Insert Type Vortex Flow Meter
Insert Type Vortex Flow Meter
Product overview
Vortex flow meter is a kind of flow meter that uses piezoelectric crystal as the detecting element to transmit a standard signal proportional to the flow
The instrument can be directly with the instrumentation system, can also be used with computers and centralized system supporting the measurement of flow
parameters of different media. The instrument is based on the detection principle of fluid vortex street, the detection of vortex street piezoelectric
crystal does not contact with the medium, the instrument has a simple structure, good versatility and high stability.
Vortex flow meters can be used for flow detection and measurement of various gases, liquids and steam.
Vortex flow meter can be used with the company's production of intelligent flow totalizer supporting, but also with other instrumentation manufacturers of
intelligent instrumentation supporting the use of a strong generality.
Second, the working principle of vortex flow meter is the basic principle of Carmen vortex principle, that is, "vortex vortex separation frequency is proportional to
the flow rate" flow meter flow body diameter and the nominal caliber of the instrument is basically the same. As shown in Figure 1, the flow of the body
inserted into an approximate isosceles triangle of the column, the axis of the column and the measured direction of flow of media perpendicular to the
bottom surface facing the fluid.
When the measured medium flows through the column, alternating vortices on both sides of the column, vortex generation and separation, in the
column downstream of the formation of a staggered arrangement of two rows of vortices, that is, "vortex street". Theoretical analysis and experiments
have proved that the frequency of vortex separation is directly proportional to the column side of the medium flow rate.
Where.
f - frequency of vortex separation at the
column side (H z); V - velocity at the column
side (m/s).
d - width of the column's flow-facing surface (m).
Sr - Strouhal number. It is a constant that depends on the shape of the column cross-section and is essentially independent of the nature of the fluid and the
Figure - Vortex in a
round tube III. Product
Features
Sensor measuring probe using a special process package, high temperature resistance up to 350C Sensitive components sealed in the probe body, the
detection element does not contact the measurement medium, long service life sensor compensation design, improve the instrument seismic structure is
simple, no moving parts, high durability in the specified Reynolds number range, the measurement of the medium is not affected by the temperature,
pressure, viscosity of the flow meter can be used in explosion-proof occasions, good safety range ratio Wide, up to 10:1 15:1
Strong versatility, can measure the unclean gas, liquid
four, technical parameters
Ambient temperature: (-40~55)° C.
5.3 Determination of the connection: vortex sensor connection is divided into four types of flange mounted, flange connection, threaded connection,
clamp connection, each connection has its own characteristics, according to the actual needs of the user site to determine the appropriate mode of
connection, the commonly used connection for the flange mounted and flange connection
Calculation 1: First calculate the lower case flow limit Qp determined by density Eq.
blank page
15 15 65 125 460
20 20 65 125 460
25 25 65 125 460
40 39 75 145 470
50 49 75 160 481
65 64 75 180 497
80 79 80 195 510
Then, it is necessary to provide adequate ventilation measures. c. Mechanical vibration and shock: The structure of the flowmeter is robust and will not be damaged
d. Flow meter installation location should be sufficient space around the installation of the flow meter should be installed in high places as far as possible
to have a working platform, in order to facilitate the installation and maintenance. In addition, in order to maintain and check the convenience, there
should be available near the measuring instrument with the AC 220V power socket.
e. The flow meter is best installed indoors, must be installed outdoors, there should be sun and moisture-proof measures.
f. Flow meters should be installed away from high-power motors, frequency converters, high-power transformers and radio transceivers, otherwise, it may
cause the meter not to work properly.
(2) Requirements for installation piping
a. The upstream and downstream sides of the flow meter must have long enough straight sections of the same diameter. The length should be in accordance
with the following table
. French card-mounted (flange-connected) flow meter
straight pipe section piping conditions
Concentric tapering tube, fully
open valve Concentric tapering
tube, fully open valve
Upstream 90-degree straight elbow or
T-fitting Upstream
>15D
>20D
>20D
>5D
>5D
>5D
Pipeline conditions
>25D
Owl 40D
>50D
>5D
>5D
>5D
Titanium into the type
flowmeter straight pipe section
pipe situation
The first name of the threshold of the dolphin fling billy goat sympathetic
grapefruit veterinary kick tapering tube, the whole valve concentric
tapering tube, the whole valve
Upstream 90-degree straight elbow or
T-fitting Upstream
>30D
>50D
>50D
>10D
>20D
>20D
Pipeline conditions
>50D
>80D
Konjac 45D
Downstream
>20D
Sturgeon 25D
>20D
b. In the specified length of the straight pipe section, the pipe inlet section and flow section visually should be straight. In order to ensure that the
measured medium full pipe, the flow meter should try to avoid installation in the regulating valve, half-open gate valve downstream. Generally not in the
expansion of the pipe after the installation of the flow transmitter.
c. The flowmeter can be installed vertically, horizontally or at any other angle. When the flowmeter is installed on a vertical or inclined pipe, the fluid flow
direction
It should be bottom-up. d. When it is necessary to install pressure-taking or temperature-measuring points near the flowmeter, the pressure-taking point
should be outside of 3D after the flowmeter, and the temperature-measuring point should be outside of 5D after the flowmeter. e. In order to facilitate the
maintenance of the flowmeter, the installation of a by-pass pipe is strongly recommended. In the need to clean the pipeline or the installation of the
flowmeter pipeline can not be cut off, it is necessary to install a bypass pipe.
(3) Installation Precautions
The following must be observed during installation.
a. The measured medium flow direction must be consistent with the flow direction head marking on the flow meter
b. When installing the card-type flowmeter, you can ensure that the pipe and the flowmeter flow body concentric through the special concave flange
concave surface. And pay attention to the gasket can not go deep into the pipe.
(4) Insertion of the vortex flowmeter into a pipe requires an 87 round hole in the mounting.
Weld the connection flange supplied with the meter to the round hole, requiring that the open flange stub must be perpendicular to the pipe and that the axis
of the stub coincides with the centerline of the pipe. As shown in Figure V.
The short pipe of the connecting flange has machined tabs which are aligned with the outer wall of the pipe and then welded.
a. Determine whether to install a ball valve as needed. In the maintenance of fashion dismantling flowmeter allows interruption of flow, then do not need to
install ball valves; if not allowed to interrupt the flow, then need to install ball valves. Ball valves are supplied by our company, model: Q41F16(DN80), if you
need to install ball valves, you must specify when ordering.
b. If you need to install a ball valve, first install the ball valve on the open flange, then open the ball valve, and then install the insertion vortex flowmeter on the ball
valve, see Figure III. If it is not necessary to install the ball valve, then directly install the insertion vortex flowmeter on the open flange, when installing, please
note that the speed measurement body should be in the center of the pipe.