiple operation modes through Molded case switching mechanisms
the addition of configurable options. provide a compact, cost-effective and
Contactor Type service entrance-rated solution, as
This is the most common and typically they eliminate the need for additional
Manual Mode most economical switching mechanism upstream protective devices. Each
In manual mode, both initiation and type. Contactors are constructed as an molded case mechanism individually
operation are performed manually, electrically controlled, double-throw complies with industry standard ULT 489,
typically by pushing a button or moving switch where a single operator opens which covers low-voltage molded case
a handle. Initiation occurs locally. one set of power contacts while closing switches and circuit breakers.
a second set. In an open transition design,
a mechanical interlock is often employed Molded case switching mechanisms are
Non-Automatic Mode
to prevent simultaneous closure of both ideal for applications that require integral
In non-automatic mode, the operator overcurrent protection.
contact sets. In a closed transition design,
manually initiates a transfer by pressing
the mechanical interlock is absent.
a button or rotating a switch that causes
Unlike a circuit breaker, a contactor is Power Frame Type
an internal electromechanical device
not designed to provide overcurrent Power frame switches are larger, faster
to electrically operate the switching
protection or interrupt short-circuit and more powerful than molded case
mechanism. Initiation can occur locally
fault current. switches, and are capable of handling
or remotely.
Contactor switching mechanisms are fast up to 5000 A.
Automatic Mode and flexible, but don’t offer overcurrent A two-step stored energy technology is
In automatic mode, the transfer switch protection. utilized that permits manual and electrical
controller is self-acting and completely operation under load.
manages both initiation and operation. Molded Case Type
When an application requires integral
Initiation is triggered when the automatic Routinely used for closing and interrupting overcurrent protection, power circuit
controller senses an unavailability or loss a circuit between separable contacts under breakers are configured with an electronic
of source power followed by operation both normal and abnormal conditions, trip unit that facilitates selective
of the switching mechanism. molded case switches feature simple coordination.
designs and are capable of supporting
either a mechanically operated, over- Power frame switching mechanisms
Switching Mechanism center toggle or a motor operator.They are a good fit for applications vulnerable
The switching mechanism is the part are typically assembled in an enclosed to large fault currents.
of a transfer switch that is physically housing constructed of insulating material.
responsible for carrying the rated Each power frame switch or circuit
electrical current and shifting the load When configured for use in a transfer breaker individually complies with
connection from one power source switch, a pair of molded case switches industry standard UL 1066, which covers
to another. are operated via a common, interlocking low-voltage power circuit breakers.
mechanical linkage.
Note: For more detail, reference Eaton
Publication WP140001EN.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-25
Fixed Mounting
Drawout Mounting
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-26
For simplicity, multiple power poles are Arc Chutes Contactor type switching mechanisms
eliminated from the common transfer Switching mechanisms include arc that provide a “neutral-position” are
switch symbol used in one-line drawings. chutes, housed within an arc chamber referred to as 3-position, otherwise,
constructed of high-dielectric high- they are termed 2-position. All molded
strength material, that are mounted over case and power frame type switching
each set of main contacts. Arc chutes are mechanisms provide a “neutral-position”.
constructed of metal plates designed to Applications (e.g., inductive loads)
extinguish an electrical arc and protect specifying open-delayed transition
the main contacts. will require a transfer switch with a
“neutral-position”.
Switched Neutral
For three-phase power applications
requiring that the neutral conductor
be switched, transfer switches can be
configured with a fully rated fourth pole
that performs identical to the individual
phase (A, B, C) power poles. For single-
phase applications, a fully rated third pole
can be configured.
Figure 25.3-19. Transfer Switch
Schematic Drawing A switched neutral is commonly used
when the transfer switch is fed by
In open transition transfer switches, separately derived power sources. The
the main contacts are mechanically benefits of using a switched neutral
interlocked preventing both sets from include the following:
being closed at the same time. This ■ Inhibits circulating ground current
action prevents the inadvertent electrical from flowing between power sources
paralleling of the two power sources on the neutral conductor that can
that can differ in voltage, frequency cause nuisance tripping of the ground
and phase. fault relay at the de-energized or
Closed transition designs do not include unconnected source
a mechanical interlock and will permit ■ Prevents de-sensitizing the ground
simultaneous paralleling of the power fault relay at the energized or
sources when they are electrically Arc Chutes connected source
synchronized, however, an electrical ■ Eliminates the need for complex
interlock is used to limit the paralleling ground fault sense wiring
time (typically 100 ms) to comply with Operator Device
public utility interconnect specifications. The operator device drives the power Note: For more detail, reference Eaton White
pole main contacts open or closed. Paper IA08700002E.
Power poles also include features to Depending on the switching mechanism
mitigate arcing and erosion of the main type, this is accomplished using an For closed transition transfer switches,
contacts such as arcing contacts, arc electric solenoid, electric motor or a the switched neutral pole operates as
runners and arc chutes. spring stored energy mechanism. “make-before-break” and simultaneous
closure or overlapping of the neutral
Some operator device designs allow contacts is limited to 100 ms.
the source 1 main contacts to be driven
independently of the source 2 main For open transition transfer switches,
contacts. This permits the load to remain the switched neutral pole operates in
disconnected from either of the power a “break-before-make” fashion and
sources for a programmed time delay eliminates potential problems that can
or until the residual load voltage decays occur with a three-pole solid neutral or
below a programmed threshold. When three-pole overlapping neutral (not offered
the load is disconnected in this manner, by Eaton) configuration.
the transfer switch is said to be in a
center-off or “neutral-position”.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-27
The likelihood of a ground fault occurring during the time period Bypass Isolation Automatic Transfer Switches
that neutral contacts are simultaneously closed or overlapped is For simplified maintenance and improved uptime, bypass
just as likely as any other time but perhaps slightly more. When isolation automatic transfer switches provide dual switching
transferring between power sources, dynamic changes are functionality and redundancy for critical applications. The
introduced into the system such as moving contacts, vibration primary switching mechanism (automatic transfer switch)
and energizing previously de-energized conductors that may handles the day-to-day distribution of electrical power to the
push and pull equipment and cables in different directions. load, while the secondary switching mechanism (bypass switch)
serves as a backup or redundant device. During repair or
Configuration Advantages Disadvantages
maintenance procedures, service personnel can bypass power
Three-pole Lower cost Nuisance tripping of around the automatic transfer switch through the bypass to
ground fault (GF) relay ensure that critical loads remain powered without interruption.
on de-energized or
unconnected source. In some bypass isolation transfer switch designs, the bypass
De-sensitizing the switch is fully automatic and self-acting providing increased
ground fault relay redundancy. When in the automatic bypass mode of operation,
at the energized or the control logic continues to monitor the normal power source
connected source.
and will automatically initiate a transfer to the alternate source
Added complexity to should the normal source fail.
implement ground
fault relay circuit to A bypass isolation transfer switch is frequently selected for use
prevent nuisance in healthcare, as well as in other critical applications, because it
tripping of ground fault
relay at de-energized or allows the automatic transfer switch (ATS), and in some cases
unconnected source. the bypass switch, to be drawn out and isolated from the power
Four-pole No circulating ground Higher cost source(s) to facilitate regular maintenance, inspection and testing
(switched neutral) current (eliminates as prescribed by code (NFPA 110).
nuisance tripping of
ground fault relay
at de-energized or
unconnected source
and desensitizing
ground fault relay
at energized or
connected source).
Three-pole May be less expensive During the time when
(overlapping neutral) than four-pole if over- both neutrals are
lapping neutral is connected, the same
not fully rated. disadvantages as a
three-pole switch exists.
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-28
Service Entrance Transfer Switches Arc Flash Reduction Service entrance transfer switch
Facilities with a single utility connection When required by the National Electrical construction can vary in the marketplace
and a single emergency power source will Code (NEC), integral overcurrent and care should be taken by the
often have an automatic transfer switch protection can be configured with consulting engineer to consider when
located at the service entrance to ensure technology to reduce clearing time, such the transfer equipment needs to be
that critical loads can quickly and safely as an Arcflash Reduction Maintenance “fully UL1008 Listed” and marked for
shift to emergency power (generator) if System (ARMS), resulting in lower use at 100% of rated current.
utility power is interrupted. Non-critical incident energy at all downstream The phrase “fully UL 1008 listed” is
loads are often inhibited or shed from work locations. used to describe the entire transfer
connection to the emergency power switch enclosure assembly—including
source to avoid capacity overload. A circuit breaker equipped with ARMS
can improve worker safety by providing the integral circuit breaker and power
Service entrance rated transfer switches a simple and reliable method to reduce bus—which has passed rigorous
include integral overcurrent protection fault clearing time. For applications temperature rise performance testing
and a disconnect means allowing them to where the highest continuous current required by the UL 1008 standard for
be installed directly at the point of service trip setting of the overcurrent device in a transfer switch equipment.
entrance which eliminates the need for circuit breaker is rated (or can be adjusted
separate upstream device(s), including to) 1200 A or higher, a method to reduce
additional power connections. As clearing time is required per NEC 240.87.
required they can also include ground
fault protection. When the ARMS maintenance mode is
enabled, an integral analog trip circuit
provides an accelerated instantaneous
trip. To facilitate maximum arc flash
reduction while avoiding nuisance
tripping, the ARMS pickup level is
adjustable.
Note: Overcurrent protection device modeled is Eaton Magnum DS circuit breaker (520MC or 1150+
trip). When Eaton MCCB (310+ trip) is used as the protection device, maximum clearing time (ARMS)
Figure 25.3-21. Service Entrance Transfer Switch is 0.03 sec. Arcing fault current and incident energy values derived using SKM System Analysis
with Integral Overcurrent Protection Saves software Incident energy is calculated immediately downstream of transfer switch load.
Space and Cost
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-29
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-30
When applying a transfer switch short-circuit WCR, it’s important Short-Time Withstand Closing Rating
to note that UL 489 Listed circuit breakers include a magnetic, Typically applied in critical electrical circuits where the overcurrent
built-in instantaneous override that can’t be defeated or disabled. protection device is a circuit breaker, equipped with an adjustable
For molded case breakers, the override is fixed at approximately electronic trip capable of providing intentional delay, that allows
10–12 times the nominal trip or frame rating. For insulated case for selective coordination within the distribution system. In
breakers, the override is fixed at approximately 13–18 times the many cases, the instantaneous response of the circuit breaker
nominal trip or frame rating. is disabled.
For many years, fuses and thermal-magnetic circuit breakers When a transfer switch carries an optional short-time WCR, it will
(UL 489) have successfully been used to provide overcurrent always be qualified by a maximum time duration. Values typically
protection for short-circuit rated transfer switches. Today, circuit range between 0.1 and 0.5 seconds correlating with a circuit
breakers are more commonly configured with an electronic trip breaker’s short-time response. To ensure proper protection, the
unit having a short-time element (LS, LSI, LSG, LSIG) allowing circuit breaker short-time settings must be coordinated with the
the short-time pick-up/delay to be adjusted. maximum time duration of the marked short-time WCR.
When a circuit breaker’s short-time element adjustments Short-time WCRs are frequently utilized in circuits where the
are set to maximum, the protection provided can be similar overcurrent protective device is a UL 1066 circuit breaker, such
to that of a fuse or thermal-magnetic circuit breaker. However, as UL 1558 switchgear.
adjusting the settings to something less than maximum can
provide shorter clearing times and increased protection at Transfer switches with a short-time WCR and maximum
lower level faults when compared to a fuse (Figure 25.3-22) time duration of 0.5 seconds offer the greatest flexibility
or a thermal-magnetic circuit breaker. As a result, UL 489 to the specifying engineer when designing a selectively
breakers equipped with a short-time element have the ability coordinated system.
to provide “better protection” compared to a fuse or a circuit
breaker without a short-time element.
Life Expectancy
Transfer switches are periodically exercised upon a loss of
normal power or when conducting routine testing. Many
designs include control logic with a plant exerciser capable
of initiating a test automatically based on a programmed
schedule (weekly, biweekly, monthly).
Assuming a transfer switch is exercised once a week through
scheduled testing or a power outage condition, an approximation
of life expectancy can be made based on UL 1008 endurance test
criteria that is conducted with and without rated current.
Table 25.3-9. UL 1008 Endurance Testing
Transfer Switch Number of Operation Cycles Total
Rating (Amperes) With Current Without Current
EATON www.eaton.com
Power Frame Type Transfer Switches Design Guide DG140003EN
ATS and Bypass Isolation ATS Effective February 2020
Application Fundamentals 25.3-31
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. DG140003EN / Z23483 All other trademarks are property
February 2020 of their respective owners.