Lect # 4_8_Distribution Substation
Lect # 4_8_Distribution Substation
Transmission system planning, Complex power in balanced three phase transmission lines. Power flow in transmission lines.
Performance Analysis of Transmission system
Transmission line constants, Bundled conductors, Parallel lines, , Steady state power limit and voltage regulation in Short transmission lines.
Medium transmission line, A, B, C & D constants. Nominal and nominal T circuits. Analysis of Long transmission lines, Line and load
compensation, series and shunt compensation. Environmental effects of overhead lines.
Undergorund Cables
Types of underground cables, Cable installation techniques, Electric stress, dielectric constant, charging current, insulation resistance, skin effect
and proximity effect, current carrying capcity of cables.
Distribution System Planning
Importance of distribution system planning, load forecasting. Factors affecting distribution system planning, planning methods, computer
applications, distribution automation and control, Distribution system in Pakistan, Planning constraints in Pakistan
Distribution Substation
Distribution substation, Substation bus schemes. Rating of Distribution substation, limitation of service area. Square and hexagonal service area.
Distribution transformer, distribution transformer efficiency, parallel operation of transformers, vector groups
Design Considerations for Primary and Secondary Distribution Systems
Primary distribution feeders, Primary feeder voltage level and loading, Design considerations for Radial feeders, Economic design of secondary
lines, voltage fluctuation. Voltage regulation, Distribution system voltage control, line drop compensator.
2
Distribution Substation
• Distribution substation,
• Substation bus schemes
• Rating of Distribution substation
• Limitation of service area
• Square and hexagonal service area
• Distribution transformer
• Distribution transformer efficiency
• Parallel operation of transformers & vector groups
3
SUBSTATION / GRID STATION
❖ Substation is an integral part of a power system and form
important links between the generating station, transmission
systems, distribution systems and the load points.”
❖ switchgear,
❖ bus bars,
6
Function of Switchgear
➢ One of the basic functions of switchgear is protection,
which is interruption of short-circuit and overload fault
currents while maintaining service to unaffected circuits.
7
Bus bar
Current CT
Disconnect Circuit Disconnect
breaker
8
9
Essential Features of Switchgear
10
Switching Equipment
➢ Switches
➢ Fuses
➢ Circuit breakers
➢ Relays
➢ Bus-bars
➢ Instruments and instrument transformers
➢ Lightning / Surge arrestors
➢ Control Panels
➢ And many more
11
12
13
Fuses
14
Circuit Breakers
A circuit breaker can make or break a circuit either manually or
automatically under all conditions viz, no-load, full load and
short circuit conditions.
15
Purpose of circuit breakers (switchgear)
The main purpose of a circuit breaker is to:
• Carry fault current without blowing itself open (or up!) i.e. no distortion
due to magnetic forces under fault conditions.
16
Relays
Relays are electrical switches that open or close another circuit
under certain conditions.
Relay Purpose
19
Bus-bars
➢ Bus-bars are copper rods or thin walled
tubes and operate at constant voltage.
Types of Bus-bars
⚫ Single Bus-bar System
⚫ Single Bus-bar System with sectionalisation
⚫ Duplicate Bus-bar System
20
Reclosers
➢ Reclosers are self-contained, mechanical switching
devices used throughout overhead distribution systems
to detect and automatically isolate overcurrent
conditions.
21
Busbars:
❖ Various incoming and outgoing circuits are connected to bus
bars. Bus bars receive power from incoming circuits and
deliver power to outgoing circuits.
2
2
2
3
Isolators or Disconnecting Switches:
❖ Isolators are provided for isolation from live parts for the purpose of
maintenance. Isolators are located at either side of the circuit
breaker. Isolators are operated under no load. Isolator does not have
any rating for current breaking or current making. Isolators are
interlocked with circuit breakers
24
Earthing Switch
❖ Earthing Switch is used to discharge the voltage on the circuit to the
earth for safety. Earthing switch is mounted on the frame of the
isolators. It is located for each incoming transmission line and each
side of the bus bar section
❖ Earthing Switch is necessary
to earth the conducting parts
before maintenance and also
to provide deliberate short-
current while testing. This
enables various tests to be
performed on the Switchgear
or item of equipment, such as
testing the current
Transformer of measuring the
operating time of breakers,
without having to open the
enclosure.
25
❖ The use of earth switches is to send any trapped
charge in the line into ground after the line is switched
off.
❖ When isolator OPEN condition earth switch is CLOSED. Here any induction
that passes thro' earth switch to ground. When isolator in CLOSED condition
earth switch should be open
26
Shunt Reactors
❖ Shunt Reactors are used for long EHV transmission lines to
control voltage during low – load period. Shunt reactors are also
used to compensate shunt capacitance of transmission line during
low load periods. Usually Shunt reactors are un-switched
27
Series Reactors
❖ Series reactors are used to limit short – circuit current and to limit
current surges associated with fluctuating loads. Series reactors
are located at the strategic locations such that the fault levels are
reduced.
28
Shunt Capacitance
❖ Shunt capacitors are used for compensating reactive power of
lagging power factor. Shunt Capacitors are used for improving the
power factor. It is also used for voltage control during heavy lagging
power factor loads. Shunt Capacitors are located at the receiving
stations and distribution substations. Shunt Capacitors are switched
in during heavy loads and switched – off during low loads.
29
Circuit Breakers
❖ circuit breaker is a switching device which can be operated
manually as well as automatically for controlling and protection of
electrical power system respectively.
❖ As the modern power system deals
with huge currents, the special
attention should be given during
designing of circuit breaker to safe
interruption of arc produced during
the operation of circuit breaker.
30
Types of Circuit Breaker
❖ According to the type of ARC quenching medium CBs can be divided
as;
1. Air Circuit Breaker
2. Oil Circuit Breaker
3. Vacuum Circuit Breaker
4. SF6 Circuit Breaker
❖ According to their services the circuit breaker can be divided as;
1. Outdoor circuit breaker
2. Indoor breaker
❖ According to the operating mechanism of CBs can be divided as;
1. Spring operated circuit breaker
2. Pneumatic circuit breaker
3. Hydraulic circuit breaker
❖ According to the voltage level of installation types of CBs are referred as;
1. High voltage circuit breaker
2. Medium voltage circuit breaker
3. Low voltage circuit breaker
31
Instrument Transformers
❖ Current or voltage instrument transformers are necessary for
isolating the protection, control and measurement equipment from
the high voltages of a power system, and for supplying the
equipment with the appropriate values of current and voltage -
generally these are 1A or 5Α for the current coils, and 120 V for the
voltage coils.
❖ The behavior of current and voltage transformers during and after the
occurrence of a fault is critical in electrical protection since errors in the signal
from a transformer can cause maloperation of the relays.
❖ In addition, factors such as the transient period and saturation must be taken
into account when selecting the appropriate transformer.
❖ When only voltage or current magnitudes are required to operate a relay then
the relative direction of the current flow in the transformer windings is not
important. However, the polarity must be kept in mind when the relays
compare the sum or difference of the currents
32
Current Transformer
33
Example 1:
A 250 : 5, current transformer is used along with an ammeter. If ammeter
reading is 2.7 A,. estimate the line current.
H.W PROBLEM # 01
A 500 : 5, current transformer is used along with an ammeter. If ammeter
reading is 3 A,. estimate the line current.
34
Why Secondary of C.T. Should not be Open ?
Secondary of C.T. should not be kept open.
❖ It should be shorted or must be connected in series with a low resistance
coil such as current coils of wattmeter, coil of ammeter etc.
❖ Current through secondary becomes zero hence the ampere turns produced by
secondary which generally oppose primary ampere turns becomes zero.
❖ As there is no counter m.m.f., Unopposed primary m.m.f. (Ampere turns) produce high
flux in the core. This produces excessive core losses, heating the core beyond limits.
❖ Similarly heavy e.m.fs will be induced on the primary and secondary side. This may
damage the insulation of the winding. This is dangerous from the operator point of view
as well.
❖ Hence never open the secondary winding circuit of a current transformer while its primary
winding is energized. Thus most of the C.Ts have a short circuit link or a switch at
secondary terminals. When the primary is to be energized, the short circuit link must be
closed so that there is no danger of open circuit secondary.
35
Potential Transformer
These are extremely accurate ratio step down
transformers. The windings are low power rating
windings. Primary winding consists of large number
of turns while secondary has less number of turns
and usually rated for 110 V, irrespective of the
primary voltage rating.
The primary is connected across the high voltage line while secondary is
connected to the low range voltmeter coil. One end of the secondary is always
grounded for safety purpose. The connections are shown in the figure .
36
VTs or PTs Design Characteristics
❖ With voltage transformers (VTs) it is essential that the voltage from
the secondary winding should be as near as possible proportional
to the primary voltage.
❖ In order to achieve this, VTs are designed in such a way that the voltage
drops in the windings are small and the flux density in the core is well below
the saturation value so that the magnetization current is small;
37
Station Batteries
❖ The heart of a substation is the battery bank. If this were to fail, an
electric utility could expose all feeders associated with the station
to a condition where they could not ever trip in a fault. Not only
that, but any backup devices, such as the main breaker on the
low-voltage side or the high-voltage side protection of the power
transformer, would all be inoperative, leaving the transmission grid
protection as the only possible backup.
38
❖ There are two major types of battery banks used for substation
applications; lead acid and nickel cadmium. The nickel cadmium
battery banks are about twice the cost of lead acid for the same size
bank.
40
The two round cylinders half-way up on
right are line-traps for power-line carrier.
41
Substation Grounding / Earthing
43
Switchgear Accommodation
Switchgear for low voltages may be entirely enclosed within a building. For
transmission levels of voltage (high voltages over 66 kV), often switchgear
will be mounted outdoors
44
Outdoor substation with switchgear equipment
45
Substation Bus Schemes
❖ Electrical and physical arrangements of the switching and
busing at the sub transmission voltage level are determined
by the selected substation scheme. Selection of a particular
substation scheme is based upon safety, reliability,
economy, simplicity, and other considerations.
46
1. Single Bus Scheme
Advantages:
1. Lowest cost
Disadvantages:
1. Failure of bus or any circuit breaker
results in shutdown of entire
substation.
2. Difficult to do any maintenance.
3. Bus can not be extended without
completely deenergizing the
substation.
4. Can be used only where loads can
be interrupted or have other supply
arrangements.
47
2. Double Bus – Double Breaker Scheme
Advantages:
1. Each circuit has two dedicated
breakers.
2. Has flexibility in permitting feeder
circuits to be connected to either
bus.
3. Any breaker can be taken out of
service for maintenance.
4. High reliability.
Disadvantages:
1. Most expensive.
2. Would lose half the circuit for
breaker failure if circuits are not
connected to both buses.
48
3. Main and transfer bus scheme
Advantages:
• Low initial and ultimate cost.
• Any breaker can be taken out of
service for maintenance.
• Potential devices may be used on
the main bus for relaying.
Disadvantages:
• Requires one extra breaker for the
bus tie.
• Switching is somewhat complicated
when maintaining a breaker.
• Failure of bus or any circuit breaker
results in shutdown of entire substation.
49
4. Double bus - single breaker scheme
Advantages:
• Permits some flexibility with two operating
buses.
• Either main bus may be isolated for
maintenance.
• Circuit can be transferred readily from one
bus to the other by use of bus – tie breaker
and bus selector disconnect switches.
Disadvantages:
• One extra breaker is required for the bus tie.
• 4 switches are required per circuit.
• Bus protection scheme may cause loss of substation when it
operates if all circuits are connected to that bus.
• High exposure to bus faults.
• Bus – tie breaker failure takes entire substation out of service.
50
5. Ring bus scheme
Advantages:
• Low initial and ultimate cost.
• Flexible operation for breaker
maintenance.
• Any breaker can be removed
for maintenance without
interrupting load.
• Requires only one breaker per
circuit.
• Does not use main bus.
• Each circuit is fed by 2
breakers.
• All switching is done with
breakers.
Disadvantages:
• Automatic reclosing and protective relaying circuitry rather complex.
51
6. Breaker and a half scheme
Advantages:
• Most flexible operation.
• High reliability.
• Breaker failure of bus side removes only
one circuit from service.
• All switching is done with breakers,
• Simple operation.
• Either main bus can be taken out of
service at any time for maintenance.
• Bus failure done not removes any feeder
from service.
1. Disadvantages:
2. One and half breakers per circuit.
3. Relaying and automatic reclosing are somewhat involved singe
the middle breaker must be responsive to either of its associated
circuits.
52
. Table of configurations
Configuration Reliability Cost Available area
Highly reliable —
Double Bus duplicated components; High cost — duplicated Greater area — twice as
single failure normally components many components
isolates single
component
.Double Bus, Moderately reliable — Moderate cost — more Moderate area — more
Single Breaker depends on arrangement components components
of components and bus
➢ A fault in a circuit means any failure which hinders with the normal flow of current.
➢ Most faults on transmission lines of 115kV and higher are caused by lightning, which
results in the flashover of insulators.
➢ The high voltage between a conductor and the grounded supporting tower causes
ionization, which provides a path to ground for the charge induced by the lightning
stroke.
➢ Once the ionized path to ground is established, the resultant low impedance to
ground allows the flow of current from the conductor to ground and through the
ground to the grounded neutral of a transformer or generator, thus completing the
circuit.
➢ A fault on the power system which gives rise to symmetrical fault currents (i.e. equal
fault currents in the lines with 120o displacement) is called symmetrical fault.
➢ A fault may occur on a power system due to a number of reasons. Some of the
common causes have their origins in natural disturbances like lightning, high speed
winds, earthquakes.
➢ Generators, transformers, and other protective switchgear may fail due to insulation
breakdown.
➢ There may be accidental faults such as falling of a tree along a line, vehicles
colliding with supporting structures, airplane crashing with the line, birds shorting
the electrical transmission/ distribution line.
56
▪ Sometime interruption also results in creating faults. Contamination (puncture) of
insulators may also result in a fault. Sometimes, small animals like rats, lizards enter
switch gear to create faults. Thus, symmetrical faults can also be defined as:
▪ A fault in which all three phase are shorted to one another and to ground is
known as three phase short circuit fault or symmetrical faults.
▪ A three phase short circuit occurs rarely but it is most severe type of fault
involving largest currents. For this reason the balanced short circuit calculations
are performed to determine these large currents to be used to determine the
rating of the circuit breakers.
▪ Faults can cause system to become unstable. Hence, it is necessary that upon the
occurrence of fault , the faulty section should be disconnected as rapidly as possible
so that the normal operation of the rest of the system is not affected. If this is not
done, the equipment may be damaged and the power supply may disrupted.
▪ The relays should immediately detect the existence of the fault and initiate circuit
breaker operation to disconnect the faulty section.
57
➢ The purpose of fault analysis is to determine the values of voltages and currents at
different points of the system during the fault.
➢ Such analysis enables us to select appropriate protective schemes, relays, and circuit
breakers in order to save the system from the abnormal condition within minimum
time.
➢ Note: The assumptions for short circuit calculations are same as for per unit system
reactance diagram.
➢ When a short circuit occurs at any point in a system, the short-circuit current is
limited by the impedance of the system up to the point of fault.
60
❑ Selection of Circuit Breakers (Cont):
➢ There are a few different criteria to consider when selecting a circuit
breaker including voltage, frequency, interrupting capacity, continuous current
rating, unusual operating conditions and product testing.
Voltage Rating
➢ The overall voltage rating is calculated by the highest voltage that can be applied
across all end ports, the distribution type and how the circuit breaker is directly
integrated into the system. It is important to select a circuit breaker with enough
voltage capacity to meet the end application.
Frequency
➢ Circuit breakers up to 600 amps can be applied to frequencies of 50-120 Hz. Higher
than 120 Hz frequencies will end up with the breaker having to derate. A general rule
of thumb is the higher the ampere rating in a specific frame size the greater the
derating needed.
61
❑ Selection of Circuit Breakers (Cont):
Continuous Current Rating
➢ A general rule of thumb for circuit breaker manufactures is to calibrate their
standard breakers at 104° F.
Note: To calculate the circuit breaker size, simply divide the adjusted wattage by 240
volts to find the rated amperage needed for your subpanel. Often, the result is not a
common circuit breaker size. and you can simply round up to the next
higher size of the breaker
62
❑ Reactor Control of Short Circuit Currents:
▪ A reactor is a coil of number of turns designed to have a large inductance as
compared to its ohmic resistance.
▪ With the fast expanding power system, the fault level (i.e. the power available to
flow into a fault) is also rising.
▪ The circuit breakers connected in the power system must be capable of dealing with
maximum possible short-circuit currents that can occur at their points of connection.
▪ Generally, the reactance of the system under fault conditions is low and fault
currents may rise to a dangerously high value.
▪ If no steps are taken to limit the value of these short-circuit currents, not only will
the duty required of circuit breakers be excessively heavy, but also damage to lines
and other equipment will almost certainly occur.
▪ In order to limit the short-circuit currents to a value which the circuit breakers
can handle, additional reactances known as reactors are connected in series
with the system at suitable points.
▪ Reactors limit the flow of short-circuit current and thus protect the equipment from
overheating as well as from failure due to destructive mechanical forces. 63
❑ Reactor Control of Short Circuit Currents:
▪ Troubles are localised or isolated at the point where they originate without
communicating their disturbing effects to other parts of the power system. This
increases the chances of continuity of supply.
▪ They permit the installation of circuit breakers of lower rating.
▪ Modern generators are designed to have sufficiently large reactance to protect them
in even dead short circuits at their terminals. Thus, these reactors may only be
used in old generators having low values of reactance.
65
❑ Disadvantages of Generator Reactors:
▪ There is a constant voltage drop and power loss in the reactors even during normal
operation.
▪ If a bus-bar or feeder fault occurs close to the bus-bar, the voltage at the bus-bar will
be reduced to a low value with the result that generators may lose synchronism and
supply may be interrupted.
▪ Due to these disadvantages and also since modern power station generators have
sufficiently large leakage reactance to protect them against short-circuit, it is not a
common practice to use separate reactors for the generators.
66
❑ Feeder Reactors:
▪ When the reactors are connected in series with each feeder, they are known as
feeder reactors.
▪ Since most of the short-circuits occur on feeders, a large number of reactors are used
for such circuits. 67
❑ Advantages of Feeder Reactors:
▪ Two principal advantages are claimed for feeder reactors:
▪ Firstly, if a fault occurs on any feeder, the voltage drop in its reactor will not affect
the bus bars voltage so that there is a little tendency for the generator to lose
synchronism.
▪ Secondly, the fault on a feeder will not affect other feeders.
▪ There is a constant power loss and voltage drop in the reactors even during normal
operation.
▪ If the number of generators is increased, the size of feeder reactors will have to be
increased to keep the short-circuit currents within the ratings of the feeder circuit
breakers.
68
❑ Bus-bar Reactors:
▪ When the reactors are connected in series with each Bus-bar, they are known as
Bus-bar reactors.
▪ The limitations of generator and feeder reactors can be overcome by locating the
reactors in the bus-bars.
▪ There are two methods for this purpose, namely;
✓ Ring system and
✓ Tie-Bar system.
❑ Ring System:
▪ In this system, bus-bar is
divided into sections and
these sections are
connected through
reactors.
▪ This is the most common
method of connection of
reactors. 69
❑ Ring System:
▪ Under normal operation, each generator supplies feeder connected to its own section
and there will be no current through the reactors.
▪ Thus, there is no voltage drop or power loss or very little power loss in the reactor
during normal operation. Generally, one feeder is fed from one generator only.
▪ The principal advantage of the system is that if a fault occurs on any feeder, only
that bus bar section is affected to which it is connected. The other sections continue
to operate normally.
▪ One generator (to which the particular feeder is connected) mainly feeds the fault
current while the current fed from other generators is small due to the presence of
reactors.
▪ Therefore, only that section of bus-bar is affected to which the feeder is connected,
the other sections being able to continue in normal operation
70
Rating of distribution substation
77
Comparison of square shaped and hexagonal shaped service
areas For Equal Voltage drops
Consider a square shaped distribution pattern
A4 = area served by feeder l4= feeder length D= load density
Consider a hexagonal shape
A6 = area served by feeder l6= feeder length D= load density
For the same conductor and considering only primary feeder
Voltage drop in square shaped area is given by
%VD4 = 2*K*D*l43 /3
Voltage drop in hexagonal shaped service area is given by
%VD6 = (2*K*D*l63) /3√3
For same voltage drop %VD4 = %VD6
2*K*D*l43 /3 = (2*K*D*l63) /3√3 l43 = l63 /√3
l4 = 0.833 l6
Total area served by square shaped distribution system is
TA4 = 4* l42
Total area served by hexagonal shaped distribution system is
TA6 = 6 * l62/√3
TA6 = 6 * l62/√3 = √3 l62 = √3 l6 2 = 1.25
TA4 4* l42 2 l42 2 * (0.833 l6 )2
TA6 = 1.25 TA4
Therefore Hexagonal shaped service area can supply area equal to 1.25
78
times the square shaped area.
For Same Current limiting capacity
Consider a square shaped distribution pattern
A4 = area served by feeder l4= feeder length D= load density
TA4= Total area covered = 4*l42 I4= current carried by
feeder
I4 = S4 /(√3*VL) = D*A4/ (√3*VL) = D*l42/(√3*VL)
Consider a hexagonal shape
A6 = area served by feeder = l62/√3 l6= feeder length D= load
density
TA6= Total area covered = 6*l62/√3 I6= current carried by
feeder
I6 = S6 /(√3*VL) = D*A6/ (√3*VL) = D*(l62/√3) /(√3*VL)
For equal current carrying capacity I4 = I6
D*l42 = D*l62
√3*VL 3*VL
l42 = l62
l6 = 1.3161 l4
Now comparing total area served
TA6 = 6 * l62/√3 = √3 * l62 = √3 * ( 1.3161 l4 ) 2 = 1.5
TA4 4* l42 2 l42 2 l42
TA6 = 1.5 TA4
So hexagonal shaped distribution pattern can serve 1.5 times area
79
served by square shaped distribution pattern
Example # ]
A 3 – phase 4.16 kV star – grounded feeder feeder main has # 04 copper
conductors with an equivalent spacing of 37 in. between phase
conductors and a lagging – load power factor of 0.9.
a) Determine the K constant.
80
SOLUTION
(a)
Vr = Vb = 2400 V line to neutral voltage
From equation for cons tan t K
(r cos + x sin ) (1000 / 3)
K = Pu V
Vr . Vb
Therefore the per unit voltage drop per kilovoltam pere mile is
(1.503 × 0.9 + 0.7456 × 0.4359 ) (1000 / 3)
K =
2400 2
= 0.0001 VDPu / (kVA . mi)
81
Example # 2
SOLUTION
The percent voltage drop in the main is
% VD = s × K × S n
= 1.0 mi × 0.01 %VD / (k VA . mi) × 500 k VA
= 5 .0 %
82
Example # 3
The feeder shown in the figure below has the same
characteristics as given in example 2, but the 500 kVA load is
uniformly distributed along the feeder main. Calculate the
percent voltage drop in the main.
SOLUTION
% VD = s × K × S n
Where the effective feeder length s is It can be seen that the
negative effect of the lumped
1 – sum load on the % VD
s = = 0.5 mi worse than the one for the
2
uniformly distributed load.
Therefore Figure also shows the
% VD = 1 / 2 × K × S n conversion of the uniformly
distributed load to a lumped –
= 0.5 × 0.01 %VD / (k VA . mi) × 500 k VA sum load located at point a
fro the voltage drop
= 2.5 % calculation.
83
Example # 4.
The feeder shown in the figure below has the same
characteristics as given in exampl.2, but the 500 kVA load has
an increasing load density. Calculate the percent voltage drop in
the main.
SOLUTION
The percent voltage drop in the main is
% VD = s × K × S n
Where the effective feeder length s is
2 The negative effect of the
s = l = 0.6667 mi load with increasing load
3
density is worse than
Therefore uniformly distributed load but
2 better than lumped – sum
% VD = l × K × S n load.
3
= 0.6667 mi × 0.01 %VD / (k VA . mi) × 500 k VA
= 3 .3 3 %
84
Numerical (5) : - The following figure shows a 3 phase, 4wire,
11 kV feeder originating from a substation and supplying
Jamshoro Society, located at a distance of 1 km. The colony
is square shaped (2 km X 2 km) with a uniformly distributed
load density of 1000 kVA/km2. The feeder also supplies Kotri
hostel which is located at a further distance of 2 km and has
a lumped load of 2000 kVA. The K constant of the conductor
is 0.0003% VD/kVA.km. Calculate line to neutral voltages at
a,b,c and d.
Jamshoro Society
Kotri
85
Solution
Consider NED staff colony (2 km * 2 km),
So area of the NED staff colony = 4 km2
Load density of the NED staff colony is D = 1000 kVA / km2
So load of the NED staff colony will be S1 = 4*1000 = 4000 kVA
Given that load of J-3 hostel is 2000 kVA
Section ab
Length of the section is 1 km
Total load is lumped at point (b)
Sab = S1 + S2 = 4000 + 2000 = 6000 kVA
Hence voltage drop in the section for load lumped at the end will
be
%VDab = (lab) * (K)(S) = (1*1) (0.0003)(6000) = 1.8%
So voltage drop in ab is = 1.8*11/100 = 0.198 kV
So voltage at point (b) will be
Vb = 11 – 0.198 = 10.802 kV
Line to neutral voltage at (b) will be
Vb ln = 10.802 / √3 = 6.237 kV
86
Section bc
Length of the section is 2 km
Total load is sum of S1 and S2, where S1 is uniformly distributed and S2 is lumped
at the end
% voltage drop in the section will be
%VDbc = (1/2*2)(0.0003)(4000) + (1*2)(0.0003)(2000) = 2.4%
So voltage drop in bc is = 2.4*10.802/100 = 0.26 kV
So voltage at point (c) will be
Vc = 10.802 – 0.26 = 10.543 kV
Line to neutral voltage at (c) will be
Vcln = 10.543 / √3 = 6.087 kV
Section cd
The length of the section is 2 km
Total Load is S2 = 2000 kVA, lumped at the end of the section
%VDcd = (1*2)(0.0003)(2000) = 1.2%
So voltage drop in cd is = 1.2*10.543/100 = 0.1265 kV
So voltage at point (d) will be
Vd = 10.543 – 0.1265 = 10.42 kV
Line to neutral voltage at (c) will be
Vlnd = 10.543 / √3 = 6.016 kV 87
Results
Line to line and line to neutral voltages are given below
B 10.802 6.237
C 10.543 6.087
D 10.42 6.016
88
Numerical (17): - Assume a square shaped distribution
service area. Four feeders serves an area of (2a*2a). the
load density is D kVA/mi2and it is uniformly distributed.
Each feeder main is three phase four wire grounded wye
with multi grounded common neutral open wire. Length of
each feeder is (a) mi and area served by the last lateral is
(a*d) mi2. The power factor of all the loads is Cosθ lagging.
The impedance of feeder main line is rm + jxm Ω/mi and
impedance of the lateral is rl + j xl Ω/mi. VLL is line to line
voltage , which is also normal operating voltage
Also assume that the laterals are also three
phase four wire grounded wye with multi
ground common neutral open wire. Show
that the percentage voltage drop at the end
of the lateral is
89
Solution
Length of the main feeder is ‘a’ mi, Area served by the main feeder
is (a*a) = a2 mi2 .
Total load served by substation is S = D*A = D(2a) 2 = 4 Da2 =
Load served by each feeder main will be Sm = Da2
Current in each main feeder will be
VDm = Im (rm Cosθ + xm Sinθ) = Da2 (rm Cosθ + xm Sinθ) /(√3 *VLL)
VDl = Il (rl Cosθ + xl Sinθ) = Da*d (rl Cosθ + xl Sinθ) /(√3 *VLL)
91
Numerical (18): - Figure shows a three phase four wire
grounded wye distribution system supplied by an express
feeder and main feeder. Each primary feeder serves an area
of length s and width d, Assuming lagging power factor for
all loads and that D=uniformly distributed load density, VLL =
operating line to line voltage, rm + jxm is per mile impedance
of express and main feeder, rl + jxl is per mile impedance of
the lateral. Determine in terms of given data. The per unit
voltage drop in
(i) Express feeder
(ii) Main feeder
(iii) Primary lateral
Solution
96
97
98
Numerical (20): - Consider a square shaped distribution area
as shown in figure below. The square area is 4 mi2 and has
number of three phase laterals. Load is uniformly distributed
and load density is 2000 kVA/mi2. Load has a power factor of
0.90 lagging, demand factor of 0.6 and diversity factor of 1.2.
there are two sites available for substations A and B as
shown in fig. K constant for main feeder is 0.0004 and for
lateral is 0.00095. If site A is selected there will be 16 laterals
and if B is selected there will be 32 laterals. Compare the
selection of the substation location by calculating voltage
drops.
99
100
For Substation A
Main feeder will be 2 mi long with uniformly distributed load
So voltage drop in the main feeder will be
%VDm = l * Km *S =( ½ *2)(0.0004)(4000) = 1.6 %
There are 16 laterals each having a length of 2 mi and load of (S/16) kVA,
uniformly distributed along the length.
So voltage drop in the lateral will be
%VDl = l * Kl *S =( ½ *2)(0.00095)(4000/16) = 0.2375 %
So total percentage voltage drop for substation A will be
%VDA = %VDm + %VDl = 1.6 + 0.2375 = 1.8375%
For Substation B
Main feeder will be 3 mi long. 1 mi has load lumped at the end and 2 mi has
load uniformly distributed along the length. So voltage drop in the main feeder
will be
%VDm = ( 1*1)(0.0004)(4000) +( ½ *2)(0.0004)(4000) = 1.6 + 1.6 = 3.2 %
There are 32 laterals each having a length of 1 mi and load of (S/16) kVA,
uniformly distributed along the length. So voltage drop in the lateral will be
%VDl = l * Kl *S =( ½ *1)(0.00095)(4000/16) = 0.11875 %
So total percentage voltage drop for substation A will be
%VDA = %VDm + %VDl = 3.2 + 0.11875 = 3.32% 101
Numerical (6): - For the figure given below find the voltage
drop to the farthest consumer. Given Km=0.01 and Kl=0.015
Main feeder
The load is (2*518)kVA lumped at the end of the feeder
So percentage voltage drop in the main feeder will be
%VDm = (1)*l*Km*S
%VDm = (1)(3200/5280)(0.01)(2*518)
%VDm = 6.475%
Lateral
The load is (518) kVA and is uniformly distributed along the
length of lateral
So percentage voltage drop in the lateral will be
%VDl = (½ )*l*Kl*S
%VDl = (½)(5760/5280)(0.015)(518)
%VDl = 4.238%
Total Voltage drop up to last consumer
%VD = %VDm + %VDl
%VD = 6.475 + 4.238
%VD = 10.71% 102
Design Considerations for Primary
and Secondary Distribution Systems
• Primary distribution feeders,
• Primary feeder voltage level and loading,
• Design considerations for Radial feeders,
• Economic design of secondary lines,
• Voltage fluctuation
• Voltage regulation,
• Distribution system voltage control & line drop
compensator.
103
Design considerations for primary system
105
Loading of Primary feeder
106
Primary feeder routing
Primary feeder is run through the area and its routing is affected by
1. Feeder load
2. Future load growth
3. Load density
4. Physical barriers
5. Voltage drop
6. Development practices
7. Total cost
Number of feeders
Factors affecting number of feeders are
1. Load density
2. Feeder length
3. Feeder limitations
4. Voltage drop
5. Conductor size
6. Substation capacity
7. Area to be served 107
Conductor size
108
Prove that doubling the feeder voltage of a specified load
causes the voltage drop in the primary circuit to be reduced
to one fourth of its previous value
109
110
Types of Radial Distribution system
111
2. Improved radial system
112
3. Radial type feeder with express feeder
113
4. Loop type primary feeder
114
Voltage Square Rule
It is given that for a specified percentage voltage drop, the
feeder loading is purely a function of feeder voltage level. It is
expressed as
Voltage Square factor = (V L.N new / V L.N old)2
For example, if the voltage is doubles for the same percentage
voltage, it can supply the same power four times the distance or
four times the power for same distance
115
Area Coverage Principle
116
Numerical (23): - A village is supplied by 11 kV radial feeder
of 3 km and has a uniformly distributed load of 1000 kVA. If
the voltage is increased to 33 kV. How much new load and
new area can be served. What will be the new length of the
feeder/
117
Design considerations of Secondary system
118
Design considerations of Secondary system
❖ Secondary system is the part of power system from distribution transformer to
consumer terminals. While designing a distribution system, future load growth
and load pattern must be considered. Most important factor in the design of
secondary system is economics. Most economical system design, which
corresponds to a load growth projection must be selected.
❖ Since only a small percentage of total faults are due to secondary systems, so
major considerations after cost becomes secondary I2R losses in the
transformer and secondary circuits, voltage drop and voltage flicker. So some
of the factors affecting design of the secondary systems are capacity of
transformer and service lines, investment costs of secondary system
components, cost of labor, capital cost and inflation rates.
Figure above shows the layout and one particular pattern having one
123
span of secondary lines on both sides of distribution transformer.
Following are the notations commonly used
ST = Transformer capacity (kVA)
Isec = Per unit existing current based on ST (Ampere)
PT Fe = Transformer core losses at rated voltage and frequency
PT cu = Transformer copper losses at rated kVA
ASL = Area of the conductor of service line
ρSL = R4esistivity of conductor of service line
ASD = Size of the conductor for service line
ρSD = R4esistivity of conductor of service drop
126
How TAC can be allocated on per customer basis
TAC can be allocated on per customer basis by dividing total TAC
by number of consumers served by the particular secondary
system.
128
❖ In the US, such structuring has had several effects. One that
is relevant to the August 14 blackout is that vast amount of
electricity now flow through the grid through great distances.
For example, large industrial costumers in the Eastern US
routinely shop for power in Midwest. Since the system was not
originally designed to deal with such these volumes, the grid
has been under stress. Investment on transmission has only
been a fraction of what is needed. Another effect has been
that in order to maximize profits, utilities have cut their
expenses by working with low power margins capacities. The
introduction of multiple players means that for a stable and
reliable electric grid, different power generators, transmitters
and users have to follow very strict rules. But given the anti-
regulatory sentiment that accompanies the new-liberal
economic ideology that underlies restructuring, it should not
be surprising that the agencies or institutions that could set
and enforce rules are relatively weak.
129
❖ All of these changes resulting from deregulation have led to
greater un-reliability of the grid. North American has seen a
number of grid collapses in recent years, including the one in
august 14,2003.The event illustrates how complex ,tightly
coupled systems, like the electric grid are prone to accidents.
Small failures can quickly cascade. On 14th august there
were 10,000 individual events across 34000 square miles of
transmission lines and 290 transmission units that all took
place over a 9 second period leading to the blackouts. Alarm
system at First energy corporation, the utility that owned the
transmission lines, whose failure triggered the black out, did
not properly notify the utility, of the failure of one of the major
transmission line. Malfunctioning of computers at First Energy
prevented its technicians from understanding the cause of
failing transmission lines.
130
❖ Restructuring of electrical sector has taken place in broader context
with markets and private capitals being entrusted with various
functions that were formerly under control preview of Governments.
Under this philosophy, the notion that people were entitled to cheap
and reliable electricity supply came under attack. Hence in the
current restructuring scheme, availability to poor or other wise
disadvantageous customer has not been given high priority. Similarly
environmental considerations also take a second consideration to
profit. Thus other considerations in electricity sector restructuring
may affect a large number of people especially in the long term. So
for the matters have largely been articulated by NGOs, such as
Paryas in Pune, India, International energy initiative and the world
resources institute. This has to change. For these consideration to
play a vital role public must intervene and shape restructuring
process. People around the world have paid a heavy price by letting
Government bureaucracies and politicians operate the electricity
sector as they saw fit. Market is no more to be treated to protect the
public good.
❖ One elliptical intersense from August 14 blackout is the excessive
reliance on such complex systems is dangerous. In the case of
blackout the consequences were grave but this sort of massive in
case of nuclear weapon command and control system could load to
131
catastrophic.
Reliability Issue
132
How Restructuring affects the Reliability
❖ Diffusion of responsibility
❖ Disjoined responsibility and authority
❖ Diffused decision making
❖ Unbundling of services
❖ Unrelated cost and benefits
❖ Tragedy of common
Primary Transmission System Voltages are 500kV & 220kV (EHV Voltages)
Secondary Transmission System Voltages are 132kV & 66kV (H.V Voltages)
Utilization System Voltages are 415 Volts (3-Phase) & 230 Volts (1-Phase)
134
POWER SYSTEM CAPABILITY
NAME OF POWER INSTALLED CAPABILITY
PLANT CAPACITY
HYDEL'S
Total Hydel 6516 5554
GENCO's
GENCO - I
Total GENCO - I 1024 840
GENCO - II
Total GENCO - II 2437 1927
GENCO - III
Total GENCO -III 1961 1530
GENCO - IV
Total GENCO - IV 150 30
IPP's
TOTAL THERMAL 9699 8917
IPP'S
TOTAL SOLAR 100 100
WIND IPP'S
TOTAL WIND 306 306
TOTAL SYSTEM 22193 19204
135
DISCO's :- LOAD DEMAND & SUPPLY (JAN - 2016)
Name of Company DEMAND ALLOCATED DRAWN
(MW) (MW) (MW)
137
TYPES OF DISTRIBUTION TRANSFORMERS
➢ Power Transformers
➢ Autotransformers
➢ Distribution Transformers
➢ Instrument Transformers
138
Power Transformers
They are normally oil immersed used for substations and connection to
large commercial and industrial customers. Smaller power transformers
may be dry types used primarily for commercial customers.
➢Power transformers are designed for very high efficiency, and are
routinely maintained.
➢Power transformers are well protected both for safety and economy.
139
EPDU/NNS/DIST TRAN/LUCES M. WLATER COFFER 140
Autotransformers
They are one winding transformers, often used in transmission and sub
transmission substations. figure “a”
Note:
Primary & secondary sides are not
isolated from each other. That means
primary and secondary neutral is
common.
141
3 – phase Autotransformer
142
151