Keypad 6139v8
Keypad 6139v8
N6752V8 8/98
REMOTE KEYPADS
6128, 6137, 6137R, 6138, 6139, & 6139R
INSTALLATION GUIDE
6128 6137/6137R 6138 6139/6139R
KEYPAD FEATURES Fixed-Word Fixed-Word 1-Line Alpha 2-Line Alpha
Keypad Keypad Keypad Keypad
Backlit Display No Yes (see note below) Yes (see note below) Yes (see note below)
Dedicated Panic Keys No Yes Yes Yes
Flush Mount Option No No Yes Yes
All the above keypads have backlit keys, are keypad addressable, have a Red ARMED indicator and a Green READY indicator.
ADEMCO CONTROLS ▼ ▼ ▼ ▼
VIA16*/4110XM* / 4110DL* Yes Yes, 6137 No No
VIA30P†*/ VIA30PSE†* Yes Yes, 6137 Yes Yes, 6139
GENERAL INFORMATION
All keypads allow panic alarm activation (if enabled in control
The 6128, 6137, 6137R, 6138, 6139, and 6139R Remote Keypads are programming). For the 6128, panic alarms are activated by pressing
keypad addressable (no DIP switches), and are intended for use with key pairs [1] & [✱], [✱] & [#], and [3] & [#]. The 6137/6137R, 6138, and
the controls listed in the table above. They can be set for the non- 6139/6139R are equipped with dedicated single keys for panic
addressable operation (address 31) if required by the control with activation — keys A, B, and C (the D key is not used as panic), which
which they are used. are equivalent to the [1] & [✱], [✱] & [#], and [3] & [#] keys,
Note: The 6137R and 6139R have red bezels instead of gray. respectively.
Otherwise, they are exactly the same as the 6137 and 6139,
Single panic keys (A, B, and C) must be held down for at least
respectively.
2 seconds to activate an alarm.
The 6128 and 6137 are fixed-word keypads that provide two-digit
numerics for zone identification, and a set of pre-designated English A set of adhesive-backed labels with some typical panic symbols (i.e.,
language prompts (e.g., ALARM, AWAY, STAY, CHECK, etc.) for fire, police, personal emergency, etc.) is provided. These labels can be
indicating the system's status. The 6138 is a one-line alpha keypad placed on or next to the keys to identify each key's function for the end
that displays a 2-line message one line at a time. user (as determined by the control panel's capability and programming;
The 6139 is a two-line alpha keypad equipped with a programmable 2- see the control's instructions).
line, 32-character (16 characters per line) English language display for
complete zone identification (if descriptors are programmed), plus
WIRING AND INSTALLATION
system status. To display the second line of information, press the [#]
key. Press the [#] key again to return to the first line of information. The keypads can be surface mounted directly to a drywall, or to a
The display automatically returns to the first line of information if no single- or double-gang electrical box. For flush mounting the 6138 and
key is pressed for three seconds. 6139/6139R to drywall, use the optional 6139TRK Flush Mount Kit
(6128 & 6137/6137R cannot be flush mounted).
Note: After pressing the [#] key to view the second line or return to
the first line, wait at least three seconds before entering a control panel 1. Remove the case back by pushing down two "snaps." See diagram on
command (e.g., arm the system). the next page.
The keys on the keypads are located behind a decorative door, and are 2. Route wiring from the control panel through the opening in the case
continuously backlit for convenience. The inside of the decorative door back.
has space for a zone ID label (supplied) on which the installer can write 3. Mount the case back to a wall or electrical box.
descriptions of each zone for handy user reference.
4. Plug the supplied flying lead connector into the keypad PC board NOTE: The keypad will not enter address mode if the panel to which
and splice the panel wiring to it, or wire directly to the terminal it is connected is in programming mode.
block on the PC board (wire colors are marked next to terminals). 2. Set the current address to "00": Press [0] to clear the current "tens"
Wire colors and functions are described in the SPECIFICATIONS digit. The cursor will move to the "ones" digit position. Press [0] to
section. clear the current "ones" digit. The cursor will move back to the
5. Re-attach the keypad to its case back.
"tens" digit position.
6. Remove the clear protective films from the LCD display and keypad
3. Enter the keypad's address: Enter the proper "tens" digit of the
labels. keypad's address. The cursor will move to the "ones" digit position.
Enter the proper "ones" digit of the keypad's address. Note that
address "31" sets the keypad to non-addressable mode.
4. Exit address mode:
Press [✱] to save the displayed address and exit address mode.
Remove VIEWING THE KEYPAD ADDRESS
case back
by pushing Press and hold down the [1] and [3] keys at the same time for about 3
down the
2 “snaps”
seconds. The current address is displayed. No key entry is allowed.
ARMED READY
along the Press any key to exit or wait 10 seconds to exit viewing mode.
1 2 3 keypad’s
OFF AWAY STAY SPECIFICATIONS
top edge
4 5 6
MAX TEST BYPASS and pulling Physical:
7 8 9 the case 6128: 4-3/4"H x 5-3/4"W x 1"D (121mm x 146mm x 25.4mm)
INSTANT CODE CHIME apart.
6137/6137R: 4-3/4"H x 6-1/4"W x 1"D (121mm x 159mm x 26mm)
*
READY
0
PANIC
#
6138/6139/6139R: 4-3/4"H x 6-3/4"W x 1-1/4"D
(121mm x 159mm x 32mm)
LOCATION OF DEDICATED Wiring: Red: +12VDC
PANIC KEYS. “D” KEY NOT USED
FOR PANIC FUNCTIONS.
(all Keypads) Black: Ground.
Blue: If present, not used.
Green: Data to control panel.
Yellow: Data from control panel.
SETTING THE KEYPAD ADDRESS Current:
The keypad can be set for an address of 0-31 (the keypad will not 6128: 40mA sounder on, 20mA standby, alarm sounder off.
accept entries greater than 31), which is stored in EEROM memory. 6137/6137R: 85mA (ARMED LED lit, LCD backlight and sounder on),
The keypad's default address is 31 (non-addressable mode–some early reduces to 40mA when panel is operating in standby
versions of 6139/6139R default to 11). mode (backlight off).
To change the keypad's address, do the following: 6139/6139R: 100mA (ARMED LED lit, LCD backlight and sounder
1. Enter address mode: Power up (plugin) the keypad. Within 60 on), reduces to 40mA when panel is operating in standby
seconds of power-up, press and hold down the [1] and [3] keys at the mode (backlight off).
same time for 3 seconds. (If unable to enter address mode, power up
and try again.) Displays:
6138: 1 x 16 alpha-numeric supertwist LCD, backlit.
The current keypad address will be displayed, and the cursor will be
under the "tens" digit. If 10 seconds have passed with no key entry, 6139,6139R: 2 x 16 alpha-numeric supertwist LCD, backlit.
the keypad automatically exits address mode. You must power 6128, 6137: Fixed-Word LCD (6137 backlit).
down, power up and start address mode again. Sounder: Piezo-electric (fire alarm is loud, pulsing single tone;
(all Keypads) burglary alarm is loud, continuous, dual
tone).
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL FOR DETAILS ON LIMITATIONS OF THE ENTIRE ALARM SYSTEM.