A breaker which used vacuum as an arc extinction medium is called a vacuum circuit breaker. In
this circuit breaker, the fixed and moving contact is enclosed in a permanently sealed vacuum
interrupter. The arc is extinct as the contacts are separated in high vacuum. It is mainly used for
medium voltage ranging from 11 KV to 33 KV.
Vacuum circuit breaker has a high insulating medium for arc extinction as compared to the
other circuit breaker. The pressure inside the vacuum interrupter is approximately 10 -4 torrent
and at this pressure, very few molecules are present in the interrupter. The vacuum circuit
breaker has mainly two phenomenal properties.
1. High insulating strength: In comparison to various other insulating media used in circuit
breaker vacuum is a superior dielectric medium. It is better than all other media except air
and SF6, which are employed at high pressure.
2. When an arc is opened by moving apart the contacts in a vacuum, an interruption occurs
at the first current zero. With the arc interruption, their dielectric strength increases up to
a rate of thousands time as compared to other breakers.
The above two properties make the breakers more efficient, less bulky and cheaper in cost. Their
service life is also much greater than any other circuit breaker, and almost no maintenance are
required.
The fixed and moving contacts of the breaker are placed inside the arc shield. The pressure in a
vacuum interrupter at the time of sealing off is kept at about 10 -6 torr. The moving contacts of
the circuit breaker are move through a distance of 5 to 10 mm depending upon the operating
voltage.
The metallic bellows made of stainless steel is used to move the moving contacts. The design of
the metallic bellows is very important because the life of the vacuum circuit breaker depends on
the ability of the component to perform repeated operations satisfactorily.
The density of vapour depends on the current in the arcing. Due to the decreasing mode of
current wave their rate of release of vapour fall and after the current zero, the medium regains its
dielectric strength provided vapour density around the contacts reduced. Hence, the arc does not
restrike again because the metal vapour is quickly removed from the contact zone.
Current Chopping in Vacuum Circuit Breaker
Current chopping in vacuum circuit breaker depends on the vapour pressure and the electron
emission properties of the contact material. The chopping level is also influenced by the thermal
conductivity–lower the thermal conductivity, lower is the chopping level.
It is possible to reduce the current level at which chopping occurs by selecting a contact material
which gives out sufficient metal vapour to allow the current to come to a very low value or zero
value, but this is rarely done as it affects the dielectric strength adversely.
Because of the above-mentioned attribute of vacuum circuit breaker, it is capable of handling the
severe recovery transients associated with short-line faults without any difficulty.
A vacuum circuit breaker is a kind of circuit breaker where the arc quenching takes place in
vacuum medium. The operation of switching on and closing of current carrying contacts and
interrelated arc interruption takes place in a vacuum chamber in the breaker which is called
vacuum interrupter.
Because of the short gap and excellent recovery of vacuum circuit breaker, they are very
useful as very high speed making switches in many industrial applications.
When the voltage is high and current to be interrupted is low these breakers have definite
superiority over the other breakers.
For low fault interrupting capacities the cost is low in comparison to other interrupting
devices.
Because of the least requirements of maintenance, these breakers are very suitable for the
system which requires voltage from 11 to 33 kV