Compilation Problems in Ec 3
Compilation Problems in Ec 3
in
EE 312 – ELECTRICAL CIRCUITS 3
Star/Delta Connections
1. Three equal impedances each having a resistance of 20 Ω and reactance
of 15 Ω are connected in star to a 400 V, 3-phase, 50 Hz system.
Calculate:
a. The line current, (iii) The power factor, and
b. The power consumed. [Ans. 9.24 A ; 0.8 (lag) ; 5120 W]
12. Three identical coils connected in delta across 400 V, 50 Hz, 3- phase
supply takes a line current of 17.32 A at power factor 0.5 lagging.
Determine: (i) The current in each phase, and (ii) Resistance,
inductance and impedance of each phase winding. [Ans. 10 A ; 20 Ω ;
0.11 H, 40 Ω]
14. Calculate (i) line current and (ii) the total power absorbed when
three coils each having a resistance of 10 Ω and reactance of 7 Ω are
connected (a) in star and (b) in delta across a 400 V, 3-phase supply.
[Ans. 18.93 A, 10750 W ; 56.7 A, 32250 W]
ESSU-ACAD-710.a | Version 5
Effectivity Date: March 15, 2024
2
15. A delta-connected balanced 3-phase load is supplied from a 3-phase
400 V supply. The line current is 20 A and power taken by the load is
10000 W. Find: (i) Impedance in each branch; and (ii) The line current,
power factor and power consumed if the same load is connected in star.
[Ans. 34.6 Ω, 20/3 A, 0.7217, 3330 W]
18. Three 100 Ω non-inductive resistances are connected in (i) star (ii)
delta across a 400 V, 50 Hz, 3-phase mains. Calculate the power taken
from the supply system in each case. In the event of one of the three
resistances opened, what would be the value of the total power taken
from the mains in each of the two cases. [Ans. 1600 W ; 4800 W]
19. A 3-phase delta connected load; each phase of which has an inductive
reactance of 40 Ω and a resistance of 25 Ω, is fed from the secondary
of a 3-phase star-connected transformer, which has phase voltage of 240
V. Draw the circuit diagram of the system and calculate: (i) The current
in each phase of the load, (ii) The voltage across each phase of the
load, (iii) The current in the transformer secondary windings, and (iv)
The total power taken from the supply and its power factor.
[Ans. 8.8 A ; 415.7 V ; 15.3 A ; 5820 W]
20. Three similar resistors are connected in star across 400 V, 3-phase
supply. The line current is 5 A. Calculate the value of each resistor.
To what value line voltage be changed to obtain the same current with
the resistors connected in delta? [Ans. 46.2 Ω ; 133.3 V]
21. A 3-phase, star-connected system with 230 V between each phase and
neutral has a resistance of 4, 5 and 6 Ω respectively in three phases.
Calculate:(i) The current flowing in each phase, (ii) The neutral
current, and(iii) The total power absorbed. [Ans. 57.5 A, 46 A, 38.3
A ; 16.71 A ; 32610 W]
24. While performing a load test on a 3-phase wound rotor induction motor
by two wattmeters method, the readings obtained on two wattmeters were
+ 12.5 kW and – 4.8 kW and the line voltage was 440 V. Calculate : (i)
Power drawn by the motor, (ii) Power factor, and (iii) Line current.
[Ans. 7.7 kW ; 0.2334 ; 43.3 A]
26. A 3-phase, 500 V motor load has a power factor of 0.4. Two wattmeters
connected to measure the power show the input to be 30 kW. Find the
reading on each instrument. [Ans. 35 kW ; – 5 kW]
28. Two wattmeters used to measure the power input in a 3-phase circuit
indicate 1000 W and 500 W respectively. Find the power factor of the
circuit (i) when both wattmeter readings are positive ; and (ii) when
the latter is obtained by reversing the current coil connections. [Ans.
0.866 (lag) ; 0.1889 (lag)]
29. Two wattmeters connected to read the total power in a 3-phase system
supplying a balanced load read 10.5 kW and – 2.5 kW respectively.
Calculate the total power and the power factor. Draw suitable phasor
diagram, explain the significance of(i) equal wattmeter readings ; and
(ii) a zero reading on one wattmeter.[Ans. 8 kW ; 0.3348 (lag) (i) unity
p.f., (ii) 0.5 p.f.]
ESSU-ACAD-710.a | Version 5
Effectivity Date: March 15, 2024
4
30. The power input to a l000 V, 3-phase induction motor running on full-
load is measured by two wattmeters which indicate 300 kW and 100 kW
respectively. Determine:(i) Input, (ii) Line current,(iii) Power factor,
and (iv) Output if the efficiency of the motor is 92%.[Ans. 400 kW ;
303.5 A ; 0.756 (lag) ; 368 kW]
31. Two wattmeters are used for measuring the power input and the power
factor of an over-excited synchronous motor. If the readings of the
meters are – 2.0 kW and + 7.0 kW respectively, calculate the input and
power factor of the motor. [Ans. 5 kW ; 0.3057 (leading)]
32. The power input to a 2-kV, 50 Hz, 3-phase motor running on full-load
at an efficiency of 90 percent is measured by two wattmeters which
indicate 300 kW and 100 kW respectively. Calculate: (i) Input, (ii)
Power factor, (iii) Line current, and (iv) Output.[Ans. 400 kW ; 0.756
(lag) ; 153 A ; 360 kW]
37. A balanced load is supplied from a 3-phase, 400 V, 3-wire system whose
power is measured by two wattmeters. If the total power supplied is 26
kW at 0.75 power factor lagging, find the readings of each of the two
wattmeters. [Ans. 19.62 kW ; 6.38 kW]
ESSU-ACAD-710.a | Version 5
Effectivity Date: March 15, 2024
5
38. A 3-phase 4-wire, star-connected system supplies only non-inductive
load. The current in line R is 8 A, the current in line Y is 10 A and
the current in line B is 6 A. The voltage from each line to neutral is
120 V. Find:(i) Wattage shown by each of the three wattmeters, and (ii)
Power taken by the lighting load. [Ans. 960 W, 1200 W, 720 W ; 2880 W]
Prepared by:
Engr. Ronnie A. Cadalin, REE, RME, MATVE
ESSU-ACAD-710.a | Version 5
Effectivity Date: March 15, 2024
6