S6561_PC40-02-12 Spec Sheet

The PowerCommand® 40-02/12 Transfer Switch Control is a microprocessor-based system designed for monitoring and controlling generator sets and load transfer for emergency power applications. It features a customizable human-machine interface with an LCD display, extensive diagnostics, and configurable inputs/outputs for various applications. The control is compliant with multiple standards and offers robust communication capabilities, making it suitable for a wide range of power system solutions.

Uploaded by

Mohamed Megahed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views5 pages

S6561_PC40-02-12 Spec Sheet

The PowerCommand® 40-02/12 Transfer Switch Control is a microprocessor-based system designed for monitoring and controlling generator sets and load transfer for emergency power applications. It features a customizable human-machine interface with an LCD display, extensive diagnostics, and configurable inputs/outputs for various applications. The control is compliant with multiple standards and offers robust communication capabilities, making it suitable for a wide range of power system solutions.

Uploaded by

Mohamed Megahed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Specification Sheet

PowerCommand® 40-02/12
Transfer Switch Control
GTEC Transfer Switches

DESCRIPTION
The PowerCommand® 40-02/12 Transfer Switch
Control is a sophisticated microprocessor-based
control with the basic features you need for primary
source and generator set monitoring, generator set
starting and load transfer functions for emergency
standby power applications. The control features a
highly customizable customer inputs/outputs which
can be tailored to suit a wide range of application
requirements.
The control human machine interface (HMI) includes
a LCD display with tactile-feel soft-switches for easy
operation and screen navigation. All data on the control can be viewed by scrolling through screens
with the display scroll button. The control displays the current active fault, fault occurrences and time-
ordered history of the 10 previous faults with respect to Real Time Clock Stamp and Engine Running
Time.
FEATURES
Digital display – The PowerCommand® 40- PC & Front Panel Configurations – The
02/12 offers a clear back-lit LCD 4-line text modules can be easily configured using the PC
display, showing system status, contextual icons software. Selected front panel editing is also
and warnings. The display is also equipped with available.
9 red and green LEDs indicating operational
Ease of service and access – Built-in plug-and-
status.
play control with minimized point-to-point
Modbus network communication – Modbus connections and compatible terminal markings
network communications capable. Optional simplify servicing.
Modbus RTU RS485 connection (1 serial port).
Complete product line – Cummins is a single
Diagnostics and reporting – Detailed event source supplier with full scope of power system
logging with enhanced fault codes, alert lists, solutions, integration and service capability, from
power event history, and source statistics paralleling to system level controls, switchgear
enhances diagnostic capability during service and remote connectivity.
events and provides the ability to meet any
Warranty and service – Products are backed by
reporting requirements.
a comprehensive warranty and a worldwide
Dry Contact (Volt Free) Relays – Configurable network of distributors with factory-trained
volt-free digital inputs and outputs make the service technicians.
PowerCommand® 40-02/12 fully flexible to suit a
wide variety of applications.

S-6561 (Issued: 05/2021) cummins.com


Isometric (ISO) projection: front views

Human Machine Interface (HMI) capabilities

Display scroll LED indicates


button source on load
available

LED indicates
Info button source on
load available
LED indicates
source power
connected
LED
indicates
Tactile push source load
button available
transfers load
to S1
Tactile push button
transfers load to S2
Tactile push
button selects Tactile push
‘Stop’ mode button selects
‘Auto’ mode

Tactile push button Tactile push button


selects ‘Manual’ selects ‘Auto’ mode
mode LED Indicates ‘Auto’
mode

S-6561 (Issued: 05/2021) cummins.com


Control functions
Transfer Inhibit Configurable Input/Output
When transfer inhibit external input is active, the This feature allows the configurable inputs to be
control does not automatically transfer the configured to perform any of the below
transfer switch to a standby source even when assignable input functions and configurable
the preferred source fails. output pins to perform any of the below
Retransfer Inhibit assignable output functions:
When retransfer inhibit external input is active, Assignable input functions:
the control does not automatically retransfer the • Alarm Mute
transfer switch to a preferred source even when • Alarm Reset
the preferred source returns. • Auto Restore Inhibit
Real Time Clock • Auto Start Inhibit
• Auxiliary S1 Fail
This feature is used by the control for fault and • Auxiliary S2 Ready
event time stamping and as a reference for • Charger AC Failure
exerciser schedules and exception schedules. • External Panel Lock
Test - Remote • Inhibit Scheduled Run
Test feature allows the user to automatically test • Lamp Test
• Load Shedding
the standby source and the transfer switch. The
• Open / Close S1 and S2
test command can be issued from the remote
• Remote Start Off Load
source. • Remote Start On Load
The test has following types available: • S1 / S2 Closed Auxiliary
• Remote Start On Load • S1 / S2 Load Inhibit
• Remote Start Off Load • S2 Transfer inhibit
• Simulate S1 / S2 Available
Preferred Source Selection
Assignable output functions:
Using this feature the user can swap the priority
of the sources which are preferred and standby. • Close S1 Or S2
• Close S1 / S2 / N Output
Exerciser Scheduler • Common Warning
The Scheduler allows the user to configure pre- • Cooling Down
set automatic starting and stopping of the • Digital Input A – K
Generator as well as stopping the ATS carrying • Elevator Control
out a transfer (when in Auto mode). • Fail to Start / Stop
• Loading Frequency Not Reached
BANK 1 / BANK 2
• Loading Voltage Not Reached
Each Bank of the Exercise Scheduler is used to
• Open S1 / S2 Output
give up to 8 scheduled runs per bank, 16 in total. • Return Delay in Progress
This run schedule is configurable to repeat every • Start Delay in Progress
7 days (weekly) or every 28 days (monthly). Do • System in Auto Mode
Not Transfer, Off Load and On Load. Each • System in Manual Mode
scheduler bank configured differently either to • System In Start Inhibit Mode
weekly or monthly based exercises. • System in Test Off-Load Mode
Source Availability • System in Test On-Load Mode
This feature monitors the frequency and voltage Voltage sensing
sensors on the preferred and standby sources to 3-phase sensing on Source 1 and Source 2 (up
determine and declare the availability status of to 600 Vac with no need for additional PTs). Plant
the two sources, irrespective of which source is battery voltage monitoring.
connected to the load. It declares the states as
event codes. Preferred/Standby Available -
active inactive.

S-6561 (Issued: 05/2021) cummins.com


Time Delays Supported applications
The following adjustable time delays are built into Application Types
the transfer switch control. External modules to
accomplish these delays are not required. • Utility - Generator Set
• Start Delay (Also known as Time Delay Engine Communications
Start, TDES adjustable from 0 to 10 hours) The PowerCommand® 40-02/12 Transfer Switch
• Warming (Also known as Time Delay Normal to Control features an optional network
Emergency, TDNE adjustable from 0 to 1 hour)
communication module.
• Elevator Delay (Also known as Time Delay
Elevator, TDEL adjustable from 0 to 5 minutes) Features include:
• Non-sync Transfer Time (Also known as Time • Optional Modbus® RTU RS485
Delay Programmed Transition, TDPT adjustable communication module (1 isolated serial port)
from 0.5 s to 10 minutes) • USB port for service tool interface
• Return Delay (Also known as Time Delay
Emergency to Normal, TDEN adjustable from 0 Protection
to 5 hours) Phase rotation sensing
• Cooling (Also known as Time Delay Engine
Cool-down, TDEC adjustable from 0 to 1 hour) • Source 1 and Source 2
Source Statistics Under-Voltage sensing
The control displays the following source • 3-phase normal, 3-phase emergency
statistics: • Accuracy: ±2 % of full-scale phase to phase
• Phase to neutral voltage range 50Vac to
• S1 Connected 414Vac.
• S1 Available • Phase to phase voltage range 86Vac to
• S2 Connected 717Vac.
• S2 Available
• S1 Voltage L1-N Overvoltage sensing
• S1 Voltage L-L • 3-phase normal, 3-phase emergency
• S1 Frequency • Accuracy: ±2 % of full-scale phase to phase
• S2 Voltage L1-N • Phase to neutral voltage range 52Vac to
• S2 Voltage L-L 416Vac.
• S2 Frequency • Phase to phase voltage range 90Vac to
• Auto / Manual Mode 720Vac.
• Warning Alarms Over/under frequency sensing
• Event Log • Normal and emergency
• Current operational status • Accuracy: ±0.2 Hz
• Load current (A) • Frequency range 3.5 – 75 Hz
• Plant Battery Voltage
Events
The control displays information on up to 10
events displayed in chronological order,
beginning with the most recent event, about
either source. The event information shall include
the following:
• Failure modes
• Warning
• Tests and exercises
• User-driven inputs (e.g., override, transfer
inhibit)

S-6561 (Issued: 05/2021) cummins.com


Environment

Operating Temperature
Control operates over an ambient temperature range: -30 ºC to 70 ºC.
Range

The control operates after being exposed to Storage Temperatures in the range of -40 ºC to
Storage Temperature
85 ºC. The LCD display functions after being exposed to storage temperatures of -30 ºC to 80
Range
ºC.

Ingress Protection The front panel is to be IP65.

Codes and Standards

The PC40-02/12 control is a UL Capable of being used on systems


Recognized Component Marked for compliant with NFPA 70, 99 and 110
United States and Canada. (Level 1).

The control is IEEE C37.90.2 certified. Control and display as installed in a


Capable of being used on IEEE 446 transfer switch enclosure comply1 with
compliant systems; Recommended NEMA 4X and IP65 at the transfer switch
Practice for Emergency and Standby level - if the transfer switch enclosure is
Power Systems. also NEMA 4X & IP65 compliant.

Capable of being used on systems


suitable for use in emergency, legally
® required and Standby and Critical
RoHS The control is RoHS compliant. NEC Operations Power Systems (COPS)
applications per NEC 700, 701, 702 and
708.

The unit is designed to comply with


Fulfills the requirements of relevant European directive 72/23/EEC by
European product directives. LVD complying with harmonized European
safety standard BS EN 60950

The control is tested to meet the following CE Electromagnetic Compatibility (EMC) standards for EN
61000 series (electromagnetic compatibility):
EMC EN 61000-6-2 Generic Immunity Standard
EN 61000-6-4 Generic Emissions

For more information contact your local Cummins distributor or visit


cummins.com

Our energy working for youTM


©2020 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy
working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.

S-6561 PD00000757 (05/2024)

S-6561 (Issued: 05/2021) cummins.com