Code Study

The document contains multiple service calculation worksheets for single-family dwellings with varying square footage and electrical loads. Each worksheet includes detailed calculations based on the National Electrical Code (NEC) guidelines, providing total VA and amp requirements for electrical service. Additionally, it includes demand load calculations for cooking appliances and motors, along with necessary wire sizes for different amperages.

Uploaded by

pcnishant
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views9 pages

Code Study

The document contains multiple service calculation worksheets for single-family dwellings with varying square footage and electrical loads. Each worksheet includes detailed calculations based on the National Electrical Code (NEC) guidelines, providing total VA and amp requirements for electrical service. Additionally, it includes demand load calculations for cooking appliances and motors, along with necessary wire sizes for different amperages.

Uploaded by

pcnishant
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 9

Code Study

Use the Standard Method for these Service Calculations

Service Calculation Worksheet #1

This service calculation is based on a single family dwelling of 3000 square foot
with the following electrical loads:

1- 12 kw electric range
20 kw of electric space heating (1 central elect. heating unit)
1- 5 kw electric water heater
1-central air conditioner, 9 kw
1- dishwasher, 1 kw
1- disposal, 0.9 kw
1- electric clothes dryer, 4500 watt

After you have worked the problem, check your answer here

Service Calculation Worksheet #2

This service calculation is based on a single family dwelling of 2000 square foot
with the following electrical loads:

1- 14 kw electric range
25 kw of electric space heating (electric baseboard heat)
1- 5 kw electric water heater
1-central air conditioner, 9 kw
1- dishwasher, 1 kw
1- disposal, 0.9 kw
1- electric clothes dryer, 4500 watt
1- compactor 1 kw
1- well pump 3/4 hp, 240 volt (560 va)

After you have worked the problem, check your answer here
Service Calculation Worksheet #3

This service calculation is based on a single family dwelling of 1500 square foot
with the following electrical loads:

1- 12 kw electric range
1- electric clothes dryer, 5500 watt
all space heating and water heating are gas

After you have worked the problem, check your answer here

Service Calculation Worksheet #4

This service calculation is based on a single family dwelling of 2500 square foot
with the following electrical loads:

1- 13 kw electric range
28 kw of electric space heating (electric baseboard heat)
1- 4500 kw electric water heater
1-central air conditioner, 12 kw
1- dishwasher, 1.2 kw
1- disposal, 0.5 kw
1- electric clothes dryer, 4500 watt
1- well pump 3/4 hp, 240 volt (560 va)

After you have worked the problem, check your answer here

Service Calculation Worksheet #5

This service calculation is based on a single family dwelling of 1500 square foot
with the following electrical loads:

2 each 4kw wall mounted ovens and one 5.1 kw counter-mounted cooking unit
1- 4.5 kw water heater
1- 1.2 kw dishwasher
1- 5 kw clothes dryer
6- 7 amp, 240 volt room air conditioners (remember to convert to va)
1- 1.5 kw permanently installed space heater
After you have worked the problem, check your answer here

Solution to Service Calculation Worksheet 1

NEC Service Calculation 1


NEC Ref. Load VA
220-3a gen ltg, 3000 sf x 3= 9000 --
220-16a 2 small appliance, 1500 ea= 3000 --
220-16b Laundry = 1500 --
T 220-11 total gen lt, small appl., Laundry = 13500 --
T 220-11 apply demands, 1st 3000 3000
T 220-11 balance(10500) at 35 percent 3675
220-18 dryer (minimum 5k) 5000
220-19 range (from col C) 8000
add fixed appliance x 100 percent (not 4 or
220-17 6900
more)
220-21 larger of heat/ AC 20000
VA Total 46575
Amps divide by 240 = 194
310- 2/0
200 Amp service wire:
15(b)6 copper

Back to Service Calculation 1

Solution to Service Calculation Worksheet 2


NEC Service Calculation 2
NEC Ref. Load VA
220-3a gen ltg, 2000 sf x 3= 6000 --
220-16a 2 small appliance, 1500 ea= 3000 --
220-16b Laundry = 1500 --
total gen lt, small appl., Laundry =
T 220-11 --
10500
T 220-11 apply demands, 1st 3000 3000
T 220-11 balance(7500) at 35percent 2625
220-18 dryer (minimum 5k) 5000
range (note1, increase col C by 10
220-19 8800
percent)
220-17 add fixed appliance x 75 percent 6345
220-21 larger of heat/ AC 25000
VA Total 50770
Amps divide by 240 = 211.54
310- 3/0
225 Amp service wire:
15(b)6 copper

Back to Service Calculation 2


Solution to Service Calculation Worksheet 3

NEC Service Calculation 3


NEC Ref. Load VA
220-3a gen ltg, 1500 sf x 3= 4500 --
220-16a 2 small appliance, 1500 ea= 3000 --
220-16b Laundry = 1500 --
total gen lt, small appl., Laundry =
T 220-11 --
9000
T 220-11 apply demands, 1st 3000 3000
T 220-11 balance(6000) at 35 percent 2100
220-18 dryer (minimum 5k) 5500
220-19 range (12 kw) 8000
VA Total 18600
Amps divide by 240 = 77.5
310- 4
100 Amp service wire:
15(b)6 copper

Back to Service Calculation 3

Solution to Service Calculation Worksheet 4

NEC Service Calculation 4


NEC Ref. Load VA
220-3a gen ltg, 2500 sf x 3= 7500 --
220-16a 2 small appliance, 1500 ea= 3000 --
220-16b Laundry = 1500 --
total gen lt, small appl., Laundry =
T 220-11 --
12000
T 220-11 apply demands, 1st 3000 3000
T 220-11 balance(9000) at 35 percent 3150
220-18 dryer (minimum 5k) 5000
range (note1, increase col C by 5
220-19 8400
percent)
220-17 add fixed appliance x 75 percent 5070
220-21 larger of heat/ AC 28000
VA Total 52620
Amps divide by 240 = 219.25
310- 3/0
225 Amp service wire:
15(b)6 copper

Back to Service Calculation 4

Solution to Service Calculation Worksheet 5

NEC Service Calculation 5


NEC Ref. Load VA
220-3a gen ltg, 1500 sf x 3= 4500 --
220-16a 2 small appliance, 1500 ea= 3000 --
220-16b Laundry = 1500 --
total gen lt, small appl., Laundry =
T 220-11 --
9000
T 220-11 apply demands, 1st 3000 3000
T 220-11 balance(6000) at 35 percent 2100
220-18 dryer (minimum 5k) 5000
220-19 col
cooking appliances (13.1 x .55) 7200
A
220-17 add fixed appliances x 100 percent 5700
220-21 larger of heat/ AC 10080
VA Total 33080
Amps divide by 240 = 137.8
1
310-15(b)6 150 Amp service wire:
copper

Back to Service Calculation 5

Ranges Worksheet

1. What is the demand load for 1 range rated 11 kw?

2. What is the demand load for 1 range rated 9 kw?

3. What is the demand load for 3 ranges each rated 11 kw?

4. What is the demand load for 15 ranges each rated 9 kw?

answers:

1. 8 kw

2. 8 kw

3. 14 kw

4. 30 kw

Table 220-19, Note 1: For ranges individually rated more than 12 kw but not more
than 276 kw, the maximum demand in Column C shall be increased by 5 percent
for each kw of rating or major fraction thereof by which the rating of each
individual range exceeds 12 kw:

Using column C and note 1:

5. What is the demand for 1 range rated at 16 kw?

6. What is the demand for 6 ranges rated at 18 kw each?

7. What is the demand for 5 ranges rated at 18 kw each?

8. What is the demand for 20 ranges rated at 14 kw each?

Answers:

5. 16 - 12= 4. 4 x 5 percent= 20 percent. Increase the column C value for 1 range


by 20 percent. 8 x 1.20 =9.6 kw
6. 18 - 12 = 6 x 5 percent = 30 percent. Increase the column C value for 6 ranges
by 30 percent. 21 x 1.30 = 27.3 kw

7. 18 - 12 = 6 x 5 percent = 30 percent. Increase the column C value for 5 ranges


by 30 percent. 20 x 1.30 = 26 kw

8. 20 - 12 = 8 x 5 percent = 40 percent. Increase the column C value for 20


ranges by 40 percent. 35 x 1.4= 49 kw

Using column A and note 2:

9. What is the demand load for the service or feeder supplying the following
ranges?

1 range rated at 20 kw

4 ranges rated at 15 kw each

2 ranges rated at 9 kw each

10. What is the demand for the service or feeder supplying the following ranges?

2 ranges rated at 20 kw each

3 range rated at 10 kw each

2 range rated at 14 kw each

Answers:

20 + 60 + 24 = 104 divide by 7 = 14.85 - 12= 3 x 5percent =15 percent above


the column C value for 7 ranges. 22 x 1.15=25.3 kw

10

40 + 36 + 28 = 104 divide by 7 = 14.85 - 12 = 3 x 5 percent = 15 percent above


the column C value for 7 ranges. 22 x 1.15 = 25.3 kw

11. What is the demand load for two 3 kw cooking appliances in a dwelling unit?

from column A, 6000 x 75 percent = 4.5kw

12. What is the demand load for one 6 kw cooking appliance in a dwelling unit?
from column B, 6000 x 80 percent = 4.8kw

13. What is the demand load for two 3 kw ovens and one 6 kw cook top in a
dwelling unit?

from column A, 6000 x 75 percent = 4.5kw, from column c, 6000 x 80 percent =


4.8 kw, add 4.5 kw to 4.8 kw for a total demand of 9.3 kw

Motors Worksheet

1.

10 hp FLC = 28
15 hp FLC = 42
20 hp FLC = 54
10 hp = number 10 THHN
15 hp = number 6 THHN
20 hp = number 4 THHN

2. 67.5 + 28 + 42 = 137.5 from Table 310-16, use 1/0 THHN

34 x 1.75 = 59.5, round up to 60 amps per 430-52c(1) exception 1

3. 34 x 1.25 = 42.5, number 8 THHN per table 310-16

4. 34 x 2.5 = 85, round up to 90 amp

5. Conductors

Motor 1, 22 AMP table 430-150, x 1.25 430-22, =27.5, table 310-16, number 10
THHN wire
Motor 2, 28 amps table 430-150, x 1.25 430-22, =35, table 310-16, number 10
THHN
feeder, 35 + 22 = 57, table 310-16, number 6 THHN
short circuit, ground fault protection

Ground Fault and Short Circuit Protection:


22 x 2.5 = 55 round up to 60 amp per 430-52c(1) exception 1 and 240-6
28 x 2.5 = 70 feeder: 70 + 22= 92, round down to 90 amps per 430-62

6. Time Delay fuses:

22 x 1.75 = 38.5 = 40 amps, round up to next standard size per 430-52c(1)


exception 1
28 x 1.75 = 49 =50 amps