1769-ECR
1769-ECR
Original Instructions
Topic Page
Summary of Changes 2
1769-ECL Left End Cap and 1769-ECLK Left End Cap 5
1769-ECL and 1769-ECLK Dimensions 5
1769-ECR and 1769-ECRK Right End Cap 6
1769-ECR and 1769-ECRK Dimensions 7
Specifications 8
Environmental Specifications 8
Certifications 9
Additional Resources 9
Summary of Changes
This publication contains new and updated information as indicated in the following table.
Topic Page
Updated certification and warning information. Throughout
The following information applies when operating Informations sur l’utilisation de cet équipement en
this equipment in hazardous locations. environnements dangereux.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
use in Class I Division 2 Groups A, B, C, D, Hazardous Locations
and nonhazardous locations only. Each product is supplied Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
with markings on the rating nameplate indicating the indiquent le code de température pour les environnements
hazardous location temperature code. When combining
products within a system, the most adverse temperature dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
code (lowest “T” number) may be used to help determine température le plus faible) peut être utilisé pour déterminer le
the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
local Authority Having Jurisdiction at the time of installation. autorités locales qualifiées au moment de l'installation.
WARNING: AVERTISSEMENT:
Explosion Hazard – Risque d’Explosion –
• Do not disconnect equipment • Couper le courant ou s'assurer que
unless power has been removed or l'environnement est classé non
the area is known to be dangereux avant de débrancher
nonhazardous. l'équipement.
• Do not disconnect connections to • Couper le courant ou s'assurer que
this equipment unless power has l'environnement est classé non
been removed or the area is known dangereux avant de débrancher les
to be nonhazardous. Secure any connecteurs. Fixer tous les connecteurs
external connections that mate to externes reliés à cet équipement à l'aide
this equipment by using screws, de vis, loquets coulissants, connecteurs
sliding latches, threaded filetés ou autres moyens fournis avec ce
connectors, or other means produit.
provided with this product. • La substitution de composants peut
• Substitution of components may rendre cet équipement inadapté à une
impair suitability for Class I, utilisation en environnement de Classe
Division 2. I, Division 2.
• If this product contains batteries, • S'assurer que l'environnement est classé
they must only be changed in an non dangereux avant de changer les
area known to be nonhazardous. piles.
2 3
118 mm
(4.65 in.)
Specifications
Attribute 1769-ECL, 1769-ECLK 1769-ECR, 1769-ECRK
Current draw at 5.1V DC 5 mA
Current draw at 24V DC 0 mA
Operating altitude 2000 m (6562 ft)
North American temp code T3C
IEC temp code — T4
Shipping weight, approx 130 g (0.286 lb)
Enclosure type rating None (open style)
Environmental Specifications
Attribute 1769-ECL, 1769-ECLK 1769-ECR, 1769-ECRK
Operating temperature
IEC 60068-2-1 (Test Ad, Operating Cold)
0 > Ta > 60 °C (32 > Ta > 140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Nonoperating temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating -40 > Ta > 85 °C (-40 > Ta > 185 °F)
Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity 5…95% noncondensing
Vibration
5 g, 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Operating shock
DIN rail mount: 20 g; Panel mount: 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Nonoperating shock
DIN rail mount: 30 g; Panel mount: 40 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions
Group 1, Class A
CISPR 11
ESD immunity
8 kV air discharges
IEC 61000-4-2
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz
Radiated RF immunity
10V/m with 200 Hz 50%Pulse 100% AM at 900 MHz
IEC 61000-4-3
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
Certifications
Certifications(1) 1769-ECL, 1769-ECLK 1769-ECR, 1769-ECRK
UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for U.S. and
c-UL-us
Canada. See UL File E334470
European Union 2014/30/EU EMC Directive, compliant with:
CE EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Australian Radiocommunications Act, compliant with:
RCM
AS/NZS CISPR 11; Industrial Emissions
European Union 2014/30/EU ATEX Directive,
compliant with:
EN 60079-15; Potentially Explosive
Atmospheres, Protection ‘n’
(II 3 G Ex nA IIC T4 Gc)
Ex — EN 60079-0; General Requirements (Zone 2)
IECEx; Correspond to Zone 2 classification to
IEC 60079-0.The type of protection is ‘Ex nA
IIC T4 Gc’ according to IEC 60079-15.
Reference IECEx certificate number IECEx
UL 20.0078X.
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Additional Resources
These documents contain additional information concerning related products from Rockwell
Automation.
Resource Description
Provides information on how to install any 1769 Compact I/O
Compact I/O Modules, publication 1769-IN088A module.
1769 Compact I/O Modules Specifications,
Provides technical data for 1769 Compact I/O modules.
publication 1769-TD006
Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell
publication 1770-4.1 Automation industrial system.
Product Certifications website,
Provides declarations of conformity, certificates, and other
http://www.rockwellautomation.com/global/certification/ certification details.
overview.page
Technical Support Knowledgebase Articles, How-to Videos, FAQs, Chat, User https://
Center Forums, and Product Notification Updates. rockwellautomation.custhelp.com/
Local Technical
http://www.rockwellautomation.com/
Support Phone Locate the phone number for your country. global/support/get-support-now.page
Numbers
Find the Direct Dial Code for your product. Use the code to http://www.rockwellautomation.com/
Direct Dial Codes
route your call directly to a technical support engineer. global/support/direct-dial.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions
on how to improve this document, complete the How Are We Doing? form at http://
literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
At the end of life, this equipment should be collected separately from any unsorted
municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, Compact I/O, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400