3F2 - VS01 - M-Anm-3f2ds0 - CBST - SDR-000056

The document outlines the key plan and notes for the Riyadh Metro Project, specifically for the deep underground station ventilation shaft. It includes specifications for materials, welding, and structural connections, emphasizing the importance of verifying dimensions and reading all drawings in conjunction with relevant documents. Additionally, it provides a pretension chart for structural connection fasteners and references a specific drawing number for further details.

Uploaded by

razaimran861
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views16 pages

3F2 - VS01 - M-Anm-3f2ds0 - CBST - SDR-000056

The document outlines the key plan and notes for the Riyadh Metro Project, specifically for the deep underground station ventilation shaft. It includes specifications for materials, welding, and structural connections, emphasizing the importance of verifying dimensions and reading all drawings in conjunction with relevant documents. Additionally, it provides a pretension chart for structural connection fasteners and references a specific drawing number for further details.

Uploaded by

razaimran861
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

KEY PLAN:


24
AH)
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

SH -07
.3
SE

0
LINE 3.
3F2

LINE 1

A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

SH.47
M22 176 221

M22 205 257

SH.34
SH.38 SH.46
M27 267 334

M30 326 408


MU-02
SPR-02

M36 475 595


MAU-05
MAU-03

SPR-01 MU-01

SH.33
Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
SH.42

M-ANM-3F2DS0-CA00-EDR-200039

C
1
H
1
VENTILATION SHAFT 3F2 -VS01
PROJECT

V1
RIYADH METRO PROJECT
PACKAGE 2
LINE 3

H
1
H
1
ARRIYADH NEW MOBILITY

V1
ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE

GRADE LEVEL PLAN LAYOUT DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
KEY PLAN
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 01 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.

3D VIEW WITH GRATING AND DECK SHEET 9. FINISH 2 HR FIRE RATED.


10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221

M22 205 257

M27 267 334

M30 326 408

M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039

PROJECT

RIYADH METRO PROJECT


PACKAGE 2
LINE 3

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT

3D VIEW WITHOUT GRATING & DECK SHEET 3D VIEWS


ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 02 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A B C D A B C D
A* A* A- NOTES:-

8049 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.

8044 2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR


COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).

228 3052 3035 1732 3019 3035 1732 4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
5 5 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:

1637
1637

7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B


7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
SHS150*150*5.0 SHS100*100*5.0 7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
SHS150*150*5.0 SHS100*100*5.0 system
SHS100*100*5.0 SHS150*150*5.0 SHS150*150*5.0 SHS150*150*5.0
SHS150*150*5.0 7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
4 4 7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 WITH GRADE 8.8.
SHS100*100*5.0 8. A. Welding Specification:
SHS100*100*5.0 A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
SHS100*100*5.0 SHS100*100*5.0

3886
3886

9. FINISH 2 HR FIRE RATED.


10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.
6081 TABLE J3.1M
Minimum Bolt Pretension, KN"
SHS100*100*5.0
Bolt Size, mm A325M Bolts A490M Bolts
10970

10972
SHS150*150*5.0 SHS100*100*5.0 SHS150*150*5.0 M16 91 114
3 3 M20 142 179
SHS100*100*5.0 SHS100*100*5.0 SHS150*150*5.0 M22 176 221
SHS150*150*5.0
M22 205 257

M27 267 334

M30 326 408

M36 475 595


SHS100*100*5.0 Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

3886
3886

B- REFERENCE DRAWING:-
SHS100*100*5.0 M-ANM-3F2DS0-CA00-EDR-200039

SHS100*100*5.0 SHS100*100*5.0
3052 3036
SHS150*150*5.0
SHS150*150*5.0 SHS100*100*5.0
SHS100*100*5.0
SHS150*150*5.0
1 2
2 2
SHS150*150*5.0
SHS100*100*5.0 SHS150*150*5.0 SHS150*150*5.0
SHS100*100*5.0 SHS100*100*5.0

1565
1565

SHS100*100*5.0

PROJECT

1 1 RIYADH METRO PROJECT


PACKAGE 2
LINE 3

ARRIYADH NEW MOBILITY

PLAN @ T.O.S LEVEL 592.795 ANCHOR BOLT PLAN @ LEVEL +592.350 ORIGINATOR CHECK REVIEW APPROVAL
SCALE 1:1 SCALE 1:1 R.T R.T R.T L.M
DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
STRUCTURAL PLANS - 01
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 03 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A B C D A- NOTES:-
A*
A B C D 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
A*
SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.

8174 8174 3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).


4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE

56 1309 1350 1350 1350 1350 1350 60 MEASUREMENTS PRIOR TO EXECUTION.


5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
60 1305 1350 1350 1350 1350 1350 60 ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
60

60

56
60
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
5 5 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
1107

1107

SHS100*100*5.0
SHS100*100*5.0

SHS100*100*5.0
SHS100*100*5.0
1107

1111
L100*10 7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
SHS100*100*6.0
SHS100*100*6.0 7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
1005

1005

1005
SHS100*100*5.0 7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,

1005
4 4 MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
SHS150*150*5.0 SHS100*100*5.0 7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
SHS150*150*5.0 SHS100*100*6.0 WITH GRADE 8.8.
RHS100*100*5 8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
1172

1172

1172
1172
SHS100*100*5.0 A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
SHS100*100*6.0 WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.

1300

1300
1293

10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE

1293
SHS100*100*5.0 REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
SHS100*100*6.0
AISC360-10.
SHS100*100*5.0

1300

1300
1306

1306
11072

11106
11072
3 3
SHS100*100*5.0 SHS100*100*6.0
1200

1200

1200
1200
SHS100*100*6.0
1417

1417

1417
1417
SHS100*100*5.0 B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039

SHS100*100*6.0

SHS100*100*5.0
1200

1200

1200
1200
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0
2 2 SHS100*100*6.0
SHS100*100*5.0

SHS100*100*5.0

SHS100*100*5.0

SHS100*100*5.0
SHS100*100*5.0
1286

1286
1251

1251
6 L100*10 5
1 1
PROJECT

60
60

SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0


60

60
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
60 1343 1350 1357 1343 1350 1350 60 SHS100*100*6.0
RIYADH METRO PROJECT
PACKAGE 2
60 1342 1350 1350 1350 1350 1350 60 LINE 3
8212
8212
ANCHOR BOLT PLAN @ LEVEL +594.300
SCALE 1:1

PART PLAN FOR GRATING @ LEVEL +594.300 ARRIYADH NEW MOBILITY

SCALE 1:1
ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
STRUCTURAL PLANS - 02
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 04 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

A B C
A*
A B C
A* 3F2
LINE 3.

6321
6321
LINE 1
246 3040 3036 234 3052 3036

194 532 2173 782 2253 466 193 533 2173 782 2253 466
A- NOTES:-
L220*75*6 L220*75*6 L220*75*6
4 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE

450
4 SPECIFICATIONS.
450

456
RHS150*100*5.0 RHS150*100*5.0 2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
RHS150*100*5.0
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
L220*75*6 4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
IPE200 IPE200
SHS100*100*5.0 SHS100*100*5.0 ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50

3886

3136
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
3885

3125
3136

3861

system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
L220*75*6 A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
2067 1950 2015 TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE

750
INSTALLATION OF ANCHOR SITE.
IPE240 IPE240 3

7923
750

11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART


3 AISC360-10.
IPE240
TABLE J3.1M
Minimum Bolt Pretension, KN"

9336
Bolt Size, mm A325M Bolts A490M Bolts
9339

M16 91 114

IPE200 IPE200 SHS100*100*5.0 M20 142 179


SHS100*100*5.0
M22 176 221
L220*75*6
L220*75*6 M22 205 257

M27 267 334


3887
M30 326 408

3886
M36 475 595

3136
Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
3886

3861
3136

as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039

SHS100*100*5.0

450
L220*75*6
L220*75*6
450

456

RHS150*100*5.0 RHS150*100*5.0 2
SHS100*100*5.0
2
L220*75*6 L220*75*6 L220*75*6 L220*75*6
RHS150*100*5.0 PROJECT
RHS150*100*5.0
190 525 2213 762 2273 466 RIYADH METRO PROJECT
1566

1493
525 2213 762 2272 466
1567

PACKAGE 2
1523

LINE 3
192 6238

1
1

ARRIYADH NEW MOBILITY

PLAN @ T.O.S LEVEL 597.471 ORIGINATOR CHECK REVIEW APPROVAL

SCALE 1:1 PART PLAN FOR DECK SHEET @ T.O.S LEVEL 597.471 R.T R.T R.T L.M
SCALE 1:1 DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
STRUCTURAL PLANS - 03
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 05 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
A B C D ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
A*
A B C D ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
A* WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
8088 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
8082 BEARING SURFACE UNLESS SHOWN OTHERWISE.
269 3054 3035 1731 7. MATERIAL:
263 3054 3035 1731 7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50

A
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy

+597.691 194 525 2213 762 2273 466 1656 +597.691


188 525 2213 762 2273 466 1656 system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
220

220
L220*75*6 L220*75*6 L220*75*6
L220*75*6 L220*75*6 L220*75*6 L220*75*6 L220*75*6 L220*75*6 L220*75*6 MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
+597.471 +597.471
8. A. Welding Specification:
RHS150*100*5.0 RHS150*100*5.0 RHS150*100*5.0 RHS150*100*5.0 A1.Welding Shall BE IN Conformance With AWS 01.1
RHS150*100*5.0 RHS150*100*5.0 A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
RHS150*100*5.0
RHS150*100*5.0

A
(E-70XX ELECTRODES).
SHS150*150*5.0 DETAIL [ A ]
1581

1581
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
SHS100*100*5.0 WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
SHS100*100*5.0 TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
SHS150*150*5.0 9. FINISH 2 HR FIRE RATED.
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0 10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
+595.890 +595.890 REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
SHS100*100*5.0 DETAIL [ B ] INSTALLATION OF ANCHOR SITE.
SHS100*100*5.0 SHS100*100*5.0
610

610
SHS100*100*5.0 11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
SHS100*100*5.0 SHS100*100*6.0
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 AISC360-10.
+595.270 +595.270
5341

5341
SHS150*150*5.0 SHS150*150*5.0 SHS150*150*5.0 TABLE J3.1M
SHS100*100*5.0 DETAIL [ C ] SHS100*100*6.0 Minimum Bolt Pretension, KN"
970

970
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 Bolt Size, mm A325M Bolts A490M Bolts
SHS100*100*6.0 SHS100*100*5.0 SHS100*100*5.0
SHS100*100*6.0 SHS100*100*6.0
SHS100*100*5.0 M16 91 114
+594.300 +594.300 M20 142 179

SHS100*100*5.0 SHS100*100*5.0 M22 176 221


SHS100*100*5.0 SHS100*100*5.0 M22 205 257
SHS100*100*5.0
1515

1515
M27 267 334

M30 326 408

M36 475 595


SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

+592.795 +592.795 B- REFERENCE DRAWING:-


SHS100*100*5.0 SHS100*100*5.0
M-ANM-3F2DS0-CA00-EDR-200039
+592.350 +592.350
445

445

PROJECT

RIYADH METRO PROJECT


PACKAGE 2
LINE 3

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
CROSS SECTIONS - 01
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 06 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
A* A B C D KK
AH
)

(MA LINE 4

8049

230 3052 3035 1732 LINE 4 LINE 6 LINE 2

1304 1350 1350 1350 1350 1345 LINE 2


LINE 6
LINE 1
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
+595.270 LINE 5

15

970
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
LINE 3.
3F2

+594.300
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0 LINE 1

2930

1515
A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


+592.795 SPECIFICATIONS.

445
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
+592.350
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
1 2 3 4 5
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE

10978 INSTALLATION OF ANCHOR SITE.


11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.
1569 3886 3886 1637 TABLE J3.1M
Minimum Bolt Pretension, KN"

1494 450 3136 750 3136 450 1561 Bolt Size, mm A325M Bolts A490M Bolts
220

L220*75*6 M16 91 114


L220*75*6
SHS100*100*5.0 M20 142 179
+597.691
M22 176 221
+597.471
RHS150*100*5.0 L220*75*6
M22 205 257
SHS100*100*5.0 SHS100*100*5.0 RHS150*100*5.0
M27 267 334

M30 326 408


1581

M36 475 595


SHS100*100*5.0 Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

SHS150*150*5.0 B- REFERENCE DRAWING:-


SHS100*100*5.0 M-ANM-3F2DS0-CA00-EDR-200039
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0

+595.890
SHS100*100*5.0
610

SHS100*100*6.0
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
SHS100*100*6.0 SHS100*100*6.0
SHS100*100*6.0
+595.270
5341

SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0


SHS100*100*6.0 SHS100*100*6.0 SHS150*150*5.0 SHS100*100*5.0 SHS100*100*6.0 SHS100*100*6.0
970

SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0

+594.300

PROJECT
1515

RIYADH METRO PROJECT


PACKAGE 2
SHS100*100*5.0 SHS100*100*5.0 LINE 3
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0
+592.795
445

SHS100*100*5.0
SHS100*100*5.0
+592.350

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
CROSS SECTIONS - 02
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 07 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1
1 2 3 4 5
LINE 5
1 2 3 4 5
10978 10991
1569 3886 3886 1637 1582 3886 3887 1636 LINE 3.
+597.691 +597.691 3F2
1494 450 3136 750 3136 450 1561
220

220
L220*75*6 L220*75*6

+597.471 +597.471 LINE 1


RHS150*100*5.0 SHS100*100*5.0 SHS100*100*5.0 RHS150*100*5.0 RHS150*100*5.0
IPE240
1581

1581
SHS100*100*5.0
SHS100*100*5.0 SHS150*150*5.0

SHS100*100*5.0
SHS100*100*5.0 A- NOTES:-
SHS100*100*5.0 SHS100*100*5.0
+595.890 +595.890 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
610

15

610
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SPECIFICATIONS.
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
+595.270 +595.270
5341

5341
SHS100*100*6.0
SHS100*100*6.0 SHS100*100*6.0 SHS150*150*5.0 COMPUTED.
SHS100*100*6.0 SHS150*150*5.0
SHS100*100*6.0 SHS100*100*6.0
970

970
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
SHS100*100*6.0 SHS100*100*6.0 4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
SHS100*100*5.0
8 3
+594.300
4 +594.300
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
SHS100*100*5.0 ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
1515

1515
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
SHS150*150*5.0 SHS100*100*5.0 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 BEARING SURFACE UNLESS SHOWN OTHERWISE.
SHS100*100*5.0 7. MATERIAL:
+592.795 +592.795 7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
SHS100*100*5.0
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
+592.350 +592.350 7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
445

445
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

1 2 3 4 5
11004
1 2 3 4 5
1595 3886 3887 1636
+597.691
1520 456 3125 762 3125 456 1561 11011
220

B- REFERENCE DRAWING:-
L220*75*6 L220*75*6 M-ANM-3F2DS0-CA00-EDR-200039
L220*75*6 L220*75*6 L220*75*6 1602 3886 3886 1637
+597.471
SHS100*100*5.0 SHS100*100*5.0
1286 1200 1417 1200 1300 1300 1172 1005 1132
PL10*211.2 14 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
SHS100*100*6.0
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
1581

SHS100*100*6.0 SHS100*100*6.0
9 SHS100*100*5.0
+595.270
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0
SHS100*100*6.0 SHS100*100*6.0 SHS100*100*6.0
+595.890 SHS100*100*6.0
SHS150*150*5.0
610

SHS100*100*5.0 7 +594.300

2485
10

2930
+595.270
5341

SHS100*100*5.0 SHS150*150*5.0 SHS150*150*5.0 SHS100*100*6.0


SHS100*100*6.0 SHS100*100*5.0
970

SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 3
+594.300
SHS100*100*5.0 SHS100*100*5.0 +592.795 PROJECT
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0
1515

SHS100*100*5.0 SHS100*100*5.0 +592.350 RIYADH METRO PROJECT


11
445
SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0
PACKAGE 2
SHS100*100*5.0 LINE 3
+592.795
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0
+592.350
445

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
CROSS SECTIONS - 03
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 08 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET


_ _
SEE RGR FOR DESIGN REFERENCE & DETAILS
KEY PLAN:


24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
A B C D MEASUREMENTS PRIOR TO EXECUTION.
A B C D
A* A* 5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
8055 BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
8068 236 3052 3036 1731 7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
249 3052 3035 1732 system
191 535 2173 782 2253 2122 7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
180 480 5288 466 1656 +597.691

220
+597.691 7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
220

RHS150*100*5.0 L220*75*6 RHS150*100*5.0 L220*75*6 L220*75*6


17 WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
+597.471 +597.471 A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
SHS100*100*5.0
IPE200 RHS150*100*5.0 SHS100*100*5.0 (E-70XX ELECTRODES).
RHS150*100*5.0 RHS150*100*5.0 A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
IPE240 IPE240 IPE200 IPE200 IPE240 RHS150*100*5.0 WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.

1581
1581

SHS100*100*5.0 9. FINISH 2 HR FIRE RATED.


SHS150*150*5.0 SHS150*150*5.0 10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
SHS100*100*5.0 SHS100*100*5.0 INSTALLATION OF ANCHOR SITE.
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0 11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
SHS100*100*5.0
AISC360-10.
+595.890 +595.890 SHS100*100*5.0
SHS100*100*5.0

610
TABLE J3.1M
610

Minimum Bolt Pretension, KN"


SHS100*100*6.0 SHS100*100*5.0
+595.270 Bolt Size, mm A325M Bolts A490M Bolts
+595.270

5341
5341

SHS150*150*5.0 SHS150*150*5.0 M16 91 114


SHS100*100*6.0
SHS100*100*6.0

970
M20 142 179
970

SHS100*100*6.0
8 RHS100*100*5
M22

M22
176

205
221

257

M27 267 334


+594.300 +594.300
M30 326 408
SHS100*100*5.0 SHS100*100*5.0
SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0 M36 475 595
Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

1515
1515

SHS100*100*5.0 B- REFERENCE DRAWING:-


M-ANM-3F2DS0-CA00-EDR-200039

SHS100*100*5.0 SHS100*100*5.0 SHS100*100*5.0


SHS100*100*5.0 SHS100*100*5.0

+592.795 +592.795
SHS100*100*5.0

+592.350 +592.350

445
445

PROJECT

RIYADH METRO PROJECT


PACKAGE 2
LINE 3

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
CROSS SECTIONS - 04
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 09 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:

B1


24
)
AH
KK
(MA LINE 4

B2 B2 LINE 2
5 LINE 4 LINE 6
110
100 LINE 2
LINE 6
5 LINE 1
27 115
SHS 100*100*5
LINE 5

24
END SHS NOTCH PLATE

2
330x100x10mm
FILLET WELD 6mm Size 45 10 45
LINE 3.
3F2
SHS 150x150x5mm SHS 100*100*5
2 END CAP

53
80x35x5mm

35
LINE 1
42

2 M 12
THROUGH
BOLTS 2 END CAP
LENGTH 100MM . 80x35x5mm
176

A- NOTES:-
2 M 12
GUSSET BRACING 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
THROUGH
PLATE SPECIFICATIONS.
BOLTS
274X10 MM. FILLET WELD 6mm Size
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
LENGTH 100MM . COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
GUSSET BRACING 4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
PLATE MEASUREMENTS PRIOR TO EXECUTION.
274X10 MM. 5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
B1 system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
DETAIL "11" SECTION B1-B1 MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.

scale 1:10 scale 1:10 7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
DETAIL [ D ] A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221

M22 205 257

M27 267 334

M30 326 408

M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039

SHS 100*100*5
SHS 150x150x5mm

GUSSET BRACING 150


SHS 100*100*5
PLATE
278X10 MM.
END SHS NOTCH PLATE
PROJECT
330x100x10mm
SHS 150x150x5mm
105

RIYADH METRO PROJECT


45 10 45

PACKAGE 2
10

LINE 3
35

2 M 12
THROUGH
BOLTS
LENGTH 100MM .
2 M 12
THROUGH
BOLTS FILLET WELD
LENGTH 100MM . ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SECTION B2-B2 DETAIL "11-3D" GUSSET BRACING


PLATE
scale 1:10 278X10 MM.
SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
DETAILS-01
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 10 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:

L1
N

END PLATE - 250 x 100 x 10 mm. THK.


24
H)
KKA
(MA LINE 4

RHS1150*100*5
LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1
SHS 100x100x6mm
SHS 100x100x6mm

N N STEEL STIFFNER A- NOTES:-


Q Q STEEL STIFFNER 100x100x10mm L1
100x100x10mm 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
CJB WELD
CJB WELD DETAIL "14" SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
BASE PLATE COMPUTED.
BASE PLATE 300x220x12mm 3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
330x220x12mm
25mm Thk. NON SHRINKABLE 4 NOS. M12 BOLTS (Grade A490M) 4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
25mm Thk. NON SHRINKABLE GROUT MIN. COMPRESSVE
GROUT MIN. COMPRESSVE STRENGTH 50MPa CJB WELD 5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
STRENGTH 50MPa
RHS150*100*5 ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
TOP OF UPSTAND WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
TOP OF UPSTAND 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
4 ANCHOR BOLTS
4 ANCHOR BOLTS 7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
HIT-HY 200-R +HIT-V-F 7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
HIT-HY 200-R +HIT-V-F GRADE (8.8) M16x300mm 7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
GRADE (8.8) M16x300mm WITH CHEMICAL INJECTION system
WITH CHEMICAL INJECTION 7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
· A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A

DETAIL "5" DETAIL "6" WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.

scale 1:10 · 9. FINISH 2 HR FIRE RATED.


scale 1:10 SECTION L1-L1
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
scale 1:10 11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

IPE200 Bolt Size, mm A325M Bolts A490M Bolts

STEEL STIFFNER STEEL STIFFNER M16 91 114

100x100x10mm
FILLET WELD
100x100x8mm
4 ANCHOR BOLTS
PL10*110 M20

M22
142

176
179

221
HIT-HY 200-R +HIT-V-F
GRADE (8.8) M16x300mm
SHS 100x100x6mm
IPE240 O
M22

M27
205

267
257

334
WITH CHEMICAL INJECTION
M30 326 408
3 BOLTS M12 M36 475 595

60 25 50 15
Gr. A490M Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-

15 50 25
M-ANM-3F2DS0-CA00-EDR-200039

FILLET WELD
5 5 6 6

4 ANCHOR BOLTS
HIT-HY 200-R +HIT-V-F
GRADE (8.8) M16x300mm DETAIL "17"
WITH CHEMICAL INJECTION
scale 1:10
IPE200
IPE200 PL10*110 O
PROJECT

RIYADH METRO PROJECT


IPE240 PACKAGE 2
SHS 100*100*6
LINE 3

SECTION Q - Q SECTION N - N ARRIYADH NEW MOBILITY

scale 1:10 scale 1:10


ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
· ·
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
· ·
SECTION O-O
scale 1:10 SHAFT
· · 30 50 80 30 DETAILS-02
· · 6 ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 11 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


24
)
AH
KK
(MA LINE 4

Plan view of typical floor layout Opening Propping Fixing LINE 4 LINE 6 LINE 2

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1

A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL

Deck notation BEARING SURFACE UNLESS SHOWN OTHERWISE.


7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
LEGEND : 7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy

60

46
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221

M22 205 257


Closure plate in 2mm flat
steel strip to suit remainder
M27 267 334
of floor area to a maximum
of 245mm. M30 326 408

M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039
SIDE DETAIL EDGE WITH PLATE END DETAIL

PROPPED EDGE TRIM

PROJECT

RIYADH METRO PROJECT


PACKAGE 2
LINE 3

INSTALLATION OF DECK ONTO LEADER ANGLE

END CANTILEVER BUTT JOINT END DETAIL WITH CLOSURE


ARRIYADH NEW MOBILITY

TYPICAL WALL DETAILS


ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
DETAILS-03

CHANGE OF DIRECTION CHANGE OF DIRECTION WITH LEADER ANGLE


CONNECTION TO STRUCTURAL WALL CF60 ANM DRAWING NUMBER

M-ANM-3F2DS0 -CBST -SDR-000056


REVISION

B
SHEET
13 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:

®
ComFlor 60


SHS 100x100x5mm

24
H)
KKA
(MA LINE 4

E CJB WELD

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

LINE 3.
3F2

LINE 1
E
Colour side when
Colorcoat FD® deck is
specified DETAIL "7"
scale 1:10 A- NOTES:-

SHS 100x100x5mm 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SPECIFICATIONS.
CJB WELD 2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
Gauge Yield Zinc Coating Maximum Minimum 7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
(mm) Substrate (N/mm2) Surface Finish mass** (g/m2) Length (mm) Length (mm) WITH GRADE 8.8.
· 8. A. Welding Specification:
® ® A1.Welding Shall BE IN Conformance With AWS 01.1
0.90 Steel 350 Galvatite *Colorcoat FD Z 275 12000 800
· A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
1.00 Steel 350 Galvatite® *Colorcoat FD® Z 275 12000 800 (E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
1.20 Steel 350 Galvatite® *Colorcoat FD® Z 275 12000 800 WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
*Also available in a galvanized substrate with a painted topcoat available in white as standard.
**Minimum zinc coating mass, total both sides.
SECTION E-E 9. FINISH 2 HR FIRE RATED.
ComFlor®, Galvatite® and Colorcoat FD® are registered trademarks of Tata Steel UK Limited. Manufactured to BS EN 10346 scale 1:10 10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221

M22 205 257

SHS150*150*5.0 M27

M30
267

326
334

408

M36 475 595


SHS150*150*5.0 Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

B- REFERENCE DRAWING:-
M-ANM-3F2DS0-CA00-EDR-200039

SHS150*100*5.0

FILLET WELD 5mm Size


PL20*207.7
207

SHS150*100*5.0
35
50
45

PROJECT
10

RIYADH METRO PROJECT


115 PACKAGE 2
18

2 M12A490 LINE 3
0

FLT10*110

ARRIYADH NEW MOBILITY

SHS100*100*5.0
SHS100*100*5.0 2 M12A490 CHECK REVIEW APPROVAL
ORIGINATOR

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
SHAFT
DETAIL "9" DETAIL "9-3D" DETAILS-04
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 13 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


C1

24
)
AH
KK
(MA LINE 4

LINE 6 LINE 2
LINE 4

LINE 2
LINE 6
LINE 1

LINE 5

SHS 150x150x5mm

C2 C2 LINE 3.

30
3F2

55
LINE 1
SHS 100x100x5mm SHS 100x100x5mm

130
100

50
30

A- NOTES:-

55

25
1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
130

100

SPECIFICATIONS.

50
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
2 M12 THROUGH 25 100 25 COMPUTED.
BOLT 3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE

25
40 50 MEASUREMENTS PRIOR TO EXECUTION.
SHS 100x100x5mm 150 5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
FILLET WELD 2 M12 THROUGH
BOLT SECTION [ H - H ] WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL
25 100 25 SCALE: 1:6
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
150 7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
C1 MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
DETAIL "8" SECTION C1 - C1 REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
scale 1:10 scale 1:10 11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.

TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221


K1 2 BOLTS M12 K1 M22 205 257
K2 Gr. A490M
M27 267 334
PL 95X10MM
M30 326 408

M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

PL 95X10MM B- REFERENCE DRAWING:-


M-ANM-3F2DS0-CA00-EDR-200039
2 BOLTS M12
SHS 100x100x5mm Gr. A490M
Grating
SHS 100X6 SHS 100X6

5
50 100 typ.
SHS 150x150x5mm
SHS 100x100x5mm

DETAIL "15" SEC.( K2-K2 )


K2
scale 1:10 scale 1:10
50

80

PROJECT
60 10
100

RIYADH METRO PROJECT


2 BOLTS M12 6 typ. 6 typ. PACKAGE 2
Gr. A490M
LINE 3
PL 95X10MM

60 10 80

ARRIYADH NEW MOBILITY

SHS 100X6 SHS 100X6


ORIGINATOR CHECK REVIEW APPROVAL
6 typ.
R.T R.T R.T L.M
SHSH 100X5 SCALES ORIGINAL SIZE A1
SECTION [ G - G ] · SHS 100 x 100 x 5 mm. THK. DATE
A1= 1: 100
SCALE: 1:6
22.06.2023 A3= 1: 200
0 100 200

SEC.( K1-K1 ) · ALL PLATES 10 mm. THK.


SECTION C2 - C2 · 4 NOS. M12 BOLTS (Grade A490M)
scale 1:10 scale 1:10 SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
· CJB WELD UNLESS NOTED
SHAFT
DETAILS-05
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 14 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


24
)
AH
KK

A
(MA LINE 4

SHS100*100*5.0 LINE 2
LINE 4 LINE 6

180
LINE 2
LINE 6
LINE 1

LINE 5

65
SHS100*100*5.0

24
LINE 3.

50
3F2
2M 12 THROUGH
BOLTS
LENGTH 100MM 55
. LINE 1
55 110

50
35

295
A- NOTES:-

1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE


SHS100*100*5.0
SPECIFICATIONS.
PL10*110 2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR

34
COMPUTED.

50
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).

50
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
MEASUREMENTS PRIOR TO EXECUTION.

65
5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS

24
SHS100*100*5.0 WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.

7
6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL

180
BEARING SURFACE UNLESS SHOWN OTHERWISE.
7. MATERIAL:
7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
SHS100*100*5.0 7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
45 10 45
system
100 7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,

A
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.

DETAIL "10" SECTION A-A SECTION [ A - A ]


7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
scale 1:10 scale 1:10 SCALE: 1:6
8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
AISC360-10.
BASE PLATE H H TABLE J3.1M
350x180x12mm Minimum Bolt Pretension, KN"
SHS 150x150x5mm Bolt Size, mm A325M Bolts A490M Bolts
25mm Thk. NON SHRINKABLE M16 91 114
GROUT MIN. COMPRESSVE M20 142 179

STRENGTH 50MPa M22 176 221

CJB WELD M22 205 257

M27 267 334


TOP OF UPSTAND EXISTING RCC M30 326 408

WALL M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
as specified in ASTM specification for A325M and A490M bolts with UNC threads.

SHS 100*100*5mm B- REFERENCE DRAWING:-


M-ANM-3F2DS0-CA00-EDR-200039

4 ANCHOR BOLTS
HIT-HY 200-R +HAS-U
GRADE (8.8) M16x300mm
WITH CHEMICAL INJECTION

DETAIL "2"
scale 1:10
SHS 150x150x5mm PROJECT
SHS 100x100x5mm
4 ANCHOR BOLTS RIYADH METRO PROJECT
HIT-HY 200-R +HAS-U 2M 12 THROUGH PACKAGE 2
GRADE (8.8) M16x300mm BOLTS LINE 3
WITH CHEMICAL INJECTION LENGTH 100MM
CJB WELD .

SHS 100*100*5 MM
ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M


DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

· SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
· DETAIL "10-3D"
SHAFT
DETAILS-06
·
SECTION H - H ANM DRAWING NUMBER REVISION SHEET

scale 1:10 M-ANM-3F2DS0 -CBST -SDR-000056 B 15 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _


KEY PLAN:


Grating = 30mm X 5mm

24
)
AH
KK
(Spacing = 30mm) (MA LINE 4
Cross bar = 5mm X 5mm
(Spacing = 50mm) I
SHS 150x150x5mm PLATE 30x5mm
A A CJB WELD FILLET WELD LINE 4 LINE 6 LINE 2

SHS 100x100x5mm EXISTING RCC


CJB WELD LINE 2
LINE 6
WALL
LINE 1
4 ANCHOR BOLTS
BASE PLATE HIT-HY 200-A +HIT-V-F LINE 5
320x190x12mm GRADE (8.8) M16x300mm
WITH CHEMICAL INJECTION FILLET WELD
25mm Thk. NON SHRINKABLE
GROUT MIN. COMPRESSVE LINE 3.
3F2
STRENGTH 50MPa
TOP OF UPSTAND
LINE 1
FILLET WELD
4 ANCHOR BOLTS
HIT-HY 200-R +HIT-V-F
GRADE (8.8) M16x150mm PLATE
WITH CHEMICAL INJECTION 200x150x10mm
A- NOTES:-
2 M12 THROUGH
BOLT
10mm thk. STEEL 1. THE NOTES SHALL BE READ IN CONJUNCTION WITH THE
SPECIFICATIONS.
STIFFNER
2. DO NOT SCALE FROM DRAWINGS, ALL DIMENSIONS SHOULD BE READ OR
FILLET WELD COMPUTED.
3. DIMENSIONS ARE GIVEN IN MM (U.N.O.).
4. ALL LEVELS AND DIMENSIONS ARE TO BE VERIFIED BY SITE
4 ANCHOR BOLTS MEASUREMENTS PRIOR TO EXECUTION.
HIT-HY 200-A +HIT-V-F I 5. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT
DETAIL "1" SECTION A - A GRADE (8.8) M12x150mm SECTION I - I ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL,
ELECTRICAL, TELECOMMUNICATION AND LANDSCAPE DRAWINGS: AS
WITH CHEMICAL INJECTION
scale 1:10 scale 1:10 scale 1:10 WELL AS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.

DETAIL "3" 6. ANCHOR BOLTS SHOULD BE SET PERPENDICULAR TO THE THEORETICAL


BEARING SURFACE UNLESS SHOWN OTHERWISE.

scale 1:10 7. MATERIAL:


7.1. HOT DIP GALVANIZED TUBES >> ASTM A500 GR B
7.2. STEEL PLATES & ROLLED SECTIONS >> ASTM A572 GR 50
7.3. Grating>> Mild steel with Hot dip galvanized + paint three coat epoxy
system
7.4. HEXAGONAL BOLTS >> BLACK HIGH STRENGTH WITH GRADE 10.9,
MINIMUM PRETENSION VALUE AS PER AISC 360 CHAPTER J.
· ·
7.5. ANCHOR BOLTS FROM HILTI >> HOT DIP GALVANIZED FINISH
WITH GRADE 8.8.
· 8. A. Welding Specification:
A1.Welding Shall BE IN Conformance With AWS 01.1
· · A2.Welding ELECTRODES SHALL BE COMPLYING WITH AWS CODE
(E-70XX ELECTRODES).
· A3.THE NOTE SPECIFIED WELDING CABLES IN ANGLE WILL HAVE A
WELD THK. 0.7 TIMES THE THK. OF THE PLATES IN CONTACT AND 0.8
TIMES OF THE THICK. IF IT IS EXECUTED IN EITHER SIDES.
9. FINISH 2 HR FIRE RATED.
10. BASE PLATE ANCHOR SPACING SHALL BE SPACED CONSIDERING THE
REBAR CLASH AND "REBAR SCANNING SHALL BE DONE BEFORE THE
INSTALLATION OF ANCHOR SITE.
Grating = 30mm X 5mm 11. STRUCTURAL CONNECTION FASTENER PRE-TENSION CHART
(Spacing = 30mm) AISC360-10.
Cross bar = 5mm X 5mm X
(Spacing = 50mm) TABLE J3.1M
Minimum Bolt Pretension, KN"

Bolt Size, mm A325M Bolts A490M Bolts

M16 91 114

M20 142 179

M22 176 221

M22 205 257

M27 267 334

M30 326 408

M36 475 595


Equal to 0.70 times the minimum tensile strength of bolts.rounded off to nearest KN"
ANGULAR as specified in ASTM specification for A325M and A490M bolts with UNC threads.

100x100x10mm
B- REFERENCE DRAWING:-
8mm thk. STEEL STIFFNER M-ANM-3F2DS0-CA00-EDR-200039
@@EVERY 400mm X
ANCHOR BOLT
GRADE (808) M12x120mm
@EVERY 400mm
6mm FILLET WELD
DETAIL "4"
scale 1:10

PROJECT

RIYADH METRO PROJECT


PACKAGE 2
LINE 3
Grating = 30mm X 5mm
(Spacing = 30mm)
Cross bar = 5mm X 5mm
(Spacing = 50mm) 8mm thk. STEEL STIFFNER
@EVERY 400mm

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

R.T R.T R.T L.M

1000
DATE SCALES ORIGINAL SIZE A1
A1= 1: 100
22.06.2023 A3= 1: 200
0 100 200

SUBJECT TITLE
DEEP UNDER GROUND STATION 3F2 (VS-01) VENTILATION
ANGULAR ANCHOR BOLT 6mm FILLET WELD
SHAFT
SEC.( X-X ) 100x100x10mm GRADE (808) M12x120mm
@EVERY 400mm
DETAILS-07
scale 1:10
ANM DRAWING NUMBER REVISION SHEET

M-ANM-3F2DS0 -CBST -SDR-000056 B 16 OF 16

ALTERNATE DOCUMENT NUMBER REVISION SHEET

SEE RGR FOR DESIGN REFERENCE & DETAILS _ _