0% found this document useful (0 votes)
10 views

Motor Starting

The document provides a step-by-step guide for sizing an Auto Transformer Starter for motor starting, detailing necessary motor data, calculations for full load current, voltage tapping ratios, and component ratings. It compares Auto Transformer and Star-Delta starters, highlighting their purposes, current and torque characteristics, and when to use each method. The guide concludes with a recommendation for selecting the appropriate starter based on motor load and application requirements.

Uploaded by

gebrihans.sahle
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views

Motor Starting

The document provides a step-by-step guide for sizing an Auto Transformer Starter for motor starting, detailing necessary motor data, calculations for full load current, voltage tapping ratios, and component ratings. It compares Auto Transformer and Star-Delta starters, highlighting their purposes, current and torque characteristics, and when to use each method. The guide concludes with a recommendation for selecting the appropriate starter based on motor load and application requirements.

Uploaded by

gebrihans.sahle
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

Auto Transformer Starter Sizing for Motor Starting – Step-by-Step Guide

1. Understand the Purpose


An Auto Transformer Starter reduces the starting current and voltage of an induction motor
during startup. It provides a smooth start, reducing mechanical and electrical stress.

2. Collect Required Motor Data


You need the following motor information:

 Rated Motor Power (kW or HP)


 Rated Voltage (V)
 Rated Current (A)
 Starting Current (as a multiple of full load current, typically 5 to 7 times)
 Motor Efficiency (usually between 0.85 and 0.95)
 Power Factor (typically 0.8 lagging)
 Starting Time (seconds)
 Duty Cycle (how often it starts per hour)

3. Determine the Motor Full Load Current (FLC)


Use this formula:

FLC (A) = (Motor Power (kW) × 1000) / (√3 × Voltage × Efficiency × Power Factor)

Example:

 Motor Power = 75 kW
 Voltage = 400 V
 Efficiency = 0.9
 Power Factor = 0.85

FLC = (75 × 1000) / (1.732 × 400 × 0.9 × 0.85) = approx. 141.4 A

4. Choose Voltage Tapping Ratio for the Auto Transformer


Typical tapping ratios are: 50%, 65%, 80%

These percentages reduce the starting current proportionally.

Example:

 Tapping = 65%
 Starting current becomes (0.65)^2 = 0.4225 = 42.25% of direct-on-line starting current

So if DOL starting current is 6 × FLC, then:

Auto Transformer Starting Current = 6 × FLC × 0.4225

= 6 × 141.4 × 0.4225 = approx. 358 A

This is the line current; the motor still sees 6 × FLC at its terminals, but the supply sees much
less.

5. Select the Auto Transformer Rating


This should be based on starting kVA, not just running kVA.

Starting kVA = √3 × Line Voltage × Starting Current / 1000

Using our example:

= 1.732 × 400 × 358 / 1000 = approx. 248 kVA

You must select an auto transformer with a short-duty rating (typically 30 seconds, 60 seconds,
or 1 minute) equal to or greater than 248 kVA.

Note: You can oversize slightly to accommodate duty cycle or ambient conditions.

6. Select the Appropriate Tapping


Based on:

 Load torque characteristics


 Desired reduction in starting current
 Supply network limitations
Low tapping (e.g., 50%) = less current but may not develop enough torque
High tapping (e.g., 80%) = more torque but higher current

Use 65% as a balanced choice unless you know the load requires more torque at start.

7. Select Contactor Ratings


Auto transformer starters use three contactors:

1. Main Contactor (M): Carries full load current


2. Star Contactor (S): Used during starting; rated for reduced current
3. Auto Transformer Contactor (T): Connects the transformer during starting; rated for
starting current

Use these guidelines:

 Main Contactor: Rated for FLC (141.4 A in our example)


 Star Contactor: Rated for motor current at the selected tap (65% of FLC = approx. 92
A)
 Auto Transformer Contactor: Rated for line starting current (358 A in our case)

Use AC3 duty class contactors, as motors are inductive loads.

8. Thermal Overload Relay Sizing


Should be rated for 100% of FLC:

 Set overload protection at 1.0 × FLC (or per motor datasheet)

In our example: Overload relay range should cover 141 A

9. Enclosure and Protection


Choose a suitable enclosure:

 IP rating depending on installation site


 Ventilation for transformer heat
 Adequate short-circuit protection using MCCB or fuses
10. Wiring Considerations
 Copper cable sized for FLC and short-circuit capacity
 Proper earthing
 Star-to-delta timer or programmable logic for switching

Summary Example (for 75 kW Motor)

 Motor Power: 75 kW
 Voltage: 400 V
 FLC: approx. 141 A
 Starting Tapping: 65%
 Starting Current (line): 358 A
 Starting kVA: 248 kVA
 Auto Transformer Rating: ≥250 kVA for 30-60 seconds
 Main Contactor: 150 A (AC3)
 Star Contactor: 100 A (AC3)
 Auto Transformer Contactor: 400 A (AC3)
 Overload Relay: 140-160 A range
 Cables: Rated for 150 A continuous

If both an Auto Transformer Starter and Star-Delta Starter are being considered (or
combined in some way), it's important to understand their differences, application contexts, and
why or when they might be used together.

However, Auto Transformer Starting and Star-Delta Starting are generally not combined
in practice — because they are two different reduced-voltage starting methods with different
wiring, timing, and performance characteristics.

But if you're asking from an analysis or comparison perspective (or designing for a scenario
where both methods are considered as options for the same motor), then here's how to handle
Auto Transformer Starter vs. Star-Delta Starter — including their sizing parameters,
selection criteria, and how you might document both in your Word report.

Comparison and Sizing Guide: Auto Transformer vs. Star-Delta Starter

1. Purpose of Each Starting Method


Auto Transformer Starter:

 Provides adjustable starting voltage via tapping (50%, 65%, 80%)


 Suitable for larger motors and long starting durations
 Allows better control over starting current and torque
 More expensive but more flexible

Star-Delta Starter:

 Reduces starting current by connecting motor windings in Star (Y) first, then Delta (Δ)
 Reduces starting voltage to 58% of line voltage
 Simple and economical for motors >10 HP (~7.5 kW) with light starting load
 Fixed torque reduction, cannot adjust

2. Current and Torque Characteristics


Starting Method Starting Voltage Starting Current Starting Torque

Direct-On-Line (DOL) 100% 600% 100%

Star-Delta 58% ~33% ~33%

Auto Transformer (65%) 65% ~42% ~42%

Auto Transformer (80%) 80% ~64% ~64%

Note: Percentages based on DOL full values.

3. Sizing Star-Delta Starter Components


Assuming the same 75 kW, 400 V, 141 A motor from before:

Motor Full Load Current (FLC):

 Same as before: ~141 A

Star-Delta Starting Current (line):

 ~33% of DOL current


 Starting current = 0.33 × 6 × 141 = ~279 A
Contactor Ratings for Star-Delta

Star-Delta uses three contactors:

1. Main Contactor (KM1): Carries full load current (141 A)


2. Star Contactor (KM2): Carries phase current during star connection
o Current = FLC / √3 ≈ 81.5 A
3. Delta Contactor (KM3): Carries full load current after changeover (141 A)

Sizing Table (Star-Delta)


Component Duty Type Required Current Rating

Main Contactor AC3 150 A

Star Contactor AC3 90 A

Delta Contactor AC3 150 A

Overload Relay - 140–160 A

4. When to Use Each


Criteria Auto Transformer Star-Delta

Motor Power > 75 kW ✅ Yes ❌ Not ideal

High Starting Torque Required ✅ Adjustable ❌ Low torque

Long Starting Time ✅ Suitable ❌ Not suitable

Cost Sensitive ❌ Expensive ✅ Economical

Adjustable Starting Conditions ✅ Yes ❌ Fixed

More Complex Control Logic ✅ Yes ✅ Yes

5. Final Recommendation Section (For Report)


Suggested Template for Your Word Document:
Motor Starting Mechanism Analysis – 75 kW Induction Motor

Options Evaluated:

 Auto Transformer Starter (65% tapping)


 Star-Delta Starter

Summary Table:

Criteria Auto Transformer Star-Delta

Starting Current 358 A (~42%) 279 A (~33%)

Starting Torque ~42% ~33%

Flexibility High (tapping) Low (fixed)

Cost Higher Lower

Suitability (>75 kW) Good Not preferred

Contactor Sizing Up to 400 A Up to 150 A

Application Suitability High torque loads Low inertia

Recommendation:
For high-torque or high-inertia loads (e.g., compressors, conveyors), Auto Transformer Starter
with 65% tapping is recommended. For simple, low-cost installations with low starting load,
Star-Delta may be considered for motors below 50–75 kW.

You might also like